2-2403-052 Carbon County School District - Food Warehouse HVAC-Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- NS26-39
- Issued by
- Cache County, Utah
About this file
These documents are engineering and construction design plans for a Carbon County School District Food Distribution Warehouse Air Conditioning project located in Utah. The project involves replacing existing HVAC and mechanical systems, including demolishing current evaporative coolers, radiant tube heaters, and installing new rooftop units (RTUs), ductless heat pump systems, and associated electrical and plumbing infrastructure. The project includes four Trane YHC 072 rooftop units, each with 150,000 BTU gas input, two Mitsubishi ductless heat pump systems (one indoor and one outdoor unit), and comprehensive electrical and plumbing system modifications.
The project appears to be fully funded and is designed to upgrade the mechanical systems of an existing food distribution warehouse. The electrical system modifications include updating panel boards, disconnects, and wiring to support the new equipment, with careful attention to existing electrical service capacity. The total estimated electrical demand addition is 141.9 amps, which will be accommodated by the existing 400-amp service that has approximately 248.7 amps remaining. The gas piping schedule indicates a total gas demand of 1,274,000 BTU, with provisions for connecting the new rooftop units and potentially retaining some existing tube heaters. The design emphasizes compliance with local and national electrical and mechanical codes, and includes detailed specifications for equipment installation, wiring, and system integration.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
A AMPS
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPS INTERRUPTING
CAPACITY
AWG AMERICAN WIRE GAUGE
B BATTERY
BC BARE COPPER
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
C CONDUIT
CO CARBON MONOXIDE
CT CURRENT TRANSDUCER
CU COPPER MATERIAL
DED DEDICATED
DFA DROP FROM ABOVE
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMERGENCY/EGRESS
EMT ELECTRICAL METALLIC
TUBING
ENT ELECTRICAL NON-METALLIC
TUBING
ER EXISTING TO BE RELOCATED
EX EXISTING TO REMAIN
FMC FLEXIBLE METAL CONDUIT
GC GENERAL CONTRACTOR
GEC GROUND ELECTRICAL
CONDUCTOR AT SES
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFEP GROUND FAULT EQUIPMENT
PROTECTOR
GND GROUND
IMC INTERMEDIATE METAL CONDUIT
IG ISOLATED GROUND
KCMIL 1000 CIRCULAR MILS (MCM)
LF LOW FREQUENCY, 520 HZ
LFMC LIQUID-TIGHT FLEXIBLE METAL
CONDUIT
LFNC LIQUID-TIGHT FLEXIBLE NON-
METAL CONDUIT
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
N1 NEMA 1
N3R NEMA 3R
N NEW
NL NIGHT LIGHT, BYPASS LOCAL
SWITCHING
PC PLUMBING CONTRACTOR
POC POINT OF CONNECTION
POS POINT OF SALES
R RELOCATED
RX RECEIVER
RM ROOF MOUNTED
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC
CONDUIT
SBJ SYSTEM BONDING JUMPER
SCA SHORT CIRCUIT AMPERES
TX TRANSMITTER
TC TEMPERATURE CONTROL
CONTROLLER
TR TAMPERPROOF
UG UNDERGROUND
UNO UNLESS NOTED
OTHERWISE
VA VOLT/AMPS
VIF VERIFY IN FIELD
W WATTS
WP WEATHERPROOF/NEMA 3R
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE
CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS
INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT
DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO
BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE
PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN
WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID
ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL
SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE
SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE,
THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY
INCOMPLETE SYSTEM SHALL BE MADE COMPLETE AND OPERABLE.
2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE
ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE
ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA
COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS
WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE GREATER THAN
SPECIFIED AND/OR DIMENSIONED ON THE PLANS.
3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE
NECESSARY BY INTERFERENCE WITH OTHER WORK.
4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR
FOR THE CONNECTIONS OF ALL EQUIPMENT SHOWN ON THE PLANS - ARCHITECTURAL,
MECHANICAL, ETC.
5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE
CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING
IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE
CORRECTED AT THE CONTRACTORS EXPENSE.
6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND
LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE
AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS
AND SPACE THAT EQUIPMENT IS BEING INSTALLED WITHIN.
7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT
LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM.
VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS
NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.
8. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING
CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT
GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE
ELECTRICAL SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
9. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING
CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS OR CABINETS AND SHALL
MOVE THE PANELS AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS
NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.
10. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE
INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT,
BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.
11. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY
ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE OF 10 FEET WITHOUT
REQUIRING ADDITIONAL COST TO THE PROJECT.
12. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT
IS SET IN PLACE USING INDUSTRY STANDARD METHODS AND PRACTICES.
13. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH
STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH
GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN
DIRECT CONTACT WITH THE SOIL.
14. FLEXIBLE CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL
CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS
OF FLEXIBLE OR SEALTITE CONDUIT SHALL NOT BE GREATER THAN 72" INCHES.
15. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE.
16. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL
SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE
APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE
CONTRACTORS EXPENSE.
17. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB
RATED NYLON PULL CORD.
18. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS,
WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR).
THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION
PURPOSES WILL BE AT THE COST OF THE ELECTRICAL CONTRACTOR.
19. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120/277VAC BRANCH
CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN)+1#12(CU,THHN)GND IN 3/4"
EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC
BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 125' TO ACCOMMODATE FOR
VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES
ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.
20. CONDUCTORS SHALL BE COPPER, 600VAC RATED, TYPE THHN/THWN-2 UNLESS
OTHERWISE NOTED. CONDUCTORS SIZES UP TO #10AWG SHALL BE SOLID AND #8AWG
AND LARGER SHALL BE STRANDED.
21. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE
EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND
OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR
SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE
DIRECTED BY THE EQUIPMENT SUPPLIER.
22. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER
COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER,
PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND
EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION
FROM THE PREMISES.
23. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY
ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY
INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR
WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S
EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE OF EQUIPMENT
AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.
24. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL
CONTRACTOR TO PROVIDE CONDUIT AND DEVICE MOUNTING BOXES FOR
THERMOSTATS AND OTHER MECHANICAL CONTROLS.
25. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH
MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN
AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED
WITH THE ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL
WIRING METHODS.
26. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE
CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS
PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE
THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT
COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.
27. SUBMIT A SCALED LAYOUT (1/4" = 1') OF ALL ELECTRICAL ROOMS BASED ON THE
ELECTRICAL GEAR AND EQUIPMENT SUBMITTALS.
28. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT
SWITCHES INDICATING THE CIRCUIT IT IS TIED TO. USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER.
LABELS LENGTH SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.
29. FUSED DISCONNECTS TO BE HEAVY DUTY.
GENERAL NOTES
E
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:3
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
E L
E C
T R
IC
A
L T
IT
L
E S
H E
E T
E-001
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
E_ELECTRICAL SYMBOL SCHEDULE
SYMBOL
Schedule Description
Schedule Description MOUNTING COMMENTS
CONVENIENCE
OUTLET,
CUSTOM HEIGHT
44", UNLESS
INDICATED
OTHERWISE
(6)
CONVENIENCE
OUTLET,
WEATHER
PROOF
18"
CONVENIENCE
OUTLET,
CUSTOM HEIGHT
44", UNLESS
INDICATED
OTHERWISE
(6)
NON FUSED
DISCONNECT
(13) (14)
E_EQUIPMENT SYMBOL SCHEDULE
SYMBOL Schedule Description MOUNTING COMMENTS
PANEL BOARD, SURFACE 6'-6" TO TOP
PANEL BOARD, SURFACE 6'-6" TO TOP
PANEL BOARD, SURFACE 6'-6" TO TOP
MAIN POWER DISTRIBUTION PANEL
PANEL BOARD, SURFACE 6'-6" TO TOP
MAIN POWER DISTRIBUTION PANEL
SEE PLANS (13) (14)
ELECTRICAL SHEET INDEX
E-001 ELECTRICAL TITLE SHEET
ED-101 ELECTRICAL DEMO PLAN
E-111 POWER & SYSTEMS FLOOR PLAN
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
E-602 ELECTRICAL SCHEDULES
NO. DATE DESCRIPTION
F
1 2 3 4 5
A
B
C
D
ED-101
'B'
'C'
'MD'
'A'
'L'
'F'
'CT CABINET'
'METER'
'D'
(E)
(E)
(E)
(E)
(E) (E)
(E)(E)
(E)
(E)
(E)
ED-101
ED-101
DISCONNECT
F-7,9,11
(ER)
DISCONNECT
F-1,3,5
(ER)
DISCONNECT
F-2,4,6
(ER)
DISCONNECT
F-8,10,12
(ER)
DISCONNECT
B-6,8,10 C-8,10,12
(ER)
'MSD'
FLOOR LEVEL 1
100' - 0"
PANEL 'D' (E) DISCONNECT
D-8,10,12 (E)
DISCONNECT
D-2,4,6 (E)
COMPRESSOR
RIGHT (E)
COMPRESSOR
RIGHT (E)
FLOOR LEVEL 1
100' - 0"
LEVEL 1 TOW
110' - 0"
SOUTHEAST
FREEZER UNIT
(ER)
NORTHEAST
FREEZER UNIT
(ER)
DISCONNECT
F-2,4,6
(ER)
DISCONNECT
F-8,10,12
(ER)
FLOOR LEVEL 1
100' - 0"
LEVEL 1 TOW
110' - 0"
DISCONNECT
B-6,8,10
(ER)
DISCONNECT
C-8,10,12
(ER)
SOUTH
FREEZER
WEST UNIT
(ER)
SOUTH
FREEZER
EAST UNIT
(ER)
SOUTHWEST
FREEZER
UNIT
(ER)
NORTHWEST
FREEZER
UNIT
(ER)
DISCONNECT
F-1,3,5 F-7,9,11
(ER)
E: EXISTING TO REMAIN
EN: EXISTING TO BE REPLACED WITH NEW
ER: EXISTING TO BE RELOCATED
EX: EXISTING TO BE REMOVED AND OFFERED UP TO THE OWNER
FOR FIRST RIGHTS OF REFUSAL. PROPERLY AND LEGALLY
DISPOSE OF MATERIAL IF REFUSED.
GENERAL DEMOLITION KEY
E
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:4
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
E L
E C
T R
IC
A
L D
E M
O P
L A
N
ED-101
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
1/8" = 1'-0"ED-101
1 ELECTRICAL DEMO PLAN 1/4" = 1'-0"ED-101
2 PANEL D
DEMOLITION GENERAL NOTES
A FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR
CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING
OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL
EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR
REPLACE AS REQUIRED.
B FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/DATA WIRING
AS NECESSARY FOR CONTINUITY OF ANY WIRING ORIGINATING OUTSIDE
THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA
EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR
REPLACE AS REQUIRED.
D DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES AND
BACK BOXES AS NECESSARY WHERE NEW WALL CONSTRUCTION WILL
INTERSECT AN EXISTING WALL. FURNISH AND INSTALL CONDUIT AND WIRE
AS REQUIRED FOR CONTINUITY OF CIRCUIT(S).
E CONTRACTOR TO COORDINATE WITH OWNER FOR ITEMS TO BE
SALVAGED PRIOR TO DEMOLITION. CONTRACTOR RESPONSIBLE FOR
DISPOSING OF ANY MATERIAL THAT THE OWNER DOES NOT WANT TO
KEEP.
F EC SHALL COORDINATE WITH ALL OTHER TRADES DURING DEMOLITION
AND CONSTRUCTION TO FACILITATE TIMELY WORK.
G ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF DEBRIS AT ALL TIMES.
H CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS, CEILINGS ETC. TO
MATCH EXISTING CONDITIONS. PENETRATIONS SHALL BE SEALED WITH
FIRE RATED CAULK.
1/4" = 1'-0"ED-101
3 2 DISCONNECTS - RACK MOUNTED
1/4" = 1'-0"ED-101
4 4 DISCONNECTS - RACK MOUNTED
KEYNOTES
1 EXISTING DISCONNECT TO BE RELOCATED WITH CONDENSING UNIT. REMOVE
COMPLETE EXISITNG CIRCUIT BACK TO SOURCE BREAKER IN PANEL 'F'.
W P
F
F
1 2 3 4 5
A
B
C
D (E) 'B' 'A'
'MD'
'C'
'F'
'L'
'CT CABINET'
'METER'
'D'
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
DHP-1
DFC-1
RTU-3
D- 5,7,9
RTU-4
F- 7,9,11
(E)
F- 18
Control Panel - ATC
F-24
D- 11,13,15
RTU-1
RTU-2
F- 1,3,5
F- 2,4,6
F- 8,10,12
B- 6,8,10
C- 8,10,12
A- 7,9,11
A- 1,3,5
'MSD'
F- 14,16
E
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:4
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
P O
W E
R
S Y
S T
E M
S F
L O
O R
P L
A N
E-111
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
1/8" = 1'-0"E-111
1 POWER & SYSTEMS FLOOR PLAN
KEYNOTES
1 UNIT SUPPLIED WITH A CONVENIENCE OUTLET WITH POWER PROVIDED BY SINGLE
POINT CONNECTION.
FIRE
EXIT
44"
18"
48"
WITHIN 18"
96"
72"
84"
18"
WITHIN 60"
80"
44" 44"
FINISHED FLOOR
NOTES:
1. THE ELCTRICAL CONTRACTOR SHALL
VERIFY THE EXACT LOCATION OF ALL
TELEVISION OUTLETS WITH THE
ARCHITECT PRIOR TO INSTALLATION.
2. ALL DEVICES SHOWN ON THE DETAIL ARE
FOR REFERENCE OF MOUNTING HEIGHTS
ONLY. THE ELECTRICAL CONTRACOR
SHALL FIELD ADJUST THE HEIGHTS OF THE
DEVICES AS REQUIRED FOR PROPER
MOUNTING OF THE DEVICES.
3. ALL DEVICES REQUIRES FOR THE
PROJECT MAY NOT APPEAR ON THIS
DETAIL. ALL ITEMS SHOWN ON THIS DETAIL
MAY NOT BE REQUIRED FOR THIS
PROJECT.
4. FIRE ALARM NORN/STROBES ARE TO BE
MOUNTED NO HIGHER THAN 96" AND NO
LOWER THAN 80" TO CENTER OF DEVICE.
STRUCTURE
STRUCTURE
STRUCTURE STRUCTURE
ALL THREAD (SIZE AS
REQUIRED) 3/8" MIN.
BEAM CLAMPS OR
HANGER CLAMPS (AS
REQUIRED BY WEIGHT
SUPPORTED)
RACEWAY. (3/4" - 6")
CONDUIT HANGER
BEAM CLAMPS OR
HANGER CLAMPS
(AS
REQUIRED BY
WEIGHT
SUPPORTED)
RACEWAY. (3/4" - 6")
NOTES:
1. WIRE SHALL NOT BE USED AS A
COMPONENT OF ANY RACEWAY
HANGER SYSTEM.
2. DO NOT NOT SUPPORT ANY
RACEWAY THAN THAN 1" FROM
BOTTOM CORD OF STEEL
TRUSSES.
CL
6"
LC
5 4
(TYP.)
EMT
(TYP.)
EMT
EMT
EMT
NOTES:
1. TYP. FOR WOOD AND METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN. COORDINATE RING DEPTH TO BE
FLUSH WITH FINISHED SURFACE, UNLESS NOTED OTHERWISE.
3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCH. AND
MECH. DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.
4. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN
THE SAME STUD SPACEMUST BE SEPARATED BY A MIN. OF 6"
HORIZONTAL DISTANCE.
5. ELECTRICAL BOXES INSTALLED IN FIRE RESISTANT WALLS OR
PARTITIONS SHALL COMPLY WITH IBC 714.3.2.
6. INSULATED THOAT EMT CONNECTOR.
7. CADDY FASTENER, THROUGH STUD CABLE/CONDUIT SUPPORT
'FB12P'.
8. ADUSTABLE BAR HANGER.
9. TYPICAL DEVICE JUNCTION BOX.
REFER TO SECTION
FOR ATTACHMENT OF
ALL THREAD ROD TO
KINDORF CHANNEL
1 1/2"x1 1/2"-12GA. KINDORF
CHANNEL OR APPROVED
SUBSTITUTE
3/8" ALL THREAD,
MINIMUM. INCREASE
ROD SIZE IF WEIGHT
REQUIRES PER ROD
MANUFACTURERS
RECOMMENDATIONS.SUPPORT CONDUIT
WITH KINDORF STRAP
OR APPROVED
SUBSTITUTE.
BEAM CLAMPS OR
HANGER CLAMPS AS
REQUIRED BY WEIGHT
SUPPORTED
PROVIDE 25% SPACE CAPACITY
NUT
WASHER
WASHER
NUT
E
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:4
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
E L
E C
T R
IC
A
L D
E T
A
IL
S
E-501
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
NO SCALEE-501
1 MOUNTING HEIGHT DETAIL
NO SCALEE-501
2 RACEWAY SUPPORT METHODS DIAGRAM
NO SCALEE-501
3 ROUGH-IN DETAIL
NO SCALEE-501
4 TRAPEZE SUPPORT DETAIL
E
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:4
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
E L
E C
T R
IC
A
L S
C H
E D
U L
E S
E-601
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
TNotes:
Total Est. Demand: 30.0 A
Total Conn.: 30.0 A
Total Est. Demand: 10806 VA
Total Conn. Load: 10806 VA
Motor 10806 VA 100.00% 10806 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 30.0 A 30.0 A 30.0 A
Total Load: 3602 VA 3602 VA 3602 VA
17 SPARE 5 20 A 1 - 0 0 18
15 OUTLET UNDER PANEL A 2 20 A 1 - 0 0
- 2 20 A 2 AIR HANDLER
13 OFFICE 2 20 A 1 - 0 0 14
11 GARAGE DOOR / OUTLET ON COLUMN 2 20 A 1 - 0 0
- 2 50 A 2 CONDENSER
9 0 3602 10
7 0 3602 8
SPARE 5 40 A 3 -
0 3602
- 3 40 A 1,2 SOUTH FREEZER - WEST UNIT (CU-3)
3 SPACE 4 -- 1 - -- 0 - 1 20 A 2 CONDESER RECEPTACLE 4
1 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 2
CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 200.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A
Supply From: Phases: 3 Mains Type: MAIN CB
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL
Branch Panel: B EXISTING
Notes:
Total Est. Demand: 0.0 A
Total Conn.: 0.0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Motor 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 0.0 A 0.0 A 0.0 A
Total Load: 0 VA 0 VA 0 VA
11 0 0 12
220V OUTLET 2 20 A 2 -
0 0 10
7 SOUTH FREEZER LIGHTS 2 20 A 1 - 0 0
- 3 40 A 1,2 SOUTH FREEZER - EAST UNIT (CU-4)
5 SOUTH FREEZER HEAT TAPE 2 20 A 1 - 0 0 6
3 OUTLET BY PANEL 2 20 A 1 - 0 0 4
1 FREEZER ALARM 2 20 A 1 - 0 0
- 3 30 A 5 SPARE
CKT Circuit Description Code BRK P Size A (VA) B (VA) C (VA) Size P BRK Code Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 200.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A
Supply From: MD Phases: 3 Mains Type: MLO
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL
Branch Panel: C EXISTING
Notes:
Total Est. Demand: 0.0 A
Total Conn.: 0.0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Motor 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 0.0 A 0.0 A 0.0 A
Total Load: 0 VA 0 VA 0 VA
11 0 0 12
9 0 0 10
NORTHWEST FREEZER UNIT (CU-1) 1,3 50 A 3 -
0 0
- 3 100 A 2 PANEL 'B'
5 0 0 - 1 20 A 5 SPARE 6
3 0 0 - 1 20 A 5 SPARE 4
SOUTHWEST FREEZER UNIT (CU-2) 1,3 40 A 3 -
0 0 - 1 20 A 5 SPARE 2
CKT Circuit Description Code BRK P Size A (VA) B (VA) C (VA) Size P BRK Code Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 200.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A
Supply From: MD Phases: 3 Mains Type: MAIN CB
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL
Branch Panel: A EXISTING
BY THE EXTERNAL FORMATION OF ICE ON THE ENCLOSURE.
INGRESS OF WATER (RAIN, SLEET, SNOW); AND THAT WILL BE UNDAMAGED
WITH RESPECT TO HARMFUL EFFECTS ON THE EQUIPMENT DUE TO THE
OBJECTS (FALLING DIRT), AND THAT PROVIDE A DEGREE OF PROTECTION
EQUIPMENT INSIDE THE ENCLOSURE AGAINST INGRESS OF SOLID FOREIGN
HAZARDOUS PARTS, THAT PROVIDE A DEGREE OF PROTECTION OF THE
PROVIDE A DEGREE OF PROTECTION TO PERSONNEL AGAINST ACCESS TO
3R ENCLOSURES CONSTRUCTED FOR EITHER INDOOR OR OUTDOOR USE THAT
ENCLOSURE AGAINST INGRESS OF SOLID FOREIGN OBJECTS (FALLING DIRT).
THAT PROVIDE A DEGREE OF PROTECTION OF THE EQUIPMENT INSIDE THE
PROTECTION TO PERSONNEL AGAINST ACCESS TO HAZARDOUS PARTS AND
1 ENCLOSURES CONSTRUCTED FOR INDOOR USE THAT PROVIDE A DEGREE OF
RATING NEMA STANDARDS / DEFINITIONS
NEMA ENCLOSURES
K2 = 12.9 x [ 1 + 0.00323 x [T2 - 75] ]
CALCULATION USED TO ADJUST K FACTORS FOR 60 °C AND 90 °C CONDUCTORS:
K FACTORS USED: 60 °C = 12.275, 75 °C = 12.9, 90 °C = 13.525
SECTION 8.4.1 [ADDENDUM C] AND IECC C405.9.
BRANCH VOLTAGE DROP MUST NOT EXCEED 5 PERCENT PER ASHRAE 90.1,
PERCENT, THESE TABLES CANNOT BE USED. THE COMBINED FEEDER PLUS
WHERE FEEDER CIRCUIT VOLTAGE DROP [AT DESIGN LOAD] EXCEEDS 2
MAINTAIN A TARGET MAXIMUM OF 3 PERCENT VOLTAGE DROP.
1-WAY DISTANCES IN FEET FOR BRANCH CIRCUITS [AT DESIGN LOAD] THAT
THE PURPOSE OF THESE TABLES IS TO DISPLAY THE MAXIMUM ALLOWABLE
1 PH VD CALCULATION USED: 2 x K x Q x I x [D / ECM] 3 PH VD CALCULATION USED: 1.732 x K x Q x I x [D / ECM]
VOLTAGE DROP NOTES
Notes:
Total Est. Demand: 141.9 A
Largest Motor 10950 VA 125.00% 13688 VA Total Conn.: 134.3 A
Receptacle 180 VA 100.00% 180 VA Total Est. Demand: 51124 VA
Other 500 VA 100.00% 500 VA Total Conn. Load: 48386 VA
Motor 36756 VA 100.00% 36756 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Conn. Load: 48386 VA
10 SPARE 3 100.0 A 100.0 A 0 VA --
9 SPARE 3 100.0 A 100.0 A 0 VA --
8 PANEL 'D' 3 250.0 A 250.0 A 21900 VA CIRCUIT 11,13,15
7 SPACE 1 -- -- -- --
6 PANEL 'A' 3 200.0 A 200.0 A 0 VA CIRCUIT 10,12,14
5 SPACE 1 -- -- -- --
4 PANEL 'C' 3 200.0 A 200.0 A 0 VA CIRCUIT 4,6,8
3 SPACE 1 -- -- -- --
2 PANEL 'L' 3 200.0 A 200.0 A 0 VA CIRCUIT 2
1 PANEL 'F' 3 200.0 A 200.0 A 26486 VA CIRCUIT 1
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: NEMA 1 MCB Rating: 400.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 400.0 A
Supply From: Phases: 3 Mains Type: MLO
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating:
Switchboard: MD Existing
TOTAL ESTIMATED DEMAND ADDITION = 141.9 AMPS.
400 AMP EXISTING SERVICE - 151.3 AMPS = 248.7 AMPS REMAINING
121.02 AMPS X 125% = 151.3 AMPS
CURRENT DEMAND : 43.6kW @ 208 VOLT 3 PHASE = 121.02 AMPS
23-May-2023 THROUGH 24-MAY-2024
AT 125% OF MAXIMUM DEMAND IN RECENT 12 MONTH PERIOD.
AT 125% OF MAXIMUM DEMAND IN RECENT 12 MONTH PERIOD.
PER 2020 NEC 200.87, EXISTING LOAD CAN BE DETERMINED
ESTIMATED DEMAND
60 7.20 - - - - - - - - - - - 58
57.5 6.90 - - - - - - - - - - - 60 55 6.60 - - - - - - - - - - - 63
52.5 6.30 - - - - - - - - - - - 66 50 6.00 - - - - - - - - - - 73 69
47.5 5.70 - - - - - - - - - - 77 73 45 5.40 - - - - - - - - - - 81 77
42.5 5.10 - - - - - - - - 51 90 86 82 40 4.80 - - - - - - - 57 54 96 91 87
37.5 4.50 - - - - - - - 61 58 102 97 93 35 4.20 - - - - - - - 65 62 109 104 99
32.5 3.90 - - - - - - - 70 67 118 112 107 30 3.60 - - - - - 46 80 76 73 128 122 116
27.5 3.30 - - - - 52 50 88 83 79 139 133 127 25 3.00 - - - - 57 55 96 92 87 153 146 139
22.5 2.70 - - 38 67 64 61 107 102 97 171 162 155 20 2.40 - 45 43 76 72 69 121 115 109 192 183 174
17.5 2.10 - 52 49 87 82 78 138 131 125 219 209 199 15 1.80 63 60 57 101 96 92 161 153 146 256 244 232
12.5 1.50 76 72 69 121 115 110 193 184 175 307 293 279 10 1.20 95 91 86 152 144 138 242 230 219 384 366 349
7.5 0.90 127 121 115 203 193 184 322 307 292 513 488 465 5 0.60 191 182 173 304 289 276 484 460 439 769 732 698 A kVA 20 25 30 30 35 40 40 50 55 55 65 75
°C 60 75 90 60 75 90 60 75 90 60 75 90
WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU
VOLTAGE DROP - 120/1
60 12.48 - - - - - - - - - - - 100
57.5 11.96 - - - - - - - - - - - 105 55 11.44 - - - - - - - - - - - 110
52.5 10.92 - - - - - - - - - - - 115 50 10.40 - - - - - - - - - - 126 121
47.5 9.88 - - - - - - - - - - 133 127 45 9.36 - - - - - - - - - - 141 134
42.5 8.84 - - - - - - - - 89 156 149 142 40 8.32 - - - - - - - 99 95 166 158 151
37.5 7.80 - - - - - - - 106 101 177 169 161 35 7.28 - - - - - - - 114 108 190 181 173
32.5 6.76 - - - - - - - 122 117 205 195 186 30 6.24 - - - - - 79 139 133 126 222 211 201
27.5 5.72 - - - - 91 87 152 145 138 242 230 220 25 5.20 - - - - 100 95 167 159 152 266 253 242
22.5 4.68 - - 66 117 111 106 186 177 169 296 282 269 20 4.16 - 78 75 131 125 119 209 199 190 333 317 302
17.5 3.64 - 90 86 150 143 136 239 228 217 381 362 346 15 3.12 110 105 100 175 167 159 279 266 253 444 423 403
12.5 2.60 132 126 120 211 200 191 335 319 304 533 507 484 10 2.08 165 157 150 263 251 239 419 399 380 667 634 605
7.5 1.56 221 210 200 351 334 319 559 532 507 889 846 807 5 1.04 331 315 301 527 502 479 839 798 761 1334 1269 1211 A kVA 20 25 30 30 35 40 40 50 55 55 65 75
°C 60 75 90 60 75 90 60 75 90 60 75 90
WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU
VOLTAGE DROP - 208/1
60 21.62 - - - - - - - - - - - 116
57.5 20.71 - - - - - - - - - - - 121 55 19.81 - - - - - - - - - - - 127
52.5 18.91 - - - - - - - - - - - 133 50 18.01 - - - - - - - - - - 146 139
47.5 17.11 - - - - - - - - - - 154 147 45 16.21 - - - - - - - - - - 162 155
42.5 15.31 - - - - - - - - 103 181 172 164 40 14.41 - - - - - - - 115 109 192 183 174
37.5 13.51 - - - - - - - 122 117 205 195 186 35 12.61 - - - - - - - 131 125 220 209 199
32.5 11.71 - - - - - - - 141 135 237 225 215 30 10.81 - - - - - 92 161 153 146 256 244 233
27.5 9.91 - - - - 105 100 176 167 159 280 266 254 25 9.01 - - - - 115 110 193 184 175 308 293 279
22.5 8.11 - - 77 135 128 122 215 204 195 342 325 310 20 7.21 - 91 86 152 144 138 242 230 219 385 366 349
17.5 6.30 - 104 99 174 165 158 276 263 251 440 418 399 15 5.40 127 121 115 203 193 184 323 307 293 513 488 466
12.5 4.50 153 145 139 243 231 221 387 368 351 616 586 559 10 3.60 191 182 173 304 289 276 484 461 439 770 733 699
7.5 2.70 255 243 231 406 386 368 646 614 586 1027 977 932 5 1.80 383 364 347 609 579 553 969 922 879 1540 1466 1398 A kVA 20 25 30 30 35 40 40 50 55 55 65 75
°C 60 75 90 60 75 90 60 75 90 60 75 90
WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU
VOLTAGE DROP - 208/3
AT
TS
NE
TUFO
HA
R E
I G
E N
F P
R O
IS
S
E
O LAN
JAMES BRIAN
KORHORN, JR
#13060801-2202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:2
:4
A M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
E L
E C
T R
IC
A
L S
C H
E D
U L
E S
E-602
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
Notes:
Total Est. Demand: 0.0 A
Total Conn.: 0.0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 0.0 A 0.0 A 0.0 A
Total Load: 0 VA 0 VA 0 VA
41 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 42
39 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 40
37 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 38
35 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 36
33 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 34
31 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 32
29 RADIANT HEATER CONTROL 2 20 A 1 - 0 0 30
27 SOUTH RANDIANT GAS HEATER 2 20 A 1 - 0 0 28
25 EAST RADIANT GAS HEATER 2 20 A 1 - 0 0
- 3 60 A 2 PANEL 'C'
23 WEST RADIANT GAS HEATER 2 20 A 1 - 0 0 - 1 20 A 5 SPARE 24
21 NORTH RADIANT GAS HEATER 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 22
19 EXIT SIGN EAST WALL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 20
17 SOUTH OUTLET BY MAIN PANEL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 18
15 NORTH OUTLET BY MAIN PANEL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 16
13 CENTER LIGHTS 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 14
11 SOUTH MIDDLE LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 WATER HEATER 12
9 SOUTH LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 WATER HEATER 10
7 LTG CONTACT / DOCK LVLR / GARAGE... 2 20 A 1 - 0 0 - 1 20 A 2 EXTERIOR LIGHTS 8
5 NORTH MIDDLE LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 OFFICE BASE BOARD HEATERS 6
3 NORTH LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 OFFICE BASE BOARD HEATERS 4
1 GARAGE UNIT HEATER 2 20 A 1 - 0 0 - 1 20 A 2 RESTROOMS 2
CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT
Enclosure: NEMA1 MCB Rating: 200.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A
Supply From: MD Phases: 3 Mains Type: MCB
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: L EXISTING
Notes:
Total Est. Demand: 73.5 A
Total Conn.: 73.5 A
Receptacle 180 VA 100.00% 180 VA Total Est. Demand: 26486 VA
Other 500 VA 100.00% 500 VA Total Conn. Load: 26486 VA
Motor 25806 VA 100.00% 25806 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings for Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 78.7 A 78.7 A 66.5 A
Total Load: 9253 VA 9253 VA 7980 VA
41 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 42
39 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 40
37 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 38
35 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 36
33 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 34
31 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 32
29 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 30
27 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 28
25 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 26
23 SPACE 4 -- 1 - -- 180 12 1 20 A 3 CONVENIENCE OUTLET BY DHP-1 24
21 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 22
19 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 20
17 0 500 12 1 20 A 3 CONTROL PANEL - ATC 18
FREEZER LIGHTS 2 20 A 2 -
0 1953 16
13 FREEZER OUTLETS / DOOR HEATER 2 20 A 1 - 0 1953
- 2 20 A 1,3 DHP-1 / DFC-1
11 3650 0 12
9 3650 0 10
RTU-4 1,3 50 A 3 -
3650 0
- 3 40 A 1,2 SOUTHEAST FREEZER UNIT (CU-6)
5 3650 0 6
3 3650 0 4
RTU-3 1,2 50 A 3 -
3650 0
- 3 50 A 1,2 NORTHEAST FREEZER UNIT (CU-5)
CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT
Enclosure: NEMA1 MCB Rating: 200.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A
Supply From: MD Phases: 3 Mains Type: MCB
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: F EXISTING
Notes:
Total Est. Demand: 68.4 A
Total Conn.: 60.8 A
Total Est. Demand: 24638 VA
Largest Motor 10950 VA 125.00% 13688 VA Total Conn. Load: 21900 VA
Motor 10950 VA 100.00% 10950 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare
3 = Provide New Breaker for New Load 4 = Space to Remain
1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain
Code:
Total Amps: 60.8 A 60.8 A 60.8 A
Total Load: 7300 VA 7300 VA 7300 VA
17 SPACE 4 -- 1 - -- 0 - 1 20 A 2 FREEZER LIGHTS 18
15 3650 0 - 1 20 A 2 FANS / CONDENSORS 16
13 3650 0 - 1 20 A 2 WORK PLUGS 14
RTU-2 1,3 50 A 3 -
3650 0 12
9 3650 0 10
7 3650 0
- 3 20 A 2 COMPRESSOR RIGHT
RTU-1 1,3 50 A 3 -
3650 0 6
3 GARAGE DOOR OPENERS 2 20 A 1 - 0 0 4
1 SPARE 5 20 A 1 - 0 0
- 3 20 A 2 COMPRESSOR LEFT
CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 250.0 A
Mounting: SURFACE Wires: 4 Mains Rating: 250.0 A
Supply From: MD Phases: 3 Mains Type: MLO
Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL
Branch Panel: D EXISTING
SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN.
GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/
16. INDOOR UNIT POWERED FROM OUTDOOR UNIT WITH LINE VOLTAGE
15. CONTROLLED WITH LIGHTS
14. DUCT DETECTOR IN RETURN AIR DUCT
13. DIRECT CONNECTION SIZE TO FACILITATE INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.
12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL
11. VARIABLE FREQUENCY DRIVE NOTES:
10. NEMA 3R NON-FUSED DISCONNECT SWITCH
9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER F2 = NON-INDUCTIVE FUSE (CLASS RK1)
8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER F1 = INDUCTIVE FUSE (CLASS RK5)
7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:
6. MAGNETIC STARTER
5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.
4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.
3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.
2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.
1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.
REMARKS: REMARKS:
HP = HORSEPOWER FLA = FULL LOAD AMPERES MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)
W = WATTS MCA = MINIMUM CIRCUIT AMPACITY STR = STARTER PL = POLE
KW = KILOWATTS VA = VOLT AMPERES DISC = DISCONNECT OCPD = OVERCURRENT PROTECTIVE DEVICE
V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT
ABBREVIATIONS:
RTU-4 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B
RTU-3 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B
RTU-2 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B
RTU-1 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B
DHP-1 DCTLS HEAT PUMP 208/1 9 MCA 7.2 1 2 12 12 3/4" 20 C1 20/2 15 - 9A
DFC-1 DCTLS FAN COIL 208/1 1 MCA 0.8 1 2 12 12 3/4" 15 C1 - - - 16A
SETS QTY SIZE GND SIZE MOCP SIZE/PL SIZE SIZE
V/PH LOAD FLA
WIRE COND OCPD/
TYPE
DISC FUSE NEMATYPE DESCRIPTION
ELECTRICAL OVER CURRENT PROTECTION STR
REMARKS
EQUIPMENT SCHEDULE
SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN.
GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/
16. INDOOR UNIT POWERED FROM OUTDOOR UNIT WITH LINE VOLTAGE
15. CONTROLLED WITH LIGHTS
14. DUCT DETECTOR IN RETURN AIR DUCT
13. DIRECT CONNECTION SIZE TO FACILITATE INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.
12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL
11. VARIABLE FREQUENCY DRIVE NOTES:
10. NEMA 3R NON-FUSED DISCONNECT SWITCH
9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER F2 = NON-INDUCTIVE FUSE (CLASS RK1)
8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER F1 = INDUCTIVE FUSE (CLASS RK5)
7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:
6. MAGNETIC STARTER
5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.
4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.
3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.
2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.
1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.
REMARKS: REMARKS:
HP = HORSEPOWER FLA = FULL LOAD AMPERES MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)
W = WATTS MCA = MINIMUM CIRCUIT AMPACITY STR = STARTER PL = POLE
KW = KILOWATTS VA = VOLT AMPERES DISC = DISCONNECT OCPD = OVERCURRENT PROTECTIVE DEVICE
V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT
ABBREVIATIONS:
CU-6 SOUTHEAST FREEZER UNIT 208/3 30.3 MCA 24.2 1 3 8 10 3/4" 40 C1 - - - -
CU-5 NORTHEAST FREEZER UNIT 208/3 44 MCA 35.2 1 3 6 10 1" 50 C1 - - - -
CU-4 SOUTH FREEZER - EAST UNIT 208/3 37.5 MCA 30.0 1 3 8 10 3/4" 40 C1 - - - -
CU-3 SOUTH FREEZER - WEST UNIT 208/3 37.5 MCA 30.0 1 3 8 10 3/4" 40 C1 - - - -
CU-2 SOUTHWEST FREEZER UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 40 C1 - - - -
CU-1 NORTHWEST FREEZER UNIT 208/3 44 MCA 35.2 1 3 6 10 1" 50 C1 - - - -
SETS QTY SIZE GND SIZE MOCP SIZE/PL SIZE SIZE
V/PH LOAD FLA
WIRE COND OCPD/
TYPE
DISC FUSE NEMATYPE DESCRIPTION
ELECTRICAL OVER CURRENT PROTECTION STR
REMARKS
EQUIPMENT SCHEDULE
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
20"x8"
20"/8"FO
(E)
FD
SD
MD
MBD
BD
CD
20"Ø
EA
OA
TA
RLA
RA
SA
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR - LOW PRESSURE
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS SYMBOLS AND TAGS
CFMID
NECK SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
CFMTYPE (SEE SCHEDULE)
NUMBER OF SLOTS / SLOT WIDTH /
ACTIVE SLOT LENGTH (PLENUM LENGTH)
/ NECK SIZE
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GEA GREASE EXHAUST AIR
SEA SMOKE EXHAUST AIR
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
FLUE EXHAUST GAS FLUE
CA COMBUSTION AIR
OA CONDITIONED OUTSIDE AIR
VAV-XX
10' - 0"
(E)VAV-XX
VAV-XX
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
D DEGREE
DB DRY BULB
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EA EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MUA MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
OA OUTSIDE AIR
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
RA RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
RDO ROOF DRAIN OVERFLOW
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
SA SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TRENCH DRAIN
TDR TEMPERATURE DROP
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
SECTION TOTAL TRACK LENGTH
BOTTOM OF EQUIPMENT
ELEVATION
590 lb
RTU-XX
4.0 ton
RTU-XX
115000 Btu/h
115 CFH
RTU-XX
Htg: 3.7 GPM
VAV-XX
HEATING
COIL
FLOW OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY
VAV BOX
ROOFTOP UNIT
DATA DEVICE TAGS
DAMPER TAGS
VAV-XX
RTU-XX
EQUIPMENT ID
SYMBOL
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
EXISTING RELOCATED
EQUIPMENT (R)VAV-XX
POINT WHERE EXISTING IS TO BE DEMOLISHED
Room
EXISTING PIPE TAG
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
1/8" / 12" SLOPE
INVERT: -105' - 1"
(E)
HVAC SYMBOLS
SQUARE
SUPPLY DIFFUSER
RECTANGULAR
SUPPLY DIFFUSER
RECTANGULAR
RETURN GRILLE
SQUARE
RETURN GRILLE
ROUND SUPPLY
DIFFUSER
RECTANGULAR
EXHAUST GRILLE
SQUARE
EXHAUST GRILLE
SA SUPPLY AIR - MEDIUM PRESSURE
6"Ø
CD1 /100
8"x8"
CD1 /200
12"x12"
RG1 /500
8"Ø
RG2 /180
12"Ø
EG2 /300
8"x8"
EG3 /150
BLOW PATTERNS
3-WAY
4-WAY
2-WAY
2-WAY
CORNER
1-WAY
CEILING
SIDEWALL
14"x14"
SWS1 /300
16"x16"
SWE1 /400
28"x12"
SWR1 /600
LS1 /200
2/1.00"/5'-0"/10"Ø
5' - 0"
LINEAR SLOT
24"x24"
RG4 /800
PLENUM RETURN GRILLE
WITH SOUND BOOT
12"Ø
CD5 /400
LINEAR BAR GRILLES
48"x6"
LB1 /300
2"
PIPING SYMBOLS
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN
THIS SET OF DRAWINGS.
CHWS
CWV
CA
CD
LPCR
CWR
CWS
DCW
FCW
SCW
DHW
DHW140°
DHWR
DHWR140°
GV
GW
HWR
HWS
NG
OV
OW
PD
V
W
SHWR
SHWS
LPS
RD
RDO
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
LOW PRESSURE CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
FILTERED COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRCULATION
HOT WATER RECIRCULATION 140°
GREASE VENT
GREASE WASTE
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
LOW PRESSURE STEAM
ROOF DRAIN
ROOF DRAIN OVERFLOW
REFL
REFS
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
4"
4"
REFHG REFRIGERANT-HOT GAS DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
PG PROPANE GAS
TYPE (SEE SCHEDULE)
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
4000 SF
6" RD-1
4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN
4" FS-4FLOOR SINK
4" DD-29 DECK DRAIN4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13
HUB DRAIN
DRAIN TAGS
"P" - INDICATES
PRIMER CONNECTION
FIXTURE UNITS
FLOW CONTROL
DRAIN
4" RD-12
COMBINATION
DRAINS
ROOF DRAIN4" RD-15
ROOF AREA
SERVED BY DRAIN
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
WATER CLOSET -
WALL HUNG - ADA WC-1
U-1
1 WFU
LAV-1A
1.5 CWFU
1.5 HWFU
LAV-1A
FIXTURE UNITS
4" WCO
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
4" WCO
TYPE (SEE SCHEDULE)
WC-1A
CAP
PLUG
GWR
GWS
GROUND LOOP WATER RETURN
GROUND LOOP WATER SUPPLY
NPCW NON-POTABLE COLD WATER
NPHW NON-POTABLE HOT WATER
8" COTG CLEANOUT TO GRADE
PIPE CONNECTION SIZE
NER NET ENERGY LOOP RETURN
NES NET ENERGY LOOP SUPPLY
HPCR
HPS
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM
CO2 MEDICAL GAS - CARBON DIOXIDE (CO2)
HE MEDICAL GAS - HELIUM (HE)
IA MEDICAL GAS - INSTRUMENT AIR
MA MEDICAL GAS - MEDICAL AIR
MV MEDICAL GAS – MEDICAL VACUUM
N2 MEDICAL GAS – NITROGEN (N2)
N2O MEDICAL GAS – NITROUS OXIDE (N2O)
O2 MEDICAL GAS – OXYGEN (O2)
WAGD WASTE ANESTHESIA GAS DISPOSAL
GHWR GLYCOL HEATING WATER RETURN
GHWS GLYCOL HEATING WATER SUPPLY
VALVE SIZE
R E
G I S
T E R
E
D
PROFESSIONA
L
E N
G I N
E E
R
No. 353492
S
T A
TE OF UTA
H
LADD M.
BIRCH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
REVISIONS
SUBMITTAL:
SHEET NO.
STAMP:
PROJECT NUMBER
F ile
P a th
P ri n t D a te
REVIEW - NOT FOR
CONSTRUCTION
230 N. 1680 E.
Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255
10.18.2024
A u to d e s k D o c s /C
A R
B O
N S
C H
O O
L D
IS
T
R
IC
T F
O O
D D
IS
T
R
IB
U T
IO
N
W A
R E
H O
U S
E A
IR
C
O N
D
IT
IO
N
IN
G
/2
C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
P v
.r v t
/1
/2
:5
:5
P
M
240255
C a rb o n S c h o o l D is tr ic t
F o o d
D is tr ib u ti o n W a re h o u s e
A ir
C o n d it io n in g
M E
C H
A N
IC
A
L T
IT
L
E S
H E
E T
M-000
C A
R B
O N
C O
U N
T Y
S C
H O
O L
D
IS
T R
IC
T
MECHANICAL SHEET INDEX
M-000 MECHANICAL TITLE SHEET
M-001 MECHANICAL GENERAL NOTES
MD-101 MECHANICAL DEMO PLAN
M-101 MECHANICAL FLOOR PLAN
M-501 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
P-001 PLUMBING ABBREVIATION & NOTES
PD-101 PLUMBING DEMO PLAN
P-101 PLUMBING FLOOR PLAN
P-501 PLUMBING DETAILS & SCHEDULES
MECHANICAL GENERAL NOTES
1. COORDINATE EXACT PLACEMENT OF DIFFUSERS, GRILLES AND REGISTERS WITH ARCHITECTURAL
REFLECTED CEILING PLAN, TYPICAL.
2. SEE DETAIL FOR DIFFUSER CONNECTIONS TO DUCTWORK, TYPICAL.
3. BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE NECK INLET SIZE OF THE DIFFUSERS,
REGISTER OR GRILLE IT SERVES UNLESS NOTED OTHERWISE, TYPICAL.
4. COORDINATE EXACT MOUNTING LOCATION OF ALL THERMOSTATS WITH LATEST REVISION OF
ARCHITECTURAL ELEVATION AND FURNISHINGS PLANS, TYPICAL.
5. THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE OR COMBINATION FIRE/SMOKE
DAMPERS AT ALL LOCATIONS SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO MEET
THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION LOCATIONS.
DAMPERS ARE TO BE PROVIDED WITH SHUTOFF/TEST SWITCH AT EACH LOCATION.
6. PROVIDE AND INSTALL TURNING VANES IN ALL SQUARE LOW PRESSURE DUCTWORK AT ELBOWS OR
TEES, TYPICAL.
7. INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND SERVICEABLE LOCATIONS, MEETING ALL
MANUFACTURERS REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.
8. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. REFER TO MECHANICAL SPECIFICATIONS
FOR EXTENT OF DUCT INSULATION AND LINER AND ADJUST SHEET METAL DIMENSION.
9. PROVIDE AND INSTALL REMOTE DAMPER OPERATORS FOR ALL DAMPERS INSTALLED ABOVE
INACCESSIBLE CEILING, SEE MECHANICAL SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS,
TYPICAL.
10. PROVIDE AND INSTALL HIGH EFFICIENCY TAKE-OFF FITTINGS AND BALANCING DAMPER AT ALL
BRANCH CONNECTIONS TO LOW PRESSURE DUCTWORK. PROVIDE BALANCING DAMPERS AT EACH
BRANCH TAKE OFF TO SERVE DIFFUSER OR GRILLE AS WELL AS WHERE INDICATED.
11. PROVIDE AND INSTALL HIGH EFFICIENCY OR CONICAL TAKE-OFFS AT ALL BRANCH CONNECTIONS TO
MEDIUM PRESSURE DUCTWORK.
12. WHERE DUCTWORK CROSSES, SUPPLY DUCTWORK IS USUALLY BELOW RETURN AND EXHAUST
DUCT. RETURN DUCTWORK IS USUALLY BELOW EXHAUST DUCTS.
13. AT LOCATIONS WHERE DIFFUSERS OR GRILLES ARE UNDER DUCTWORK, CONTRACTOR TO
FABRICATE TRANSITION BOOT FROM FLEX CONNECTION TO DIFFUSER OR GRILLE WITH BALANCING
DAMPER, TYPICAL.
14. THE MECHANICAL CONTRACTOR SHALL PROVIDE CEILING MOUNTED ACCESS DOORS FOR ALL FIRE, SMOKE AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED ABOVE INACCESSIBLE CEILING. FIELD
VERIFY EXACT INSTALLATION LOCATIONS PRIOR TO COMMENCING WORK AND COORDINATE
INSTALLATIONS WITH LATEST ARCHITECTURAL REFLECTED CEILING PLANS.
15. ALL VAV BOXES TO HAVE REHEAT COILS, EXCEPT AS NOTED. PROVIDE EQUIPMENT TAG TO MATCH SCHEDULE. PROVIDE A MINIMUM OF TWO DUCT DIAMETERS OF STRAIGHT ROUND DUCT TO INLET OF
VAV BOX. BOX SHALL BE HARD CONNECTED (CONICAL) TO MEDIUM PRESSURE DUCT, TYPICAL.
16. PROVIDE ACCESS DOORS TO ACCESS VAV BOX CONTROLS ABOVE HARD CEILINGS. PROVIDE
MINIMUM 24" X 24".
17. FLEX DUCT IS REQUIRED FOR ALL DIFFUSERS AND GRILLES INSTALLED IN LAY-IN CEILINGS. FOR DIFFUSERS AND GRILLES IN HARD LID CEILINGS, THE DUCTWORK SHALL BE EXTENDED ALL THE WAY
TO THE DIFFUSER AND SHALL BE CONNECTED WITH A HARD CONNECTION OR A FLEX DUCT
CONNECTION WITH A MUD RING AND LAY-IN DIFFUSER AS SHOWN ON PLANS.
18. THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE
CONTRACT DOCUMENTS.
19. PROVIDE ACCESS TO ALL TEMPERATURE CONTROLS ABOVE CEILING. LOCATE IN ACCESSIBLE LOCATION. WHERE THERE ARE HARD CEILINGS THE CONTRACTOR SHALL PROVIDE 24" X 24" ACCESS
DOOR.
20. SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.
21. CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE SENSORS AT 5'-0" AFF, A MINIMUM
OF 8" FROM LIGHT SWITCH,…