2-MarpleLibrary Preliminary DD Package 2026.pdf

PDF 5 MB Posted

Attached to
MARPLE TOWNSHIP LIBRARY IMPROVEMENTS
Solicitation number
Not on record
Issued by
Delaware County, Brodheadsville CDP, Pennsylvania

About this file

Summary

This document is a Preliminary Design Development Package for the Marple Township Library interior renovation project located at 2599 Sproul Road, Broomall, Pennsylvania. The package includes comprehensive lighting design specifications prepared by BOLD, LLC for a library alteration project serving a 10,579-square-foot nonresidential building. The design encompasses lighting fixtures for multiple functional areas including an adult section, circulation desk, children's areas, teen area, and vestibule. The lighting design specifies five primary fixture types: VODE surface-mounted linear ambient luminaires (LA-01A and LA-01B) totaling 742 linear feet across various zones, EUREKA suspended pendant fixtures in 28-inch (4 fixtures at 25W each) and 46-inch (3 fixtures at 49.9W each) diameters for the teen area, CORONET recessed linear luminaires for the vestibule (48 linear feet at 7W per foot), USAI recessed downlights (4 fixtures at 15W each) for the vestibule, and wall-mounted circulation desk signage (1 fixture at 60W estimated). The total proposed lighting power is 7,549.3 watts against an allowed capacity of 11,831 watts under 2021 IECC compliance standards. Sealed bids are being received through the PennBID Program until 11:00 AM on November 19, 2026, with a 60-day bid withdrawal restriction period.

The project is being funded in part by Keystone Grants for Public Library Facilities, managed by Marple Township in Delaware County, Pennsylvania. All lighting systems are specified with 0-10V dimming control capability and are integrated into a control system using occupancy sensors, astronomical time-clock triggering, and wall-mounted keypads with preset dimming scenes (90%, 50%, 30%, and off settings). The design recommends Lutron Electronics as the lighting control system manufacturer with Lutron Palladiom keypads. Emergency lighting provisions, control system commissioning, and all fixture finishes require coordination with the electrical engineer and architect. The electrical contractor is responsible for verifying all run-length configurations, field measurements, and compliance with manufacturer lead times, which range from 2 to 8 weeks. All lamps must be replaced with new units at the end of the construction phase prior to commissioning and owner occupancy. Bidders are required to provide broken-down unit pricing by fixture type, manufacturer-verified lead times based on quantities, and anticipated ship dates, with bids that lack unit pricing rejected as incomplete.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE: THESE DRAWINGS ARE FOR INTERNAL REVIEW AND REFERENCE ONLY. REFER TO ARCHITECTURAL, INTERIOR DESIGN OR ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION AND DIMENSIONED LOCATION OF LIGHTING FIXTURES.

BOLD, LLC

NEW YORK OFFICE

151 WEST 25TH ST | 11TH FLOOR

NEW YORK, NY |10001

212.674.6500

WWW.BOLDLLC.COM

© 2024 BOLD, LLC

DRAWING NO:

PROJECT NO:

SCALE:

D R

AW

IN

G T

IT

LE

IS

SU

AN

C

E:

D

AT

E:

N O

T

FO

R C

O N

ST

R

U C

TI

O

N

LT-200

3/16" = 1' 0"

N2640

D

ES

IG

N

D

EV

EL

O

PM

EN

T 9/

/2

R

EF

LE

C

TE

D

C

EI

LI

N

G

FI

R

ST

F

LO

O

R

PL

AN

M

AR

PL

E

TO

W

N

SH

IP

L

IB

R

AR

Y

S

PR

O U

L R

D , B

R O

O M

AL

L, P A

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-04

AutoCAD SHX Text Z:105-a

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:102-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-04

AutoCAD SHX Text Z:105-a

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-05

AutoCAD SHX Text Z:105-b

AutoCAD SHX Text

LA-01A

AutoCAD SHX Text Z:100-a

AutoCAD SHX Text

LA-03B

AutoCAD SHX Text Z:104-b

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-03A

AutoCAD SHX Text Z:104-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:103-a

AutoCAD SHX Text

NOT IN BOLD SCOPE

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LA-01B

AutoCAD SHX Text Z:101-a

AutoCAD SHX Text

LD-SIGNAGE

AutoCAD SHX Text Z:101-b

FIXTURE SCHEDULE

MARPLE TOWNSHIP LIBRARY

DESIGN DEVELOPMENT

TYPE CAD

SYMBOL

LUMINAIRE

MANUF.DESCRIPTION LUMINAIRE PART NUMBER TOTAL

WATTS VOLTS TRANSFORMER/

DRIVER MOUNTING LOCATIONLAMP INFO CONTROL

TYPE NOTESLAMP

MANUFACTURER

LAMPS

LAMP

WATTS

LA-01A VODE

SURFACE

MOUNTED,

NARROW PROFILE

1.38"W x 0.60"H

LINEAR, HIGH

EFFICIENCY OMNI-

DIRECTIONAL,

AMBIENT DIRECT

LUMINAIRE.

SYSTEM REQUIRES

#(707-Z2-SL-[SYSTEM LENGTH]-

[RAIL LENGTH]-T7-0-[REMOTE

POWER]-AE-X-0-Z-SO-30-S4-0-WH

-0)

6.6 PER EE REMOTE ELECT SURFACE

MOUNTED

THROUGHOU

TN/A 0-10V

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED.

FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO

ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT

ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH

LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE

DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE

CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT

CONDITIONS. FIELD VERIFICATION OF DIMENSIONING

REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP

DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS

FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF

N/A 1 6.6W/ft. W/ft.

LA-01B VODE

SURFACE

MOUNTED,

NARROW PROFILE

1.38"W x 0.60"H

LINEAR, HIGH

EFFICIENCY OMNI-

DIRECTIONAL,

AMBIENT DIRECT

LUMINAIRE.

SYSTEM REQUIRES

#(707-Z2-SL-[SYSTEM LENGTH]-

[RAIL LENGTH]-T7-0-[REMOTE

POWER]-AE-X-0-Z-SO-30-S4-0-WH

-0)

6.6 PER EE REMOTE ELECT SURFACE

MOUNTED

CIRCULATION

AND

CHILDREN'S

AREA

N/A 0-10V

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED.

FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO

ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT

ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH

LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE

DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE

CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT

CONDITIONS. FIELD VERIFICATION OF DIMENSIONING

REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP

DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS

FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF

N/A 1 6.6W/ft. W/ft.

LA-03A EUREKA

SUSPENDED

NOMINAL 28"

DIAMETER HIGH

EFFICIENCY STATIC

WHITE, AMBIENT

DIRECT LED LIGHT

RING PENDANT.

FIXTURE PROVIDED

WITH LIGHT

DISTRIBUTION

#(4246-28-LED-30-90-[VOLTAGE

PER EE]-DV-AC-[CABLE LENGTH]-

RC1-RCC-[CANOPY FINISH PER

ARCH/ID]-[POWER CORD FINISH

PER ARCH/ID]-[EXTERIOR SHADE

FINISH PER ARCH/ID])

25 PER EE INTEGRAL ELECT PENDANT

MOUNTED TEEN'S AREAN/A 0-10V

FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY

ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER

EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR

DESIGNER. EC TO VERIFY FIXTURE CEILING

MOUNTING TYPE AND SUSPENSION AGAINST

ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.

N/A 1 25W W

LA-03B EUREKA

SUSPENDED

NOMINAL 46"

DIAMETER HIGH

EFFICIENCY STATIC

WHITE, AMBIENT

DIRECT LED LIGHT

RING PENDANT.

FIXTURE PROVIDED

WITH LIGHT

DISTRIBUTION

#(4246-46-LED-30-90-[VOLTAGE

PER EE]-DV-AC-[CABLE LENGTH]-

RC1-RCC-[CANOPY FINISH PER

ARCH/ID]-[POWER CORD FINISH

PER ARCH/ID]-[EXTERIOR SHADE

FINISH PER ARCH/ID])

49.9 PER EE INTEGRAL ELECT PENDANT

MOUNTED

TEEN'S AREA

AND STUDY

ROOMS

N/A 0-10V

FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY

ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER

EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR

DESIGNER. EC TO VERIFY FIXTURE CEILING

MOUNTING TYPE AND SUSPENSION AGAINST

ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.

N/A 1 49.9W W

LA-04 CORONET

RECESSED

MOUNTED 3.5"

WIDE LINEAR

AMBIENT DIRECT

LED LIGHT

LUMINAIRE WITH

REGRESSED

DIFFUSING LENS.

FIXTURE PROVIDED

WITH LIGHT

#(RAY4.R-[LENGTH/CUSTOM PATT]

-30-MED-UNV-DB-[FINISH PER

ARCH/ID]-F-SD-NA-NA-NA-CST

CORNERS)

7 PER EE INTEGRAL ELECT RECESSED VESTIBULEN/A 0-10V

FINISH TO BE VERIFIED PER ARCH. MOUNTING TO BE

VERIFIED PER GC. MANUFACTURER TO PROVIDE

SHOP DRAWINGS INDICATING RUN

LENGTHS AND CONFIGURATIONS FOR VARIOUS

LENGTH CONDITIONS. VOLTAGE TO VERIFIED PER

ELECTRICAL ENGINEER. FIXTURE TO BE

PROVIDED WITH REMOTE DIMMABLE POWER

SUPPLIES CAPABLE OF 0-10V CONTROL. POWER

SUPPLY TO BE LOCATED IN ACCESSIBLE,

DRY, VENTILATED LOCATION COORDINATED BY

N/A 1 7W/ft. W/ft.

LA-05 USAI

RECESSED

MOUNTED,

NOMINAL 2"

APERTURE HIGH

EFFICIENCY

AMERICAN-MADE

ADJUSTABLE

#(SL2_RA-F-L08H-15V2M-30KH-30-

SP-[BAFFLE FINISH PER ARCH/ID]-

[TRIM FINISH PER ARCH/ID]-RT-

UNV-D6E)

15 PER EE INTEGRAL ELECT RECESSED VESTIBULEN/A 0-10V

VERIFY FIXTURE FINISH PER ID. VOLTAGE PER EE.

FINISH TO BE VERIFIED PER ARCH/INTERIOR

DESIGNER. MOUNTING TO BE VERIFIED PER GC.

VOLTAGE TO BE VERIFIED PER ELECTRICAL

ENGINEER.

N/A 1 15W W

LD-

SIG

NAG

E

TBDSIGNAGE BY

OTHERS 60 PER EE TBD WALL

MOUNTED

CIRCULATION

DESKN/A TBD

SIGNAGE BY SIGN FABRICATOR. LIGHTING TO BE

BETWEEN 2700K AND 3500K CCT DEPENDING ON

COLOR OF BACKLIT SIGN. FINAL PRODUCT SHOULD

APPEAR 3000K CCT. SIGN TO BE DIMMABLE AND TIED

TO LIGHTING CONTROL SYSTEM. FABRICATOR TO

ENSURE BACKLIGHT IS NOT VISIBLE WITH NO

"DIODING". SIGN SHOULD BE EVENLY ILLUMINATED

AND NOT EDGE LIT FROM SIDES. WATTAGE IS

ESTIMATED ALLOWANCE.

N/A 1 60W W

Page 1 of 2Revision: 0Project: N2640 09/14/2026

GENERAL NOTES

1. Electrical Contractor responsible for verification of all run length configurations and quantities. All continuous run lengths must be continuously illuminated,hairline seams only, unless otherwise noted.

2. Electrical Contractor to verify all voltages, lamp types, field measurements, etc as required.

3. Electrical Contractor to field verify all mounting conditions and provide all hardware necessary to complete installation for full system operation.

4. Electrical Contractor shall verify the type of ceiling, coordinated with architectural and/or electrical drawings prior to purchase of fixtures.

5. Electrical Contractor must comply with maximum do not exceed remote distance of power supplies per manufacturers recommendation.

6. By bidding on this lighting design package, the Contractor acknowledges that lead times for fixtures can range from 2-8 weeks. BOLD will not approve or accept substitutions resulting from the Electrical Contractor's failure to account for lead times.

7. All remote transformers shall be located at an accessible, sound attenuated, ventilated location where indicated on the electrical drawings.

8. The client shall not hold consultant liable for re-design services due to cost overruns if they choose not to define targeted budgets.

9. Manufacturer must provide shop drawings for all continuously illuminated run lengths or custom sized panels, to be coordinated with architectural and/or electrical drawings.

10. Distributors must provide anticipated ship dates upon return of approved lighting fixture submittals.

11. Distributors must provide manufacturer-verified lead times based on fixture quantities.

12. Distributors must provide broken down unit prices by type. Bids that do not include unit pricing will be rejected as incomplete.

13. All emergency related electrical characteristics must be verified by the Electrical Engineer or Electrical Contractor.

14. All LED Retrofit lamps on dimming system must be for 120v only. For high-voltage applications, Electrical Contractor must verify with manufacturer prior to specification and purchase of system.

15. See architectural and/or electrical drawings for fixture locations, quantities and/or run length configurations.

BOLD is not responsible for final locations, quantities and/or run length configurations.

16. Manufacturer labels shall be turned away from public view. No construction notations shall be visible in areas exposed to public view.

17. All lighting fixtures shall be supplied with lamps, color filters and accessories as specified.

18. Electrical Contractor to replace all lamps with new lamps at the end of construction phase prior to commissioning phase and owner occupancy or project opening.

19. All measurements indicated in BOLD lighting plans are approximate. Electrical contractor is required to make field measurements based on actual site conditions to develop complete orders and install systems per drawings and specifications.

20. Electrical Engineer must provide required compatibility interfaces, if required, for compatibility to selected lighting control system.

21. All lighting fixtures installed in architectural details and/or millwork details must be confirmed and installed per BOLD recommended criteria (ie. aperture opening, visual cutoff angles, aiming angles, etc.).

22. All lighting fixture finishes to be reviewed and approved by Architect and/or Interior Designer prior to purchase.

ABBREVIATED TERMS

LINE- LINE VOLTAGE DIMMABLE

ELV- REVERSE-PHASE ELECTRONIC LOW VOLTAGE DIMMING

FWD ELV- FORWARD-PHASE ELECTRONIC LOW VOLTAGE DIMMING

MLV- MAGNETIC LOW VOLTAGE (FORWARD PHASE) DIMMING

DMX- DMX512 CONTROL

DALI- DALI CONTROL

2-WIRE- LUTRON 2-WIRE DIMMING

3-WIRE- LUTRON 3-WIRE DIMMING

ECO- LUTRON ECOSYSTEM

NON-DIM- NON-DIMMING or SWITCHED

0-10V- 0-10V DIMMING

VIF- VERIFY IN FIELD

TBD- TO BE DETERMINED

TBC- TO BE CONFIRMED

LOCATION SHEET # ZONE DESCRIPTION FIXTURE TYPE LAMP/ SOURCE TYPE LOAD TYPE DRIVER TYPE DIMMING FIXTURE WATTS QTY.

TOTAL

WATTS

NOTES REV.

GROUND FLOOR

ADULT SECTION (100)

THROUGHOUT V2-LT100.0 100-a

SURFACE MOUNTED, NARROW

PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-

DIRECTIONAL, AMBIENT DIRECT

LUMINAIRE. SYSTEM REQUIRES

REMOTE, OPTIMIZED POWER

DISTRIBUTION POWER SUPPLIES

LA-01A N/A 0-10V

REMOTE

ELECT

D 6.6 w/ft. 622 ft. 4105.2w

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE

INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID

SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-

FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED

BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF

DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS

INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH

CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS

REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM

PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH

PER ARCHITECT.

` 4,105.2w

CIRCULATION (101)

CIRCULATION AND CHILDREN'S AREA V2-LT100.0 101-a

SURFACE MOUNTED, NARROW

PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-

DIRECTIONAL, AMBIENT DIRECT

LUMINAIRE. SYSTEM REQUIRES

REMOTE, OPTIMIZED POWER

DISTRIBUTION POWER SUPPLIES

LA-01B N/A 0-10V

REMOTE

ELECT

D 6.6 w/ft. 120 ft. 792.0w

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE

INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID

SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-

FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED

BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF

DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS

INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH

CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS

REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM

PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH

PER ARCHITECT.

CIRCULATION DESK V2-LT100.1 101-b SIGNAGE BY OTHERS LD-SIGNAGE N/A 0 TBD D 60.0w 1 60.0w

SIGNAGE BY SIGN FABRICATOR. LIGHTING TO BE BETWEEN 2700K AND 3500K

CCT DEPENDING ON COLOR OF BACKLIT SIGN. FINAL PRODUCT SHOULD

APPEAR 3000K CCT. SIGN TO BE DIMMABLE AND TIED TO LIGHTING CONTROL

SYSTEM. FABRICATOR TO ENSURE BACKLIGHT IS NOT VISIBLE WITH NO

"DIODING". SIGN SHOULD BE EVENLY ILLUMINATED AND NOT EDGE LIT FROM

SIDES. WATTAGE IS ESTIMATED ALLOWANCE.

` 852.0w

CHILDREN (102)

THROUGHOUT V2-LT100.0 102-a

SURFACE MOUNTED, NARROW

PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-

DIRECTIONAL, AMBIENT DIRECT

LUMINAIRE. SYSTEM REQUIRES

REMOTE, OPTIMIZED POWER

DISTRIBUTION POWER SUPPLIES

LA-01A N/A 0-10V

REMOTE

ELECT

D 6.6 w/ft. 236 ft. 1557.6w

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE

INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID

SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-

FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED

BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF

DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS

INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH

CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS

REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM

PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH

PER ARCHITECT.

` 1,557.6w

CHILDREN (103)

CIRCULATION AND CHILDREN'S AREA V2-LT100.0 103-a

SURFACE MOUNTED, NARROW

PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-

DIRECTIONAL, AMBIENT DIRECT

LUMINAIRE. SYSTEM REQUIRES

REMOTE, OPTIMIZED POWER

DISTRIBUTION POWER SUPPLIES

LA-01B N/A 0-10V

REMOTE

ELECT

D 6.6 w/ft. 68 ft. 448.8w

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE

INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID

SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-

FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED

BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF

DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN

LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS

INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH

CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS

REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM

PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH

PER ARCHITECT.

` 448.8w

ZONE SCHEDULE

N2640 - MARPLE TOWNSHIP LIBRARY

09/14/2026

BRIAN ORTER LIGHTING DESIGN, LLC.

151 WEST 25TH STREET 11TH FLOOR / NEW YORK, NY 10001 / 212 674 6500

LOCATION SHEET # ZONE DESCRIPTION FIXTURE TYPE LAMP/ SOURCE TYPE LOAD TYPE DRIVER TYPE DIMMING FIXTURE WATTS QTY.

TOTAL

WATTS

NOTES REV.

ZONE SCHEDULE

N2640 - MARPLE TOWNSHIP LIBRARY

09/14/2026

TEEN (104)

TEEN'S AREA V2-LT100.0 104-a

SUSPENDED NOMINAL 28"

DIAMETER HIGH EFFICIENCY

STATIC WHITE, AMBIENT DIRECT

LED LIGHT RING PENDANT.

FIXTURE PROVIDED WITH LIGHT

DISTRIBUTION OPTIMIZED, LOW-

GLARE, DOT-FREE DIFFUSING LENS

MEDIA.

LA-03A N/A 0-10V

INTEGRAL

ELECT

D 25.0w 4 100.0w

FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN

FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR

DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND

SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.

TEEN'S AREA AND STUDY ROOMS V2-LT100.0 104-b

SUSPENDED NOMINAL 46"

DIAMETER HIGH EFFICIENCY

STATIC WHITE, AMBIENT DIRECT

LED LIGHT RING PENDANT.

FIXTURE PROVIDED WITH LIGHT

DISTRIBUTION OPTIMIZED, LOW-

GLARE, DOT-FREE DIFFUSING LENS

MEDIA.

LA-03B N/A 0-10V

INTEGRAL

ELECT

D 49.9w 3 149.7w

FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN

FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR

DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND

SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.

` 249.7w

VESTIBULE (105)

VESTIBULE V2-LT100.0 105-a

RECESSED MOUNTED 3.5" WIDE

LINEAR AMBIENT DIRECT LED

LIGHT LUMINAIRE WITH

REGRESSED DIFFUSING LENS.

FIXTURE PROVIDED WITH LIGHT

DISTRIBUTION OPTIMIZED, LOW-

GLARE, DOT-FREE DIFFUSING LENS

MEDIA. SYSTEM INTENDED TO BE

PROVIDED WITH CUSTOM MITERED

ANGLED CORNERS.

LA-04 N/A 0-10V

INTEGRAL

ELECT

D 7.0 w/ft. 48 ft. 336.0w

FINISH TO BE VERIFIED PER ARCH. MOUNTING TO BE VERIFIED PER GC.

�MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS

AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. VOLTAGE TO

�VERIFIED PER ELECTRICAL ENGINEER. FIXTURE TO BE PROVIDED WITH

REMOTE DIMMABLE POWER SUPPLIES CAPABLE OF 0-10V CONTROL. POWER

�SUPPLY TO BE LOCATED IN ACCESSIBLE, DRY, VENTILATED LOCATION

COORDINATED BY ARCHITECT. PROVIDE ALL ADDITIONAL MOUNTING

�ACCESSORIES, END CAPS LEADER/JUMPER CABLES AS REQUIRED FOR FULL

SYSTEM OPERATION.

VESTIBULE V2-LT100.0 105-b

RECESSED MOUNTED, NOMINAL 2"

APERTURE HIGH EFFICIENCY

AMERICAN-MADE ADJUSTABLE LED

DOWNLIGHT WITH CONICAL

REGRESSED FULL LENSED TRIM.

LA-05 N/A 0-10V

INTEGRAL

ELECT

D 15.0w 4 60.0w

VERIFY FIXTURE FINISH PER ID. VOLTAGE PER EE. FINISH TO BE VERIFIED

PER ARCH/INTERIOR DESIGNER. MOUNTING TO BE VERIFIED PER GC.

VOLTAGE TO BE VERIFIED PER ELECTRICAL ENGINEER.

` 396.0w

TOTAL WATTS: 7,609.3w

END OF ZONE SCHEDULE

ABBREVIATED TERMS:

LINE- LINE VOLTAGE DIMMABLE 2-WIRE- LUTRON 2-WIRE DIMMING

ELV- REVERSE-PHASE ELECTRONIC LOW VOLTAGE DIMMING 3-WIRE- LUTRON 3-WIRE DIMMING

FWD ELV- FORWARD-PHASE ELECTRONIC LOW VOLTAGE DIMMING ECO- LUTRON ECOSYSTEM

MLV- MAGNETIC LOW VOLTAGE (FORWARD PHASE) DIMMING NON-DIM- NON-DIMMING or SWITCHED

DMX- DMX512 CONTROL 0-10V- 0-10V DIMMING

DALI- DALI CONTROL VIF- VERIFY IN FIELD

BRIAN ORTER LIGHTING DESIGN, LLC.

151 WEST 25TH STREET 11TH FLOOR / NEW YORK, NY 10001 / 212 674 6500

212 674 6500 / 151 West 25th Street 11th Floor / New York, NY 10001 www.boldllc.com

PROJECT: N2640- Marple Township Library Preliminary Lighting Control Narrative – Design Development 09/14/2026

Summary

- FOH astronomical timeclock triggering with scene based. Preset scenes for specific time of day/year.

- FOH keypads as indicated below.

- BOH on/off switch keypads for BOH areas as required.

General Lighting Control The general lighting control system shall be controlled via user keypads and time-clock settings. Keypads shall be engraved, easy to read, and backlit. Any keypad shall be capable of recalling any preprogrammed scenes. The lighting control system shall be capable of triggering any zones based on astronomical sunrise and sunset, as well as arbitrary times as needed. Timeclock shall compensate for daylight savings time and leap year adjustment if required and retains power failure memory. Timer shall be capable of controlling any zone on the system independently and shall be able to recall preprogrammed scenes. The system shall be capable of automatic scene adjustments based on building operation guidelines. The lighting control system shall include hardwired, facility locked programming ports for the purpose of setting lighting levels and recalling scenes.

The lighting control system shall be capable of interfacing with Wi-Fi-enabled handheld device (e.g. Apple iPad) for setting lighting levels and recalling presets. Wi-Fi interface shall possess a lockable “programmer mode” capable of setting levels and recording presets, and a “user mode” with preset recall and temporary level adjustment only. Licenses for mobile device operation for both the operator and the lighting designer shall be included in the system bill of materials, and the commissioning agent shall be prepared to install and configure both licenses at the time of aim & adjust. The general lighting control system commissioning agent shall coordinate with building IT, other installers, and integrators as required for a fully functioning system, including Wi-Fi access for both programming and daily operation.

System programming interface shall possess a password protected access capable of setting levels and recording presets, and creating and editing timeclock events, as well as preset recall and temporary level adjustment. Mobile device operation for both the operator and the lighting designer shall be included in the system bill of materials, and the commissioning agent shall be prepared to install and configure system access at the time of aim & adjust. The general lighting control system commissioning agent shall coordinate with building IT, other installers, and integrators as required for a fully functioning system for both programming and daily operation.

The general contractor shall be responsible for scheduling control system commissioning in accordance with manufacturer’s submittal documents or three (3) weeks prior to the desired start of commissioning, whichever is greater.

The provided wall-box control/keypad(s) shall be coordinated with the electrical engineer and to be located at an accessible location as indicated on the architectural and/or electrical drawings. The keypad engraving shall be responsible by the electrical contractor and/or commissioned control specialist to be coordinated with the architect/interior designer.

Emergency Lighting:

The Control System shall include capability and all necessary components for designating certain circuits as emergency lighting circuits.

Quantity, locations and required equipment TBD by Electrical Engineer and to be documented within the Electrical Drawings.

Dimmer Rack(s):

Dimmer Rack and Interface locations is dependent upon size of rack(s) to be located at locations indicated on the Architectural drawings and/or Electrical drawings.

Final location to be coordinated with Architect and Client.

Interfaces – General (Lighting Control System) All interfaces indicated below should be tied to an astronomical time clock and to be used for manual override only. All interfaces listed below are inclusive of all front of houses spaces.

A. One (1) Wi-Fi enabled handheld control devices (e.g. Apple iPad/iPhone and/or laptop) with control software/app.

a. (1) Handheld control devices to be provided by operations. Ownership/operations to confirm.

b. Handheld control devices must be capable of controlling all spaces tied to the lighting control system.

B. Library

a. One single-gang, 4-button keypad with 4 preset scenes to be located behind the circulation desk with one duplicate keypad located at desired BOH location. All keypads are recommended to be locked and only accessible by operations.

b. One single-gang, 4-button keypad with 4 preset scenes to be located at Staff point desk.

c. Provide all code required sensors. Sensors to be dual technology to include passive infrared and ultrasonic sensing.

d. For all BOH support spaces provide code-required switching and sensors. All sensors to be dual technology to include passive infrared and ultrasonic.

All keypads must be concealed from direct view of guests. All locations to be coordinated with the Architect, Interior Designer and/or control system integrator, to be approved by the owner.

212 674 6500 / 151 West 25th Street 11th Floor / New York, NY 10001 www.boldllc.com

Daily Time-Clock Scenes/Global Scenes Scene does not exist on physical keypad. It is a daily programmed scene triggered by system clock.

Sequence of Operations

Below is the lighting control intent for the project. The size and scale of the system shall be determined upon selection of the control system. All lighting fixtures tied to the control system must be provided with the required dimming ballast, drivers and/or compatibility interfaces capable 1% dimming minimum. Provide all required ceiling mounted occupancy/vacancy sensors as required per local code compliance. All vacancy/occupancy sensors shall be dual-technology (Infrared and Ultra Sonic) ready.

All front of house spaces shall be dimmable and tied to the lighting control system coordinated with the Astronomical time-clock and to be override by wall box control or handheld control device. The wall station control shall be located at all spaces notated in section “Interfaces- General”, hidden from public view and only accessible to operations staff.

All lighting controls are to be recalled via keypads indicated above. All areas shall be programmed with scenes corresponding to the following times of day (times TBC by owner/operator), and shall fade naturally between scenes and to be set to a 3 to 5 second maximum fade delay:

*Subject to change, pending Project Design.

The keypad shall include the following scenes with preliminary dimming percentages. Final lighting level settings to be done on-site with lighting designer and operations during opening of project. Bill of materials shall include ample time for any trouble shooting and light level settings.

Scene Name Preset Default Levels Dimming Delay (s)

Scene 1 High All on at 90% 3-5 seconds

Scene 2 Medium All on at 50% 3-5 seconds

Scene 3 Low All on at 30% 3-5 seconds

Scene 4 All Off All off at 0% 3-5 seconds

ALL RECOMMENDED LIGHT LEVELS TO BE CONFIRMED ON SITE WITH LUTRON COMMISSIONER AND CLIENT.

All noted Scenes above are to be indicated and pre-set by the lighting control systems integrator as set baseline. All lighting scenes will be set during BOLD final commissioning of design (Aim & Adjust Phase). All lights will be adjusted with lux level meter readings to meet the following minimum standard criteria established IES (Illuminating Engineering Society) design standards.

All scenes shall be accessible at any time through button stations and connected wireless devices.

Recommended Lighting Control System BOLD recommends Lutron Electronics as the project Lighting Controls manufacturer and to be used as the basis of design guidelines and benchmarked against other approved controls vendors. All recommended keypads to Lutron Palladiom 4-button for single gang and 8-button for double gang.

Recommended Manufacturers (Smart Controls)

- Lutron (Quantum or equal)

- Lutron (Athena)

Recommended Manufacturers (Wallbox Controls)

- Lutron (Athena)

MARPLE TOWNSHIP LIBRARY

J R KELLER LLC

09/14/2026

DESIGN DEVELOPMENT

0REVISION:

SURFACE MOUNTED, NARROW PROFILE 1.38"W x 0.60"H

LINEAR, HIGH EFFICIENCY OMNI-DIRECTIONAL, AMBIENT

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01A

THROUGHOUT

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 1 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

W/ft.

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01A

THROUGHOUT

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 2 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01A

THROUGHOUT

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 3 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01A

THROUGHOUT

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 4 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01A

THROUGHOUT

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 5 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01B

CIRCULATION AND CHILDREN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 6 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01B

CIRCULATION AND CHILDREN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 7 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01B

CIRCULATION AND CHILDREN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 8 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01B

CIRCULATION AND CHILDREN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 9 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED

POWER DISTRIBUTION POWER SUPPLIES

D es cr ip tio n Type

LA-01B

CIRCULATION AND CHILDREN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 10 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

VODE

Manufacturer

#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)

Part Number

PER EE

Voltage

REMOTE ELECT

Ballast/Trans/Drvr

SURFACE MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es

FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.

PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.

N/A

Project: N2640

Input Watts

6.6

6.6

Lamp Watts

SUSPENDED NOMINAL 28" DIAMETER HIGH EFFICIENCY

STATIC WHITE, AMBIENT DIRECT LED LIGHT RING PENDANT.

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,

LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.

D es cr ip tio n Type

LA-03A

TEEN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 11 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

EUREKA

Manufacturer

#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-

[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])

Part Number

PER EE

Voltage

INTEGRAL ELECT

Ballast/Trans/Drvr

PENDANT MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS

AND DRAWINGS.

N/A

Project: N2640

Input Watts

Lamp Watts

W

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,

LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.

D es cr ip tio n Type

LA-03A

TEEN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 12 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

EUREKA

Manufacturer

#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-

[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])

Part Number

PER EE

Voltage

INTEGRAL ELECT

Ballast/Trans/Drvr

PENDANT MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS

AND DRAWINGS.

N/A

Project: N2640

Input Watts

Lamp Watts

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,

LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.

D es cr ip tio n Type

LA-03A

TEEN'S AREA

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 13 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

EUREKA

Manufacturer

#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-

[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])

Part Number

PER EE

Voltage

INTEGRAL ELECT

Ballast/Trans/Drvr

PENDANT MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS

AND DRAWINGS.

N/A

Project: N2640

Input Watts

Lamp Watts

SUSPENDED NOMINAL 46" DIAMETER HIGH EFFICIENCY

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,

LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.

D es cr ip tio n Type

LA-03B

TEEN'S AREA AND STUDY ROOMS

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 14 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

EUREKA

Manufacturer

#(4246-46-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-

[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])

Part Number

PER EE

Voltage

INTEGRAL ELECT

Ballast/Trans/Drvr

PENDANT MOUNTED

Mounting

Lamps Per Fixture

0-10V

Control Type

N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS

AND DRAWINGS.

N/A

Project: N2640

Input Watts

49.9

49.9

Lamp Watts

FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,

LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.

D es cr ip tio n Type

LA-03B

TEEN'S AREA AND STUDY ROOMS

Lo ca tio n

M A

R

PL

E

TO

W N

SH

IP

L

IB

R A

R Y

W

ES

T

TH

S

T

TH

F

LO

O

R N

EW

Y

O R

K, N

Y

W W

W .B

R

IA

N O

R

TE

R .C

O M

D

ES

IG

N

D

EV

EL

O

PM

EN

T

Page 15 of 27Revision: 0 Date: 09/14/2026

Notes Notes

So ur ce In fo

3000K/90+CRI

ColorLamp Manufacturer

N/A

Lamp Info/Part #

Fi xt ur e

In fo rm at io n

EUREKA

Manufacturer

#(4246-46-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-

[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])

Part…

This is the start of the file's text. The full file is on GovTribe.