2-MarpleLibrary Preliminary DD Package 2026.pdf
PDF 5 MB Posted
- Attached to
- MARPLE TOWNSHIP LIBRARY IMPROVEMENTS
- Solicitation number
- Not on record
- Issued by
- Delaware County, Brodheadsville CDP, Pennsylvania
About this file
Summary
This document is a Preliminary Design Development Package for the Marple Township Library interior renovation project located at 2599 Sproul Road, Broomall, Pennsylvania. The package includes comprehensive lighting design specifications prepared by BOLD, LLC for a library alteration project serving a 10,579-square-foot nonresidential building. The design encompasses lighting fixtures for multiple functional areas including an adult section, circulation desk, children's areas, teen area, and vestibule. The lighting design specifies five primary fixture types: VODE surface-mounted linear ambient luminaires (LA-01A and LA-01B) totaling 742 linear feet across various zones, EUREKA suspended pendant fixtures in 28-inch (4 fixtures at 25W each) and 46-inch (3 fixtures at 49.9W each) diameters for the teen area, CORONET recessed linear luminaires for the vestibule (48 linear feet at 7W per foot), USAI recessed downlights (4 fixtures at 15W each) for the vestibule, and wall-mounted circulation desk signage (1 fixture at 60W estimated). The total proposed lighting power is 7,549.3 watts against an allowed capacity of 11,831 watts under 2021 IECC compliance standards. Sealed bids are being received through the PennBID Program until 11:00 AM on November 19, 2026, with a 60-day bid withdrawal restriction period.
The project is being funded in part by Keystone Grants for Public Library Facilities, managed by Marple Township in Delaware County, Pennsylvania. All lighting systems are specified with 0-10V dimming control capability and are integrated into a control system using occupancy sensors, astronomical time-clock triggering, and wall-mounted keypads with preset dimming scenes (90%, 50%, 30%, and off settings). The design recommends Lutron Electronics as the lighting control system manufacturer with Lutron Palladiom keypads. Emergency lighting provisions, control system commissioning, and all fixture finishes require coordination with the electrical engineer and architect. The electrical contractor is responsible for verifying all run-length configurations, field measurements, and compliance with manufacturer lead times, which range from 2 to 8 weeks. All lamps must be replaced with new units at the end of the construction phase prior to commissioning and owner occupancy. Bidders are required to provide broken-down unit pricing by fixture type, manufacturer-verified lead times based on quantities, and anticipated ship dates, with bids that lack unit pricing rejected as incomplete.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-Marple Township Public Library - AE RFP Keystone Approved for PennBid.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: THESE DRAWINGS ARE FOR INTERNAL REVIEW AND REFERENCE ONLY. REFER TO ARCHITECTURAL, INTERIOR DESIGN OR ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION AND DIMENSIONED LOCATION OF LIGHTING FIXTURES.
BOLD, LLC
NEW YORK OFFICE
151 WEST 25TH ST | 11TH FLOOR
NEW YORK, NY |10001
212.674.6500
WWW.BOLDLLC.COM
© 2024 BOLD, LLC
DRAWING NO:
PROJECT NO:
SCALE:
D R
AW
IN
G T
IT
LE
IS
SU
AN
C
E:
D
AT
E:
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
LT-200
3/16" = 1' 0"
N2640
D
ES
IG
N
D
EV
EL
O
PM
EN
T 9/
/2
R
EF
LE
C
TE
D
C
EI
LI
N
G
FI
R
ST
F
LO
O
R
PL
AN
M
AR
PL
E
TO
W
N
SH
IP
L
IB
R
AR
Y
S
PR
O U
L R
D , B
R O
O M
AL
L, P A
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-04
AutoCAD SHX Text Z:105-a
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:102-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-04
AutoCAD SHX Text Z:105-a
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-05
AutoCAD SHX Text Z:105-b
AutoCAD SHX Text
LA-01A
AutoCAD SHX Text Z:100-a
AutoCAD SHX Text
LA-03B
AutoCAD SHX Text Z:104-b
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-03A
AutoCAD SHX Text Z:104-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:103-a
AutoCAD SHX Text
NOT IN BOLD SCOPE
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LA-01B
AutoCAD SHX Text Z:101-a
AutoCAD SHX Text
LD-SIGNAGE
AutoCAD SHX Text Z:101-b
FIXTURE SCHEDULE
MARPLE TOWNSHIP LIBRARY
DESIGN DEVELOPMENT
TYPE CAD
SYMBOL
LUMINAIRE
MANUF.DESCRIPTION LUMINAIRE PART NUMBER TOTAL
WATTS VOLTS TRANSFORMER/
DRIVER MOUNTING LOCATIONLAMP INFO CONTROL
TYPE NOTESLAMP
MANUFACTURER
LAMPS
LAMP
WATTS
LA-01A VODE
SURFACE
MOUNTED,
NARROW PROFILE
1.38"W x 0.60"H
LINEAR, HIGH
EFFICIENCY OMNI-
DIRECTIONAL,
AMBIENT DIRECT
LUMINAIRE.
SYSTEM REQUIRES
#(707-Z2-SL-[SYSTEM LENGTH]-
[RAIL LENGTH]-T7-0-[REMOTE
POWER]-AE-X-0-Z-SO-30-S4-0-WH
-0)
6.6 PER EE REMOTE ELECT SURFACE
MOUNTED
THROUGHOU
TN/A 0-10V
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED.
FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO
ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT
ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH
LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE
DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE
CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT
CONDITIONS. FIELD VERIFICATION OF DIMENSIONING
REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP
DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS
FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF
N/A 1 6.6W/ft. W/ft.
LA-01B VODE
SURFACE
MOUNTED,
NARROW PROFILE
1.38"W x 0.60"H
LINEAR, HIGH
EFFICIENCY OMNI-
DIRECTIONAL,
AMBIENT DIRECT
LUMINAIRE.
SYSTEM REQUIRES
#(707-Z2-SL-[SYSTEM LENGTH]-
[RAIL LENGTH]-T7-0-[REMOTE
POWER]-AE-X-0-Z-SO-30-S4-0-WH
-0)
6.6 PER EE REMOTE ELECT SURFACE
MOUNTED
CIRCULATION
AND
CHILDREN'S
AREA
N/A 0-10V
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED.
FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO
ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT
ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH
LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE
DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE
CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT
CONDITIONS. FIELD VERIFICATION OF DIMENSIONING
REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP
DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS
FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF
N/A 1 6.6W/ft. W/ft.
LA-03A EUREKA
SUSPENDED
NOMINAL 28"
DIAMETER HIGH
EFFICIENCY STATIC
WHITE, AMBIENT
DIRECT LED LIGHT
RING PENDANT.
FIXTURE PROVIDED
WITH LIGHT
DISTRIBUTION
#(4246-28-LED-30-90-[VOLTAGE
PER EE]-DV-AC-[CABLE LENGTH]-
RC1-RCC-[CANOPY FINISH PER
ARCH/ID]-[POWER CORD FINISH
PER ARCH/ID]-[EXTERIOR SHADE
FINISH PER ARCH/ID])
25 PER EE INTEGRAL ELECT PENDANT
MOUNTED TEEN'S AREAN/A 0-10V
FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY
ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER
EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR
DESIGNER. EC TO VERIFY FIXTURE CEILING
MOUNTING TYPE AND SUSPENSION AGAINST
ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.
N/A 1 25W W
LA-03B EUREKA
SUSPENDED
NOMINAL 46"
DIAMETER HIGH
EFFICIENCY STATIC
WHITE, AMBIENT
DIRECT LED LIGHT
RING PENDANT.
FIXTURE PROVIDED
WITH LIGHT
DISTRIBUTION
#(4246-46-LED-30-90-[VOLTAGE
PER EE]-DV-AC-[CABLE LENGTH]-
RC1-RCC-[CANOPY FINISH PER
ARCH/ID]-[POWER CORD FINISH
PER ARCH/ID]-[EXTERIOR SHADE
FINISH PER ARCH/ID])
49.9 PER EE INTEGRAL ELECT PENDANT
MOUNTED
TEEN'S AREA
AND STUDY
ROOMS
N/A 0-10V
FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY
ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER
EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR
DESIGNER. EC TO VERIFY FIXTURE CEILING
MOUNTING TYPE AND SUSPENSION AGAINST
ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.
N/A 1 49.9W W
LA-04 CORONET
RECESSED
MOUNTED 3.5"
WIDE LINEAR
AMBIENT DIRECT
LED LIGHT
LUMINAIRE WITH
REGRESSED
DIFFUSING LENS.
FIXTURE PROVIDED
WITH LIGHT
#(RAY4.R-[LENGTH/CUSTOM PATT]
-30-MED-UNV-DB-[FINISH PER
ARCH/ID]-F-SD-NA-NA-NA-CST
CORNERS)
7 PER EE INTEGRAL ELECT RECESSED VESTIBULEN/A 0-10V
FINISH TO BE VERIFIED PER ARCH. MOUNTING TO BE
VERIFIED PER GC. MANUFACTURER TO PROVIDE
SHOP DRAWINGS INDICATING RUN
LENGTHS AND CONFIGURATIONS FOR VARIOUS
LENGTH CONDITIONS. VOLTAGE TO VERIFIED PER
ELECTRICAL ENGINEER. FIXTURE TO BE
PROVIDED WITH REMOTE DIMMABLE POWER
SUPPLIES CAPABLE OF 0-10V CONTROL. POWER
SUPPLY TO BE LOCATED IN ACCESSIBLE,
DRY, VENTILATED LOCATION COORDINATED BY
N/A 1 7W/ft. W/ft.
LA-05 USAI
RECESSED
MOUNTED,
NOMINAL 2"
APERTURE HIGH
EFFICIENCY
AMERICAN-MADE
ADJUSTABLE
#(SL2_RA-F-L08H-15V2M-30KH-30-
SP-[BAFFLE FINISH PER ARCH/ID]-
[TRIM FINISH PER ARCH/ID]-RT-
UNV-D6E)
15 PER EE INTEGRAL ELECT RECESSED VESTIBULEN/A 0-10V
VERIFY FIXTURE FINISH PER ID. VOLTAGE PER EE.
FINISH TO BE VERIFIED PER ARCH/INTERIOR
DESIGNER. MOUNTING TO BE VERIFIED PER GC.
VOLTAGE TO BE VERIFIED PER ELECTRICAL
ENGINEER.
N/A 1 15W W
LD-
SIG
NAG
E
TBDSIGNAGE BY
OTHERS 60 PER EE TBD WALL
MOUNTED
CIRCULATION
DESKN/A TBD
SIGNAGE BY SIGN FABRICATOR. LIGHTING TO BE
BETWEEN 2700K AND 3500K CCT DEPENDING ON
COLOR OF BACKLIT SIGN. FINAL PRODUCT SHOULD
APPEAR 3000K CCT. SIGN TO BE DIMMABLE AND TIED
TO LIGHTING CONTROL SYSTEM. FABRICATOR TO
ENSURE BACKLIGHT IS NOT VISIBLE WITH NO
"DIODING". SIGN SHOULD BE EVENLY ILLUMINATED
AND NOT EDGE LIT FROM SIDES. WATTAGE IS
ESTIMATED ALLOWANCE.
N/A 1 60W W
Page 1 of 2Revision: 0Project: N2640 09/14/2026
GENERAL NOTES
1. Electrical Contractor responsible for verification of all run length configurations and quantities. All continuous run lengths must be continuously illuminated,hairline seams only, unless otherwise noted.
2. Electrical Contractor to verify all voltages, lamp types, field measurements, etc as required.
3. Electrical Contractor to field verify all mounting conditions and provide all hardware necessary to complete installation for full system operation.
4. Electrical Contractor shall verify the type of ceiling, coordinated with architectural and/or electrical drawings prior to purchase of fixtures.
5. Electrical Contractor must comply with maximum do not exceed remote distance of power supplies per manufacturers recommendation.
6. By bidding on this lighting design package, the Contractor acknowledges that lead times for fixtures can range from 2-8 weeks. BOLD will not approve or accept substitutions resulting from the Electrical Contractor's failure to account for lead times.
7. All remote transformers shall be located at an accessible, sound attenuated, ventilated location where indicated on the electrical drawings.
8. The client shall not hold consultant liable for re-design services due to cost overruns if they choose not to define targeted budgets.
9. Manufacturer must provide shop drawings for all continuously illuminated run lengths or custom sized panels, to be coordinated with architectural and/or electrical drawings.
10. Distributors must provide anticipated ship dates upon return of approved lighting fixture submittals.
11. Distributors must provide manufacturer-verified lead times based on fixture quantities.
12. Distributors must provide broken down unit prices by type. Bids that do not include unit pricing will be rejected as incomplete.
13. All emergency related electrical characteristics must be verified by the Electrical Engineer or Electrical Contractor.
14. All LED Retrofit lamps on dimming system must be for 120v only. For high-voltage applications, Electrical Contractor must verify with manufacturer prior to specification and purchase of system.
15. See architectural and/or electrical drawings for fixture locations, quantities and/or run length configurations.
BOLD is not responsible for final locations, quantities and/or run length configurations.
16. Manufacturer labels shall be turned away from public view. No construction notations shall be visible in areas exposed to public view.
17. All lighting fixtures shall be supplied with lamps, color filters and accessories as specified.
18. Electrical Contractor to replace all lamps with new lamps at the end of construction phase prior to commissioning phase and owner occupancy or project opening.
19. All measurements indicated in BOLD lighting plans are approximate. Electrical contractor is required to make field measurements based on actual site conditions to develop complete orders and install systems per drawings and specifications.
20. Electrical Engineer must provide required compatibility interfaces, if required, for compatibility to selected lighting control system.
21. All lighting fixtures installed in architectural details and/or millwork details must be confirmed and installed per BOLD recommended criteria (ie. aperture opening, visual cutoff angles, aiming angles, etc.).
22. All lighting fixture finishes to be reviewed and approved by Architect and/or Interior Designer prior to purchase.
ABBREVIATED TERMS
LINE- LINE VOLTAGE DIMMABLE
ELV- REVERSE-PHASE ELECTRONIC LOW VOLTAGE DIMMING
FWD ELV- FORWARD-PHASE ELECTRONIC LOW VOLTAGE DIMMING
MLV- MAGNETIC LOW VOLTAGE (FORWARD PHASE) DIMMING
DMX- DMX512 CONTROL
DALI- DALI CONTROL
2-WIRE- LUTRON 2-WIRE DIMMING
3-WIRE- LUTRON 3-WIRE DIMMING
ECO- LUTRON ECOSYSTEM
NON-DIM- NON-DIMMING or SWITCHED
0-10V- 0-10V DIMMING
VIF- VERIFY IN FIELD
TBD- TO BE DETERMINED
TBC- TO BE CONFIRMED
LOCATION SHEET # ZONE DESCRIPTION FIXTURE TYPE LAMP/ SOURCE TYPE LOAD TYPE DRIVER TYPE DIMMING FIXTURE WATTS QTY.
TOTAL
WATTS
NOTES REV.
GROUND FLOOR
ADULT SECTION (100)
THROUGHOUT V2-LT100.0 100-a
SURFACE MOUNTED, NARROW
PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-
DIRECTIONAL, AMBIENT DIRECT
LUMINAIRE. SYSTEM REQUIRES
REMOTE, OPTIMIZED POWER
DISTRIBUTION POWER SUPPLIES
LA-01A N/A 0-10V
REMOTE
ELECT
D 6.6 w/ft. 622 ft. 4105.2w
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE
INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID
SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-
FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED
BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF
DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS
INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH
CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS
REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM
PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH
PER ARCHITECT.
` 4,105.2w
CIRCULATION (101)
CIRCULATION AND CHILDREN'S AREA V2-LT100.0 101-a
SURFACE MOUNTED, NARROW
PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-
DIRECTIONAL, AMBIENT DIRECT
LUMINAIRE. SYSTEM REQUIRES
REMOTE, OPTIMIZED POWER
DISTRIBUTION POWER SUPPLIES
LA-01B N/A 0-10V
REMOTE
ELECT
D 6.6 w/ft. 120 ft. 792.0w
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE
INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID
SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-
FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED
BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF
DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS
INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH
CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS
REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM
PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH
PER ARCHITECT.
CIRCULATION DESK V2-LT100.1 101-b SIGNAGE BY OTHERS LD-SIGNAGE N/A 0 TBD D 60.0w 1 60.0w
SIGNAGE BY SIGN FABRICATOR. LIGHTING TO BE BETWEEN 2700K AND 3500K
CCT DEPENDING ON COLOR OF BACKLIT SIGN. FINAL PRODUCT SHOULD
APPEAR 3000K CCT. SIGN TO BE DIMMABLE AND TIED TO LIGHTING CONTROL
SYSTEM. FABRICATOR TO ENSURE BACKLIGHT IS NOT VISIBLE WITH NO
"DIODING". SIGN SHOULD BE EVENLY ILLUMINATED AND NOT EDGE LIT FROM
SIDES. WATTAGE IS ESTIMATED ALLOWANCE.
` 852.0w
CHILDREN (102)
THROUGHOUT V2-LT100.0 102-a
SURFACE MOUNTED, NARROW
PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-
DIRECTIONAL, AMBIENT DIRECT
LUMINAIRE. SYSTEM REQUIRES
REMOTE, OPTIMIZED POWER
DISTRIBUTION POWER SUPPLIES
LA-01A N/A 0-10V
REMOTE
ELECT
D 6.6 w/ft. 236 ft. 1557.6w
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE
INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID
SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-
FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED
BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF
DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS
INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH
CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS
REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM
PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH
PER ARCHITECT.
` 1,557.6w
CHILDREN (103)
CIRCULATION AND CHILDREN'S AREA V2-LT100.0 103-a
SURFACE MOUNTED, NARROW
PROFILE 1.38"W x 0.60"H LINEAR, HIGH EFFICIENCY OMNI-
DIRECTIONAL, AMBIENT DIRECT
LUMINAIRE. SYSTEM REQUIRES
REMOTE, OPTIMIZED POWER
DISTRIBUTION POWER SUPPLIES
LA-01B N/A 0-10V
REMOTE
ELECT
D 6.6 w/ft. 68 ft. 448.8w
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE
INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID
SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE.
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-
FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED
BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF
DIMENSIONING REQUIRED. PROVIDE CONTINUOUS ILLUMINATED RUN
LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS
INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH
CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS
REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM
PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH
PER ARCHITECT.
` 448.8w
ZONE SCHEDULE
N2640 - MARPLE TOWNSHIP LIBRARY
09/14/2026
BRIAN ORTER LIGHTING DESIGN, LLC.
151 WEST 25TH STREET 11TH FLOOR / NEW YORK, NY 10001 / 212 674 6500
LOCATION SHEET # ZONE DESCRIPTION FIXTURE TYPE LAMP/ SOURCE TYPE LOAD TYPE DRIVER TYPE DIMMING FIXTURE WATTS QTY.
TOTAL
WATTS
NOTES REV.
ZONE SCHEDULE
N2640 - MARPLE TOWNSHIP LIBRARY
09/14/2026
TEEN (104)
TEEN'S AREA V2-LT100.0 104-a
SUSPENDED NOMINAL 28"
DIAMETER HIGH EFFICIENCY
STATIC WHITE, AMBIENT DIRECT
LED LIGHT RING PENDANT.
FIXTURE PROVIDED WITH LIGHT
DISTRIBUTION OPTIMIZED, LOW-
GLARE, DOT-FREE DIFFUSING LENS
MEDIA.
LA-03A N/A 0-10V
INTEGRAL
ELECT
D 25.0w 4 100.0w
FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN
FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR
DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND
SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.
TEEN'S AREA AND STUDY ROOMS V2-LT100.0 104-b
SUSPENDED NOMINAL 46"
DIAMETER HIGH EFFICIENCY
STATIC WHITE, AMBIENT DIRECT
LED LIGHT RING PENDANT.
FIXTURE PROVIDED WITH LIGHT
DISTRIBUTION OPTIMIZED, LOW-
GLARE, DOT-FREE DIFFUSING LENS
MEDIA.
LA-03B N/A 0-10V
INTEGRAL
ELECT
D 49.9w 3 149.7w
FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN
FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR
DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND
SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS AND DRAWINGS.
` 249.7w
VESTIBULE (105)
VESTIBULE V2-LT100.0 105-a
RECESSED MOUNTED 3.5" WIDE
LINEAR AMBIENT DIRECT LED
LIGHT LUMINAIRE WITH
REGRESSED DIFFUSING LENS.
FIXTURE PROVIDED WITH LIGHT
DISTRIBUTION OPTIMIZED, LOW-
GLARE, DOT-FREE DIFFUSING LENS
MEDIA. SYSTEM INTENDED TO BE
PROVIDED WITH CUSTOM MITERED
ANGLED CORNERS.
LA-04 N/A 0-10V
INTEGRAL
ELECT
D 7.0 w/ft. 48 ft. 336.0w
FINISH TO BE VERIFIED PER ARCH. MOUNTING TO BE VERIFIED PER GC.
�MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS
AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. VOLTAGE TO
�VERIFIED PER ELECTRICAL ENGINEER. FIXTURE TO BE PROVIDED WITH
REMOTE DIMMABLE POWER SUPPLIES CAPABLE OF 0-10V CONTROL. POWER
�SUPPLY TO BE LOCATED IN ACCESSIBLE, DRY, VENTILATED LOCATION
COORDINATED BY ARCHITECT. PROVIDE ALL ADDITIONAL MOUNTING
�ACCESSORIES, END CAPS LEADER/JUMPER CABLES AS REQUIRED FOR FULL
SYSTEM OPERATION.
VESTIBULE V2-LT100.0 105-b
RECESSED MOUNTED, NOMINAL 2"
APERTURE HIGH EFFICIENCY
AMERICAN-MADE ADJUSTABLE LED
DOWNLIGHT WITH CONICAL
REGRESSED FULL LENSED TRIM.
LA-05 N/A 0-10V
INTEGRAL
ELECT
D 15.0w 4 60.0w
VERIFY FIXTURE FINISH PER ID. VOLTAGE PER EE. FINISH TO BE VERIFIED
PER ARCH/INTERIOR DESIGNER. MOUNTING TO BE VERIFIED PER GC.
VOLTAGE TO BE VERIFIED PER ELECTRICAL ENGINEER.
` 396.0w
TOTAL WATTS: 7,609.3w
END OF ZONE SCHEDULE
ABBREVIATED TERMS:
LINE- LINE VOLTAGE DIMMABLE 2-WIRE- LUTRON 2-WIRE DIMMING
ELV- REVERSE-PHASE ELECTRONIC LOW VOLTAGE DIMMING 3-WIRE- LUTRON 3-WIRE DIMMING
FWD ELV- FORWARD-PHASE ELECTRONIC LOW VOLTAGE DIMMING ECO- LUTRON ECOSYSTEM
MLV- MAGNETIC LOW VOLTAGE (FORWARD PHASE) DIMMING NON-DIM- NON-DIMMING or SWITCHED
DMX- DMX512 CONTROL 0-10V- 0-10V DIMMING
DALI- DALI CONTROL VIF- VERIFY IN FIELD
BRIAN ORTER LIGHTING DESIGN, LLC.
151 WEST 25TH STREET 11TH FLOOR / NEW YORK, NY 10001 / 212 674 6500
212 674 6500 / 151 West 25th Street 11th Floor / New York, NY 10001 www.boldllc.com
PROJECT: N2640- Marple Township Library Preliminary Lighting Control Narrative – Design Development 09/14/2026
Summary
- FOH astronomical timeclock triggering with scene based. Preset scenes for specific time of day/year.
- FOH keypads as indicated below.
- BOH on/off switch keypads for BOH areas as required.
General Lighting Control The general lighting control system shall be controlled via user keypads and time-clock settings. Keypads shall be engraved, easy to read, and backlit. Any keypad shall be capable of recalling any preprogrammed scenes. The lighting control system shall be capable of triggering any zones based on astronomical sunrise and sunset, as well as arbitrary times as needed. Timeclock shall compensate for daylight savings time and leap year adjustment if required and retains power failure memory. Timer shall be capable of controlling any zone on the system independently and shall be able to recall preprogrammed scenes. The system shall be capable of automatic scene adjustments based on building operation guidelines. The lighting control system shall include hardwired, facility locked programming ports for the purpose of setting lighting levels and recalling scenes.
The lighting control system shall be capable of interfacing with Wi-Fi-enabled handheld device (e.g. Apple iPad) for setting lighting levels and recalling presets. Wi-Fi interface shall possess a lockable “programmer mode” capable of setting levels and recording presets, and a “user mode” with preset recall and temporary level adjustment only. Licenses for mobile device operation for both the operator and the lighting designer shall be included in the system bill of materials, and the commissioning agent shall be prepared to install and configure both licenses at the time of aim & adjust. The general lighting control system commissioning agent shall coordinate with building IT, other installers, and integrators as required for a fully functioning system, including Wi-Fi access for both programming and daily operation.
System programming interface shall possess a password protected access capable of setting levels and recording presets, and creating and editing timeclock events, as well as preset recall and temporary level adjustment. Mobile device operation for both the operator and the lighting designer shall be included in the system bill of materials, and the commissioning agent shall be prepared to install and configure system access at the time of aim & adjust. The general lighting control system commissioning agent shall coordinate with building IT, other installers, and integrators as required for a fully functioning system for both programming and daily operation.
The general contractor shall be responsible for scheduling control system commissioning in accordance with manufacturer’s submittal documents or three (3) weeks prior to the desired start of commissioning, whichever is greater.
The provided wall-box control/keypad(s) shall be coordinated with the electrical engineer and to be located at an accessible location as indicated on the architectural and/or electrical drawings. The keypad engraving shall be responsible by the electrical contractor and/or commissioned control specialist to be coordinated with the architect/interior designer.
Emergency Lighting:
The Control System shall include capability and all necessary components for designating certain circuits as emergency lighting circuits.
Quantity, locations and required equipment TBD by Electrical Engineer and to be documented within the Electrical Drawings.
Dimmer Rack(s):
Dimmer Rack and Interface locations is dependent upon size of rack(s) to be located at locations indicated on the Architectural drawings and/or Electrical drawings.
Final location to be coordinated with Architect and Client.
Interfaces – General (Lighting Control System) All interfaces indicated below should be tied to an astronomical time clock and to be used for manual override only. All interfaces listed below are inclusive of all front of houses spaces.
A. One (1) Wi-Fi enabled handheld control devices (e.g. Apple iPad/iPhone and/or laptop) with control software/app.
a. (1) Handheld control devices to be provided by operations. Ownership/operations to confirm.
b. Handheld control devices must be capable of controlling all spaces tied to the lighting control system.
B. Library
a. One single-gang, 4-button keypad with 4 preset scenes to be located behind the circulation desk with one duplicate keypad located at desired BOH location. All keypads are recommended to be locked and only accessible by operations.
b. One single-gang, 4-button keypad with 4 preset scenes to be located at Staff point desk.
c. Provide all code required sensors. Sensors to be dual technology to include passive infrared and ultrasonic sensing.
d. For all BOH support spaces provide code-required switching and sensors. All sensors to be dual technology to include passive infrared and ultrasonic.
All keypads must be concealed from direct view of guests. All locations to be coordinated with the Architect, Interior Designer and/or control system integrator, to be approved by the owner.
212 674 6500 / 151 West 25th Street 11th Floor / New York, NY 10001 www.boldllc.com
Daily Time-Clock Scenes/Global Scenes Scene does not exist on physical keypad. It is a daily programmed scene triggered by system clock.
Sequence of Operations
Below is the lighting control intent for the project. The size and scale of the system shall be determined upon selection of the control system. All lighting fixtures tied to the control system must be provided with the required dimming ballast, drivers and/or compatibility interfaces capable 1% dimming minimum. Provide all required ceiling mounted occupancy/vacancy sensors as required per local code compliance. All vacancy/occupancy sensors shall be dual-technology (Infrared and Ultra Sonic) ready.
All front of house spaces shall be dimmable and tied to the lighting control system coordinated with the Astronomical time-clock and to be override by wall box control or handheld control device. The wall station control shall be located at all spaces notated in section “Interfaces- General”, hidden from public view and only accessible to operations staff.
All lighting controls are to be recalled via keypads indicated above. All areas shall be programmed with scenes corresponding to the following times of day (times TBC by owner/operator), and shall fade naturally between scenes and to be set to a 3 to 5 second maximum fade delay:
*Subject to change, pending Project Design.
The keypad shall include the following scenes with preliminary dimming percentages. Final lighting level settings to be done on-site with lighting designer and operations during opening of project. Bill of materials shall include ample time for any trouble shooting and light level settings.
Scene Name Preset Default Levels Dimming Delay (s)
Scene 1 High All on at 90% 3-5 seconds
Scene 2 Medium All on at 50% 3-5 seconds
Scene 3 Low All on at 30% 3-5 seconds
Scene 4 All Off All off at 0% 3-5 seconds
ALL RECOMMENDED LIGHT LEVELS TO BE CONFIRMED ON SITE WITH LUTRON COMMISSIONER AND CLIENT.
All noted Scenes above are to be indicated and pre-set by the lighting control systems integrator as set baseline. All lighting scenes will be set during BOLD final commissioning of design (Aim & Adjust Phase). All lights will be adjusted with lux level meter readings to meet the following minimum standard criteria established IES (Illuminating Engineering Society) design standards.
All scenes shall be accessible at any time through button stations and connected wireless devices.
Recommended Lighting Control System BOLD recommends Lutron Electronics as the project Lighting Controls manufacturer and to be used as the basis of design guidelines and benchmarked against other approved controls vendors. All recommended keypads to Lutron Palladiom 4-button for single gang and 8-button for double gang.
Recommended Manufacturers (Smart Controls)
- Lutron (Quantum or equal)
- Lutron (Athena)
Recommended Manufacturers (Wallbox Controls)
- Lutron (Athena)
MARPLE TOWNSHIP LIBRARY
J R KELLER LLC
09/14/2026
DESIGN DEVELOPMENT
0REVISION:
SURFACE MOUNTED, NARROW PROFILE 1.38"W x 0.60"H
LINEAR, HIGH EFFICIENCY OMNI-DIRECTIONAL, AMBIENT
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01A
THROUGHOUT
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 1 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
W/ft.
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01A
THROUGHOUT
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 2 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01A
THROUGHOUT
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 3 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01A
THROUGHOUT
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 4 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01A
THROUGHOUT
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 5 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01B
CIRCULATION AND CHILDREN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 6 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01B
CIRCULATION AND CHILDREN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 7 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01B
CIRCULATION AND CHILDREN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 8 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01B
CIRCULATION AND CHILDREN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 9 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
DIRECT LUMINAIRE. SYSTEM REQUIRES REMOTE, OPTIMIZED
POWER DISTRIBUTION POWER SUPPLIES
D es cr ip tio n Type
LA-01B
CIRCULATION AND CHILDREN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 10 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
VODE
Manufacturer
#(707-Z2-SL-[SYSTEM LENGTH]-[RAIL LENGTH]-T7-0-[REMOTE POWER]-AE-X-0-Z-SO-30-S4-0-WH-0)
Part Number
PER EE
Voltage
REMOTE ELECT
Ballast/Trans/Drvr
SURFACE MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es
FIXTURE IS RED LIST APPROVED AND BAA/BABA APPROVED. FIXTURE INTENDED TO BE INTEGRATED DISCREETLY INTO ACOUSTICAL CEILING GRID SYSTEM BY ARMSTRONG, WITHOUT ANY VISIBLE MOUNTING HARDWARE. FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED, LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA. CEILING MOUNT SYSTEM TO BE CONFIRMED BY ARCH. FIXTURE RUNS IN STRAIGHT CONDITIONS. FIELD VERIFICATION OF DIMENSIONING REQUIRED.
PROVIDE CONTINUOUS ILLUMINATED RUN LENGTHS AS REQ'D. MANUFACTURER TO PROVIDE SHOP DRAWINGS INDICATING RUN LENGTHS AND CONFIGURATIONS FOR VARIOUS LENGTH CONDITIONS. EC TO CONFIRM IF OPTIONAL 6'-0" PRE-INSTALLED WHIP IS REQ'D. EC TO VERIFY THE DIMMING COMPATIBILITY WITH CONTROL SYSTEM PRIOR TO INSTALLATION. EE TO VERIFY VOLTAGE. VERIFY FIXTURE FINISH PER ARCHITECT.
N/A
Project: N2640
Input Watts
6.6
6.6
Lamp Watts
SUSPENDED NOMINAL 28" DIAMETER HIGH EFFICIENCY
STATIC WHITE, AMBIENT DIRECT LED LIGHT RING PENDANT.
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,
LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.
D es cr ip tio n Type
LA-03A
TEEN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 11 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
EUREKA
Manufacturer
#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-
[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])
Part Number
PER EE
Voltage
INTEGRAL ELECT
Ballast/Trans/Drvr
PENDANT MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS
AND DRAWINGS.
N/A
Project: N2640
Input Watts
Lamp Watts
W
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,
LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.
D es cr ip tio n Type
LA-03A
TEEN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 12 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
EUREKA
Manufacturer
#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-
[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])
Part Number
PER EE
Voltage
INTEGRAL ELECT
Ballast/Trans/Drvr
PENDANT MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS
AND DRAWINGS.
N/A
Project: N2640
Input Watts
Lamp Watts
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,
LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.
D es cr ip tio n Type
LA-03A
TEEN'S AREA
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 13 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
EUREKA
Manufacturer
#(4246-28-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-
[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])
Part Number
PER EE
Voltage
INTEGRAL ELECT
Ballast/Trans/Drvr
PENDANT MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS
AND DRAWINGS.
N/A
Project: N2640
Input Watts
Lamp Watts
SUSPENDED NOMINAL 46" DIAMETER HIGH EFFICIENCY
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,
LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.
D es cr ip tio n Type
LA-03B
TEEN'S AREA AND STUDY ROOMS
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 14 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
EUREKA
Manufacturer
#(4246-46-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-
[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])
Part Number
PER EE
Voltage
INTEGRAL ELECT
Ballast/Trans/Drvr
PENDANT MOUNTED
Mounting
Lamps Per Fixture
0-10V
Control Type
N ot es FINAL SUSPENSION HEIGHT TO BE CONFIRMED BY ARCH AND ADJUSTED IN FIELD. VERIFY VOLTAGE PER EE. VERIFY FIXTURE FINISH PER ARCH/INTERIOR DESIGNER. EC TO VERIFY FIXTURE CEILING MOUNTING TYPE AND SUSPENSION AGAINST ARCHITECTURAL SPECIFICATIONS
AND DRAWINGS.
N/A
Project: N2640
Input Watts
49.9
49.9
Lamp Watts
FIXTURE PROVIDED WITH LIGHT DISTRIBUTION OPTIMIZED,
LOW-GLARE, DOT-FREE DIFFUSING LENS MEDIA.
D es cr ip tio n Type
LA-03B
TEEN'S AREA AND STUDY ROOMS
Lo ca tio n
M A
R
PL
E
TO
W N
SH
IP
L
IB
R A
R Y
W
ES
T
TH
S
T
TH
F
LO
O
R N
EW
Y
O R
K, N
Y
W W
W .B
R
IA
N O
R
TE
R .C
O M
D
ES
IG
N
D
EV
EL
O
PM
EN
T
Page 15 of 27Revision: 0 Date: 09/14/2026
Notes Notes
So ur ce In fo
3000K/90+CRI
ColorLamp Manufacturer
N/A
Lamp Info/Part #
Fi xt ur e
In fo rm at io n
EUREKA
Manufacturer
#(4246-46-LED-30-90-[VOLTAGE PER EE]-DV-AC-[CABLE LENGTH]-RC1-RCC-[CANOPY FINISH PER ARCH/ID]-
[POWER CORD FINISH PER ARCH/ID]-[EXTERIOR SHADE FINISH PER ARCH/ID])
Part…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .