2023_0511_Cantini_Permit_Drawings.pdf
PDF 5 MB Posted
- Attached to
- Cantini Mosaic Reinstallation
- Solicitation number
- 2023-IFB-152
- Issued by
- Allegheny County, Pennsylvania
About this file
The document is a comprehensive set of architectural and engineering permit drawings for the Cantini Mosaic Panels Design project at the Pittsburgh Regional Transit Steel Plaza Station, prepared by Landmarks SGA, LLC and WNA Engineering for the City of Pittsburgh. The project involves the reinstallation of historic mosaic panels within an existing underground corridor at 500 Ross Street, with a work area of approximately 4,400 square feet. The permit set, dated May 11, 2023, includes detailed plans for architectural, structural, and electrical modifications, focusing on carefully removing and reinstalling the mosaic artwork while maintaining the existing corridor's functionality and aesthetic.
The drawings specify a limited scope of work including tile and substrate removal, installation of new gypsum board and paint, reinstallation of mosaic panels by an art conservator, and modifications to lighting and electrical systems. The project will utilize existing infrastructure, with no changes to corridor width or introduction of protruding objects. Electrical work includes installing new suspended LED wall wash fixtures to illuminate the mosaic panels, relocating existing fire alarm devices, and using occupancy sensors for lighting control. The project adheres to the 2018 International Building Code, 2018 International Fire Code, and follows energy efficiency guidelines, with an electrical power density of 0.71 W/ft² for the highlighted artwork area.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Cantini_Mosaic_Reinstallation_(Addendum_#7_Revision).pdf | ||
| Additional_Requirements_2.docx | DOCX document | |
| Additional_Requirements.docx | DOCX document | |
| Prevailing_Wages_Rates.pdf | ||
| 2023_0511_Cantini_Permit_Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
PROJECT
SITE
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/3
/2
:5
:2 A
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
COVER SHEET
G-001
222012
PERMIT SET
05/11/2023
City of Pittsburgh
CANTINI MOSAICS PANELS DESIGN
PITTSBURGH REGIONAL TRANSIT STEEL PLAZA STATION
PERMIT SET
MAY 11, 2023
CITY OF PITTSBURGH
PROJECT TEAM
OWNER:
City of Pittsburgh 200 Ross Street, 4th Floor Pittsburgh, PA 15219 Contact: Sarah Minnaert
ARCHITECT:
Landmarks SGA, LLC 800 Vinial Street, Suite B208 Pittsburgh, PA 15212 Contact: Jessica Stuck/Amy Baade
STRUCTURAL ENGINEER:
The Gateway Engineers, Inc.
100 McMorris Road Pittsburgh, PA 15205 Contact: John Schneider
MEP ENGINEER:
WNA Engineering 800 Vinial Street, Suite A100 Pittsburgh, PA 15212 Contact: Steven Westhead
DRAWING LIST
GENERAL (COMMON TO ALL CONTRACTS)
G-001 COVER SHEET 05/11/2023
G-002 SYMBOLS, NOTES, & ABBREVIATIONS 05/11/2023
G-003 CODE & LIFE SAFETY PLAN 05/11/2023
ARCHITECTURAL (CONTRACT 01 - GENERAL CONSTRUCTION)
AD101 FIRST FLOOR DEMOLITION PLAN 05/11/2023
A-101 FIRST FLOOR PLAN & RCP 05/11/2023
A-201 INTERIOR ELEVATIONS 05/11/2023
A-501 DETAILS 05/11/2023
STRUCTURAL (CONTRACT 01 - GENERAL CONSTRUCTION)
S-100 STRUCTURAL ELEVATIONS & DETAILS 05/11/2023
ELECTRICAL (CONTRACT 02 - ELECTRICAL)
E-001 ELECTRICAL DATA SHEET 05/11/2023
E-002 ELECTRICAL DATA SHEET 05/11/2023
E-101 FIRST FLOOR - LIGHTING PLAN 05/11/2023
E-201 FIRST FLOOR - POWER PLAN 05/11/2023
E-401 ELECTRICAL SCHEDULES 05/11/2023
NO. DATE DESCRIPTION
& OR + AND
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECT OR ARCHITECTURAL
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLK(G) BLOCK OR BLOCKING
BOT BOTTOM
CAB CABINET
CF CUBIC FOOT / FEET
CFMF COLD FORMED METAL FRAMING
CIP CAST-IN-PLACE CONCRETE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEAR OPENING / CLEAN OUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CY CUBIC YARD(S)
D DEPTH
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIV DIVISION
DN DOWN
DTL DETAIL
DWG DRAWING
EA EACH
ELEC ELECTRIC / ELECTRICAL
EL/ELEV ELEVATION OR ELEVATOR
EMER EMERGENCY
EP ELECTRIC PANEL
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE(D)
ETR EXISTING TO REMAIN
EX/EXIST EXISTING
EXT EXTERIOR
F/O FACE OF
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH(ED)
FL / FLR FLOOR(ING)
FND FOUNDATION
FT FOOT / FEET
THE FOLLOWING IS A LIST OF COMMONLY USED ABBREVIATIONS THAT MAY BE UTILIZED WITHIN THE DRAWING SET. REFER TO OTHER TRADES FOR MORE EXPANSIVE TRADE-SPECIFIC ABBREVIATION LISTS. NOTE THAT SOME ABBREVIATIONS MAY HAVE MULTIPLE MEANINGS AND INTENDED MEANING MAY DEPEND ON DRAWING CONTEXT. PLEASE CONTACT ARCHITECT REGARDING ANY POTENTIALLY UNKNOWN, UNLISTED ABBREVIATIONS WITHIN THE DRAWING SET.
G NATURAL GAS
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GR GROUND LINE / GRADE LINE
GSF GROSS SQUARE FOOTAGE
GWB GYPSUM WALL BOARD
GYP BD GYPSUM BOARD
H HEIGHT, HIGH
HC HOLLOW CORE
HDW HARDWARE
HGT / HT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HAND RAIL OR HOUR
HVAC HEATING / VENTILATION / AIR CONDITIONING
HW/ HWH HOT WATER / HOT WATER HEATER
ID INSIDE DIAMETER
IN INCH(ES)
INCL INCLUDED / INCLUDING
INSUL INSULATE / INSULATED / INSULATING
INT INTERIOR
JB JUNCTION BOX
JT JOINT
KO KNOCK OUT
L LENGTH / LONG
LAM LAMINATE(D)
LB POUND
LLH/V LONG LEG HORIZONTAL / VERTICAL
LTL LINTEL
LVR LOUVER
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MED MEDIUM
MFG /MFR MANUFACTURING / MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MWT METAL WALL TRIM
NIC NOT IN CONTRACT
NO / NOM NUMBER / NOMINAL
NSF NET SQUARE FOOTAGE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OH OVERHEAD
OPP / OPH OPPOSITE / OPPOSITE HAND
PCF POUNDS PER CUBIC FOOT
PERF PERFORATED
PL PROPERTY LINE
PLF POUNDS PER LINEAL FOOT
PNT PAINT / PAINTED
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PVMT PAVEMENT
QTR QUARTER
QTY QUANTITY
R RISER
RAD RADIUS
RCP REFLECTED CEILING PLAN
REF REFERENCE
REINF REINFORCED / REINFORCING
REQD REQUIRED
RESIL RESILIENT
REV REVISION(S), REVISED
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
SALV SALVAGED
SAN SANITARY
SCHED SCHEDULE
SEC(T) SECTION
SF SQUARE FEET
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STO STORAGE
STRUC STRUCTURE / STRUCTURAL
SYM SYMMETRICAL
SYS SYSTEM
T/O TOP OF
T/C TOP OF CONCRETE / TOP OF CURB
THRES THRESHOLD
TLT TOILET
TYP TYPICAL
U/ UNDER
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W WIDTH / WIDE
W/ WITH
W/O WITHOUT
WD WOOD
WP WATER PROOFING / WORKING POINT
PROJECT LINE SYMBOLS LEGEND
Existing Items to Remain
New Construction
Hidden or Overhead Items
Existing Items to be Removed
Center Lines / Column Line
Limit of Work
PROJECT MATERIALS LEGEND
Undisturbed Earth
Compacted Fill
Topsoil
Gravel
Concrete
Sand, Grout, Parging, Stucco
Concrete Masonry (or EXIST Generic MAS / SCT)
Brick
GYP / Stud Wall (or Generic Existing Wall)
Existing Partition to be Removed
Metal
Wood
Existing MAS to be Removed
EXISTNEW
SECTION HATCH
EXISTNEW
SURFACE HATCH
Stone Cladding
Existing FLR / Area to be Removed.
Note: See Sheet Legends for sheet-specific line types not represented below.
Note: See Sheet Legends for sheet-specific material / hatch patterns not represented below.
Note: See Sheet Legends for sheet-specific line types not represented below.
PROJECT NORTH
(THICK BLACK LINE)
TRUE NORTH (GREY
DOTTED ARROW)
SHEET #
1/8" = 1'-0"
VIEW NAME
PLAN OR DETAIL
NUMBER
SHEET NUMBER
DRAWING SCALE
DRAWING NAME
A101
SIM
A101
SIM
A1.01
SIM
DRAWING REFERENCE
NUMBER
SHEET REFERENCE
NUMBER
DETAIL SECTION:
DETAIL CALLOUT:
SHEET REFERENCE
NUMBER
DRAWING REFERENCE
NUMBER
QUALIFIER
DRAWING
REFERENCE NUMBER
QUALIFIER
A101
EXTERIOR/INTERIOR ELEVATION:
A101
SIM
DRAWING REFERENCE
NUMBER
SHEET REFERENCE
NUMBER
A101
SIM
SHEET REFERENCE
NUMBER
QUALIFIER
QUALIFIER
DRAWING
REFERENCE NUMBER
SHEET REFERENCE
NUMBER
NORTH ARROW:
VIEW TITLE:
BUILDING SECTION:
WALL SECTION:
SPOT ELEVATION:
+0'-0"
Name Elevation
FLOOR LEVEL:
DRAWING REFERENCE:
SHEET
REFERENCE
NUMBER
DRAWING
REFERENCE
NUMBER
SHEET #
1/8" = 1'-0"
VIEW NAME
N
PROJECT SYMBOLS LEGEND
ROOM NAME
222.D
150 SF
*SEE DRAWING SHEETS FOR VIEW SPECIFIC ROOM TAGS
ROOM NAME
ROOM TAG:
ROOM NUMBER
ROOM AREA
WALL TAG:
WINDOW/LOUVER TAG:
DOOR TAG:
DEMO KEYNOTE TAG:
REVISION TAG:
1i
101.1
N399
GENERAL PROJECT NOTES:
1. Do not scale the drawings.
2. The Contractor is responsible for complying with all applicable codes.
3. The Contractor shall verify all dimensions in the field. Report discrepancies to the Architect for decisions prior to proceeding with the work.
4. The Contractor shall coordinate site elevations. The First Floor Top of Slab Elevation of 100’-0” on the architectural drawings is a reference point, not the actual sea level elevation.
5. Dimensions on the architectural drawings are approximate and from finishes face of GYP unless noted otherwise.
6. Provide suitable blocking in meal stud walls for all wall-mounted objects.
7. Sheets in the A-10x series are intended to show overall dimensions, general plan information, indicators of overall building sections and elevations, and scoping information pertaining for floor/roof infill, overbuild.
8. All references to structural sizes on architectural drawings shall be for reference only. Refer to structural drawings for any and all information related to the structural portion of the project.
9. All quantities shown in schedules are for reference only. Contractor to verify all quantities.
10. Materials and workmanship shall be in accordance with the Contract Documents. All products and materials shall be new unless noted otherwise.
11. Active utilities shall be adequately protected from damage. Where active utilities are encountered but not shown on drawings, the architect, the engineer, and the utility owner shall be advised; work shall be protected, supported or relocated as directed. Inactive and abandoned utilities encountered shall be reported to the Architect.
GENERAL LOGISTICS NOTES:
1. Pedestrian access shall be maintained during performance of the Work. Refer to Specification Section 011000.
2. Product and material deliveries, major lifts, material staging, or any construction activities which may disrupt passenger flow will need to be completed outside of normal daylight shift and peak revenue hours.
3. Protect all existing finishes, lighting, signage, and equipment from damage.
4. Elevators are for public use only and shall not be used for construction purposes or used by workers.
5. Contractor to secure a field office at a nearby off-site location.
6. Provide a staging plan that indicates the area of Work, proposed barrier locations, and staging and laydown areas.
7. Maintain 8' high wood barriers between Work areas and public throughout the duration of the
Work.
8. Provide lockable doors in barriers as required for equipment and material move-in and for worker use and egress.
9. Maintain dust barriers around areas of Work and activities that may create dust. Barriers shall extend to structure above, or horizontally overhead to create a full barrier. Dust barriers shall be designed to prevent dust from exiting the designated area of Work.
10. Protect fire protection devices from dust.
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
SYMBOLS, NOTES, &
ABBREVIATIONS
G-002
222012
PERMIT SET
05/11/2023
City of Pittsburgh
UP
UP
E
D.9
D
D.4
D.3
9 8 7 6
D.5
7'-2"
SUBWAY
CONCOURSE
B44
CORRIDOR
B45
MECHANICAL
B27
ELEV P-9
ELEV P-8
TO STREET
LEVEL
TO 'T'
STATION
SLOPE DN
LIMIT OF WORK AREA
MOSAIC INSTALLATION AREA
±54' - 7"
LP-5
EXIST ELECTRIC PANEL
MOSAIC INSTALLATION AREA
56'-6"
EXIST FEC
EXISTING BUILDING SUMMARY
GENERAL PROJECT DESCRIPTION
This project is the installation of a relocated wall-based artpiece, located in an existing interior corridor in a sub-grade level of 500 Ross Street.
The project area is a pedestrian corridor that provides access from the underground PRT Steel Plaza Station to the exterior 6th Street entrance.
The Work is limited, consisting of the modification of the corridor walls to accomodate the installation of a series of mosaic panels and new surrounding wall finish. Additional accent light fixtures will also in installed and operate on occupancy sensors. The existing ceiling and floor finishes will remain.
The Work will not reduce the existing corridor width, nor will it introduce protruding objects on the wall surface.
APPLICABLE CODES
2018 International Building Code (IBC) 2018 International Existing Building Code (IEBC) 2018 International Fire Code (IFC)
ZONING
Parcel Number: 2-F-250 Address: 500 Ross Street, Pittsburgh, PA 15219 Zoning District: GT-B: Golden Triangle District B Work Area: 4,400 SF
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
CODE & LIFE SAFETY
PLAN
G-003
222012
PERMIT SET
05/11/2023
City of Pittsburgh
G-0031/8" = 1'-0"
1FIRST FLOOR LIFE SAFETY PLAN
N
E
D.9
D
D.4
D.3
9 8 7 6
D.5
UP
SLOPE DN
UP
EXIST ESCALATOR
EXIST STAIR
'-9
± 96'-2"
'-3
/2
± 72'-5 1/2"
± 23'-8 1/2"
LIMIT OF WORK AREA
MOSAIC PANEL INSTALLATION AREA
± 56'-5 1/2"
MOSAIC PANEL INSTALLATION AREA
± 54'-7"
LP-5
EXIST ELECTRIC PANEL
CORRIDOR
B45
SUBWAY
CONCOURSE
B44
MECHANICAL
B27
ELEV P-8
ELEV P-9
AD101 2
AD101
TO 'T' STATION
TO
STREET
LEVEL
± 25'-3 1/4"
TYP AT MOSAIC
PANEL
INSTALLATION
AREA
TYP AT MOSAIC
PANEL
INSTALLATION
AREA
AT MOSAIC PANEL
INSTALLATION AREA
2 AT MOSAIC PANEL
INSTALLATION AREA
EXIST ELEV
CUT EXIST METAL STUD.
COORDINATE WITH NEW
WORK FOR INSTALLING
SUPPORTS FOR
REMAINING FRAMING
EXIST CONCRETE WALL
EXIST BULKHEAD TO REMAIN
EXIST TERRAZZO WALL BASE TO
REMAIN
EXIST 3-5/8" METAL STUD
A T
H
IG
H E
N D
O F
H A
L L
'-3
A
F F
/2
C L E
A R
REMOVE TILE, MORTAR,
AND BACKER BOARD
± 1 1/4"
GENERAL DEMOLITION NOTES
1. Keyed demolition notes are to aid in indicating the material and extent of items to be removed. Refer to Architectural Drawings for exact positions of new openings in existing walls, floors, or ceilings.
2. Contractor is responsible to field verify all existing conditions and dimensions prior to demolition and report any discrepancies between existing conditions and the drawings to the Architect in writing.
3. The Contractor is responsible for maintaining dust control, exiting, and life safety requirements throughout the duration of the project.
4. The Contractor is responsible for maintaining a weathertight building. Provide temporary weather protection at existing windows, walls, and/or roof openings created by demolition work as required.
5. At demolition of walls and portions of walls, the Contractor shall be responsible for patching and infill to provide a smooth working edge to match remaining adjacent surface/pattern.
6. Refer to Specification Sections 024110 “Selective Demolition” and 017329 “Cutting and Patching” for the handling of demolition items, including disposal, recycling, storage, patching, and salvage.
7. At walls shown to be removed, include the removal/relocation of all mechanical, electrical, and plumbing items.
8. Remove all abandoned or unused utilities and associated furring and chases, unless noted otherwise.
DEFINITIONS
"REMOVE" = Detatch items from existing construction and legally dispose of it off-site unless indicated to be removed and salvaged or removed and reinstalled.
"EXISTING TO REMAIN" = Existing items of construction that are not to be permanently removed and that are not otherwise indicated to be removed and salvaged, or removed and reinstalled.
"REMOVE AND REINSTALL" = Existing items of construction that are removed and reinstallated with the new Work in location noted.
AD1011/8" = 1'-0"
1DEMOLITION FLOOR PLAN
N
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
FIRST FLOOR
DEMOLITION PLAN
AD101
222012
PERMIT SET
05/11/2023
City of Pittsburgh
AD1011" = 1'-0"
2DEMOLITION WALL SECTION
NO. DATE DESCRIPTION
DEMOLITION KEYNOTES
1 REMOVE EXIST TILE, MORTAR, AND
SUBSTRATE
2 REMOVE EXIST TILE, MORTAR, AND
SUBSTRATE. REMOVE STUDS PER 2/AD101
3 REMOVE AND REINSTALL FEC
4 WALL OUTLET, ETR. REMOVE AND REINSTALL
IN PLACE AS REQD
5 REMOVE AND REINSTALL FIRE ALARM DEVICE
ALL WORK ON THIS SHEET IS PART OF CONTRACT 01 -
GENERAL CONSTRUCTION, UNLESS NOTED OTHERWISE
DEMOLITION KEYNOTES
1 REMOVE EXIST TILE, MORTAR, AND
SUBSTRATE
2 REMOVE EXIST TILE, MORTAR, AND
SUBSTRATE. REMOVE STUDS PER 2/AD101
3 REMOVE AND REINSTALL FEC
4 WALL OUTLET, ETR. REMOVE AND REINSTALL
IN PLACE AS REQD
5 REMOVE AND REINSTALL FIRE ALARM DEVICE,
COORDINATE WITH ELECTRICAL
CONTRACTOR
E
D.9
D
D.4
D.3
9 8 7 6
D.5
UP
SLOPE DN
UP
EXIST ESCALATOR
EXIST STAIR
TO 'T' STATION
'-3
/2
A-201
A-201
LIMIT OF WORK AREA
MOSAIC PANEL INSTALLATION AREA
± 56'-5 1/2"
MOSAIC PANEL INSTALLATION AREA
± 54'-7"
LP-5
EXIST ELECTRIC PANEL
CORRIDOR
B45
SUBWAY
CONCOURSE
B44
MECHANICAL
B27
ELEV P-8
ELEV P-9 EXIST ELEV
REINSTALL EXIST FEC IN
ORIGINAL LOCATION
A-501
A-501
A-501
SURFACE-MOUNTED
DIDACTIC PANEL, OFCI
SURFACE-MOUNTED
DIDACTIC PANEL, OFCI
WALL OUTLET, ETR, TYP
'-9
± 96'-2"
± 72'-5 1/2"
± 23'-8 1/2"
GYP BD, PT
TO
STREET
LEVEL
±25'-3 1/4"
GYP BD, PT
TILE ALONG WALL, GYP BD,
PT WITHIN MOSAIC PANEL
RECESS AREAS
E
D.9
D
D.4
D.3
9 8 7 6
D.5
± 10'-11"
± 10'-5"
± 11'-9 1/2"
± 10'-5"
± 10'-5"
± 10'-11"
LIMIT OF WORK AREA
52'-0"
LINEAR LIGHT FIXTURE MOUNTED
TO EXIST BULKHEAD, INSTALLED AS
CONTINUOUS BAR, COORDINATE
WITH ELECTRICAL CONTRACTOR
52'-0"
LIMIT OF WORK AREA
CORRIDOR
B45
SUBWAY
CONCOURSE
B44
MECHANICAL
B27
ELEV P-8
ELEV P-9
OCC
OCC
REINSTALL RELOCATED EXISTING FA DEVICE,
COORDINATE WITH ELECTRICAL CONTRACTOR
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
LP5-1
'-6
'-6
EXIST RECESSED DOWNLIGHT
EXIST WAYFINDING SIGNAGE (CLG MOUNT)
EXIST WALL MOUNTED SECURITY CAMERA
EXIST CLG MOUNTED EXIT SIGN
RCP LEGEND
CLG-MOUNTED WALL WASHER LIGHT
OCCUPANCY SENSOR
GENERAL FLOOR PLAN NOTES
1. Floor Plans show overall dimensioning, general plan information, drawing reference information, and scoping information. Refer to details for detailed information regarding dimensions, wall types, door numbers, and other annotations.
2. Contractor is responsible to field verify all dimensions and sizes of existing structure prior to construction. Notify the Architect of any discrepancies.
3. All items shown with dashed lines are provided for reference only and are outside the scope of this project, inclusive of mosaic panels and Z-clips for panel attachment to wall (NIC).
4. Grid lines and room names reference the 1998 Burt Hill Kosar Rittlemann Drawings for Mellon Client Service Center.
GENERAL CEILING PLAN NOTES
1. Dimensions provided to finish face of wall or surface, unless noted otherwise.
2. Spot elevations indicate approximate eleavtion from the higher floor elevation of the subway concourse to the finish face of existing ceiling finishes.
3. MEP Fixtures are shown for reference and coordination purposes only. Coordinate with "Contract 02 - Electrical" MEP drawings for fixture types and equipment information.
4. Light fixtures shall be centered in ceiling area, room, or ceiling tile, unless noted otherwise.
5. Occupancy sensors, smoke detectors, and any other ceiling-mounted equipment to be centered in ceiling tile, on light fixture centerline, and/or between lighting where possible.
A-1011/8" = 1'-0"
1FLOOR PLAN
N
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
FIRST FLOOR PLAN &
RCP
A-101
222012
PERMIT SET
05/11/2023
City of Pittsburgh
A-1011/8" = 1'-0"
2REFLECTED CEILING PLAN
N
NO. DATE DESCRIPTION
ALL WORK ON THIS SHEET IS PART OF CONTRACT 01 -
GENERAL CONSTRUCTION, UNLESS NOTED OTHERWISE
LINE OF WALL ON OPPOSITE
SIDE OF TUNNEL
END OF SLOPED
FLOOR
START OF
SLOPED FLOOR
MOSAIC INSTALLATION
± 56'-5 1/2"
'-4
'-1
'-5
'-9
/2
TERRAZZO WALL BASE EXISTING TO REMAIN, CLEAN
A-501
2 3 4 5 7
9 11
12 131 8
CT-1 IRREGULAR, WHITE, MATTE WALL TILE,
REFER TO
MOSAIC PANEL NUMBER PER MCKAY
LODGE CONSERVATION LABORATORY
NUMBERING SYSTEM, TYP
MOSAIC PANELS INSTALLED
BY ART CONSERVATOR PER
ORIGINAL DESIGN AND
LAYOUT, NIC
1'-6"
EXIST FINISHES TO REMAIN
AREA NOT IN SCOPE
'-4
/2
'-9
/2
'-3
GYP-PT WITHIN RECESSED AREA
LINEAR SUSPENDED LIGHT
FIXTURE, SEE ELEC DWGS
EQ EQ
'-2
'-0
5'-0"
/4 A-201
A-501
SURFACE MOUNTED DIDACTIC PANEL LOCATION.
DIMENSION AND DESIGN TBD. PROVIDE
BLOCKING WITHIN AREA SHOWN.
T
F
IX
T U
R E
START OF
SLOPED FLOOR
END OF SLOPED
FLOOR
EXIST DOUBLE DOORS
ON HOLD OPENS
'-5
'-9
/2
TERRAZZO WALL BASE EXISTING TO REMAIN, CLEAN
A-501
SURFACE MOUNTED DIDACTIC PANEL LOCATION.
DIMENSION AND DESIGN TBD. PROVIDE
BLOCKING WITHIN AREA SHOWN.
'-0
'-3
5'-0"
21 22 24 26 27
282523
CT-1 IRREGULAR, WHITE, MATTE WALL TILE. REFER TO
MOSAIC PANEL NUMBER PER MCKAY
LODGE CONSERVATION LABORATORY
NUMBERING SYSTEM, TYP
MOSAIC PANELS INSTALLED
BY ART CONSERVATOR PER
ORIGINAL DESIGN AND
LAYOUT, NIC
INSTALL GWB AND PT
± 23'-8 1/2"
'-3
'-9
/2
'-4
/2
'-2
MOSAIC INSTALLATION
± 54' - 7"
LINEAR SUSPENDED LIGHT
FIXTURE, COORDINATE WITH
ELECTRICAL CONTRACTOR
GYP-PT WITHIN RECESSED AREA
EQEQ /4 A-201
A-501
A-501
T
F
IX
T U
R E
REINSTALL EXIST FEC IN
ORIGINAL LOCATION
'-4
'-1
RMV EXIST WALL TILE, INSTALL GWB AND PT
± 15'-3 1/2"
EXIST EXIT SIGN TO REMAIN
GYP BD, PT
GENERAL INTERIOR ELEVATION NOTES
1. Refer to ceiling plans for ceiling types/extents.
2. Refer to electrical drawings for all receptacle locations and lighting fixtures shown on elevations.
3. Notations shown in interior elevations are present for clarifying purposes and do not represent an exhaustive index of all important components within the space. Absence of a note does not reflect a reduction in scope.
4. Refer to details for partition connection and transition details.
5. Provide blocking in walls for all wall-mounted objects, including information/didactic panels.
MOSAIC PANEL
FIELD-CUT TILE
These images from the original art installation are for reference only, and are intended solely to show general design intent for the final appearance of the irregular tiles.
The tiles are not intended to be cut exactly as depicted in the photos of the original installation.
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
INTERIOR ELEVATIONS
A-201
222012
PERMIT SET
05/11/2023
City of Pittsburgh
A-2011/4" = 1'-0"
1PLAN NORTH ELEVATION
A-2011/4" = 1'-0"
2PLAN SOUTH ELEVATION
A-2011/4" = 1'-0"
3PLAN WEST ELEVATION
A-2013" = 1'-0"
4REFERENCE - ORIGINAL INSTALLATION
±5' - 5"
NO. DATE DESCRIPTION
A-501
A-501
A-501
EXIST WALL DEPTH
5 5/8"
EXIST CONCRETE WALL
EXIST GYP BD BULKHEAD
EXIST 3-5/8" METAL STUD
SUSPENDED LINEAR LIGHT FIXTURE,
COORDINATE WITH ELECTRICAL
CONTRACTOR
MOSAIC PANEL MOUNTED TO
Z-CLIPS, NIC
V A
R
IE
S
± 2 5/8"
CLIP CONNECTOR AT EXIST STUD
WALL, SEE STRUCTURAL DWGS
OPP
1'-6" 4
PATCH BULKHEAD AS REQD
BLOCKING MOUNTED TO CONC
WALL. COORDINATE LOCATION WITH
CONSERVATOR
GYP BD, PT
EXIST CONCRETE WALL
EXIST 3-5/8" METAL STUD
1/2" CEMENT BACKER BOARD
EXIST TERRAZZO WALL BASE, CLEAN
EXIST TERRAZZO SUBSTRATE TO REMAIN
MWT-3 SS TRIM
MORTAR
CT-1 WALL TILE
MOSAIC PANEL MOUNTED TO ALUM
BACKING PANEL, NIC BY CONSERVATOR
EXIST CONCRETE WALL
EXIST 3-5/8" METAL STUD
1/2" CEMENT BACKER BOARD
MORTAR
Z-CLIP MOUNTED TO BACK OF ALUM
BACKING PANEL, NIC BY CONSERVATOR
Z-CLIP MOUNTED TO BLOCKING, NIC
BY CONSERVATOR
± 3"
WOOD BLOCKING ANCHORED TO EXIST
CONC WALL, COORDINATE FINAL LOCATION
WITH ART CONSERVATOR PRIOR TO
INSTALLATION. MOUNTING HT VARIES
CT-1 WALL TILE
1/2" GYP BOARD SURROUND
STEEL ANGLE
MTL CHANNEL TO SUPPORT EXIST STUDS,
SEE STRUCT DWGS
MWT-1 SS TILE EDGE
2.
V
IF EXIST WALL TILE AND BACKUP
CT-1 WALL TILE
MORTAR
1/2" CEMENT BACKER BOARD
EXIST STUD
MWT-2 SS EDGE PROTECTION PROFILE
1/2" GYP BD, PT
EXIST 3-5/8" METAL STUD
1/2" CEMENT BACKER BOARD
MORTAR
CT-1 WALL TILE
1/4"
SEALANT JOINT
EXIST WALL TILE AND BACKUP
CT-1 WALL TILE
MORTAR
1/2" CEMENT BACKER BOARD
EXIST STUD
MWT-1 SS TILE EDGE
NO
T F
O R C
O
NSTRUCTIO
N
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
800 VINIAL STREET, SUITE B208, PITTSBURGH, PA 15212
P. 412.265.9031 WWW.LMSGA.COM
/8
/2
:1 :2
P
M C
U s e rs
\a b a a d e \D o c u m e n ts \2
P
G H
C a n ti n i M o sa ic s R a b a a d e .r vt
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
DETAILS
A-501
222012
PERMIT SET
05/11/2023
City of Pittsburgh
A-5011" = 1'-0"
1WALL SECTION
A-5013" = 1'-0"
2WALL BASE SECTION DETAIL
A-5013" = 1'-0"
3WALL RECESS HEAD DETAIL (SILL OPP)
NO. DATE DESCRIPTION
A-5013" = 1'-0"
5PLAN DETAIL - OBTUSE OUTSIDE CORNER
A-5013" = 1'-0"
4PLAN DETAIL TILE/GYP BD INSIDE CORNER
A-5013" = 1'-0"
6PLAN DETAIL - OUTSIDE CORNER
2 3 4 5 7
9 11
12 131 8
MOSAIC PANEL PER ARCH
DRAWINGS, NIC TYPICAL
BLOCKING MOUNTED BEHIND PANELS,
FINAL LOCATION TO BE COORDINATED IN
FIELD WITH ART CONSERVATOR
18 19 21 22
24 26 27
282523
MOSAIC PANEL PER ARCH
DRAWINGS, NIC TYPICAL
BLOCKING MOUNTED BEHIND PANELS,
FINAL LOCATION TO BE COORDINATED IN
FIELD WITH ART CONSERVATOR
CUT EXISTING STUD ABOVE AND BELOW
PANEL ATTACHMENT LOCATION AFTER
INSTALLATION OF SIMPSON CLIP
SIMPSON FC32-5/97 FIXED CLIP
CONNECTOR AT EACH EXISTING
WALL STUD W/ (4) #10 SELF
DRILLING SCREWS TO WALL STUD
(2) 14" TITEN HD SCREW ANCHORS
x 1 5 8" EMBEDMENT
Z-CLIP SECURED TO
BLOCKING AND PANEL, NIC2x6 BLOCKING (x4" MINIMUM
LONGER THAN Z-CLIP)
SIMPSON FC32-5/97 FIXED CLIP
CONNECTOR AT EACH EXISTING
WALL STUD W/ (4) #10 SELF
DRILLING SCREWS TO WALL STUD
(2) 14" TITEN HD SCREW ANCHORS
x 1 5 8" EMBEDMENT
EXISTING CONCRETE WALL
MOSAIC PANEL PER ARCH DRAWINGS,
NIC
ALUMINUM MOSAIC BACKUP
PANEL, NIC
PROVIDE CONTINUOUS STUD TRACK
PROVIDE CONTINUOUS STUD TRACK
BLOCKING SECURED TO WALL WITH
16" DIAMETER TAPCON ANCHORS
(TOP AND BOTTOM) AT 6" O.C. x 1 14"
MINIMUM EMBEDMENT
(4) ANCHORS MINIMUM PER BLOCKING
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
CANTINI MOSAICS
PANELS DESIGN
PRT STEEL PLAZA STATION
STRUCTURAL ELEVATIONS
& DETAILS
S-100
222012
PERMIT SET
05/11/2023
City of Pittsburgh
S-100 1/4" = 1'-0"
1PLAN NORTH ELEVATION
S-100 1/4" = 1'-0"
2PLAN SOUTH ELEVATION
S-100 1" = 1'-0"
3PANEL SECTION
NO. DATE DESCRIPTION
S-100
S-100
DESIGN LOADING
1. ALL STRUCTURAL ELEMENTS WERE DESIGNED IN ACCORDANCE WITH THE 2015 INTERNATIONAL BUILDING
CODE (2018 IBC).
2. DEAD LOADS:
- HAVE BEEN CALCULATED VIA RELEVANT ENGINEERING SELF-WEIGHT INFORMATION
3. WIND LOADS:
- INTERIOR WALLS 5 PSF
1. ALL COLD-FORMED STEEL FRAMING WORK SHALL BE IN ACCORDANCE WITH THE MOST CURRENT EDITION OF THE CODE OF STANDARD PRACTICE FOR COLD-FORMED STEEL STRUCTURAL FRAMING, AISI 202-15.
2. STEEL USED IN THE MANUFACTURE OF COLD-FORMED STEEL FRAMING SHALL BE HOT-DIPPED GALVANIZED
WITH A MINIMUM COATING WEIGHT OF G-90.
3. FIELD CUTTING OF STUDS MUST BE DONE BY SAWING OR SHEARING. TORCH CUTTING OF COLD-FORMED
STEEL FRAMING IS NOT ACCEPTABLE.
4. ANY SPLICES IN STUDS OR JOISTS SHALL BE SPECIFICALLY DETAILED ON THE SHOP DRAWINGS AND SHALL NOT BE MADE WITHOUT THE STRUCTURAL ENGINEERS REVIEW OF APPLICABLE SPLICE DETAILS AND
CALCULATIONS.
COLD-FORMED STEEL FRAMING NOTES
1. ALL CONSTRUCTION MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF THE DRAWINGS, SPECIFICATIONS, AND THE CODES, RULES AND REGULATIONS OF THE INTERNATIONAL BUILDING
CODE, 2018 EDITION, AND ALL OTHER APPLICABLE BUILDING CODES.
2. SPECIFICATIONS, CODES, AND STANDARDS NOTED IN THE CONTRACT DOCUMENTS SHALL BE OF THE LATEST APPROVED ISSUE, INCLUDING SUPPLEMENTS, UNLESS OTHERWISE NOTED. MATERIAL SPECIFICATIONS ARE
ASTM LATEST EDITION.
3. THESE DRAWINGS HAVE BEEN PRODUCED ON THE GATEWAY ENGINEERS, INC. CADD SYSTEM. ANY OTHER MARKS AFFIXED TO THE DRAWINGS, OTHER THAN PROFESSIONAL STAMPS AND SIGNATURES, HAVE BEEN MADE WITHOUT THE THE AUTHORIZATION OF GATEWAY ENGINEERS AND ARE THEREFORE INVALID.
4. IF ANY ERRORS OR OMISSIONS APPEAR IN THESE DRAWINGS, SPECIFICATIONS, OR OTHER DOCUMENTS; THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OR ARCHITECT IN WRITING OF SUCH OMISSION OR
ERROR BEFORE PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE OWNER AND ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES. THE STRUCTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL STRUCTURAL FEATURES, U.N.O. THE ARCHITECTURAL DRAWINGS SHALL GOVERN THE WORK RELATED TO DIMENSIONS. SCALING OF DRAWINGS TO OBTAIN DIMENSIONS SHALL NOT BE DONE AT ANY TIME. IF A REQUIRED DIMENSION IS NOT PROVIDED, THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION TO THE ENGINEER FOR CLARIFICATION. U.N.O. CONTRACTOR SHALL PROVIDE EQUAL SPACING OF STRUCTURAL COMPONENTS BETWEEN OVERALL DIMENSIONS PROVIDED ON THE
DRAWINGS.
6. NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NOTES AND DETAILS ON DRAWINGS AND THESE GENERAL NOTES AND TYPICAL DETAILS ARE IN CONFLICT WITH THE PROJECT SPECIFICATIONS, CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD. CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED AS SHOWN FOR SIMILAR WORK, SUBJECT TO REVIEW BY
THE ARCHITECT AND STRUCTURAL ENGINEER.
7. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE; THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE
STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE ITEMS.
8. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE EXISTING AND NEW STRUCTURE AND ALL STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH
THE STRUCTURAL DOCUMENTS.
9. ALL STRUCTURAL SYSTEMS THAT ARE TO BE COMPOSED OF MANUFACTURED COMPONENTS TO BE FIELD ERECTED SHALL BE APPROVED BY THE CHECKING AGENCY PRIOR TO THEIR USE AND SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION IN
ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER.
GENERAL NOTES
500 ROSS STREET
PITTSBURGH, PA 15258
ALL WORK ON THIS SHEET IS PART OF CONTRACT 01-
ELECTRICAL GENERAL NOTESCODE SUMMARY
TYPICAL CIRCUITING INFORMATION
ABBREVIATIONS
A AMPERE
ABV ABOVE
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
AP ACCESS PANEL
APPROX APPROXIMATELY
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CONC CONCRETE
CONT CONTINUED
CT CURRENT TRANSFORMER
CU COPPER
CUH CABINET UNIT HEATER
DEMO DEMOLITION
DW DISHWASHER
DWG DRAWING
EA EACH
EBR ELECTRIC BASEBOARD RADIATION
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EHC ELECTRIC HEATING COIL
EMT ELECTRIC METALLIC TUBING
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EX EXISTING
FC/FCP FIRE PROTECTION CONTRACTOR
FLA FULL LOAD AMPERES
FLUOR FLUORESCENT
FT FEET
FZ FREEZER
GC GENERAL CONTRACTOR
G GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HC/MC MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
HOR HORIZONTAL
HP HORSEPOWER
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HZ HERTZ
IC INTERUPTING CAPACITY
INCAND INCANDESCENT
JB JUNCTION BOX
KVA KILOVOLT - AMPERE
KW KILOWATT
LRA LOCKED ROTOR AMPERES
LTG LIGHTING
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MED MEDIUM
MH METAL HALIDE
MIN MINIMUM
MTD MOUNTED
MTG MOUNTING
MW MICROWAVE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO. (#) NUMBER
NTS NOT TO SCALE
PH PHASE
PNL PANEL
PVC POLY VINYL CHLORIDE
R REFRIGERATOR
RLA RUNNING LOAD AMPERES
THRU THROUGH
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
WP WEATHERPROOF
WR WEATHER RESISTANT
1. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE 98 PERCENT CONDUCTIVITY COPPER, THWN/THHN, 600 VOLTS RATED UNLESS OTHERWISE NOTED. WIRE SIZES ARE #12 FOR ALL 20A CIRCUITS UNLESS NOTED OTHERWISE ON
DRAWINGS OR SCHEDULES OR IF LARGER SIZE IS REQUIRED FOR EQUIPMENT FURNISHED. ALL FEEDER CONDUCTORS SHALL BE 98 PERCENT CONDUCTIVITY COPPER, AWG SIZE AS NOTED, XHHW INSULATION, 600 VOLTS RATED, UNLESS OTHERWISE NOTED.
2. (3) #12 & #12 GND IN 3/4"C. INDICATES THREE NO. 12 AWG AND ONE NO. 12 AWG GREEN INSULATED GROUND IN A 3/4" CONDUIT. CODE SIZED GREEN GROUNDING CONDUCTOR IS TO BE PROVIDED FOR ALL BRANCH
CIRCUITS.
3. INSTALL ACCESS PANELS WHERE REQUIRED.
4. COORDINATE WITH MECHANICAL, PLUMBING AND FIRE PROTECTION CONTRACTORS FOR COMPLETE, PROPER OPERATION AND INSTALLATION OF ALL EQUIPMENT. SEE MECHANICAL & PLUMBING DRAWINGS.
5. CONTRACTOR SHALL COORDINATE INSTALLATION OF CIRCUITS, JUNCTION BOXES AND CONDUITS REQUIRED FOR SECURITY SYSTEM AND RELATED ITEMS.
6. CONTRACTOR SHALL COORDINATE INSTALLATION OF LIGHTING WITH REFLECTED CEILING PLANS. SEE ARCHITECTURAL DRAWINGS.
7. VERIFY ELECTRICAL REQUIREMENTS FOR APPLIANCES AND EQUIPMENT PRIOR TO ROUGH-IN.
8. ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES IN ORDER TO AVOID CONFLICTS.
9. THE MINIMUM CONDUIT SIZE SHALL BE 3/4".
10. WIRE TYPE SHALL BE - #8 CU AND SMALLER USE THWN/THHN, #6 CU AND LARGER USE THWN.
11. VOLTAGE DROP MINIMUM WIRE SIZING (20A CIRCUIT) USE:
A. 277V CIRCUITS GREATER THAN 195' USE #10 UNLESS OTHERWISE NOTED.
B. MINIMUM BRANCH CIRCUIT WIRE SIZE SHALL BE #12 FOR ALL 20A CIRCUITS.
C. ALL CONTROL WIRING SHALL BE AWG NO. 14 MINIMUM SIZE.
12. ALL OPENINGS IN FIRE RATED WALLS, FLOOR AND PARTITIONS FOR CONDUITS SHALL BE SEALED WITH FIRE RESISTANT CAULKING OR UL APPROVED "FIRE STOP" SYSTEM TO MAINTAIN THE FIRE RATING. PROVIDE FIRE STOP
PUTTY PAD AT ELECTRICAL OUTLET BOXES AS REQUIRED.
13. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES, DIMENSIONAL LOCATION OF FIXTURES IN DRYWALL CEILING, ETC.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING CEILING, WALLS AND COLUMN ENCLOSURES, INCLUDING FINISH IN FINAL FINISHED AREAS IF REQUIRED.
15. OWNER RESERVES THE RIGHT TO RELOCATE ANY LIGHT FIXTURE, BEFORE BEING INSTALLED WITHIN 10'-0" FROM LOCATION AS SHOWN ON PLANS AT NO ADDITIONAL EXPENSE TO THE OWNER.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND MAINTAINING ALL AREAS FREE OF TRASH AND DEBRIS AND FOR PROTECTING FINISHES.
17. NO CONDUIT SHALL BE INSTALLED EXPOSED IN AREAS OTHER THAN MECHANICAL SPACES AND ATTIC UNLESS APPROVED BY ARCHITECT.
18. MOUNTING HEIGHTS FOR ALL RECEPTACLES SHALL BE VERIFIED WITH ARCHITECT.
19. ALL DIMENSIONS INDICATED ARE TO CENTERLINE OF JUNCTION BOXES, ETC., UNLESS OTHERWISE NOTED.
20. VERIFY DEVICE COLORS IN ALL AREAS WITH ARCHITECT.
21. VERIFY ALL CATALOG NUMBERS WITH DEVICE DESCRIPTIONS BEFORE PURCHASING.
22. DO NOT INSTALL MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN JUNCTION OR PULL BOXES.
23. CIRCUIT NUMBERS ARE SHOWN FOR CLARITY AND PHASING. THE CONTRACTOR SHALL REARRANGE CIRCUITS ON EACH PANEL BOARD TO BALANCE THE LOADS ON EACH PHASE TO WITHIN PLUS OR MINUS TEN PERCENT.
BALANCE LOADS 30 DAYS AFTER OCCUPANCY AND AGAIN AT 180 DAYS AFTER OCCUPANCY.
24. PROVIDE ALL LABOR, MATERIALS, NECESSARY EQUIPMENT AND SERVICES TO COMPLETE ALL REQUIRED ELECTRICAL WORK INCLUDING ALL ADDITIONAL ITEMS REQUIRED FOR A COMPLETE AND PROPER INSTALLATION AS
INDICATED ON THE DRAWINGS OR AS REQUIRED. WORK INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING:
A. NEW INTERIOR LIGHTING.
B. NEW FIRE ALARM DEVICES.
25. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MANUFACTURER'S SHOP DRAWINGS FOR EXACT LOCATION AND ROUGH-IN DIMENSIONS OF ALL EQUIPMENT AND SHALL MAKE ALL FINAL CONNECTIONS AS
REQUIRED; I.E., POWER, CONTROL, ETC.
26. SHOULD A STRUCTURAL MEMBER, DUCT, ETC. PREVENT A LIGHT FIXTURE FROM BEING INSTALLED WHERE SHOWN ON THE DRAWINGS, THE ELECTRICAL CONTRACTOR SHALL DISCUSS ALTERNATIVE LOCATIONS WITH
ARCHITECT.
27. WIRE AND CONDUIT SIZES INDICATED SHALL BE CONTINUOUS THROUGH CIRCUIT.
28. INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND ALL APPLICABLE REGULATIONS OF GOVERNING
LOCAL, STATE, COUNTY AND FEDERAL CODES INCLUDING UTILITY COMPANIES SPECIAL REQUIREMENTS.
29. THE HOMERUN SYMBOL INDICATES HOME RUN WITH 2, 3, OR 4 CONDUCTORS AND 1 GREEN INSULATED COPPER CONDUCTOR. THE BRANCH CIRCUIT CONDUCTORS SHALL CONTINUE TO THE FIXTURES AND DEVICES
INDICATED BY THE CIRCUIT NUMBERS.
30. PANELBOARD DIRECTORIES SHALL BE ACCURATELY LABELED IN A TYPED FORMAT. DISCONNECT SWITCHES SHALL BE LABELED WITH THE LOAD SERVED BY THE SWITCH.
31. THE CONTRACTOR SHALL DETERMINE THE EXACT NUMBER OF CONDUCTORS, THE CONDUIT SIZE AND ROUTING. THE CONDUCTOR SIZES SHALL BE INCREASED IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE WHERE THE
NUMBER OF CONDUCTORS IN RACEWAY OR CABLE EXCEEDS THREE.
32. THE ELECTRICAL CONTRACTOR SHALL USE CAUTION TO AVOID DAMAGE TO EXISTING UTILITY LINES AND/OR HARM TO PERSONNEL ENGAGED IN WORKING IN THESE AREAS.
33. ALL PENETRATIONS SHALL BE INSULATED FOR SOUND.
34. DRAWINGS ARE DIAGRAMMATIC ONLY: EXACT LOCATION, MOUNTING HEIGHTS OF EQUIPMENT AND ROUTING OF RACEWAYS SHALL BE COORDINATED WITH THE EQUIPMENT REQUIREMENTS AND FIELD CONDITIONS.
35. ELECTRICAL CONTRACTOR SHALL INSTALL ALL SWITCHES, STARTERS, AND DEVICES FOR MOTOR DRIVEN EQUIPMENT FURNISHED BY OTHERS, AND PROVIDE POWER WIRING THROUGH THE DEVICES TO THE MOTORS.
36. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT BUILDING/WALL DIMENSIONS.
37. ALL MATERIALS SHALL BE NEW, FREE OF DEFECTS AND SHALL BE U.L. LISTED, BEARING U.L. LABEL OR BE LABELED OR LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY.
38. PROVIDE CLEARANCES FROM INSULATION AS REQUIRED FOR ANY ELECTRICAL DEVICE / LIGHT FIXTURE NOT IC RATED.
39. PROVIDE ALL NECESSARY CIRCUIT BREAKERS TO POWER ALL DEVICES AND EQUIPMENT.
40. ALL BLANK JUNCTION BOXES SHALL BE FURNISHED WITH A BLANK COVER.
41. FLEXIBLE METAL CONDUIT WITH PVC COATING SHALL BE USED FOR CONNECTIONS TO MOTORS AND EQUIPMENT. PROVIDE LIQUID TIGHT CONDUIT FOR EXTERIOR LOCATIONS.
42. PROVIDE PLENUM RATED CABLE IN ANY AREA WHERE THE PLENUM SPACE IS USED FOR HVAC RETURN AIR. COORDINATE EXACT LOCATIONS WITH G.C.
43. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE ORDINANCES, CODES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
44. WHERE A CONFLICT ARISES BETWEEN PLANS, SPECIFICATIONS, DETAILS, SCHEDULES, APPLICABLE CODES OR REGULATIONS; THE MOST STRINGENT SHALL APPLY
45. EACH CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES AND THE OWNER'S REPRESENTATIVE SO AS NOT TO DISRUPT PRODUCTION.
46. IF A CONTRACTOR ENCOUNTERS OR UNCOVERS CONDITIONS NOT INDICATED ON THE PLANS OR SPECIFIED; OR, IF A CONTRACTOR ENCOUNTERS CONFLICTS BETWEEN DRAWINGS OR BETWEEN A DRAWING AND THE
SPECIFICATIONS OR NOTES, HE SHALL NOTIFY THE OWNER'S REPRESENTATIVE PRIOR TO PROCEEDING WITH ANY WORK. FAILURE TO NOTIFY THE OWNER FOR RESOLUTION PRIOR TO PROCEEDING WILL MAKE THE
CONTRACTOR RESPONSIBLE FOR ALL COSTS AND CONSEQUENCES OF SUCH FAILURE.
47. ALL WORK INDICATED ON THE RESPECTIVE DRAWINGS WILL BE BY THE SPECIFIC CONTRACTOR WHOSE CONTRACT LIST THOSE DRAWINGS AS PART OF HIS WORK UNLESS SPECIFICALLY NOTED OTHERWISE.
48. NON METALLIC CABLE (ROMEX) IS NOT PERMITTED.
NOTE: ALL WIRES #12 UNLESS NOTED. ALL CONDUIT SHALL HAVE A GROUND CONDUCTOR SIZED AS PER
NEC (NOT SHOWN). ALL BRANCH CIRCUITS FROM ISOLATED GROUND PANELS SHALL CONTAIN A GROUND
CONDUCTOR SIZED AS PER N.E.C. (NOT SHOWN)
THIS PROJECT IS GOVERNED BY THE PENNSYLVANIA UNIFORM CONSTRUCTION CODES INCLUDING, BUT NOT
LIMITED TO:
1. 2018 INTERNATIONAL BUILDING CODE (IBC)
2. 2017 NATIONAL ELECTRICAL CODE (NFPA 70)
3. 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
4. 2018 INTERNATIONAL FIRE CODE (IFC)
5. 2016 NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72)
6. 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
ADDITIONAL STANDARDS AND GUIDELINES INCLUDE:
1. NFPA 101 – LIFE SAFETY CODE
EQUIPMENT TAG
EQUIPMENT MOTOR DESCRIPTION
EQUIPMENT VOLTAGE, POLES, WIRES
EQUIPMENT
CONDUIT TRADE SIZE
QUANTITY AND SIZE OF CURRENT CARRYING CONDUCTORS.
GROUNDED (NEUTRAL) CONDUCTOR SIZE (IF ANY)
GROUNDING CONDUCTOR SIZE (IF ANY)NUMBER OF PARALLEL
SETS OF CONDUIT
AND CONDUCTORS.
RTU-NE-08
8KVA,5.9KVA,1.25KVA,3HP,480V3P4W
1" C,3#8awg,#8awg N, #10G(3)
NOTES:
1. LABEL SHALL BE DISPLAYED ON ALL SWITCHBOARDS, PANELBOARDS,
TRANSFER SWITCHES AND PULL BOXES (MULTIPLE VOLTAGES).
2. NAMEPLATE SHALL BE WHITE LETTERING ON BLACK BACKGROUND.
3. IF ONLY ONE VOLTAGE IS PRESENT, LABEL SHALL INDICATE ONLY THAT
RESPECTIVE VOLTAGE.
4"
VOLTAGE
480Y/277V
PHASE A BROWN
PHASE B ORANGE
PHASE C YELLOW
NEUTRAL GREY
C O
M M
ON
W EA LT
H
O F
P E
N N S Y L V
A N
I A
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
ENGINEERING
WNA ENGINEERING, INC.
WWW.WNAENGINEERING.COM
PITTSBURGH
412.208.1372
PORTERSVILLE
724.368.8133
PHILADELPHIA
215.885.5900
CONSULTING ENGINEERS
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
PROJECT NUMBER: 22-0320
ALL WORK ON THIS SHEET IS PART OF THE CONTRACT
02-ELECTRICAL, UNLESS OTHERWISE NOTED
/1
/2
:4
:4 A
M A u to d e s k D o c s
/2 -0
C a n ti n i M o s a ic s /2
-E -R
.r v t
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
ELECTRICAL DATA
SHEET
E-001
222012
PERMIT SET
05/11/2023
CITY OF PITTSBURGH
SCALE : NO SCALEE-001
EQUIPMENT LABEL1
FIRE ALARM SYMBOLS
WALL MOUNTED FIRE ALARM SYSTEM NOTIFICATION APPLIANCE. SUBSCRIPT 'WP', WHERE
USED, INDICATES WEATHERPROOF DEVICE. SUBSCRIPTS INDICATE TYPE AS FOLLOWS:
V: VISUAL (75 CANDELA (CD) UNO)
A: AUDIO
A/V: AUDIO/VISUAL (75 CANDELA (CD) UNO)
A/V
15CD
LIGHTING SYMBOLS
O
PP
DIMMER SWITCH, MOUNTED AT 44" A.F.F. VERIFY EXACT REQUIREMENTS WITH LIGHTING
FIXTURES. , MOUNTED AT 44" A.F.F. "A" INDICATES FIXTURE CONTROL, IF REQUIRED FOR
CLARIFICATION. VERIFY EXACT COLOR WITH ARCHITECT. IF CONTROLLING LED, PROVIDE
0-10V DIMMER. DIMMER MUST BE COMPATIBLE WITH FIXTURE TYPES.
Da
POWER/RELAY PACK. "A" INDICATES FIXTURE CONTROL, IF REQUIRED FOR CLARIFICATION.
OCCUPANCY SENSOR. LOCATE AND INSTALL IN ACCORDANCE WITH MANUFACTURES
REQUIREMENTS. REFER TO LIGHTING CONTROL DETAILS FOR ADDITIONAL INFORMATION.
EXIT SIGN. SHADED AREA INDICATES FACE. PROVIDE DIRECTIONAL CHEVRONS AS INDICATED.
LIGHTING FIXTURE. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
LIGHTING FIXTURE. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
THE SYMBOLS LISTS ARE
COMPREHENSIVE. NOT ALL SYMBOLS
MAY BE USED ON THIS PROJECT
DEMOLITION/EXISTING SYMBOLS
INDICATES EXISTING TO REMAINE
INDICATES EXISTING TO BE RELOCATEDER
INDICATES NEW LOCATION OF EXISTING TO BE RELOCATED EQUIPMENT/DEVICEEL
INDICATES EXISTING
INDICATES EXISTING TO BE REMOVED.X
DESCRIPTIONSYMBOL
C O
M M
ON
W EA LT
H
O F
P E
N N S Y L V
A N
I A
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
ENGINEERING
WNA ENGINEERING, INC.
WWW.WNAENGINEERING.COM
PITTSBURGH
412.208.1372
PORTERSVILLE
724.368.8133
PHILADELPHIA
215.885.5900
CONSULTING ENGINEERS
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
PROJECT NUMBER: 22-0320
ALL WORK ON THIS SHEET IS PART OF THE CONTRACT
02-ELECTRICAL, UNLESS OTHERWISE NOTED
/1
/2
:4
:4 A
M A u to d e s k D o c s
/2 -0
C a n ti n i M o s a ic s /2
-E -R
.r v t
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
ELECTRICAL DATA
SHEET
E-002
222012
PERMIT SET
05/11/2023
CITY OF PITTSBURGH
GENERAL ELECTRICAL DEMOLITION NOTES:
1. THE SCOPE OF DEMOLITION WORK IS TO REMOVE AND/OR RELOCATE
EXISTING LIGHTING FIXTURES AND RE-CIRCUIT EXISTING LIGHTING AS SHOWN
IN THE EXISTING BUILDING. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY
TO DETERMINE THE FULL SCOPE, EXTENT, NATURE AND MANNER OF
DEMOLITION REQUIRED.
2. ONLY WORKMEN SKILLED AND KNOWLEDGEABLE IN THEIR RESPECTIVE
TRADES SHALL BE EMPLOYED IN THE DEMOLITION OF ANY WORK.
3. COORDINATE FLOOR PLANS FOR LOCATIONS OF NEW OPENINGS IN EXISTING
WALLS.
4. PROVIDE DUST BARRIERS TO SEPARATE DEMOLITION AREAS FROM OCCUPIED
SPACES.
5. AREAS, SURFACES, AND FINISHES NOT AFFECTED BY THE WORK OF THIS
CONTRACT SHALL BE PROTECTED PRIOR TO COMMENCEMENT AND UNTIL
COMPLETION OF THE WORK.
6. CONTRACTOR SHALL TAKE SPECIAL CARE TO DEMOLISH ONLY THAT WORK
WHICH IS REQUIRED TO BE DEMOLISHED AND NOT TO DISTURB WORK
WHICH IS TO REMAIN. IF, IN THE COURSE OF DEMOLITION, CONTRACTOR
DESTROYS OR DISTURBS ANY WORK WHICH IS TO REMAIN, HE SHALL, AT HIS
OWN EXPENSE, REPAIR OR REPLACE SUCH WORK AS NECESSARY. PROVIDE
PROTECTIVE COVERING ON FLOORS AND WALLS AS REQUIRED ON DEBRIS
REMOVAL ROUTE.
7. ANY CUTS AND PENETRATIONS IN EXISTING WORK REQUIRED TO
ACCOMPLISH NEW WORK SHALL BE KEPT TO AN ABSOLUTE MINIMUM AND
SHALL BE DONE NEATLY AND WITHOUT DISTURBING ADJACENT WORK TO
REMAIN. RECEIVE ARCHITECTS'S APPROVAL PRIOR TO DOING ANY CUTTING
WHICH WILL AFFECT STRUCTURAL INTEGRITY.
8. ENTIRE AREA SHALL BE LEFT BROOM CLEAN.
9. THE CONTRACTOR SHALL CONSULT THE ARCHITECT BEFORE REMOVING ANY
WORK IF HE HAS ANY QUESTION REGARDING THE INTENT OF SUCH
REMOVAL.
10. CONTRACTOR SHALL REMOVE AND RELOCATE (FOR STORAGE) OR REMOVE
AND DISPOSE OF ALL DEMOLITION ITEMS AS DIRECTED BY OWNER.
7 8 9 10
N
C O
M M
ON
W EA LT
H
O F
P E
N N S Y L V
A N
I A
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
ENGINEERING
WNA ENGINEERING, INC.
WWW.WNAENGINEERING.COM
PITTSBURGH
412.208.1372
PORTERSVILLE
724.368.8133
PHILADELPHIA
215.885.5900
CONSULTING ENGINEERS
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
PROJECT NUMBER: 22-0320
ALL WORK ON THIS SHEET IS PART OF THE CONTRACT
02-ELECTRICAL, UNLESS OTHERWISE NOTED
/1
/2
:4
:4 A
M A u to d e s k D o c s
/2 -0
C a n ti n i M o s a ic s /2
-E -R
.r v t
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
FIRST FLOOR -
DEMOLITION PLAN
ED-101
222012
PERMIT SET
05/11/2023
CITY OF PITTSBURGH
KEYED ELECTRICAL DEMOLITION NOTES:
1. XXXX
2. XXXX
SCALE : 1/8" = 1'-0"ED-101
FIRST FLOOR - ELECTRICAL DEMOLITION PLAN1
O
PP
GENERAL ELECTRICAL LIGHTING NOTES:
1. ALL CABLE ABOVE CEILING SHALL BE PLENUM RATED.
2. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
3. ALL OPENINGS IN FIRE RATED WALLS, FLOOR AND PARTITIONS FOR
CONDUITS SHALL BE SEALED WITH FIRE RESISTANT FOAM OR UL APPROVED
"FIRE STOP" SYSTEM TO MAINTAIN THE FIRE RATING. COORDINATE ALL
RATED WALLS AND UL LISTING REQUIREMENTS WITH ARCHITECTURAL
DRAWING.
4. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF
THE NEC AND ANY LOCAL AUTHORITY HAVING JURISDICTION.
5. COORDINATE EXACT FINISH AND LOCATION OF ALL LIGHT FIXTURES WITH
OWNER.
6. THE INTENT OF THE ADDTIONAL LIGHTING FIXTURES
N
7 8 9 10
A A
A A
A A
A A
A A
A A
A A
A
A A
A A
A A
A A
A A
A A
A A
LP5
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
LP5 - 1
D
LP5 - 1
EXISTING EXIT SIGN TO REMAIN
(TYPICAL)
EXISTING DOWNLIGHT TO REMAIN
(TYPICAL)
CONCOURSE
LOBBY
UTILITY RM
MECH
TUNNEL
POWER PACK
NPP16-D-EFP
DIMMING
BLACK = 120V
ORANGE = 277V
CEILING SENSOR
LOW VOLTAGE
NCM-PDT-9/10-RJB
(QTY PER PLANS)
LOAD
N NH
BLACK/ORANGE
BLUE
RED
WHITE
GRAY (-)
VIOLET (+)
CAT 5E CAT 5E
ELECTRICAL CONTRACTOR TO CONNECT ALL DEVICES WITH
CAT 5E DATA CABLE IN A DAISY CHAIN, STARTING WITH THE
SYSTEM GATEWAY THEN TO NEXT NEAREST SYSTEM
BRIDGE AND SO ON.
ALL CAT 5E CABLE RUNS NEED TO BE CHECKED WITH A CAT
5E METER FOR PROPER TERMINATION OF RJ45 CONNECTORS.
TYPICAL nLIGHT NOTES:
1.
2.
THERE ARE TWO BAR CODE STICKERS ON EACH DEVICE.
ELECTRICAL CONTRACTOR SHALL PEEL ONE OFF AND PLACE
ON FLOOR PLAN WHERE DEVICE IS LOCATED OR CREATE
SPREADSHEET WITH DEVICE LOCATIONS AND BARCODE
STICKERS.
3.
PP
O
WALLPOD
NPODM-DX
ON/OFF
D
GENERAL IECC LIGHTING NOTES:
1. THE INTENT OF THE TYPE A FIXTURE IS TO HIGHLIGHT NEW ARTWORK THAT IS
BEING RELOCATED INTO THE TUNNEL SPACE. UNDER IECC 2018 SECTION
C405.3.2.2.1 - ADDITIONAL INTERIOR LIGHTING POWER - SECTION 2: FOR SPACES
IN WHICH LIGHTING IS SPECIFIED TO BE INSTALLED IN ADDITION TO THE GENERAL
LIGHTING FOR THE PURPOSE OF DECORATIVE APPEARANCE OR FOR
HIGHLIGHTING ART OR EXHIBITS, PROVIDED THAT THE ADDITIONAL LIGHTING
POWER SHALL BE NOT MORE THAN 0.9 W/FT2(9.7 W/M2) IN LOBBIES AND NOT
MORE THAN 0.75 W/FT2(8.1 W/M2) IN OTHER SPACES. THE NEW LIGHT FIXTURES
ARE A TOTAL OF 870W TO A 1227 FT2 SPACE, MAKING OUR ENERGY DENSITY 0.71
W/FT2.
C O
M M
ON
W EA LT
H
O F
P E
N N S Y L V
A N
I A
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
PROFESSIONAL
REGISTERED
ENGINEER
No. PE-045749-E
MARY E. LEWIS
ENGINEERING
WNA ENGINEERING, INC.
WWW.WNAENGINEERING.COM
PITTSBURGH
412.208.1372
PORTERSVILLE
724.368.8133
PHILADELPHIA
215.885.5900
CONSULTING ENGINEERS
LANDMARKS SGA PROJECT NO.
REVISIONS
NOTE: DO NOT SCALE FROM DRAWINGS.
VERIFY ALL DIMENSIONS ON SITE.
ISSUE DATE:
PROJECT NUMBER: 22-0320
ALL WORK ON THIS SHEET IS PART OF THE CONTRACT
02-ELECTRICAL, UNLESS OTHERWISE NOTED
/1
/2
:4
:4 A
M A u to d e s k D o c s
/2 -0
C a n ti n i M o s a ic s /2
-E -R
.r v t
CANTINI MOSAIC
PANELS DESIGN
PRT STEEL PLAZA STATION
500 ROSS STREET
PITTSBURGH, PA 15258
FIRST FLOOR -
LIGHTING PLAN
E-101
222012
PERMIT SET
05/11/2023
CITY OF PITTSBURGH
KEYED ELECTRICAL LIGHTING NOTES:
1. FURNISH AND INSTALL DIMMING CONTROLS FOR CORRIDOR SUSPENDED
LIGHT FIXTURES. COORDINATE EXACT LIGHTING CONTROL LOCATIONS WITH
OWNER PRIOR TO ROUGH-IN.
SCALE : 1/8" = 1'-0"E-101
FIRST FLOOR - ELECTRICAL LIGHTING PLAN1
SCALE : NO SCALEE-101
TYPICAL CEILING SENSOR WITH MANUAL DIMMING OVERRIDE2
GENERAL ELECTRICAL POWER NOTES:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF
THE NEC AND ANY LOCAL AUTHORITY HAVING JURISDICTION.
2. VERIFY EXACT LOCATION OF ALL DEVICES WITH OWNER PRIOR TO ROUGH-IN.
3. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL RECEPTACLE LOCATIONS
WITH FURNITURE AND EQUIPMENT LAYOUT, REFER TO ARCHITECTURAL
PLANS AND ELEVATIONS FOR ADDITIONAL INFORMATION. FIELD
CO…