2-Bid C26-08 – SCCPSS Alternative Schools Renovation GMC PROJECT MANUAL - V4 .pdf
PDF 3 MB Posted
- Attached to
- SCCPSS Alternative Schools Renovations
- Solicitation number
- BID C26-08
- Issued by
- Chatham County, Georgia
About this file
This document is a comprehensive Project Manual for the SCCPSS (Savannah County Charter Public School System) Alternative Schools Renovation project located in Garden City, Georgia, prepared by Goodwyn Mills Cawood, LLC. The project involves renovation of an existing school facility to accommodate four different school programs: Building Bridges High School, Building Bridges Middle School, Wings Elementary, and SCELA. The project manual, dated October 3, 2025, contains detailed technical specifications across multiple divisions including architectural, structural, mechanical, electrical, and site work, with a total of 6 volumes and a project number of ASAV240002.
The project manual includes extensive technical specifications covering everything from site clearing and earthwork to complex systems like fire detection, intrusion detection, and communication enhancement systems. The renovation appears to be a comprehensive modernization effort, with specifications detailing precise requirements for materials, installation methods, quality control, and performance standards. While specific budget details are not provided in the document, the breadth and depth of the specifications suggest a significant capital investment in modernizing educational facilities. The manual emphasizes compliance with national standards, local building codes, and specific requirements of authorities having jurisdiction, indicating a thorough approach to school renovation and educational infrastructure improvement.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MANUAL
SCCPSS ALTERNATIVE SCHOOLS RENOVATION
Garden City, Georgia
October 3, 2025
Issue for Construction
Prepared By
Go od wy n M i l ls Ca w oo d, LL C
114 Ba rn a rd St .
Sui te 114 - 2B
Sav an na h , G A 314 01
T 9 12. 226. 16 67 w w w . g m c n e tw o r k . c o m
GMC PROJECT NUMBER: ASAV240002
Volume 4
OWNERSHIP OF DOCUMENTS AND DISCLAIMER
The Project Manual, Technical Specifications, Drawings, and all other documents relating to this project have been prepared for this individual and particular project, and for the exclusive use of the original Owner, developer or other party so indicated.
Actual project conditions and as-built conditions may vary significantly. Changes made during bidding, negotiations, construction, due to additions or deletions of portions of this project, and/or for other reasons, may not be indicated in these documents.
These documents may not be used or relied upon as a certification of information indicated, or used for any other project, by any third parties or other parties, for any purpose whatsoever, without the prior written consent of Goodwyn Mills Cawood, LLC, or prior to receipt of mutually agreed to compensation paid to Goodwyn Mills Cawood, LLC, therefore.
The ownership, copyrights, and all other rights to these documents are reserved by Goodwyn
Mills Cawood, LLC, including in part, all copies thereof in any form or media. Reproduction of the material contained in these documents or substantial quotation of their provisions without prior written permission of Goodwyn Mills Cawood, LLC, violates the copyright and common laws of the United States and will subject the violator to legal prosecution.
Goodwyn Mills Cawood, LLC
Post Office Box 242128
Montgomery, AL 36124-2128 and
Birmingham, Alabama
Andalusia, Alabama
Auburn, Alabama
Daphne, Alabama
Eufaula, Alabama
Huntsville, Alabama
Brentwood, Alabama
Mobile, Alabama
New Orleans, Louisiana
Opelika, Alabama
Vernon, Alabama
Atlanta, Georgia
Augusta, Georgia
Brunswick, Georgia
Savannah, Georgia
Columbia, South Carolina
Greenville, South Carolina
Nashville, Tennessee
Pensacola, Florida
Sarasota, Florida
Tampa, Florida
Charlotte, North Carolina
ARCHITECTURE■ENGINEERING■ENVIRONMENTAL■GEOTECHNICAL■INTERIOR DESIGN
LANDSCAPE ARCHITECTURE■PLANNING■SURVEYING■TRANSPORTATION
SCCPSS ALTERNATIVE SCHOOLS RENOVATION GARDEN CITY, GEORGIA
GOODWYN MILLS CAWOOD, LLC. PROJECT MANUAL TABLE OF CONTENTS
GMC PROJECT NO. ASAV240002 1 of 6
PROJECT MANUAL
TABLE OF CONTENTS
DIVISION 0 - PROCUREMENT AND CONTRACTING REQUIREMENTS:
00 00 10
00 00 20
TABLE OF CONTENTS
CONTRACT DOCUMENTS
DIVISION 1 - GENERAL REQUIREMENTS:
01 11 00
01 14 00
01 21 00
01 22 13
01 23 00
01 25 00
01 26 00
01 29 00
01 31 00
01 32 00
01 32 33
01 33 00
01 40 00
01 42 00
01 45 00
01 50 00
01 58 00
01 60 00
01 71 23
01 73 29
01 74 00
01 74 19
01 77 20
01 78 23
01 78 39
01 78 43
01 79 00
SUMMARY OF WORK
WORK RESTRICTIONS
ALLOWANCES
UNIT PRICES
ALTERNATES
SUBSTITUTION PROCEDURES
CONTRACT MODIFICATION PROCEDURES
PAYMENT PROCEDURES
PROJECT MANAGEMENT AND COORDINATION
CONSTRUCTION PROGRESS DOCUMENTATION
PHOTOGRAPHIC DOCUMENTATION
SUBMITTAL PROCEDURES
QUALITY REQUIREMENTS
REFERENCES STANDARDS AND DEFINITIONS
QUALITY CONTROL
TEMPORARY FACILITIES
PROJECT IDENTIFICATION
PRODUCT REQUIREMENTS
FIELD ENGINEERING
CUTTING AND PATCHING
CLEANING
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
PROJECT CLOSEOUT
OPERATION AND MAINTENANCE DATA
PROJECT RECORD DOCUMENTS
SPARE PARTS
DEMONSTRATION AND TRAINING
DIVISION 2 – EXISTING CONDITIONS:
02 41 19 SELECTIVE DEMOLITION
DIVISION 3 - CONCRETE:
03 30 00 CAST-IN-PLACE CONCRETE
GMC PROJECT NO. ASAV240002 2 of 6
03 36 60
03 51 13
03 62 00
SEALED CONCRETE FLOOR
CEMENTITIOUS ROOF DECK
NON-SHRINK GROUTING
DIVISION 4 - MASONRY:
04 01 05
04 22 00
MASONRY RESTORATION AND CLEANING
CONCRETE UNIT MASONRY
DIVISION 5 - METALS:
05 12 00
05 31 00
05 40 00
05 50 00
05 51 33
05 52 00
STRUCTURAL STEEL FRAMING
STEEL DECKING
COLD-FORMED METAL FRAMING
METAL FABRICATIONS
EXTERIOR ALUMINUM LADDER
METAL RAILINGS
DIVISION 6 – WOOD, PLASTICS AND COMPOSITES:
06 10 00
06 10 53
06 41 16
ROUGH CARPENTRY
MISCELLANEOUS ROUGH CARPENTRY
PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
DIVISION 7 - THERMAL AND MOISTURE PROTECTION:
07 10 00
07 19 00
07 21 16
07 26 50
07 27 26
07 41 13
07 50 01
07 54 23
07 60 00
07 71 14
07 71 29
07 72 13
07 84 00
07 84 13
07 84 43
07 92 00
07 92 19
07 95 00
DAMPROOFING
WATER REPELLENTS
BLANKET INSULATION
UNDER SLAB VAPOR BARRIER
FLUID-APPLIED MEMBRANE AIR BARRIERS
METAL ROOF PANELS (STANDING SEAM METAL ROOFS)
LOW ROOF
THERMOSPLASTIC POLYOLEFIN (TPO) MEMBRANE ROOFING
FLASHING AND SHEET METAL
MANUFACTURED COPINGS AND ROOF EDGE FASCIAS
MANUFACTURED ROOF EXPANSION JOINTS
MANUFACTURED CURBS
FIRESTOPPING
PENETRATION FIRESTOPPING
FIRE RESISTIVE JOINT SYSTEMS
JOINT SEALANTS
ACOUSTICAL JOINT SEALANTS
EXPANSION CONTROL
DIVISION 8 - OPENINGS:
08 11 13 HOLLOW METAL DOORS AND FRAMES
GMC PROJECT NO. ASAV240002 3 of 6
08 14 16
08 31 13
08 41 13
08 71 00
08 74 00
08 80 00
08 87 23
FLUSH WOOD DOORS
ACCESS DOORS AND FRAMES
ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
DOOR HARDWARE
ACCESS DOOR CONTROL HARDWARE
GLAZING
SAFETY AND SECURITY FILMS
DIVISION 9 - FINISHES:
09 05 61
09 21 16
09 22 16
09 24 00
09 29 00
09 29 20
09 30 00
09 51 13
09 54 46
09 65 00
09 65 13
09 65 66
09 68 13
09 84 33
09 91 00
09 96 00.1
09 96 00.5
09 96 46
MOISTURE VAPOR EMISSION CONTROL
GYPSUM BOARD ASSEMBLIES
NON-STRUCTURAL METAL FRAMING
CEMENT PLASTERING
GYPSUM BOARD
FINISHING GYPSUM BOARD
TILING
ACOUSTICAL PANEL CEILINGS
FELT CEILING ACOUSTICAL PANELS
RESILIENT FLOORING
RESILIENT BASE
RUBBER ATHLETIC FLOORING REPAIR AND REFINISH
TILE CARPETING
ACOUSTICAL WALL ABSORBERS, DIFFUSERS, & TILES
PAINTING
HIGH PERFORMANCE COATINGS (Exterior)
HIGH PERFORMANCE COATINGS (Interior)
INTUMESCENT PAINTING
DIVISION 10 - SPECIALTIES:
10 11 00
10 11 16
10 14 00
10 21 13
10 26 13
10 28 13
10 44 00
10 51 13
10 73 16
10 75 00
10 82 16
10 85 00
MARKERBOARDS, TACKBOARDS AND ACCESSORIES
INTERACTIVE DISPLAY PANELS (WHITE-BOARDS)
SIGNAGE
PHENOLIC-CORE TOILET COMPARTMENTS
PADDED WALL SYSTEMS
TOILET ACCESSORIES
FIRE PROTECTION SPECIALTIES
METAL LOCKERS
PREFABRICATED CANOPY
FLAGPOLE
MESH SCREENS
KNOX BOX
DIVISION 11 - EQUIPMENT:
11 31 00
11 52 13
11 66 23
APPLIANCES
PROJECTION SCREENS
GYMNASIUM EQUIPMENT
GMC PROJECT NO. ASAV240002 4 of 6
11 66 47
ELECTRONIC SCOREBOARDS
DIVISION 12 - FURNISHINGS:
12 24 13
12 35 53
12 36 61
12 66 00
ROLLER WINDOW SHADES
WOOD LABORATORY CASEWORK
SOLID SURFACING COUNTERTOPS
TELESCOPING STANDS REPAIR AND REFURBISHMENT
DIVISION 13 – SPECIAL CONSTRUCTION:
NOT USED
DIVISION 14 – CONVEYING EQUIPMENT:
14 42 16 VERTICAL PLATFORM WHEELCHAIR LIFT
DIVISION 21 -FIRE SUPPRESSION:
21 05 00
21 05 23
21 05 53
21 13 00
21 30 00
COMMON WORK RESULTS FOR FIRE SUPPRESSION
VALVES FOR FIRE-SUPPRESSION PIPING
IDENTIFICATION FOR FIRE SUPPRESSION
FIRE-SUPPRESSION SPRINKLER SYSTEMS
FIRE PUMPS
DIVISION 22 - PLUMBING:
22 05 00
22 05 17
22 05 19
22 05 23
22 05 29
22 05 53
22 07 19
22 10 05
22 10 06
22 30 00
22 40 00
GENERAL PLUMBING REQUIREMENTS
SLEEVES AND SLEEVE SEALS FOR PIPING
METERS AND GAUGES FOR PLUMBING PIPING
GENERAL-DUTY VALVES FOR PLUMBING PIPING
SUPPORTS FOR PIPING AND EQUIPMENT
IDENTIFICATION FOR PIPING AND EQUIPMENT
PLUMBING PIPING INSULATION
PLUMBING PIPING
PLUMBING PIPING SPECIALTIES
PLUMBING EQUIPMENT
PLUMBING FIXTURES
DIVISION 23 -HEATING, VENTILATING, AND AIR CONDITIONING:
23 05 00
23 05 16
23 05 17
23 05 19
23 05 23
23 05 29
23 05 33
23 05 48
GENERAL HVAC REQUIREMENTS
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING
SLEEVES AND SLEEVE SEALS FOR HVAC PIPING
METERS AND GAUGES FOR HVAC PIPING
GENERAL-DUTY VALVES FOR HVAC PIPING
SUPPORTS FOR HVAC PIPING AND EQUIPMENT
HEAT TRACING FOR HVAC PIPING
VIBRATION AND SEISMIC CONTROLS FOR HVAC
GMC PROJECT NO. ASAV240002 5 of 6
23 05 53
23 05 93
23 07 13
23 07 19
23 09 00
23 09 34
23 09 93
23 21 13
23 21 14
23 21 23
23 23 00
23 25 00
23 31 00
23 33 00
23 33 00
23 34 00
23 37 00
23 38 13
23 40 00
23 52 16
23 57 00
23 65 14
23 74 16
23 74 33
23 81 26
23 81 46
23 82 39
IDENTIFICATION FOR PIPING AND EQUIPMENT
TESTING, ADJUSTING, AND BALANCING FOR HVAC
DUCT INSULATION
HVAC PIPING INSULATION
INSTRUMENTATION AND CONTROLS FOR HVAC
VARIABLE-FREQUENCY CONTROLLERS FOR HVAC
SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
HYDRONIC PIPING
HYDRONIC SPECIALTIES
HYDRONIC PUMPS
REFRIGERANT PIPING
HVAC WATER TREATMENT
HVAC DUCTS AND CASINGS
AIR DUCT ACCESSORIES
DUCTWORK AND DUCT ACCESSORIES
HVAC FANS
AIR OUTLETS AND INLETS
COMMERCIAL-KITCHEN HOODS
HVAC AIR CLEANING DEVICES
CONDENSING BOILERS
HEAT EXCHANGERS FOR HVAC
INDUCED-DRAFT COOLING TOWERS
PACKAGED ROOFTOP HEAT PUMPS
DEDICATED OUTDOOR AIR UNITS
SPLIT-SYSTEM AC AND HEAT PUMPS
WATER-SOURCE UNITARY HEAT PUMPS
ELECTRIC HEATERS
DIVISION 26 -ELECTRICAL:
26 05 05
26 05 19
26 05 26
26 05 29
26 05 33.13
26 05 33.16
26 05 36
26 05 53
26 09 23
26 21 00
26 24 16
26 27 26
26 28 13
26 28 16.16
26 32 13
26 36 00
26 51 00
26 56 00
SELECTIVE DEMOLITION FOR ELECTRICAL
CONDUCTORS AND CABLES
GROUNDING AND BONDING
HANGERS AND SUPPORTS
CONDUIT FOR ELECTRICAL SYSTEMS
BOXES FOR ELECTRICAL SYSTEMS
CABLE TRAYS FOR ELECTRICAL SYSTEMS
IDENTIFICATION FOR ELECTRICAL SYSTEMS
LIGHTING CONTROL DEVICES
LOW-VOLTAGE ELECTRICAL SERVICE ENTRANCE
PANELBOARDS
WIRING DEVICES
FUSES
ENCLOSED SWITCHES
ENGINE GENERATORS
TRANSFER SWITCHES
INTERIOR LIGHTING
EXTERIOR LIGHTING
GMC PROJECT NO. ASAV240002 6 of 6
DIVISION 27 – COMMUNICATIONS:
27 51 16
27 51 29.17
CLASSROOM INTERCOM SYSTEMS
RADIO COMMUNICATION ENHANCEMENT SYSTEMS
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY:
283111
284600
BUILDING INTRUSION DETECTION
FIRE DETECTION AND ALARM
DIVISION 31 – EARTHWORK:
31 10 00
31 20 00
31 25 00
SITE CLEARING
EARTH MOVING
EROSION AND SEDIMENTATION CONTROL
DIVISION 32 – EXTERIOR IMPROVEMENTS:
32 12 16
32 13 13
32 16 13
32 17 23
32 18 16
32 31 13
ASPHALT PAVING
CONCRETE PAVING
CURBS AND GUTTERS
PAVEMENT MARKINGS
PLAYGROUND SAFETY SURFACING
PLAYGROUND FENCE AND GATES
DIVISION 33 – UTILITIES:
33 10 00
33 30 00
33 40 00
WATER UTILITIES
SANITARY SEWERAGE
STORMWATER UTILITIES
END OF TABLE OF CONTENTS
GOODWYN MILLS CAWOOD, LLC CLASSROOM INTERCOM SYSTEMS
GMC PROJECT NO. ASAV240002 275116 - 1 of 5
SECTION 275116
CLASSROOM INTERCOM SYSTEMS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. IP intercom system.
1.2 RELATED REQUIREMENTS
A. Section 260526 - Grounding and Bonding.
1.3 REFERENCE STANDARDS
A. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
1.4 SYSTEM DESCRIPTION
A. Replacing existing analog public address and intercom system for voice with new IP based public address and intercom system, existing call buttons to be reused, speakers and administrative phones to be replaced in same locations.
1.5 SUBMITTALS
A. Shop Drawings: Indicate electrical characteristics and connection requirements. Indicate layout of equipment mounted in racks and cabinets, component interconnecting wiring, and wiring diagrams of field wiring to speakers and remote input devices.
B. Product Data: Provide data showing electrical characteristics and connection requirements for each component.
C. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
D. Project Record Documents: Record actual locations of speakers, control equipment, and outlets for input/output connectors.
E. Operation Data: Include instructions for adjusting, operating, and extending the system.
F. Maintenance Data: Include repair procedures and spare parts documentation.
1.6 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience with service facilities within 100 miles of Project.
B. Installer Qualifications: Authorized installer of specified manufacturer with service facilities within 100 miles of Project.
GMC PROJECT NO. ASAV240002 275116 - 2 of 5
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Bogen Communications, Inc 7000 Series
B. Johnson Controls / Simplex.
C. Rauland.
2.2 INTERCOM SYSTEM
A. Provide required components for a complete and operational system to replace existing analog system with full functionality of a new IP based system.
1. Features:
a. Shall be IP based.
b. Speakers shall be 2x2 talkback speakers utilizing existing speaker wire.
c. Existing call buttons shall remain and operate with new system.
d. Provide pre-alert tone to classrooms for intercom calls and general announcements.
e. Ability to produce user defined tone signals for time tones or emergency tones.
f. Shall be connected to fire alarm system to be overridden in the event of a fire alarm.
g. Ability to select the tone on an all-call basis from any, administrative telephones.
h. The system shall have a Windows° based PC administration programming tool which allows the administrative personnel to easily manage Audio Sources, Class Change schedules, paging groups, time updates, holiday schedules and day/night mode operation from their desktop PC. Systems that require propriety consoles, special LCD displays or solely utilize DTMF for changes to perform these functions shall not be acceptable.
B. System Cabinet: Rack mounted or wall mounted.
2.3 COMPONENTS
A. Speakers: 8 inch (200 mm)
1. Corridor Speakers: The speaker shall be a Bogen Model CSD2X2VR Drop-In Ceiling Speaker or equal, which shall be fully enclosed and constructed of industrial grade steel. It shall be comprised of a damped high-compliance factory-mounted 8" loudspeaker that shall consist of an 8" treated paper main cone, a secondary high frequency cone, and a 10 ounce magnet. The unit shall have a 70V/25V transformer with power taps of 4, 2, 1, 0.5, and 0.25 watts, selectable by rotaryswitch. Tap speakers at 1 watt.
2. Classroom Speakers: The speaker shall be a Bogen Model CSD2X2 Drop-In Ceiling Speaker or equal, which shall be fully enclosed and constructed of industrial grade steel. It
GMC PROJECT NO. ASAV240002 275116 - 3 of 5 shall be comprised of a damped high-compliance factory-mounted 8" loudspeaker that shall consist of an 8" treated paper main cone, a secondary high frequency cone, and a 10 ounce magnet. The unit shall have a 70V/25V transformer with power taps of 4, 2, 1, 0.5, and 0.25 watts, selectable by rotaryswitch. Tap speakers at .5 watts.
3. Recessed Speakers: The loudspeaker assembly shall be a Bogen model S86T725PG8UVR or equal, 8" cone-type loudspeaker, having a frequency response of at least 50 Hz to 12 kHz. Axial sensitivity shall be 95 dB, measured at 1-watt/4 feet. The loudspeaker shall have a 6 oz. ceramic magnet and a 3/4" voice coil. A transformer, capable of matching an 8-ohm loudspeaker to a 25-volt or 70-volt line, and providing power taps of 4, 2, 1, 1/2, 1/4, and 1/8 watts shall be included. The loudspeaker shall be assembled on a 13" steel ceiling grille, finished in bright white semi-gloss enamel. Assembly depth shall be 3-1/4".
Tap speakers at 2 watts.
4. Exterior Recessed Speakers: The loudspeaker shall be a Lowell 8C10MRB-T72. Bogen Model FMH15T, flange-mount, reentrant type horn loudspeaker. The frequency response shall be 600 Hz to 14 kHz. Rated power output shall be 15 watts, RMS continuous when driven by a 70V or 25V amplifier system. Dispersionshall be 100º. Sound pressure level, measured 1 meter on axis with 15-watt input shall be at least 115 dBspl and 104 dBspl with a 1-watt input. The unit shall incorporate a seven-position weather-sealed switch, to allow matching the loudspeaker to a 70V or 25V constant-voltage line. Power handling capacity shall be adjustable at 15, 7.5, 3.6, 1.8, or 0.9 watts for 70V systems and 15, 7.0, 1.8, 0.9, 0.5, 0.25, or 0.125 watts for 25V systems. The loudspeaker shall be of weatherproof, vandal-resistant, all-metal construction. The loudspeaker shall include a self-aligning, field-replaceable diaphragm. Screw terminals shall be provided for connection to the audio line and a strain relief for the audio line will be provided. Mount speaker in existing flush mounted box and repaint and reuse existing grille. with a new heavy-duty cast aluminum grille, and an adapter ring shall be available separately to complete installation of the speaker. Tap exterior speakers at 7 watts.
B. Administrative Phones:
1. Reception Desk: The Nyquist VoIP Admin Phone (NQ-T1100) or equal with Color Touch display panel shall show the time of date, the station numbers, and the call-in priority of staff stations that are calling in. Depending upon the system CoS programming, a VoIP Admin Phone can display menus to activate Zone Paging, All-Call Paging, Emergency All-Call Paging, alarm signals, audio files, and external functions. The Staff phone has been designed with two RJ-45 Gigabit Ethernet ports one for connection to a PoE port on the LAN and one pass through for connecting a PC or other networked device. The phone can be desk or wall mountable with included bracket.
2. All other phone stations: The Nyquist VoIP Staff Phone (NQ-T2000) or equal with LCD display panel shall show the time of date and the station numbers and call-in priority of staff stations that are calling in. Depending upon the system CoS programming, a VoIP Staff Phone can display menus to activate Zone Paging, All-Call Paging, Emergency All- Call Paging, alarm signals, audio files, and external functions. The Staff phone has been
GMC PROJECT NO. ASAV240002 275116 - 4 of 5 designed with two RJ-45 Gigabit Ethernet ports one for connection to a PoE port on the LAN and one passthrough for connecting a PC or other networked device. Desk or wall mountable with included bracket.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Splice cable only in accessible junction boxes or at terminal block units.
C. Make cable shields continuous at splices and connect speaker circuit shield to equipment ground only at amplifier.
D. Install input circuits in separate cables and raceways from output circuits.
E. Provide protection for exposed cables where subject to damage.
F. Support cables above accessible ceilings to keep them from resting on ceiling tiles. Use spring metal clips or plastic cable ties to support cables from structure for ceiling suspension system.
Include bridle rings or drive rings.
G. Use suitable cable fittings and connectors.
H. Connect reproducers to amplifier with matching transformers.
I. Ground and bond equipment and circuits in accordance with Section 260526.
3.2 FIELD QUALITY CONTROL
A. Measure and record sound power levels at designated locations.
3.3 ADJUSTING
A. Adjust transformer taps for appropriate sound level.
B. Adjust devices and wall plates to be flush and level.
3.4 CLOSEOUT ACTIVITIES
A. Demonstration: Demonstrate operation of system to Owner's personnel.
1. Use operation and maintenance data as reference during demonstration.
2. Briefly describe function, operation, and maintenance of each component.
B. Training: Train Owner's personnel on operation and maintenance of system.
1. Use operation and maintenance manual as training reference, supplemented with additional training materials as required.
2. Provide minimum of two hours of training per site.
GMC PROJECT NO. ASAV240002 275116 - 5 of 5
3. Location: At project sites.
3.5 MAINTENANCE
A. Provide service and maintenance of public address system for 2 years from Date of Substantial Completion.
END OF SECTION 275116
GOODWYN MILLS CAWOOD, LLC RADIO COMMUNICATION ENHANCEMENT SYSTEMS
GMC PROJECT NO. ASAV240002 275129.17 - 1 of 12
SECTION 275129.17
RADIO COMMUNICATION ENHANCEMENT SYSTEMS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Active equipment.
B. Battery secondary power source.
C. Passive components.
1.2 RELATED REQUIREMENTS
A. Section 078400 - Firestopping.
B. Section 260526 - Grounding and Bonding.
C. Section 260553 - Identification for Electrical Systems: Identification products and requirements.
D. Section 284600 - Fire Detection and Alarm.
1.3 ABBREVIATIONS AND ACRONYMS
A. AHJ: Authorities having jurisdiction.
B. BDA: Bi-directional amplifier.
C. DAS: Distributed antenna system.
D. ERCES: Emergency responder communication enhancement system.
E. FACU: Fire alarm control unit.
F. FPGA: Field programmable gate array.
G. GROL: General radio operators license.
H. RF: Radio frequency.
I. UHF: Ultra high frequency.
J. VHF: Very high frequency.
1.4 DEFINITIONS
A. BDA: Active RF-emitting device, wired with coaxial cables, for amplification of band-selective or multi-band RF signals via uplink to base station and via downlink from base station to portable two-way radios for enhanced signals and improved coverage; also referred to as analog or digital signal boosters.
GMC PROJECT NO. ASAV240002 275129.17 - 2 of 12
B. Fiber DAS Master/Remote: Active RF-emitting device, wired with fiber-optic backbone, for distributing band-selective or multi-band RF signals via uplink to master/remote station and via downlink from master/remote station to portable two-way radio for enhanced signals and improved coverage.
C. ERCES: In-building, two-way radio communication enhancement system application. Installed to enhance effective operation of radio communications systems for fire, emergency medical services, or law enforcement agencies within building or structure. System used by firefighters, police, and other emergency services personnel.
D. Public Safety/First Responder: Public safety or first responder agencies charged with responsibilities of responding to emergency situations including, but not limited to, law enforcement departments, fire departments, and emergency medical companies.
1.5 REFERENCE STANDARDS
A. 47 CFR 90.219 - Use of Signal Boosters; Current Edition.
B. ICC (IFC) - International Fire Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
C. ISO 9001 - Quality Management Systems — Requirements; 2015, with Amendment (2024).
D. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.
E. NEMA EN 10250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2024.
NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
NFPA 72 - National Fire Alarm and Signaling Code; Most Recent Edition Cited by Referring Code or Reference Standard.
F. NFPA 1221 - Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems; 2019, with Amendment (2021).
G. NFPA 1225 - Standard for Emergency Services Communications; 2022.
H. UL 2524 - Emergency Responder Communication Enhancement Systems; Current Edition, Including All Revisions.
1.6 ADMINISTRATIVE REQUIREMENTS
A. Coordinate work with other sections, including fire alarm systems and associated communications cabling. See "Related Requirements" above.
B. Retransmission Agreement: Provide prior written approval from FCC license holder(s) of systems being enhanced; meet to review their established criteria for installation prior to beginning work; do not energize system before obtaining written approvals.
GMC PROJECT NO. ASAV240002 275129.17 - 3 of 12
C. Active RF-emitting devices and other active system components require FCC certification prior to installation.
1.7 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for products, including ratings, configurations, standard wiring diagrams, dimensions, finishes, service condition requirements, and installed features.
C. Shop Drawings:
1. Submit installation documentation required for plan review and permitting by AHJ and frequency license holder(s), including but not limited to floor plans showing locations of fire alarm system or other interconnects, enlarged drawn to identified scale plan view, and riser diagrams.
2. Show locations of components, circuits, and raceways; mark components with identifiers used in control unit programming.
3. Include system interconnection schematic riser diagram showing proposed and approved cable size and type; coordinated with floor plans and describing circuit class, survivability, and application specific information required by NFPA 72.
4. Include typical wiring diagrams for devices, equipment, interconnects, annunciators, passive components, and active equipment.
5. Include requirements and control unit diagrams for interfacing with other systems.
D. iBwave Design: Include iBwave software-simulated radio propagation modeling with heat maps showing predicted signal coverage levels within building.
E. Standby battery calculations.
F. Inspection and Test Reports:
1. Installer to submit inspection and test plan prior to closeout demonstration.
2. Field quality control reports inclusive of test results.
G. Installer qualifications.
H. Project Record Documents:
1. Submit complete project record drawings within 14 calendar days after initial acceptance test.
2. Provide record drawings similar to shop drawings, but revised to reflect changes made during construction.
GMC PROJECT NO. ASAV240002 275129.17 - 4 of 12
3. Upon completion of project, submit test records along with system diagrams, iBWave design, equipment specifications, RF link budget calculations, record submittals, and relevant design data as required by AHJ.
1.8 RF PRECONSTRUCTION BUILDING SURVEY FOR ERCES
A. Comply with requirements and standards for initial survey for public safety radio signal strength in accordance with NFPA 1225 (or NFPA 1221) and ICC (IFC).
B. Perform survey after building is substantially completed and prior to start of installation of electrical wiring.
C. Conduct survey using calibrated RF spectrum analyzer, system-compatible radio, or another suitable instrument with traceable NIST certificate of calibration. Analyze RF signal strength of ERCES signal into building and determine if amplification or distribution of signal is required.
Determine, measure, calculate and document inbound and outbound signal strengths as required by code.
D. Public safety radio signal level inside Owner's facility determined per code, ordinance, or AHJ requirements.
E. Follow acceptance testing procedure requirements listed in "Field Quality Control" in Part 3.
F. Include report summary and recommendation if ERCES design is required.
1.9 QUALITY ASSURANCE
A. Comply with requirements in accordance with the following:
1. AHJ.
2. Frequency license holder(s).
3. Local fire department.
4. Applicable local codes.
5. OSHA.
6. ICC (IFC).
7. NFPA 72.
8. NFPA 1225.
B. Register installed systems with FCC signal booster registry, regardless of system classification.
C. Obtain permits necessary for installation prior to commencement of work. Include permit costs and inspection fees.
D. Telephone Operators License: Tests conducted, documented, and signed by person in possession of FCC GROL. Testing personnel have certified and authorized by active RF-
GMC PROJECT NO. ASAV240002 275129.17 - 5 of 12 emitting equipment manufacturer in requirements for installation and operation of their equipment. Provide personnel qualifications as acceptable to AHJ and frequency license holder(s).
E. RF Preconstruction Building Survey Personnel: Performed by FCC technician holding current GROL license.
F. Designer Qualifications:
1. ERCES design performed by RF system designer.
2. iBwave Level 2 or higher certified personnel.
G. Manufacturer Qualifications: Certified for compliance with ISO 9001.
H. Installer Qualifications:
1. Company with minimum three years documented experience with similar systems and providing contract maintenance service as regular part of their business.
2. Familiar with products to be installed through documented manufacturer training, authorization, or equivalent demonstrated experience.
a. Honeywell Basis of Design System: Specialized training as provided by Honeywell Premier representative.
3. At least three years experience with radio communication systems.
4. FCC licensed and manufacturer certified for ERCES installation.
5. Licensed electrical or systems contractor in the State in which the Project is located.
I. Product Evaluation and Listing Organization Qualifications: Organization engaged in evaluation of products and services, including those recognized by OSHA as Nationally Recognized Testing Laboratory (NRTL), and acceptable to AHJ and frequency license holder(s).
1.10 DELIVERY, STORAGE, AND HANDLING
A. Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly identifying product name and manufacturer.
B. Store materials in clean, dry area indoors in accordance with manufacturer’s instructions.
C. Protect materials from damage during handling and installation.
1.11 FIELD CONDITIONS
A. Maintain field conditions within manufacturer's required service conditions during and after installation.
GMC PROJECT NO. ASAV240002 275129.17 - 6 of 12
1.12 WARRANTY
A. See Section 017800 - Closeout Submittals for additional warranty requirements.
B. System Equipment: Three years from date of final acceptance.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Bi-Directional Amplifier (BDA) or Fiber Distributed Antenna System (DAS) - Basis of Design:
Fiplex by Honeywell; www.buildings.honeywell.com/us/en/products/by-brand/fiplex/bda-and-fiber-das-system/#sle.
B. Source Limitations: Where possible, furnish system components and accessories produced by one manufacturer and obtained from one supplier.
2.2 TWO-WAY RADIO COMMUNICATION ENHANCEMENT SYSTEMS
A. Provide new ERCES to provide complete coverage in-building for public safety agencies as required by AHJ, consisting of required components (e.g., equipment, conduit, boxes, wiring, connectors, hardware, supports, accessories, software, system programming, and integration) as necessary for complete operating system that provides functional intent indicated. System users receive and transmit radio signals from two-way radios within building.
1. Basis of Design:
a. Fiplex by Honeywell BDA.
B. Products: Listed, classified, and labeled as suitable for purpose intended.
C. All Enclosures Color: Painted red with external labeling as required by AHJ.
D. Minimum System Components:
1. Active RF-emitting device.
2. Cabling.
3. Antennas.
4. Cable taps.
5. Connectors.
6. Power splitters.
7. Dedicated annunciator.
E. External filters, duplexers, power supplies, or other non-OEM additions or modifications of original equipment are not acceptable, except where technically required and without violating
GMC PROJECT NO. ASAV240002 275129.17 - 7 of 12
UL 2524 2nd Edition certification. If required, external filters manufactured or certified by ERCES manufacturer.
F. Power Sources:
1. System Design Voltage: DC.
2. Provide monitoring integrity of power sources in accordance with NFPA 1225 (or NFPA 1221) and ICC (IFC).
3. Provide at least two independent and reliable power supplies in accordance with NFPA 1225 (or NFPA 1221) and ICC (IFC).
4. Primary: Dedicated branch circuits from facility power distribution system in accordance with NFPA 72.
5. Secondary: Storage batteries with capacity to operate system for period specified by NFPA 1225 (or NFPA 1221).
a. External uninterruptable power supplies (UPSs) are not acceptable.
b. Dedicated Battery Storage Capacity:
1) Provide 12 hours of 100 percent system operation capacity.
2) Provide 25 percent additional overall battery capacity correction factor.
G. Wiring and Wiring Methods:
1. General Requirements:
a. Comply with requirements for wiring and wiring methods in accordance with NFPA 70.
b. Conductors and Cables Installed Exposed in Spaces Used for Environmental Air (only where specifically permitted): Plenum-rated, listed and labeled as suitable for use in return air plenums.
c. Special Occupancies: Comply with NFPA 70.
d. Comply with NFPA 70 for wire and cable plenum, riser, general-purpose, limited-use, and underground applications.
2. RF Coaxial Cable: CMP plenum.
H. Radio Coverage:
1. Provide critical areas such as emergency or fire command center, fire pump room, exit stairs, exit passageways, elevator lobbies, standpipe cabinets, sprinkler sectional valve locations, and similar critical areas as specified by AHJ, with 99 percent floor area radio coverage.
GMC PROJECT NO. ASAV240002 275129.17 - 8 of 12
2. Provide general building areas with 95 percent radio coverage or as specified by AHJ.
I. ERCES Signal Strengths:
1. Minimum DAQ of 3.0 or better and equivalent signal to interference noise ratio (SINR) applicable to technology for either analog or digital.
2. Downlink: Minimum signal strength of minus 95 dBm throughout coverage area.
3. Uplink: Minimum signal strength of minus 95 dBm received at AHJ radio system or as required by AHJ.
J. Provide FCC certification for active RF-emitting system components prior to installation.
Comply with applicable sections of FCC rules, including but not limited to the following:
1. Private Land Mobile Radio Services: FCC 47 CFR 90.219.
K. Under normal operating condition, maintain antenna isolation between donor antenna and inside antennas, DAS, to 20 dB minimum.
L. Survivability from attack by fire in accordance with NFPA 72, NFPA 1225 (or NFPA 1221), ICC (IFC) or as required by AHJ.
M. ERCES Supervision: See Section 284600.
2.3 ACTIVE EQUIPMENT
A. Provide FPGA-based active RF-emitting device listed and labeled as complying with agency listings and approval requirements as follows:
1. ICC (IFC).
2. NFPA 72.
3. NFPA 1225 (or NFPA 1221).
4. FCC.
5. UL 2524 2nd Edition.
6. ROHS compliant.
B. Support the following band operation:
C. Provide public safety type system with Class A or Class B active RF-emitting device, as designated by FCC or as required by AHJ.
D. FCC ID must be displayed on product in accordance with FCC.
E. Capable of field configuration via programmable software for frequency channels with adjustable bandwidths as specified by AHJ.
F. Active RF-emitting devices support Class A or Class B operation.
GMC PROJECT NO. ASAV240002 275129.17 - 9 of 12
1. Class A: Provide channel selective type with 75 kHz, 62.5 kHz, 50 kHz, 37.5 kHz, 25 kHz, and 12.5 kHz channel bandwidth options.
2. Class B: Provide wide-band filters of greater than 75 kHz to full-band.
G. Include oscillation suppression circuitry to protect public safety radio system in case of system malfunction or other causes. Circuitry allows for real-time automated oscillation correction and immediate detection capable of generating oscillation alarm, combined with programmable limited operation or auto-shutdown if performance migration fails.
H. Include uplink noise suppression function to eliminate uplink noise while in standby (e.g., no radio transmission from within building). Systems that produce measurable level of uplink noise while in standby not acceptable.
I. Include uplink and downlink squelch, per channel, per timeslot.
J. Rated minimum of 85 dB plus/minus 2.0 dB and gain adjustable by minimum of 28 dB range.
K. Maximum Propagation Delay Range: Designer determined, adjustable and with filter delay options for compliance with system requirements or per AHJ.
L. Maximum Noise: 9 dB; throughout its published operable uplink gain range.
M. Include built-in automatic supervision of system malfunctions, including battery systems where applicable.
N. Non-OEM Equipment Add-Ons and Modifications: Not acceptable.
O. Enclosure: NEMA 250 Type 4.
P. Basis of Design Products:
1. BDA:
2.4 BATTERY SECONDARY POWER SOURCE
A. Provide equipment, not limited to chargers and system monitoring, listed and labeled as complying with agency listings and approval requirements as follows:
1. ICC (IFC).
2. NFPA 72.
3. NFPA 1225 (or NFPA 1221).
4. FCC.
5. UL 2524 2nd Edition.
6. ROHS compliant.
B. Provide power automatically when primary power source is lost.
GMC PROJECT NO. ASAV240002 275129.17 - 10 of 12
C. Battery Charger and Related Components: Provide fully enclosed waterproof NEMA EN 10250, Type 4, approved enclosure.
D. Battery Type: Rechargeable sealed lead acid; listed or component recognized by nationally recognized testing laboratory.
E. Enclosure: NEMA 250 Type 4.
F. Basis of Design Products:
1. Fiplex HONBDA-BTTY Series; BBU with built-in annunciator; 100 AH or 200 AH, 24 VDC, rechargeable batteries included.
2.5 PASSIVE COMPONENTS
A. Provide passive component requirements in RF system design as required for complete system, included but not limited to passive RF-emitters, design frequency range, gain values, radiation patterns or heat maps, voltage standing wave ratio, polarization, power handling, impedance, connector types, environmental ratings, device losses, isolation characteristics, signal rejection, component size, form factor, attenuation values, output accuracy, and thermal stability.
B. Enclosure for Passive Components: NEMA 250 Type 4.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install products in accordance with NFPA 1225 (or NFPA 1221), NFPA 72, NFPA 70, state and local codes, manufacturer's instructions, and as indicated on drawings.
B. Install products in accordance with applicable requirements of NECA 1 (general workmanship).
C. Provide dedicated 20 amp branch circuit for battery system.
D. Conceal conduit, junction boxes, and conduit supports and hangers in finished areas. Conceal or expose conduit, junction boxes, and conduit supports and hangers in unfinished areas; maintain code required access and clearances.
E. UL 2524 Listed Equipment: Do not drill holes or field fabricate openings in UL 2524 listed equipment; this voids warranty, listing, and enclosure rating.
1. Mark equipment front with identifier "DO NOT DRILL INTO THIS CABINET" label.
2. See Section 260553.
F. Donor Antenna Mounting:
1. Fixed permanently on building were approved by AHJ.
G. Provide grounding and bonding in accordance with NFPA 70 Article 250, NFPA 70 Chapter 8 Communications Systems, and manufacturer's recommendations; see Section 260526.
GMC PROJECT NO. ASAV240002 275129.17 - 11 of 12
H. Install firestopping to preserve fire resistance rating of partitions and other elements; see Section 078400.
I. Identify system wiring, components, and overcurrent protective devices for branch circuits serving ERCES; see Section 260553.
3.2 FIELD QUALITY CONTROL
A. See Section 014000 - Quality Requirements for additional requirements.
B. Perform initial and acceptance inspection and testing in accordance with NFPA 1225 (or NFPA 1221) and requirements of AHJ for ERCES; document each inspection and test.
1. System gain requires setting and documented at time of final system test.
2. Provide coverage testing in accordance with NFPA 1225 (or NFPA 1221) and ICC (IFC) and as required by AHJ.
a. Testing Procedures:
1) Test building coverage for emergency communication systems, inside and outside, to and from the building, for the following minimums indicated in Part 2 "Two-Way Radio Communication Enhancement Systems" article, "Radio Coverage."
2) Capable of being tested throughout coverage area for both uplink and downlink by local fire department; received signal strength indicator (RSSI) measurement only.
3) Perform tests for cable insulation resistance and acceptance testing procedures in accordance with ICC (IFC) and NFPA 1225 (or NFPA 1221).
4) Utilize calibrated portable radios of same make and latest model used by AHJ.
5) Utilize spectrum analyzer or similar for monitoring oscillations from RF-emitting or other system active equipment.
6) Measure gain values of every ERCES amplifier and review test result against baseline data kept on file for annual testing.
7) Divide Coverage For Testing, Options:
(a) Maximum 20 equal areas, per building floor. From center of area, use two-way communications to and from outside of building for interfacing with AHJ's public system.
(1) Comply with NFPA 1225 (or NFPA 1221) and ICC (IFC) maximum square footage per area.
(2) Failing to communicate in more than one test area is failed acceptance test.
GMC PROJECT NO. ASAV240002 275129.17 - 12 of 12
(3) Failing to communicate in two adjacent areas is failed acceptance test.
(b) Utilize radios for simultaneous voice quality checks; subjective by testing personnel. Position one radio within 10 feet (3 m) to indoor antenna and second radio distance furthest away from indoor antenna. Both radios select difference frequencies within same band for testing.
(1) Signal strength less than DAQ 3.0 is failed acceptance test.
8) Nonconforming Work:
(a) Repositioning test location for better test results is not allowed.
(b) Alter system to meet coverage requirements and reacceptance test for compliance.
3. Record rated dB and gain adjustments and documented at time of final system test.
4. Provide documentation in submittals for "initial acceptance testing requirements" in accordance with NFPA 1225 (or NFPA 1221) Chapter 20, Testing.
C. Correct defective work, adjust for proper operation, and retest until entire system complies with Contract Documents.
3.3 CLEANING
A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.
3.4 PROTECTION
A. Protect installed system components from subsequent construction operations.
END OF SECTION 275129.17
GOODWYN MILLS CAWOOD, LLC BUILDING INTRUSION DETECTION
GMC PROJECT NO. ASAV240002 283111 - 1 of 8
SECTION 283111
BUILDING INTRUSION DETECTION
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Intrusion detection system requirements.
B. Alarm control units and accessory equipment.
C. Initiating devices.
D. Alarm notification appliances.
1.2 RELATED REQUIREMENTS
A. Section 260526 - Grounding and Bonding.
B. Section 260533.13 - Conduit for Electrical Systems.
C. Section 260553 - Identification for Electrical Systems: Identification products and requirements.
D. Section 281000 - Access Control: For interface with intrusion detection system.
1.3 REFERENCE STANDARDS
A. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.
B. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
C. UL 609 - Local Burglar Alarm Units and Systems; Current Edition, Including All Revisions.
D. UL 639 - Intrusion-Detection Units; Current Edition, Including All Revisions.
E. UL 1610 - Central-Station Burglar-Alarm Units; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate compatibility of devices for the installed locations with work provided under other sections or by others.
2. Coordinate the placement of sensors and keypads with millwork, furniture, equipment, etc. installed under other sections or by others.
3. Coordinate the work with other installers to provide communication lines required for alarm control unit connection to central station.
4. Notify Architect of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
GMC PROJECT NO. ASAV240002 283111 - 2 of 8
B. Sequencing:
1. Do not install sensors and keypads until final surface finishes and painting are complete.
1.5 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for each system component. Include ratings, configurations, standard wiring diagrams, dimensions, finishes, service condition requirements, and installed features.
C. Shop Drawings: Include plan views indicating locations of system components and proposed size, type, and routing of conduits and/or cables. Include system interconnection schematic diagrams. Include requirements for interface with other systems.
D. Design Data: Include standby battery calculations.
1.6 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
B. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.
C. Installer Qualifications: Company specializing in performing the work of this section with minimum three years documented experience with intrusion detection systems of similar size, type, and complexity and providing contract maintenance service as a regular part of their business; authorized representative of control unit manufacturer.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.
B. Store products in manufacturer's unopened packaging, keep dry and protect from damage until ready for installation.
1.8 FIELD CONDITIONS
A. Maintain field conditions within manufacturer's required service conditions during and after installation.
1.9 WARRANTY
A. See Section 017800 - Closeout Submittals, for additional warranty requirements.
B. Provide minimum two year manufacturer warranty covering repair or replacement due to defective materials or workmanship.
GMC PROJECT NO. ASAV240002 283111 - 3 of 8
PART 2 PRODUCTS
2.1 INTRUSION DETECTION SYSTEM REQUIREMENTS
A. Provide new intrusion detection system consisting of all required equipment, conduit, boxes, wiring, connectors, hardware, supports, accessories, software, system programming, etc. as necessary for a complete operating system that provides the functional intent indicated.
B. Alarm Control Unit: New addressable alarm control panel located as indicated.
C. Keypads: Located as indicated.
D. Initiating Device Requirements:
1. Protected Premises: Entire building as indicated.
2. Provide motion detectors to detect intruder in designated areas.
3. Provide glass break detectors to monitor:
E. Alarm Notification and Reporting Requirements:
1. Activate alarm notification at alarm control unit and associated keypads/annunciators with appropriate zone information displayed.
2. Activate local notification appliances.
a. Interior: Provide siren located as indicated on drawings.
b. Exterior: Provide siren located as indicated on drawings.
3. Transmit alarm report to listed remote central station under contract with facility.
a. Primary Communication Means: Digital cellular communications.
b. Secondary Communication Means: Internet/intranet (IP addressing).
F. Interface with Other Systems:
1. Provide products compatible with other systems requiring interface with intrusion detection system.
2. Interface with access control system as specified in Section 281000.
G. Provide products listed, classified, and labeled as suitable for the purpose intended.
1. Local Alarm Units and Systems: Listed and labeled as complying with UL 609.
2. Central Station Alarm Units: Listed and labeled as complying with UL 1610.
H. Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits: Comply with FCC requirements of 47 CFR 15, for Class B, consumer application.
GMC PROJECT NO. ASAV240002 283111 - 4 of 8
2.2 ALARM CONTROL UNITS AND ACCESSORY EQUIPMENT
A. Manufacturers:
1. Bosch Security Systems, LLC: www.boschsecurity.us/#sle.
2. Digital Security Controls (DSC); a brand of Tyco International: www.dsc.com/#sle.
3. Honeywell International, Inc; Honeywell Security: www.buildings.honeywell.com/#sle.
B. Alarm Control Panel: Modular construction.
1. Enclosure: Lockable; provide tamper protection.
2. Power Supply:
a. Primary Power: 120 VAC; provide suitable transformer/power supply; supervised for loss of AC power.
b. Secondary Power: Standby battery; provide suitable capacity for minimum standby time required by listing requirements, applicable codes, and authority having jurisdiction, but not less than four hours; provide suitable battery charger; supervised for low battery condition; protected from accidental reversal of battery leads.
C. Alarm Initiating Circuits: Supervised.
1. Hardwired Zones: Supports both normally closed and normally open conventional (non-addressable) initiating devices.
2. Addressable Zones: Supports addressable initiating devices and modules using multiplexed polling loops.
D. Alarm Notification Circuits: Supervised.
E. Communications Interfaces: Supervised.
1. Supports system reporting to central station receivers via integral interface or accessory interface modules using:
a. Telephone lines.
b. Digital cellular network.
c. Internet/intranet (IP addressing).
F. Keypads: Supervised.
1. Provide interface to alarm control unit for system control and remote annunciation.
2. Provide visual notification of system status and zone information.
3. Provide audible notification to indicate system status, entry/exit delay, and alarm situations; provide separate distinguishable sounds for alarm and trouble conditions.
GMC PROJECT NO. ASAV240002 283111 - 5 of 8
4. Keypad Type: Only LCD or graphic touch screen keypads are acceptable. Do not use LED keypads.
a. Graphic Touch Screen Keypads: Displays system status and zone information using plain English on graphic display; touch screen interface.
b. LCD Keypads: Displays system status and zone information using plain English on alphanumeric display; illuminated keys.
G. Peripheral Devices: Supervised; provide tamper protection.
H. Output Relays:
1. Relay Modules: Form C relays (normally open and normally closed); provide tamper protection.
2. Programmable to respond to system events, according to defined scheduling, or by manual activation from keypad.
I. User Codes:
1. Each user code to be individually assignable to any defined authority level for configurable access to system features and functions.
J. Scheduling:
1. Provide time/calendar-based scheduling capability for automated system control.
2. Supports open/close schedules for control of arming/disarming and reporting.
3. Supports timed events including, but not limited to:
a. Point bypass/unbypass.
b. Relay activate/deactivate.
K. Event Log:
1. Stores system events including time, date, partition, zone, and user code where applicable.
2. Supports viewing of event log on keypads.
2.3 INITIATING DEVICES
A. Manufacturers: Same as manufacturer of alarm control units where possible.
B. General Requirements:
1. Provide devices suitable for intended application and location to be installed.
2. Outdoor Units: Weather resistant, suitable for outdoor use.
3. Addressable Systems:
GMC PROJECT NO. ASAV240002 283111 - 6 of 8
a. Addressable Devices: Individually identifiable by control unit.
b. Provide suitable addressable modules for connection to conventional (non-addressable) devices and other components that provide a dry closure output.
C. Motion Detectors:
1. Listed and labeled as complying with UL 639.
2. Passive Infrared (PIR) Motion Detectors: Designed to detect intruder by sensing movement of thermal energy between zones.
D. Glass Break Detectors:
1. Listed and labeled as complying with UL 639.
2. Suitable for the glass type to be monitored.
3. Accurately discriminates false alarms from true glass break events.
4. Furnished with selectable…