2020 TAFB Electrical Standards.pdf

PDF 466 KB Posted

Attached to
Tinker AFB Multiple Award Construction Basic Ordering Agreement (MACB) Federal contract opportunity
Solicitation number
FA813721R0022
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page 1 of 26 Revised: August 2020

TAFB ELECTRICAL STANDARDS

Tinker Air Force Base, Oklahoma

August 2020

Highlighted text indicates revisions since the 2019 Edition

1. General:

1.1 References

(a) As a minimum, all electrical work performed on Tinker AFB shall conform to the latest edition of the following codes/standards, and all applicable UFCs, ETLs, and AFIs:

(1) NFPA 70, National Electrical Code (NEC)

(2) NFPA 70E, Standard for Electrical Safety in the Workplace

(3) NFPA 72, National Fire Alarm and Signaling Code

(4) NFPA 101, Life Safety Code

(5) NFPA 170, Standard for Fire Safety and Emergency Symbols

(6) NFPA 780, Standards for Installation of Lightning Protection Systems

(7) IEEE C2, National Electric Safety Code (NESC)

(8) UFC 3-260-01, Airfield and Heliport Planning and Design

(9) UFC 3-501-01, Electrical Engineering

(10) UFC 3-520-01, Interior Electrical Systems

(11) UFC 3-530-01, Interior and Exterior Lighting and Controls

(12) UFC 3-535-01, Visual Air Navigation Facilities

(13) UFC 3-540-01, Engine-Driven Generator Systems for Backup Power Applications

(14) UFC 3-550-01, Exterior Electrical Power Distribution

(15) UFC 3-560-01, Electrical Safety

(16) UFC 3-575-01, Lightning and Static Electricity Protection Systems

(17) UFC 3-580-01, Telecommunications Building Cabling Systems Planning and Design

(18) UFC 3-600-01, Fire Protection Engineering for Facilities

(19) UFC 3-601-02, Operation and Maintenance: Inspection, Testing and Maintenance of

Fire Protection Systems

(20) UFC 4-010-01, DOD Antiterrorism Standards for Buildings

(21) UFC 4-011-06, Cyber Security for Facility-Related Control Systems

(22) UFC 4-021-01, Design and O&M: Mass Notification Systems with Change 1

(23) UFC 4-211-01, Aircraft Maintenance Hangars

(24) ANSIA/TIA/EIA 568-C, Series of Telecommunication Standards

(25) ANSIA/TIA/EIA 569-B, Commercial Building Telecommunications Cabling Standard

(26) ANSIA/TIA/EIA 607, Generic Telecommunications Grounding and Bonding(Earthing) for Customer Premises

(27) NEIS, National Electrical Installation Standards

• NECA 1, Good Workmanship in Electrical Contracting

• NEC A 90, Commissioning Building Electrical Systems

• NECA 100, Symbols for Electrical Construction Drawings (ANSI)

• NECA 101, Installing Steel Conduits (Rigid, IMC, EMT)

• NECA/NEMA 105, Standard for Installing Metal Cable Tray Systems (ANSI)

• NECA 111, Installing Nonmetallic Raceways (RNC, ENT, LFNC)

• NECA/NACMA 120, Installing Armored Cable (AC) and Metal-Clad Cable (MC)

• NECA 169, Standard for Installing and Maintaining Arc-Fault Circuit Interrupters

Page 2 of 26 Revised: August 2020

• NECA 200, Temporary Electric Power

• NECA 202, Installing Industrial Heat Tracing Systems

• NECA 230, Electric Motors and Motor Controllers

• NECA/FOA 301, Installing and Testing Fiber Optic Cables

• NECA 305, Standard for Fire Alarm System Job Practices

• NECA 331, Standard for Building and Service Entrance Grounding and Bonding

• NECA 400, Installing and Maintaining Switchboards

• NECA 402, Installing and Maintaining Motor Control Centers

• NECA/EGSA 404, Installing Generator Sets

• NECA 407, Installing Panelboards

• NECA 408, Installing and Maintaining Busways

• NECA 409, Installing and Maintaining Dry-Type Transformers

• NECA 410, Installing and Maintaining Liquid-Filled Transformers

• NECA 411, Standard for Installing and Maintaining Uninterruptible Power

Supplies (UPS) (ANSI)

• NECA 420, Standard for Fuse Applications (ANSI)

• NECA 430, Standard for Installing Medium-Voltage Metal-Clad Switchgear

• NECA/IESNA 500, Installing Indoor Commercial Lighting Systems

• NECA/IESNA 501, Installing Exterior Lighting Systems

• NECA/IESNA 502, Installing Industrial Lighting Systems

• NECA 505, Standard for Installing and Maintaining High Mast, Roadway and Area

Lighting

• NECA/BICSI 568, Installing Commercial Building Telecommunications Cabling

• NECA/MACSCB 600, Installing and Maintaining Medium-Voltage Cable

• NECA/NEMA 605, Installing Underground Nonmetallic Utility Duct

• NECA 607, Standard for Telecommunications Bonding and Grounding Planning and Installation Methods for Commercial Buildings

• NECA 700, Standard for Installing Overcurrent Protection to Achieve Selective

Coordination

1.2 Design

(a) As a minimum, all electrical design shall conform to the latest edition of the above codes/standards.

(b) To the extent possible, Unified Facility Guide Specifications (UFGS) and standard detail shall be utilized in the design. All specifications and general notes shall have the non-applicable parts edited.

(c) Existing as-built drawings (if available) may be used as guidelines, but “information must be verified by field investigation”. The Designer shall be responsible for the verification of all dimensions, measurements, and location of existing facilities, utilities, equipment and other existing conditions that may affect the design.

(d) The following items shall be taken into consideration and included as part of the design analysis:

(1) Exterior – Primary circuit availability and location.

(2) Exterior - Primary circuit loading (generally, existing primary loops at TAFB are designed for loads of 400A or less. Future loops may be designed for higher capacities as long as analysis shows that existing switchgear/substations can support the higher requirement).

(3) Existing equipment age and condition

Page 3 of 26 Revised: August 2020

(4) Transformer/panelboard/switchgear loading (existing and future).

(5) Non-linear loads (Fluorescent lighting, computers, variable frequency drives, etc.)

(6) Energy Analysis

(e) All new building wiring systems shall consider using 480/277V unless uneconomical to accomplish. Designer shall make recommendations of building voltages at the design analysis phase of each project.

(f) All new electrical transformers and distribution equipment shall have a Fault Current Calculations and Arc Flash analysis performed IAW NFPA 70E Annex “D”. Calculations shall be performed using “Easy Power” software and submitted to 72ABW/CENMP for review and approval prior to equipment installation.

(1) Contractor shall confirm the Easy Power Software Version requirement with Contracting

Officer at the beginning of the project.

(2) All Data fields in the software shall be filled out.

(3) Available Fault Current data shall be provided to the designer by 72ABW/CENMP upon request, if available.

(4) Complex projects shall be provided with separate drawing sets for One-Line Information and Fault Current / Arc Flash Data.

(5) Design/Build Projects

i. Coordination Study, Fault Current Calculations and Arc Flash Analysis shall be included no later than the 95% design submission to the Gov’t for review and approval of Design/Build Projects.

(6) A&E Design only projects

i. Fault Current calculations One-Line must be submitted using Easy Power software with the assumption clearly stated that all upstream overcurrent protection devices are in proper working condition and have been maintained and certified. For systems which no certification of the maintenance can be produced, the requirement to perform the maintenance and certification must be included in the design package for the contractor to perform this work as part of the project.

ii. The .dez file shall be included in the construction contractor’s package to complete the Fault Current calculations and Arc Flash Analsis based in the electrical distribution equipment being provided.

iii. For construction only projects, the Easy Power Model One-Line drawing shall be provided by the A&E designer and completed using Easy Power software by the construction contractor based on the approved electrical equipment being provided.

(7) Use the 0.5sec maximum arc time as a conservative, but more realistic, value when doing arc flash calculations for 208V systems which are fed from step down transformers less than 125KVA

(8) A copy of the Easy Power Model (.dez) and One-Line Drawings shall be submitted with other material submittals prior to Construction Start.

(g) Arc Flash labeling shall be installed on all new installed electrical transformers, disconnects and distribution equipment.

(1) All Arc Flash Labeling shall be “Easy Power” containing the following information.

i. Company Name

ii. Date of Arc Flash Analysis

iii. Equipment Identification

iv. Required PPE

v. Arc Flash Hazard Risk Category

vi. Incident Energy (Cal/cm2)

Page 4 of 26 Revised: August 2020

vii. Shock Protection

viii. Limited Approach Boundary

ix. Restricted Approach Boundary

1.3 Installation

(a) As a minimum, all electrical installations shall conform to the latest edition of the above codes/standards.

(b) NEIS shall be used for quality and reliability standards for construction. This criteria will be used to define acceptable industry practices for installations.

(c) Only journeymen electricians (state licensed or minimum 12,000 hours verifiable experience) or registered apprentices under the direct supervision of journeymen will be permitted to install, alter, or repair electrical systems.

(d) Material and equipment shall be a standard product of a manufacturer regularly engaged in the manufacture of the product and shall essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening. All materials in the same category shall be by a single manufacturer. Equipment from discontinued product lines shall not be accepted in new installation.

(e) All conductors shall be color-coded at panelboards, switchboard, terminations, junction boxes, manholes, hand holes, etc. Factory-applied color-impregnated insulation is required for all sizes unless waived by 72ABW/CENMP or 76 MXSG/MXDEJ. Equipment grounding conductors (EGC) shall have factory-applied color-impregnated insulation for all sizes. A green equipment-grounding conductor shall be installed with all branch circuits.

Circuit conductors shall be color coded as follows:

(1) All Configurations: Equipment Grounding Conductor, Green. (Exception: Where an isolated ground is required the isolated ground shall be identified as green with a yellow stripe.)

(2) 120V, 2-wire circuit: Grounded conductor (neutral), White; Ungrounded leg, Black.

(3) 240/120V, 1-phase, 3-wire circuit: Grounded conductor (neutral), White; Phase A, Black; Phase B, Red.

(4) 208Y/120V, 3-phase, 4-wire circuit: Grounded conductor (neutral), White; Phase A, Black; Phase B, Red; Phase C, Blue.

(5) 208V, 3-Phase, 3-wire circuit: Phase A, Black; Phase B, Red; Phase C, Blue.

(6) 480Y/277V, 3-phase, 4-wire circuit: Grounded conductor (neutral), Gray; Phase A, Brown; Phase B, Orange; Phase C, Yellow.

(7) 480V, 3-phase, 3-wire circuit: Phase A, Brown; Phase B, Orange; Phase C, Yellow.

(f) All new floor mounted electrical equipment installed in damp or wet locations shall be installed on a housekeeping pad a minimum of 3 1/2” A.F.F. Any exposed edges shall be ¾” chamfered. Electrical Equipment installed in dry areas, such as Electrical Vaults and Comm.

rooms, does not require a housekeeping pad.

1.4 Metering

1.4.1 Digital Metering

(a) Advanced Digital Metering (ADM) shall be installed in each switchboard or switchboard section (for double ended applications) for billing and energy monitoring & reduction purposes.

Advanced meters are electronic meters that have the capability to measure and record interval data and communicate that data to an Advanced Metering System (AMS).

Page 5 of 26 Revised: August 2020

(b) Monitors may also be remotely mounted between 72” and 80”Above Finished Floor (ABF).

ADM shall conform to Unified Facilities Guide Specification (UFGS) 26 27 13.10 30, except numbered terminal wiring sequence and case size may be the manufacturer’s standard.

(c) All setup parameters required by the electronic monitor shall be stored in non-volatile memory and retained in the event of a control power interruption. Any battery or other device used to provide non-volatile memory shall be user serviceable from the front of the monitor and servicing shall not require removing the monitor from the gear in which it is mounted.

(d) The ADM monitor shall maintain in non-volatile memory maximum and minimum values for each of the instantaneous values reported as well as the time and date that the minimum or maximum was set.

(e) The ADM monitor shall have the ability to communicate information to a remote data collection system.

(1) TAFB utilizes Itron MV-90xi as its (AMS) system though the CE industrial controls network. All ADM shall be compatible with MV-90xi.

(f) All new ADM shall be a Schneider ION 8650 series or next generation equivalent

(g) All necessary instrument transformers (CTs/PTs) shall be provided in the switchgear.

(h) The monitor shall be listed according to UL 508, and have an over-current withstand rating of 500 amps for 1 second.

(i) The monitor shall provide true RMS metered values accurate for distorted, non-sinusoidal wave-shapes beyond the 30th harmonic (fundamental of 60 hertz).

(j) The monitor shall be accurate to ± 0.25% of reading ± 0.05% of full scale for voltage and current metering, and ±1.0% for all power and energy functions. The accuracy shall be maintained for both light and full loads. No annual re-calibration by users shall be required to maintain these accuracy’s.

(k) Voltage and current for all phases shall be sampled simultaneously to assure high accuracy in conditions of low power factor or large waveform distortions (harmonics).

(l) The monitor shall be equipped with an integral, continuous duty, long-life display to provide local access to the following metered quantities as well as the minimum and maximum value since last reset of each quantity:

(1) Current (RMS), per phase and neutral

(2) Voltage, phase-to-phase and phase-to-neutral

(3) Real power, per phase and 3-phase total

(4) Reactive power, per phase and 3-phase total

(5) Apparent power, per phase and 3-phase total

(6) Power factor, per phase and 3-phase total

(7) Frequency

(8) Demand current, per phase and three phase average

(9) Demand real power, three phase

(10) Demand apparent power, three phase

(11) Accumulated Energy, (MWH and MVARH)

(12) THD, current and voltage, per phase

(13) K-factor, current, per phase

(m) The following demand readings shall be included as local display access and also reported by the monitoring system:

(1) Average demand current, per phase

(2) Peak demand current, per phase

(3) Average demand for real power, reactive power, and apparent power

(4) Predicted demand for real power, reactive power, and apparent power

Page 6 of 26 Revised: August 2020

(5) Peak demand for real power, reactive power, and apparent power

(6) The default demand calculations method shall be 15-minute sliding window.

(n) Where ADM is to be connected to the VLAN, contractor shall install conduit and CAT 6 cabling to the nearest Comm Rack as specified in the project SOW.

(1) Cable test result report shall be submitted to 72ABW SC with other closeout documents.

(o) ADM to be installed outdoors may use a wireless radio transceiver in lieu of a wired connection, if LAN connection is not available.

(1) The wireless radio transceiver shall be a Freewave FRG2-PE or next generation equivalent, with accompanying radio components, coaxial cable, antenna, power supply, etc.

(2) The radio components must be contained within a weather resistant enclosure, ( i.e. inside the switchgear or other properly classified enclosure).

(p) IP addresses, Ethernet gateways, and subnet masks will be provided to the installing contractor for the ADM and accompanying wireless radio transceiver, if required, by the 72ABW/CENMP Energy Team.

(q) A standard local digital meter (Volt, Amp, and Demand Amp) shall be installed on circuit breakers 600 amp and larger to include all main service switchgear and secondary switchgear branch circuits.

(1) The digital meter shall maintain in non-volatile memory maximum and minimum values for each of the values as well as the time and date that the minimum or maximum was set.

(r) Commissioning

(1) Installation contractor shall be required to provide documentation verifying proper meter calibration and verifying proper operation/readings for all digital metering during commissioning of the equipment.

(2) Installation contractor shall be required to provide documentation verifying that the ADM can establish good communications remotely with the MV-90xi AMS system, either through a wired or wireless connection.

2. Exterior Electrical Note: Any project performed by OG&E or their sub-contractors shall install all Medium

Voltage (MV) systems and equipment IAW OG&E specifications.

All other MV systems installed on TAFB shall comply with the following requirements.

2.1 General

(a) All exterior pad mounted equipment shall be installed in accordance with (IAW) the Base Facility Standard for Architectural Compatibility.

(b) Medium Voltage Transformer Pads shall be installed by the contractor per OG&E supplied specifications.

(1) Forms and Reinforcement shall be inspected and approved by OG&E prior to pouring concrete.

(c) All exterior pad mounted equipment shall have permanently affixed identification labels.

Labels shall be weather resistant, engraved, Laminated Plastic. Labels shall indicate equipment identification, rating, and circuit designation. Information for new equipment identification and circuit designation will be provided by 72ABW/CENMP.

(d) All exterior underground cables shall have permanent identification tag installed at each manhole, hand hole, pull box, or termination. Labels shall be weather resistant, engraved, metal or Laminated Plastic. Labels shall indicate at a minimum the circuit designation and To/From information. Information for circuit designation shall be provided by72ABW/CENMP.

Page 7 of 26 Revised: August 2020

(e) Disconnects for mechanical and other equipment on the outside of buildings shall be served from the rear (through the wall feeder) or bottom (below grade feeder).

(f) All bussing in electrical equipment shall be copper.

(g) Utility Lines and Structures

(1) Place utilities underground and screen above-ground equipment to minimize their visual impact.

(2) Exposed conduits, cables, and wires are prohibited.

(3) Construct underground utility system components as elements of any new or renovated facilities. When this is unfeasible, locate screened equipment on the least visible side of the building.

2.2 Underground Electrical Distribution

2.2.1 Concrete Encased Duct Bank

(a) Concrete encased conduits shall have minimum spacing between conduits as specified by NFPA 70 and UFC 3-550-01 with a minimum of 3 inches of concrete protecting them on top, bottom, and sides.

(b) The top of the concrete encasement shall be a minimum of 30” below finished grade.

(c) All concrete encased duct banks shall have a 1/0 bare copper counterpoise system installed immediately above the duct bank (6” or less) and continuous the length of the duct bank.

Counterpoise shall be connected to a ¾” x 10’ grounding electrode in each manhole and at each transformer and switching-station installation (including primary substations). Where duct bank terminates at a pole riser, counterpoise shall be connected to a ¾” x 10’ grounding electrode and bonded to the pole grounding system.

2.2.2 Direct Buried Conduit

(a) For 600V and below, where direct buried service or feeder conduit is specified in the project documents, direct buried conduit shall be Schedule-80 PVC conduit a minimum of 30” below grade. Direct buried conduit supplying individual branch circuits, such as exterior lighting or power receptacles, may be Schedule 40 PVC conduit installed at a minimum depth of 24” below grade. All conduits shall be encased with sand and compacted prior to backfilling with other materials.

(b) When PVC is used underground, all conduit which extends from excavations to above finished grade shall be galvanized rigid conduit starting from minimum depth as specified and include the 90 degree elbow. All metallic conduit which contacts the earth shall have a Factory Applied PVC Coating. PVC tape may only be used to protect threaded areas and where adapting to PVC.

(1) Exception: Fiberglass conduit may be used in lieu of PVC Coated GRC with

72ABW/CENMP approval for real property electrical systems or 76 MXSG/MXDEJ approval for non-real property electrical systems.

(c) HDPE conduit may be utilized for approved Boring applications with prior written approval by 72ABW/CENMP for real property electrical systems or 76 MXSG/MXDEJ for non-real property electrical systems.

2.2.3 All utility road and driveway crossings shall be bored and sleeved with single schedule 80 PVC or ¼”-wall steel sleeve. Roadways and driveways shall not be crossed by open cut unless approved. Wherever boring is impractical, street crossings shall be limited to three (3) days maximum (including trenching, compaction, and replacement of existing pavements).

Contractor shall provide steel matting sufficient to carry the traffic load of the excavated area.

Page 8 of 26 Revised: August 2020

2.2.4 All underground electrical and communication installations (conduit, duct bank, etc.) shall be identified using marking tape. Tape shall have the following characteristics:

(a) 5-mil plastic

(b) Brightly colored (electric – red; communication – orange)

(c) Minimum of 3 inches in width

(d) Suitably inscribed at not more than 10 feet on centers

(e) Continuous metallic backing and a corrosion resistant 1-mil metallic foil core to permit easy location of duct line.

(f) Tape shall be placed 12-inches below finished grade.

2.3 Medium Voltage Distribution

2.3.1 General

(a) Install distribution conductors in underground ducts in lieu of direct burial and/or overhead.

(b) Air vacuum type switches are required in lieu of oil insulated. SF6 switches may be used in areas where equipment size is a concern with 72ABW/CENMP approval.

(c) All primary loop switches shall be equipped with Directional Fault Indication.

2.3.2 Primary Loop Feeders

(a) Medium voltage cable shall be (minimum) 15kV-500 kcmil copper, XLP/XLPE or EPR, with 100/133% insulation, wire shield or separator tape, and an ozone/sunlight resistant PVC jacket. Concentric neutral cable shall not be used.

(b) Grounding conductor shall be (minimum) 600V- #4/0 AWG copper.

(c) Conductors shall be protected by a (minimum) 5-inch diameter concrete-encased

Schedule-40.

(d) Cables shall be routed and racked inside manhole to allow the longest possible length of spare cable in each manhole possible (minimum of 1 full loop around the interior of the manhole).

2.3.3 Primary Radial Feeders

(a) Medium voltage cable shall be (minimum) 15kV- #2 AWG copper, XLP/XLPE or EPR, with 100/133% insulation, wire shield, separator tape, and an ozone/sunlight resistant PVC jacket.

Concentric neutral cable shall not be used.

(b) Grounding conductor shall be (minimum) 600V- #2 AWG.

(c) Conductors shall be protected by a minimum 5” diameter concrete-encased Schedule-40.

(d) Cables shall be routed and racked inside manhole to allow the longest possible length of spare cable in each manhole possible.

2.3.4 Medium Voltage Branch Circuits Installed Inside Buildings shall meet the following requirements.

(a) All Conductors shall be Class B compressed strand copper.

(b) Conductor shield shall be 16 mils minimum extruded semi-conducting, thermosetting compound.

(c) Insulation shall be 220 mils average Extruded Ethylene Propylene Rubber

(d) Insulation shield shall be 32mil minimum and 60 mils maximum extruded semi-conducting, thermosetting compound.

(e) Metallic Shield shall be 5 mil bare copper tape, helically applied with minimum 25% overlap.

Page 9 of 26 Revised: August 2020

(f) Galvanized Steel Interlocked Armor with overall 85 mil minimum average thick PVC Jacket.

2.3.5 Medium Voltage Cable Terminations and Splices

(a) Terminations and splices shall be of the preformed type only, tape type are not acceptable.

(b) All cable splices and terminations shall be installed in accordance with the manufacturer’s specifications.

2.3.6 Medium Voltage Cable Testing

(a) Testing requirements shall be coordinated during design of each project.

(b) Approved testing methods are Hi-Pot and Very Low Frequency (VLF) High-Voltage testing.

(c) All new cable being hi-pot tested shall be in accordance with manufacturer’s recommendations, but not to exceed 3-times the cable voltage rating. Testing shall be performed in accordance with the methodology described in the applicable IEEE, ICEA, or AEIC standards.

(d) Existing cable being reused, or spliced into, shall be hi-pot tested at its rated insulation voltage. Testing shall be performed in accordance with the methodology described in the applicable IEEE, ICEA, or AEIC standards.

(e) Cable testing performed using VLF procedures shall be in accordance with IEEE Std. 400.2.

(f) All cable testing must be coordinated with the 72ABW/CE electric shop in advance.

(g) Cable test data and results shall be documented and signed by both the testing technician and the job supervisor. Copies of the test data/certification/results shall be submitted to the 72ABW/CE for review and approval.

(h) For new construction, the recorded test data must be submitted to and approved by the Contracting Officer.

2.4 Low Voltage Distribution

(a) Conductors shall be 600V-rated copper, with thermoplastic insulation (unless specified otherwise on the design plans).

(b) Conductors to be installed in wet locations must be UL listed for the application.

(c) Conductors shall be sized as appropriate for the application.

(d) New Feeder conductors shall be installed without splices.

(e) Existing Feeder Conductors must be replaced in full when electrical distribution equipment and panels are required to be replaced or relocated.

Exception: Splicing of feeder conductors may be performed on a case by case basis with prior written approval at the design phase of the project by 72ABW/CENMP for real property electrical systems or 76 MXSG/MXDEJ for non-real property electrical systems.

2.5 Transformers

(a) New building transformers shall be either unit substation or fully enclosed pad mounted (in lieu of pole mounted).

(b) Unit Substation: Based on existing site conditions and availability of medium-voltage feeders, transformers shall be either:

(1) Radial type fed with integral single, metal-enclosed, fused, load-interrupter switch.

(2) Loop-fed type with integral dual, metal-enclosed, fused, load-interrupter switches.

(3) Incoming section shall include surge arrestors.

(4) Outgoing sections shall be as specified in the project definition.

(5) Gear shall have copper bussing and windings.

Page 10 of 26 Revised: August 2020

(6) All Unit Substations shall be equipped with forced fan cooling, temperature monitoring with local alarm, and remote alarm capability. Power for cooling fans shall be integrally derived from the Unit Substation secondary power.

(c) Pad-Mounted: Pad mounted transformers shall meet the following criteria.

(1) Transformers shall be loop-feed type.

(2) Transformers shall be dead front type with separable load break connectors, surge arrestors, and parking bushings.

(3) Transformers shall have load break switches and primary fuses mounted inside the enclosure. Transformer fusing shall be oil-immersed, bayonet type, overload fuses in series with partial range current-limiting fuses. Fuses shall be interlocked with primary load break switches.

(4) Transformers shall have copper windings.

(5) Transformers shall have, as a minimum, four (4) 2.5% taps (2+, 2- nominal voltage).

(d) Each transformer shall be fed from a dedicated disconnect switch with overcurrent protection. The switch shall be located in the same general area as the equipment being served.

(e) Transformer primary feeders shall not be t-spliced into existing feeders in manholes or hand holes.

(f) The main primary feeder (12.47KV and larger) shall be concrete encased in underground duct bank.

(g) Transformer output voltage shall be verified at commissioning of system and load taps adjusted to provide voltage +/- 2.5% of nominal.

(h) Oil filled transformers shall utilize Mineral Insulating Oil per ASTM D3487-00 and shall be equipped with relief valves and, if pad mounted, a means of sampling the oil.

(i) Oil filled transformer installations shall comply with IEEE 979 regarding fire protection. Oil filled transformers may be physically separated from building surfaces or other oil filled transformers or may be separated by appropriate fire rated barriers. Space limitations may dictate the method of fire protection employed.

(j) Field-testing, pre-energizing, or manufacturer’s field service report shall be required unless specifically stated in project definition.

2.6 Auxiliary Power/Generators

(a) Emergency generators shall only be installed for facilities authorized for emergency power by AFCEC as required by UFC 3-540-01, ETL 13-4 and AFI 32-1062 paragraph 3. No Emergency generator shall be installed on TAFB without prior written approval from

AFCEC.

(b) The following information shall be submitted to 72ABW/CENMP for approval of the following criteria prior to ordering or installing any generator on TAFB.

(1) A justification letter, signed by the Commanding Officer of the submitting group, stating the applicable criteria which qualify the system to be supported by auxiliary power as listed in AFI 32-1062 paragraph 3. This justification letter will be needed to facilitate the required formal request for approval to AFCEC.

(2) All generators shall comply with the requirements contained in AFI 32-1062 and UFC 3- 540-01.

(3) In addition, all generators shall be equipped with the following.

i. Weather protective and sound attenuated enclosure.

ii. Engine Block Heater with Thermostatic control.

iii. In-Line Fuel Heater with Thermostatic control.

Page 11 of 26 Revised: August 2020

(4) A design analysis shall be performed prior to the installation of any generator demonstrating sizing compliance with AFI 32-1062, whether new or replacement.

(5) Generator Engines must be in compliance with all applicable regulations and permits (40 CFR 63, Subpart ZZZZ, 40 CFR 60, Subpart IIII, Title V Permit, etc.).

(6) Generator Engines shall be equipped with a Non-Resettable Runtime Hour Meter.

(7) Environmental approval of the engine emission must be received prior to ordering.

i. Submittal approval by 72ABW/CEIE shall contain the following.

a. Engine Manufacturer/Make/Model/Year

b. Engine Full Load Rating (not generator output)

c. Engine Specific EPA Emissions Certification Data

(8) Fuel storage tanks shall be double wall construction.

(9) Integral Fuel Storage Tank shall provide 24 hours of service, based on engine maximum load consumption.

(10) The contractor is responsible to provide adequate fuel to perform the manufacturer’s commissioning, Gov’t acceptance requirements, and shall turn over the generator to the Gov’t with a full tank of fuel.

(c) Static Grounding of fuel tank shall comply with NFPA 30 and UFC 3-460-03 Operation and Maintenance: Maintenance of Petroleum Systems paragraph 9.5.

(d) The emergency generator one-line diagram shall be posted at the generator location.

(1) The One Line Diagram shall contain the following information.

i.Generator Model#, Serial#, Voltage, and Size (KVA & KW), ii.Transfer Switch Size (KVA & KW), Voltage Rating, Number of Poles, Open or Closed

Transition, Location of Transfer Switch (Bldg. & Room #), if not mounted locally at the generator.

iii.Normal Power Source (Bldg. #, Room #, Panel Name), Circuit Number and Breaker Size iv.Emergency Panel Identification, Location (Bldg. & Room #), if not mounted locally at the generator.

v.Conductor Sizes (between Normal Power, Generator, Transfer Switch and Panels)

(e) Provide combination automatic transfer switches with integral manual bypass. All transfer switches shall be 4-pole with switched neutral for each permanent generator installation.

(f) Emergency generator installations shall be placed in existing equipment yards or provided with suitable enclosure (fenced yard) to hide from public view. Where suitable enclosure cannot be provided, generators shall be factory painted a base standard color as determined by 72ABW/CENMP Architects which may not be a manufacturer’s standard color.

(g) Provide non-fused disconnect and 4-pole three-way (manual transfer) switches on outside of facility for portable generator connection when authorized by AFI 32-1062 and with prior written 72ABW/CENMP approval.

2.7 Exterior Lighting – Parking Lot, Roadway, Fitness Trails, and Walking Paths

(a) Exterior lighting is a system that has direct and indirect impacts on the visual qualities of the base. During the day the fixtures and poles are visible. At night the light becomes dominant to signify safety and security and to enhance the visual character of the base. The use of consistent lighting components and the reduction of overhead utilities will help unify the base appearance.

(b) Keep mounting heights low to Control spillover light near residential areas. Any lighting fixtures mounted over 30 feet high require special review by 72ABW/CENMP.

(c) Use only aluminum or steel poles, taking into consideration the economics and aesthetics.

Page 12 of 26 Revised: August 2020

(d) All power and light poles, steel support structures and their foundations, shall be designed for NESC Heavy Loading District conditions and 100 mph wind loads on bare structure face.

(e) All parking/roadway lighting fixtures shall be supplied with Light Emitting Diode (LED) fixtures unless a written waiver from 72ABW/CENMP is obtained.

(1) LED Fixtures shall comply with current UFC 3-530-01 requirements.

(2) Color temperature of LED Exterior Lighting Fixtures shall be 4000K.

(f) Photoelectric controls with over-ride astronomical timers shall be used on all exterior lighting for energy conservation, unless specifically deleted in project requirements (such as for security lighting).

(1) All exterior building fixtures providing security illumination and at personnel entrances shall be equipped with integral motion sensor for 50%/100% illumination control for energy conservation.

(g) Where a grounding electrode is specified to be installed at light poles, the connection of the bonding conductor at the grounding electrode, and at the concrete encased reinforcement of the base, shall be either exothermic weld process, or irreversible compression connector listed for the purpose. Mechanical lugs or connections shall not be allowed.

(h) A minimum of 100 hours of “Burn-in time” shall be performed before acceptance and final inspection.

3. Interior Electrical:

3.1 General

3.1.1 Riser and one-line diagrams shall show vertical and electrical relationships. Riser shall include voltage, amperage, and short circuit interrupting capacity at each transformer, switchboard, panelboard, and motor control center. Devices shall also indicate the room location they are installed.

3.1.2 A framed One-Line Drawing shall be posted by the contractor in the Main Building Service room and/or any distribution switchgear room where new electrical equipment is installed or modifications are made.

3.1.3 All new electrical equipment shall be flush mounted except where noted otherwise on the design plans.

3.1.4 Grounding Requirements

(a) Provide ¼” thick x 2” tall grounding bus bar in all electrical rooms/vaults for interconnection of panels, transformers, etc. to the main building grounding electrode system.

(b) All grounding electrodes shall be copper clad with a minimum size of ¾” diameter x 10’ long.

(c) The Main Building Grounding Electrode Conductor (GEC) for new construction, and GEC for all switchgear associated with electrical vaults renovations, shall be identified with a military grade heat shrinkable Tyco TMS-SCE type wire identification sleeve for testing

IAW AFI 32-1065.

(1) Where the GEC is concealed inside of a switchgear compartment and not readily accessible from the exterior, a permanent label shall be affixed to the compartment door where the GEC is terminated.

Page 13 of 26 Revised: August 2020

3.2 Interior Wiring System

3.2.1 General

(a) Each branch circuit shall be installed with a dedicated neutral conductor, if a neutral conductor is required.

(b) Junction box covers shall be clearly identified with the following information.

(1) Panelboard from which the power originates.

(2) Panelboard Circuit numbers

(3) Voltage present within the junction box

(c) All wiring devices (receptacles, switches, etc.) shall have a minimum rating of 20 amps.

(d) All wiring device cover plates shall be clearly identified with a Brady Label Maker, or equal, printer ¼” tall, black characters on white or clear tape label, containing the following information.

(1) Panelboard from which the power originates.

(2) Panelboard Circuit number(s).

(e) PlugTail type Receptacles are not allowed on TAFB.

(f) Combination receptacle with USB charger are not allowed on TAFB.

3.2.2 Conduit

(a) All wiring for power, fire alarm, and controls shall be installed in metallic raceway.

Wiremold is a suitable metallic raceway for interior installations where surface mounting in finished spaces is required.

(b) Indoor medium-voltage (primary) wiring shall be in appropriately marked galvanized rigid metal conduit or cable tray.

(c) Secondary voltage wiring may be in galvanized rigid metal conduit, rigid aluminum conduit, or Electrical Metallic Tubing (EMT). Electrical Non-metallic Tubing (ENT) shall not be used.

(d) All metallic conduit fittings shall be Compression Type. No Set Screw fittings are allowed to be installed on TAFB.

(e) Flexible metal conduit (FMC) shall only be used for equipment connections (appliances, luminaries), and to fish into existing walls. FMC shall not be used for general wiring applications.

(f) Equipment that requires flexibility at connections, to include but not limited to motors and transformers, shall utilize liquid-tight flexible metal conduit (LFMC). LFMC used outdoors shall be listed and identified on the outer shield as “sun light resistant” or similar verbiage.

(g) When PVC is used underground, all conduit which extends from excavations above finished grade shall be galvanized rigid conduit, starting from minimum depth as specified and include the 90 degree elbow. All metallic conduit which contacts the earth shall have a Factory Applied PVC Coating.

(1) PVC tape may only be used to protect threaded areas and where adapting to PVC.

(2) Exception: Fiberglass conduit and 90 degree elbows may be used in lieu of PVC Coated

GRC with prior written approval from 72ABW/CENMP for real property electrical systems or 76 MXSG/MXDEJ for non-real property electrical systems.

(h) No metal-clad cable, (Type MC), shall be permitted.

(1) Exception: Metal Clad (MC) cable shall be allowed for Flexible Light Fixture Whips whether field installed or provided by the manufacturer with new luminaires.

(2) Exceptions must be approved by 72ABW/CENMP for real property electrical systems or

76 MXSG/MXDEJ for non-real property electrical systems.

Page 14 of 26 Revised: August 2020

(i) Raceways shall not be supported by suspended ceiling or suspended ceiling support wires.

Only wires installed and approved per the NEC shall be permitted for supporting raceway.

(j) All raceways shall be concealed above ceiling, under floor, or in walls, except where noted on the design plans. No exposed raceways shall be permitted on exterior building surfaces without a Written Waiver of these requirements by 72ABW/CENMP.

(k) Where possible, raceways to roof mounted equipment shall be routed beneath the roof structure to a penetration immediately adjacent to the equipment.

(l) Exposed conduit on exterior of buildings and on roofs, where approved, shall be galvanized rigid conduit or rigid aluminum conduit. Exposed conduit on exterior walls shall be painted to match the building colors.

(m) All raceway penetrations through established fire barriers shall be sealed with an approved fire stopping material.

(n) All unused conduit in renovated areas shall be removed to the source. Exception: Conduit installed in concrete or masonry walls and underground may be abandoned in place with 72ABW/CENMP approval.

(o) Factory expansion fittings are required for conduit, cable tray, and bus duct when crossing building expansion joints or changes in temperature of greater than 25 degrees F from one area to the other. LTFMC may be used between Bus Duct tap boxes with prior design submittal review and written approval by 72ABW/CENMP for real property electrical systems or 76 MXSG/MXDEJ for non-real property electrical systems.

(p) Reinforced Thermosetting Resin Conduit may be used with 72ABW/CENMP or 76 MXSG/MXDEJ Approval.

3.2.3 Wire

(a) Insulated conductors shall be copper, type THHN, unless otherwise specified on the design plans or as code requires.

(b) Insulated conductors to be installed in wet locations (i.e. below grade) shall be type THHW, THWN, THHN-2 or an approved equal.

(c) Insulated conductors used for a new service mast or a new utility pole riser shall be identified on the outer insulation layer as “sunlight resistant”.

(d) Wire shall be stranded for all sizes.

(1) Exception: Branch circuit feeders for general purpose wiring #12 may be solid for ease of wiring device termination, however #12 stranded may be used for ease of installation, only if an approved crimp termination is used at the wiring device.

(e) All unused wiring in renovated areas shall be removed to the source.

3.2.4 Busway

(a) Grounding shall be integral type, utilizing the case of the busway as the equipment grounding conductor with approved splicing and joint construction.

(b) Neutral bus, where required, shall be rated at 100% of the current carrying bus bar rating.

3.3 Transformers

3.3.1 Transformers shall meet the following criteria:

(a) All transformers shall have copper bussing and windings. Transformers 75KVA and below may have aluminum windings if approved by 72ABW/CENMP or 76 MXSG/MXDEJ.

(b) Transformers shall have, as a minimum, four (4) 2.5% taps (2+, 2- nominal voltage).

(c) Transformers serving non-linear loads shall have appropriate K-factor rating.

Page 15 of 26 Revised: August 2020

3.3.2 Transformer installation:

(a) Conductor sizing (primary and secondary) for new transformer installations shall be rated not less than 125% of the transformer rated current.

(b) All transformers shall have primary and secondary overcurrent protection sized per article 450 of the National Electrical Code.

(c) Where K-rated transformers are utilized. Neutral conductors shall be up-sized as required.

(d) Ventilation (distance from walls) shall be as specified by the manufacturer. Normally the recommended clearances are listed on the transformer data plate.

(e) Transformers shall be secured to floors using the four mounting holes provided by the manufacturer.

(f) All new raceway installations to new/existing transformers shall have insulated grounding bushings installed.

(g) There shall be no modification (i.e. drilling holes bigger) of connectors being used for conductor terminations to the transformer bushings.

(h) Connections to the MV primary bushings shall comprise of bronze bolts, bronze flat washers, bronze lock washers and bronze nuts. Bronze or cadmium bolts, flat washers, lock washers and nuts may be used on the secondary bushings.

(i) The bolts used to secure the MV cable terminations to the transformer bushing shall be of the same diameter as the manufactures hole in the transformer bushing.

(j) Conductor terminations for low voltage transformers (600 volts and less) shall be made utilizing compression style terminations.

(k) Conduit entries into transformer housings shall be made at the lower portion of the housing as indicated by the manufacturer to avoid excess heating of the primary and secondary conductors.

(l) All bolts used to secure the cable terminations to the transformer bushings shall be tightened to the torque specified for that particular diameter of bolt. Tightening shall be performed using a calibrated torque wrench. After tightening, each connection shall be marked per industry standards using a grease pen or permanent marker.

(m) All ground terminations secured to the transformer case shall have the factory paint removed prior to the installation of the ground lug. The diameter of the removed paint area shall exceed the mounting surface area of the termination to allow for inspection.

(n) All ground terminations secured to the transformer case shall comprise of a drilled hole (same diameter hole as in the ground lug), bronze bolt, bronze flat washer, bronze lock washer and bronze nut. Ventilation openings on the bottom of transformers shall not be used as bolt holes for the securing of any ground termination/bus.

(o) Bolts used to secure ground lugs to the transformer case shall be tightened to the torque specified for that particular diameter of bolt. Tightening shall be performed using a calibrated torque wrench. After tightening, each connection shall be marked per industry standards using a grease pen or permanent marker.

3.3.3 Transformer Bonding:

(a) Transformer bonding shall be completed in strict compliance with Article 250 of the NEC.

(b) Resistance readings shall be obtained, officially documented, and become a matter of record on all new grounding electrode system installations. This same requirement shall apply to any existing transformer installation to be altered/tapped due to new electrical design requirements.

Page 16 of 26 Revised: August 2020

(c) New transformer installations and existing transformers that have been altered or tapped shall not be energized until the grounding system has been inspected and approved by a government representative.

(d) All grounding electrode conductor (GEC) connections to grounding electrodes, building steel and metal bar joists shall comprise of the exothermic welding process or an approved irreversible compression connector listed for the purpose. Mechanical lugs shall only be allowed with waiver by 72ABW/CENMP or 76 MXSG/MXDEJ.

(e) All GEC connections to fire sprinkler piping, steam piping and water piping shall comprise of a pipe clamp listed for the purpose. Mechanical piping systems utilizing Victaulic connections shall not be used as a grounding electrode.

(f) All Bonding Conductors shall be stranded copper.

(g) Grounding conductor bonding terminations shall be made utilizing compression style terminations.

(h) The penetration for the GEC into the new/existing transformer shall comprise of listed bushings or metal fitted locknut. Drilling a hole or using the ventilation openings on the bottom of the transformer to install the new GEC shall not be allowed.

(i) As required for physical protection, the GEC shall be installed within a raceway. The raceway shall be either electrical metallic tubing (EMT) or rigid metal conduit (RMC).

Grounding bushings shall be installed (on both ends) of the new raceway. PVC raceways shall not be used for the physical protection of a GEC.

(j) All transformers directly feeding distribution panels shall bond the neutral at the transformer X0 terminal and to building ground reference. Neutral buss bonding is also required at the first point of service in the building.

3.3.4 Transformer output voltage shall be verified at commissioning of system and load taps adjusted to provide voltage ± 2% of nominal.

3.4 Panelboards, Switchboards, Safety Switches, Motor Control Centers

(a) Panelboards, switchboards, safety switches and motor control centers (MCCs) shall be provided with a dedicated space equal to the width and depth of the equipment and extending from the floor to a height of 6 feet above the equipment (per NEC) or to the structural ceiling, whichever is lower. No piping, ducts, or equipment foreign to the electrical installation shall be located in this space. Sprinkler protection shall be permitted if the electrical equipment is protected from water leakage.

(b) All Panelboards shall be Door-in-Door Construction.

(1) Both doors shall be equipped with lockable lever/handle.

(2) Each lockable device shall be provided with two keys, both keyed the same.

(c) All electrical distribution equipment rated 1200amps and larger shall incorporate Arc Mitigating construction and/or other Arc Energy Mitigation techniques, such as Maintenance Switching with local status indicator, which meet the intent of NFPA 70 Art. 240.87.

(d) Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others.

(1) Circuits for panelboards shall be identified using a directory located inside the panel door

(mounted behind a clear protective cover/holder). In addition, panelboard directories shall also indicate panel identifier (provided by 72ABW/CENMP), “Fed from” information, and the date of installation.

(2) A new typewritten panel schedule shall be supplied for any additions or modifications to the circuitry. Handwritten changes to the panel schedule are not acceptable.

Page 17 of 26 Revised: August 2020

(3) Circuits for switchboards and MCCs shall be identified using an engraved Laminated Plastic label at each switch position. In addition, switchboards and motor control centers shall also include an engraved Laminated Plastic label indicating switchboard/MCC identifier (provided by 72ABW/CENMP), “Fed from” information, and the date of installation.

(e) All new panelboards shall be identified using an engraved Laminated Plastic.

Example:

PANEL “PP1”

UID Identification Name

480Y/277 VOLT, 30, 4W, 400A/3P MCB

18kAIC RATING

FED FROM MDP-12 IN ROOM E101

INSTALLED DD/MM/YYYY

(1) Equipment Nameplates shall be 0.125” thick x 2”tall x 5” wide custom engraved tile, Laminated Plastic, black nameplate with white letters, to include the following information.

i. Equipment Name in 3/8" Minimum Height Lettering

ii. UID Identification Name in 1/8" Minimum Height Lettering

iii. Voltage, Ampacity Rating and Type in 1/8" Minimum Height Lettering

iv. Equipment AIC Rating in 1/8" Minimum Height Lettering

v. Feeder Source of Supply description and location in 1/8" Minimum Height Lettering

vi. Installation Date MM/DD/YYYY in 1/8" Minimum Height Lettering

(2) Mounting shall be made utilizing Stainless Steel Screws or…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .