This is a set of electrical infrastructure design plans prepared by HNTB North Carolina, P.C. for the North Yard Storage Site Construction Project, a City of Charlotte facility intended to support CATS (Charlotte Area Transit System) storage operations. The project encompasses electrical infrastructure upgrades including the installation of a new 100-ampere panel "NYS" (208/120V, 3-phase, 4-wire), conduit systems, receptacles, and associated electrical equipment to support the secured and monitored storage facility. The plans specify Schedule 40 PVC conduit with 24 inches minimum cover for underground installations, rigid galvanized steel for exposed conduit, and include detailed site plans showing conduit routing, junction boxes, and connection points from the existing Duke Energy utility transformer to new and existing panels. All electrical materials and devices must be label-listed by a North Carolina approved third-party testing agency and comply with applicable codes. The plans were prepared and approved on August 20, 2025, and include eight drawing sheets covering site plans, riser diagrams, panel schedules, and optional lighting additions.

The plans establish specific installation requirements including identification labels at every receptacle cover plate indicating originating panel and circuit number, ground fault protection for receptacles in wet areas, and photocell-controlled lighting with automatic on-off switching capability. The optional lighting addition component is noted as subject to further discussion with the contractor to determine optimal aerial and conduit runs to reduce voltage drop and costs. Contractors are required to verify the location of existing utilities and equipment prior to installation, coordinate device locations with the City's representative, and field verify amperage ratings and wire sizes of all circuit breakers in panel NYDP for inclusion in as-built documentation. The design includes provisions for future installation of gate motor controls and access control systems being installed under separate contracts.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWN BY:

CHECKED BY:

NO. DWN CHK APR

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

08/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NYS-000

TITLE SHEET

NORTH YARD STORAGE

ELECTRICAL INFRASTRUCTURE

ELECTRICAL INFRASTRUCTURE

PROJECT LOCATION

NO. DWN CHK APR

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NYS-001

INDEX

SHEET

NO.

DRAWING

NO. DESCRIPTION REVISION

0 1 2 3 4 5

0 NYS-000 TITLE SHEET

1 NYS-001 INDEX

2 NYS-002 GENERAL NOTES, ABBREVIATIONS, & SYMBOLS

3 NYS-003 SITE PLAN (SHEET 1 OF 2)

4 NYS-004 SITE PLAN (SHEET 2 OF 2)

5 NYS-005 RISER DIAGRAM

6 NYS-006 PANEL SCHEDULES

7 NYS-007 OPTIONAL LIGHTING ADDITION

8 NYS-008 OPTIONAL LIGHTING ADDITION CALCULATIONS

NO. DWN CHK APR

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NYS-002

GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

ABBREVIATIONS AND ACRONYMS

JB

X X

OE OE

ELECTRICAL INFRASTRUCTURE

ABBREVIATIONS AND ACRONYMS

18"

6"

24" MIN.

11x18 (POWER)

TYPICAL PULLBOX ELEVATION

UP TO (12) CONDUITS

TOP

OF

GRADE

TYPICAL STUB UP INSTALLATION

CAP CONDUIT TO DETER

ACCUMULATING OF RAIN

WATER

CONDUIT STUB-UP

BOOTLEG TO CONNECT TO CONDUIT

STUB-UP WHERE REQUIRED.

GRADE

24x24 (COMMS)

EXISTING CATS

LIGHTING

X

X X

X X

X

X X

X X

X X

X

X X X X X

XXXXXX

PARKING

LOT

(ASPHALT)

PANEL "NYY"

X X

X

EXISTING CATS LIGHTING

TRENCHING (AVOID)

EXISTING CATS LIGHTING

ASPHALT

LOT

ASPHALT

LOT

SOFTSCAPE

SOFTSCAPE

SOFTSCAPE

SOFTSCAPE

DRIVEWAY

(CONCRETE)

SIGNAL

HOUSE

SL

ID

IN

G

G

AT

E

SLIDING GATE

TO DUKE ENERGYEXISTING CATS

LIGHTING

CONNEX BOX

SUBSTATION

DRIVEWAY

ENTRY

X X

EX

IS

TI

N

G

SL

ID

IN

G G

AT

E

X X

X X X X X X X X X X X X X X X X X X X X X X

TWO VERTICAL

PIVOTING FENCES

CCTV

POLE

EXISTING DUKE

ENERGY TRENCHING

FOR SERVICE CONNECTION

SOFT

SCAPE

SOFTSCAPE

SIDEWALK

(CONCRETE)PARKING

LOT

DRIVEWAY

(CONCRETE)

(CONCRETE)

EXISTING

GATE MOTOR

EXISTING

GATE MOTOR

EXISTING

GATE

MOTOR

(E) PANEL "NYDP"

(208/120V 3Ø-4W)

COMMS ROOM

DRAINAGE

RAVINE

SOFTSCAPE

GRAVEL

SOFTSCAPEASPHALT

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

JB

JB

JB

JB

JB

JB

XFMR

M

INSTALL (1) 1-1/4" SCH 40 PVC CONDUIT (EA)

FOR 3 QUADPLEX OUTLETS

(N) PANEL "NYS"

(208/120V 3Ø-4W)

NYS-5

NYS-2

GEN

ASPHALT

LOT

X X

X X

X

X X X X X X X X X X X

NEW PEDESTRIAN

GATE

EXISTING

PEDESTRIAN

GATE

COMMS JB

24"X24" MIN

JB

POWER JB

11"X18" MIN

DRAWN BY:

CHECKED BY:

NO. DWN CHK APR

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

SCALE: 1/32" = 1'

NOTES:

1.) PROVIDE SCHEDULE 40 PVC WITH 24" MINIMUM OF COVER WHERE RACEWAY IS LOCATED

BELOW GRADED SURFACES.

2.) EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL.

3.) CONDUITS ARE TO STUB UP 6" IN THE CENTER OF THE EQUIPMENT, BE TIGHTLY GROUPED, SHALL BE SECURELY CAPPED IMMEDIATELY AFTER INSTALL, AND SHALL BE BE PROTECTED FROM

DAMAGE. CONDUITS SHALL HAVE PULL STRINGS PROVIDED.

4.) ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL-LISTED

BY A NORTH CAROLINA APPROVED THIRD PARTY TESTING AGENCY.

5.) AS-BUILT INFORMATION IS SHOWN AS REFERENCE. CONTRACTOR MUST VERIFY LOCATION

OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO INSTALL.

6.) RECEPTACLE ON A DEDICATED 20A CIRCUIT SHALL BE RATED 20A. PROVIDE GROUND FAULT

PROTECTION FOR ALL RECEPTACLES LOCATED IN WET AREAS.

7.) PROVIDE IDENTIFICATION LABEL ACCORDING TO SPECIFICATIONS AT EVERY RECEPTACLE

COVER PLATE INDICATING ORIGINATING PANEL AND CIRCUIT NUMBER SO THAT LABEL CAN BE

CLEARLY READ WHILE DEVICE IS IN USE WITH STANDARD PLUGS INSERTED. LABEL SHALL

DISTINCTLY IDENTIFY DEDICATED RECEPTACLES.

8.) COORDINATE DEVICE LOCATIONS WITH CITY'S REPRESENTATIVE.

NYS-003

SITE PLAN

(SHEET 1 OF 2)

M

AT

H C

LI

N

E

(S

EE

S H

EE

T

4)

ELECTRICAL INFRASTRUCTURE

SITE PLAN CONDUIT SCHEDULE

CONDUIT

ID FROM TO

CONDUIT CONDUCTORS

NOTESSIZE TYPE SIZE GND

1 PANEL NYDP PANEL NYS 1-1/4" RGS (3) #1 AWG #6 AWG SWAP TO PVC ONCE

OUTSIDE OF BUILDING.

2 PANEL NYDP PANEL NYS 1-1/4" SCH. 40 PVC (3) #1 AWG #6 AWG

3 PANEL NYS MOTOR STUB UP 1" SCH. 40 PVC - - MOTOR TO BE INSTALLED IN

FUTURE.

4 PANEL NYS MOTOR STUB UP 1" SCH. 40 PVC - - MOTOR TO BE INSTALLED IN

FUTURE.

5 PANEL NYS OUTLETS (3) 1-1/4" SCH. 40 PVC #8, #6, #4 AWG * #6 AWG *THE FURTHER THE OUTLET, THE

LARGER THE WIRE REQUIRED.

6 JB NEAR GEN NEW JB (2) 1-1/4" SCH. 40 PVC - -

JB BY GEN IS FROM COMMS ROOM.

MANY FREE CONDUIT SPACES TO USE.

INSTALLING 2ND CONDUIT AS SPARE.

7 NEW JB MOTOR STUB UP 3/4" SCH. 40 PVC - - ACCESS CONTROL BEING

INSTALLED IN OTHER CONTRACT

8 NEW JB ACCESS CONTROL

PANEL STUB UP 3/4" SCH. 40 PVC - - ACCESS CONTROL BEING

INSTALLED IN OTHER CONTRACT

9 NEW JB MOTOR STUB UP 3/4" SCH. 40 PVC - - ACCESS CONTROL BEING

INSTALLED IN OTHER CONTRACT

10 NEW JB ACCESS CONTROL

PANEL STUB UP (3) 3/4" SCH. 40 PVC - -

INSTALLING 3 CONDUITS FROM THE NEW

JB TO TERMINATE AT DIFFERENT SPOTS

SEEN IN CONDUIT IDS: 10, 11, 12

11 ACCESS CONTROL

PANEL STUB UP

PEDESTRIAN ACCESS

PANEL STUB UP (2) 3/4" SCH. 40 PVC - - ACCESS CONTROL BEING

INSTALLED IN OTHER CONTRACT

12 PEDESTRIAN ACCESS

PANEL STUB UP

NEW PEDESTRIAN

GATE 3/4" SCH. 40 PVC - - STUB UP SHOULD BE RIGHT BY GATE TO RUN

WIRES TO MAGLOCK OR OTHER MEANS OF

ELECTRIC LOCKING MECHANISM

M

AT

H C

LI

N

E

(S

EE

S H

EE

T

8)

EXISTING CATS

LIGHTING

X X

X X

X X

X X

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

ASPHALT

LOTASPHALT

LOT

ASPHALT

LOT

CCTV

POLE

INSTALL (1) 1-1/4" SCH 40 PVC CONDUIT (EA)

FOR 3 QUADPLEX OUTLETS

NYS-2NYS-6 NYS-4

DRAWN BY:

CHECKED BY:

NO. DWN CHK APR

PREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

SCALE: 1/32" = 1'

M

AT

H C

LI

N

E

NORTH YARD STORAGE

SITE PLAN

(2 OF 2)

NYS-004

004ELECTRICAL INFRASTRUCTURE

NOTES:

1.) PROVIDE SCHEDULE 40 PVC WITH 24" MINIMUM OF COVER WHERE RACEWAY IS LOCATED

BELOW GRADED SURFACES.

2.) EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL.

3.) CONDUITS ARE TO STUB UP 6" IN THE CENTER OF THE EQUIPMENT, BE TIGHTLY GROUPED, SHALL BE SECURELY CAPPED IMMEDIATELY AFTER INSTALL, AND SHALL BE BE PROTECTED FROM

DAMAGE. CONDUITS SHALL HAVE PULL STRINGS PROVIDED.

4.) ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL-LISTED

BY A NORTH CAROLINA APPROVED THIRD PARTY TESTING AGENCY.

5.) AS-BUILT INFORMATION IS SHOWN AS REFERENCE. CONTRACTOR MUST VERIFY LOCATION

OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO INSTALL.

6.) RECEPTACLE ON A DEDICATED 20A CIRCUIT SHALL BE RATED 20A. PROVIDE GROUND FAULT

PROTECTION FOR ALL RECEPTACLES LOCATED IN WET AREAS.

7.) PROVIDE IDENTIFICATION LABEL ACCORDING TO SPECIFICATIONS AT EVERY RECEPTACLE

COVER PLATE INDICATING ORIGINATING PANEL AND CIRCUIT NUMBER SO THAT LABEL CAN BE

CLEARLY READ WHILE DEVICE IS IN USE WITH STANDARD PLUGS INSERTED. LABEL SHALL

DISTINCTLY IDENTIFY DEDICATED RECEPTACLES.

8.) COORDINATE DEVICE LOCATIONS WITH CITY'S REPRESENTATIVE.

208Y/120V

UTILITY

XFMR

M

FROM

DUKE

ENERGY

EXISTING

C/T's

EXISTING

PANEL

"NYDP"

EXISTING

GRADE FIRST FLOOR

INTERIOREXTERIOR INTERIOR EXTERIOR

GRADE

NEW

PANEL

"NYS"

WIRE SIZING TABLE

CALLOUT WIRE SIZE GROUND CONDUIT

1 (3) #1 AWG #6 AWG 1 1/4" RGS

2 (3) #1 AWG #6 AWG 1 1/4" PVC

DRAWN BY:

CHECKED BY:

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NYS-005

NO. DWN CHK APRDATE REVISION BY

RISER DIAGRAM

#6G

NOTES:

1.) PROVIDE FABRICATED METAL STRUCTURAL SUPPORT

ASSEMBLY FOR NEW PANEL. ENSURE SUPPORT IS PROPERLY

GROUNDED.

2.) PROVIDE ENCLOSURE RATED FOR OUTDOOR EQUIPMENT

THAT IS NEMA 3R OR RATED SUITABLE FOR ENVIRONMENT

WHERE INSTALLED.

3.) SIMPLIFIED RISER DIAGRAM SHOWN FOR SCOPE OF WORK.

FULL FACILITY RISER DIAGRAM AVAILABLE UPON REQUEST.

NORTH YARD STORAGEPREPARED BY:

APPROVED BY:

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NYS-006

NO. DWN CHK APRDATE REVISION BY

PANEL SCHEDULES

NOTES:

1.) ALL EQUIPMENT SHALL BE SELECTIVELY COORDINATED WITH

UPSTREAM AND DOWNSTREAM BREAKERS.

2.) COORDINATE BREAKER AND WIRING SIZES WITH EQUIPMENT

MANUFACTURERS.

3.) CONTRACTORS SHALL FIELD VERIFY THE AMPERAGE RATING

AND WIRE SIZES OF ALL CIRCUIT BREAKERS IN PANEL NYDP AND

UPDATE DRAWING APPROPRIATELY FOR USE IN AS-BUILTS.

NYS-11

4X X

X X

X

X X X X

PARKING

LOT

(ASPHALT)

ASPHALT

LOT

ASPHALT

LOT

ASPHALT

(N) PANEL "NYS"

(208/120V 3Ø-4W)

New Light Fixtures (TYP) Existing Light Posts (TYP)

ASPHALT

OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X X X

XXXXXXXXXXXXXXXXXXXXXXXXXX

(E) ANTENNA POLE

(LCP AND PHOTOCELL

INSTALLED HERE)

OE OE OE OE OE OE OE OE

INSTALL (1) 3/4" SCH 40 PVC CONDUIT

TO CONNECT LIGHTING

TO "NYS" PANEL

NYS-13,15

TO REST OF LIGHTING

ASPHALT

LOT

OE

X

X

X X

X

X X

X

X X

X

OEOEOEOEOEOEOE OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE

X

X

X

X

X

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

New Light Fixtures (TYP) Existing Light Posts (TYP)

TO REST OF LIGHTING

ASPHALT

LOT

ASPHALT

LOT

OE

208Y/120V

UTILITY

XFMR

M

FROM

DUKE

ENERGY

EXISTING

C/T's

PANEL

"NYDP"

EXISTING

GRADE FIRST FLOOR

INTERIOREXTERIOR INTERIOR EXTERIOR

GRADE

NEW

100A

PANEL

"NYS"

WIRE SIZING TABLE

CALLOUT WIRE SIZE GROUND CONDUIT

1 (3) #1 AWG #6 AWG 1 1/4" RGS

2 (3) #1 AWG #6 AWG 1 1/4" PVC

LIGHTING

CONTROL PANEL

"LCPS"

PHOTOCELL

LIGHTING CONTROL NOTES:

1.) PROVIDE 'PC' PHOTOCELL WITH 5 YEAR WARRANTY.

MOUNT PHOTOCELL NEAR CONTROL PANEL FACING NORTH

AND SHIELD FROM ARTIFICIAL LIGHT SOURCES. ADJUST

SENSITIVITY AS REQUIRED BY OWNER. SET PHOTOCELL SO

THAT ON AND OFF SWITCHING WILL OCCUR WHEN THE

ILLUMINATION LEVEL OF ±10 FOOT-CANDLES IS DETECTED

BY THE PHOTOCELL DEVICE.

2.) PROVIDE AND MOUNT CONTACTOR IN NEMA 1

ENCLOSURE WITHIN CONTROL PANEL. MOUNT SELECTOR

SWITCH WITHIN CONTROL PANEL ADJACENT TO

CONTACTOR ENCLOSURE. ALL LIGHTING CONTROL

COMPONENTS SHALL BE IN A SINGLE NEMA 3R ENCLOSURE

WITH HINGED DOOR INSTALLED DIRECTLY NEXT TO NEW

PANEL NYS. PROVIDE PERMANENT NAMEPLATE ON DOOR

TO READ "STORAGE YARD LIGHTING CONTROL"

3.) AUTO OFF-ON SWITCH SHALL ALLOW MANUAL OVERRIDE

OF THE AUTOMATIC CONTROL SYSTEM. SWITCH SHALL BE

MOUNTED WITHIN CONTROL PANEL.

4.) PROVIDE MECHANICALLY HELD LIGHTING CONTACTOR

IN NEMA 1 ENCLOSURE WITH 30A BALLAST RATED

CONTACTS AND 120V COIL. CONTACTOR SHALL BE OPEN

TYPE. PROVIDE NUMBER OF POLES TO SERVE LOADS

SHOWN. CONNECT ALL STORAGE YARD LIGHTING

THROUGH LIGHTING CONTACTOR. LIGHTING CONTACTOR

SHALL BE CONTROLLED BY RELAY PANEL LCPS THROUGH

COMMON PHOTOCELL.

} 208V

CIRCUIT

NYS-13,15

SPARE

SPARE

SPARE

SPARE

LC

PC

LC

ON

OFF

AUTO

120 VOLTSH N

NOTE 4

NOTE 4

NOTE 3

NOTE 1

NOTE 2

DRAWN BY:

CHECKED BY:

NO. DWN CHK APR

PREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NORTH YARD STORAGE

OPTIONAL LIGHTING ADDITION

LIGHTING SITE PLAN AND RISER DIAGRAM

NYS-007

007ELECTRICAL INFRASTRUCTURE

SCALE: 1/128" = 1' M

AT

H C

LI

N

E

M

AT

H C

LI

N

E

M

AT

H C

LI

N

E

SCALE: 1/64" = 1'

NOTES:

1.) PROVIDE SCHEDULE 40 PVC WITH 24" MINIMUM OF COVER WHERE

RACEWAY IS LOCATED BELOW GRADED SURFACES.

2.) EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL.

3.) CONDUITS ARE TO STUB UP 6" IN THE CENTER OF THE EQUIPMENT, BE

TIGHTLY GROUPED, SHALL BE SECURELY CAPPED IMMEDIATELY AFTER INSTALL,

AND SHALL BE BE PROTECTED FROM DAMAGE. CONDUITS SHALL HAVE PULL

STRINGS PROVIDED.

4.) ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL

BE LABEL-LISTED BY A NORTH CAROLINA APPROVED THIRD PARTY TESTING

AGENCY.

5.) COORDINATE FINAL DEVICE LOCATIONS WITH CITY'S REPRESENTATIVE.

6.) AS-BUILT INFORMATION IS SHOWN AS REFERENCE. CONTRACTOR MUST

VERIFY LOCATION OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO INSTALL.

7.) LIGHTING ADDITION IS OPTIONAL AND CURRENT OPTIONAL DESIGN IS UP

FOR FURTHER DISCUSSION WITH THE CONTRACTOR TO DETERMINE OPTIMAL

AERIAL AND CONDUIT RUNS TO REDUCE VOLTAGE DROP AND COSTS.

RISER DIAGRAM W/ ADDITIONAL LIGHTING (NTS)

NO. DWN CHK APR

PREPARED BY:

APPROVED BY:DATE REVISION BY

DATE:

SHEET:

DRAWING NO.:

PROJECT NO.: n/a

CBS

CBS

CMR

CLM

8/20/25

HNTB NORTH CAROLINA, P.C.

101 SOUTH TRYON STREET, SUITE 3610

CHARLOTTE, NC 28280

(704) 372-8020

NC LICENSE NO: C-1554

NORTH YARD STORAGE

OPTIONAL LIGHTING ADDITION

LIGHTING SITE PLAN AND RISER DIAGRAM

NYS-008

008ELECTRICAL INFRASTRUCTURE

NOTES:

1.) ALL EQUIPMENT SHALL BE SELECTIVELY COORDINATED WITH

UPSTREAM AND DOWNSTREAM BREAKERS.

2.) COORDINATE BREAKER AND WIRING SIZES WITH EQUIPMENT

MANUFACTURERS.

3.) CONTRACTORS SHALL FIELD VERIFY THE AMPERAGE RATING

AND WIRE SIZES OF ALL CIRCUIT BREAKERS IN PANEL NYDP AND

UPDATE DRAWING APPROPRIATELY FOR USE IN AS-BUILTS.