2-2403-052 Carbon County School District - Food Warehouse HVAC-Drawings.pdf

PDF 2 MB Posted

Attached to
NS26-39 Carbon County School District - Construction of Warehouse Building HVAC Design
Solicitation number
NS26-39
Issued by
Cache County, Utah

About this file

These documents are engineering and construction design plans for a Carbon County School District Food Distribution Warehouse Air Conditioning project located in Utah. The project involves replacing existing HVAC and mechanical systems, including demolishing current evaporative coolers, radiant tube heaters, and installing new rooftop units (RTUs), ductless heat pump systems, and associated electrical and plumbing infrastructure. The project includes four Trane YHC 072 rooftop units, each with 150,000 BTU gas input, two Mitsubishi ductless heat pump systems (one indoor and one outdoor unit), and comprehensive electrical and plumbing system modifications.

The project appears to be fully funded and is designed to upgrade the mechanical systems of an existing food distribution warehouse. The electrical system modifications include updating panel boards, disconnects, and wiring to support the new equipment, with careful attention to existing electrical service capacity. The total estimated electrical demand addition is 141.9 amps, which will be accommodated by the existing 400-amp service that has approximately 248.7 amps remaining. The gas piping schedule indicates a total gas demand of 1,274,000 BTU, with provisions for connecting the new rooftop units and potentially retaining some existing tube heaters. The design emphasizes compliance with local and national electrical and mechanical codes, and includes detailed specifications for equipment installation, wiring, and system integration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

A AMPS

AFC AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPS INTERRUPTING

CAPACITY

AWG AMERICAN WIRE GAUGE

B BATTERY

BC BARE COPPER

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

C CONDUIT

CO CARBON MONOXIDE

CT CURRENT TRANSDUCER

CU COPPER MATERIAL

DED DEDICATED

DFA DROP FROM ABOVE

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EM EMERGENCY/EGRESS

EMT ELECTRICAL METALLIC

TUBING

ENT ELECTRICAL NON-METALLIC

TUBING

ER EXISTING TO BE RELOCATED

EX EXISTING TO REMAIN

FMC FLEXIBLE METAL CONDUIT

GC GENERAL CONTRACTOR

GEC GROUND ELECTRICAL

CONDUCTOR AT SES

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFEP GROUND FAULT EQUIPMENT

PROTECTOR

GND GROUND

IMC INTERMEDIATE METAL CONDUIT

IG ISOLATED GROUND

KCMIL 1000 CIRCULAR MILS (MCM)

LF LOW FREQUENCY, 520 HZ

LFMC LIQUID-TIGHT FLEXIBLE METAL

CONDUIT

LFNC LIQUID-TIGHT FLEXIBLE NON-

METAL CONDUIT

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

N1 NEMA 1

N3R NEMA 3R

N NEW

NL NIGHT LIGHT, BYPASS LOCAL

SWITCHING

PC PLUMBING CONTRACTOR

POC POINT OF CONNECTION

POS POINT OF SALES

R RELOCATED

RX RECEIVER

RM ROOF MOUNTED

RMC RIGID METALLIC CONDUIT

RNC RIGID NON-METALLIC

CONDUIT

SBJ SYSTEM BONDING JUMPER

SCA SHORT CIRCUIT AMPERES

TX TRANSMITTER

TC TEMPERATURE CONTROL

CONTROLLER

TR TAMPERPROOF

UG UNDERGROUND

UNO UNLESS NOTED

OTHERWISE

VA VOLT/AMPS

VIF VERIFY IN FIELD

W WATTS

WP WEATHERPROOF/NEMA 3R

XP EXPLOSION PROOF

XR EXISTING TO BE REMOVED

1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE

CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS

INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT

DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO

BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE

PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN

WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID

ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL

SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE

SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE,

THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY

INCOMPLETE SYSTEM SHALL BE MADE COMPLETE AND OPERABLE.

2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE

ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE

ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA

COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS

WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE GREATER THAN

SPECIFIED AND/OR DIMENSIONED ON THE PLANS.

3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE

NECESSARY BY INTERFERENCE WITH OTHER WORK.

4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR

FOR THE CONNECTIONS OF ALL EQUIPMENT SHOWN ON THE PLANS - ARCHITECTURAL,

MECHANICAL, ETC.

5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE

CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING

IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE

CORRECTED AT THE CONTRACTORS EXPENSE.

6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND

LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE

AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS

AND SPACE THAT EQUIPMENT IS BEING INSTALLED WITHIN.

7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT

LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM.

VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS

NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.

8. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING

CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT

GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE

ELECTRICAL SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.

9. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING

CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS OR CABINETS AND SHALL

MOVE THE PANELS AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS

NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.

10. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE

INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT,

BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.

11. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY

ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE OF 10 FEET WITHOUT

REQUIRING ADDITIONAL COST TO THE PROJECT.

12. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT

IS SET IN PLACE USING INDUSTRY STANDARD METHODS AND PRACTICES.

13. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH

STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH

GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN

DIRECT CONTACT WITH THE SOIL.

14. FLEXIBLE CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL

CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS

OF FLEXIBLE OR SEALTITE CONDUIT SHALL NOT BE GREATER THAN 72" INCHES.

15. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE.

16. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL

SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE

APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE

CONTRACTORS EXPENSE.

17. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB

RATED NYLON PULL CORD.

18. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS,

WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR).

THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION

PURPOSES WILL BE AT THE COST OF THE ELECTRICAL CONTRACTOR.

19. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120/277VAC BRANCH

CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN)+1#12(CU,THHN)GND IN 3/4"

EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC

BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 125' TO ACCOMMODATE FOR

VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES

ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.

20. CONDUCTORS SHALL BE COPPER, 600VAC RATED, TYPE THHN/THWN-2 UNLESS

OTHERWISE NOTED. CONDUCTORS SIZES UP TO #10AWG SHALL BE SOLID AND #8AWG

AND LARGER SHALL BE STRANDED.

21. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE

EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND

OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR

SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE

DIRECTED BY THE EQUIPMENT SUPPLIER.

22. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER

COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER,

PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND

EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION

FROM THE PREMISES.

23. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY

ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY

INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR

WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S

EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE OF EQUIPMENT

AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.

24. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL

CONTRACTOR TO PROVIDE CONDUIT AND DEVICE MOUNTING BOXES FOR

THERMOSTATS AND OTHER MECHANICAL CONTROLS.

25. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH

MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN

AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED

WITH THE ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL

WIRING METHODS.

26. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE

CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS

PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE

THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT

COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.

27. SUBMIT A SCALED LAYOUT (1/4" = 1') OF ALL ELECTRICAL ROOMS BASED ON THE

ELECTRICAL GEAR AND EQUIPMENT SUBMITTALS.

28. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT

SWITCHES INDICATING THE CIRCUIT IT IS TIED TO. USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER.

LABELS LENGTH SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.

29. FUSED DISCONNECTS TO BE HEAVY DUTY.

GENERAL NOTES

E

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:3

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

E L

E C

T R

IC

A

L T

IT

L

E S

H E

E T

E-001

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

E_ELECTRICAL SYMBOL SCHEDULE

SYMBOL

Schedule Description

Schedule Description MOUNTING COMMENTS

CONVENIENCE

OUTLET,

CUSTOM HEIGHT

44", UNLESS

INDICATED

OTHERWISE

(6)

CONVENIENCE

OUTLET,

WEATHER

PROOF

18"

CONVENIENCE

OUTLET,

CUSTOM HEIGHT

44", UNLESS

INDICATED

OTHERWISE

(6)

NON FUSED

DISCONNECT

(13) (14)

E_EQUIPMENT SYMBOL SCHEDULE

SYMBOL Schedule Description MOUNTING COMMENTS

PANEL BOARD, SURFACE 6'-6" TO TOP

PANEL BOARD, SURFACE 6'-6" TO TOP

PANEL BOARD, SURFACE 6'-6" TO TOP

MAIN POWER DISTRIBUTION PANEL

PANEL BOARD, SURFACE 6'-6" TO TOP

MAIN POWER DISTRIBUTION PANEL

SEE PLANS (13) (14)

ELECTRICAL SHEET INDEX

E-001 ELECTRICAL TITLE SHEET

ED-101 ELECTRICAL DEMO PLAN

E-111 POWER & SYSTEMS FLOOR PLAN

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL SCHEDULES

E-602 ELECTRICAL SCHEDULES

NO. DATE DESCRIPTION

F

1 2 3 4 5

A

B

C

D

ED-101

'B'

'C'

'MD'

'A'

'L'

'F'

'CT CABINET'

'METER'

'D'

(E)

(E)

(E)

(E)

(E) (E)

(E)(E)

(E)

(E)

(E)

ED-101

ED-101

DISCONNECT

F-7,9,11

(ER)

DISCONNECT

F-1,3,5

(ER)

DISCONNECT

F-2,4,6

(ER)

DISCONNECT

F-8,10,12

(ER)

DISCONNECT

B-6,8,10 C-8,10,12

(ER)

'MSD'

FLOOR LEVEL 1

100' - 0"

PANEL 'D' (E) DISCONNECT

D-8,10,12 (E)

DISCONNECT

D-2,4,6 (E)

COMPRESSOR

RIGHT (E)

COMPRESSOR

RIGHT (E)

FLOOR LEVEL 1

100' - 0"

LEVEL 1 TOW

110' - 0"

SOUTHEAST

FREEZER UNIT

(ER)

NORTHEAST

FREEZER UNIT

(ER)

DISCONNECT

F-2,4,6

(ER)

DISCONNECT

F-8,10,12

(ER)

FLOOR LEVEL 1

100' - 0"

LEVEL 1 TOW

110' - 0"

DISCONNECT

B-6,8,10

(ER)

DISCONNECT

C-8,10,12

(ER)

SOUTH

FREEZER

WEST UNIT

(ER)

SOUTH

FREEZER

EAST UNIT

(ER)

SOUTHWEST

FREEZER

UNIT

(ER)

NORTHWEST

FREEZER

UNIT

(ER)

DISCONNECT

F-1,3,5 F-7,9,11

(ER)

E: EXISTING TO REMAIN

EN: EXISTING TO BE REPLACED WITH NEW

ER: EXISTING TO BE RELOCATED

EX: EXISTING TO BE REMOVED AND OFFERED UP TO THE OWNER

FOR FIRST RIGHTS OF REFUSAL. PROPERLY AND LEGALLY

DISPOSE OF MATERIAL IF REFUSED.

GENERAL DEMOLITION KEY

E

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:4

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

E L

E C

T R

IC

A

L D

E M

O P

L A

N

ED-101

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

1/8" = 1'-0"ED-101

1 ELECTRICAL DEMO PLAN 1/4" = 1'-0"ED-101

2 PANEL D

DEMOLITION GENERAL NOTES

A FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR

CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING

OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL

EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR

REPLACE AS REQUIRED.

B FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/DATA WIRING

AS NECESSARY FOR CONTINUITY OF ANY WIRING ORIGINATING OUTSIDE

THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA

EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR

REPLACE AS REQUIRED.

D DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES AND

BACK BOXES AS NECESSARY WHERE NEW WALL CONSTRUCTION WILL

INTERSECT AN EXISTING WALL. FURNISH AND INSTALL CONDUIT AND WIRE

AS REQUIRED FOR CONTINUITY OF CIRCUIT(S).

E CONTRACTOR TO COORDINATE WITH OWNER FOR ITEMS TO BE

SALVAGED PRIOR TO DEMOLITION. CONTRACTOR RESPONSIBLE FOR

DISPOSING OF ANY MATERIAL THAT THE OWNER DOES NOT WANT TO

KEEP.

F EC SHALL COORDINATE WITH ALL OTHER TRADES DURING DEMOLITION

AND CONSTRUCTION TO FACILITATE TIMELY WORK.

G ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF DEBRIS AT ALL TIMES.

H CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS, CEILINGS ETC. TO

MATCH EXISTING CONDITIONS. PENETRATIONS SHALL BE SEALED WITH

FIRE RATED CAULK.

1/4" = 1'-0"ED-101

3 2 DISCONNECTS - RACK MOUNTED

1/4" = 1'-0"ED-101

4 4 DISCONNECTS - RACK MOUNTED

KEYNOTES

1 EXISTING DISCONNECT TO BE RELOCATED WITH CONDENSING UNIT. REMOVE

COMPLETE EXISITNG CIRCUIT BACK TO SOURCE BREAKER IN PANEL 'F'.

W P

F

F

1 2 3 4 5

A

B

C

D (E) 'B' 'A'

'MD'

'C'

'F'

'L'

'CT CABINET'

'METER'

'D'

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

DHP-1

DFC-1

RTU-3

D- 5,7,9

RTU-4

F- 7,9,11

(E)

F- 18

Control Panel - ATC

F-24

D- 11,13,15

RTU-1

RTU-2

F- 1,3,5

F- 2,4,6

F- 8,10,12

B- 6,8,10

C- 8,10,12

A- 7,9,11

A- 1,3,5

'MSD'

F- 14,16

E

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:4

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

P O

W E

R

S Y

S T

E M

S F

L O

O R

P L

A N

E-111

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

1/8" = 1'-0"E-111

1 POWER & SYSTEMS FLOOR PLAN

KEYNOTES

1 UNIT SUPPLIED WITH A CONVENIENCE OUTLET WITH POWER PROVIDED BY SINGLE

POINT CONNECTION.

FIRE

EXIT

44"

18"

48"

WITHIN 18"

96"

72"

84"

18"

WITHIN 60"

80"

44" 44"

FINISHED FLOOR

NOTES:

1. THE ELCTRICAL CONTRACTOR SHALL

VERIFY THE EXACT LOCATION OF ALL

TELEVISION OUTLETS WITH THE

ARCHITECT PRIOR TO INSTALLATION.

2. ALL DEVICES SHOWN ON THE DETAIL ARE

FOR REFERENCE OF MOUNTING HEIGHTS

ONLY. THE ELECTRICAL CONTRACOR

SHALL FIELD ADJUST THE HEIGHTS OF THE

DEVICES AS REQUIRED FOR PROPER

MOUNTING OF THE DEVICES.

3. ALL DEVICES REQUIRES FOR THE

PROJECT MAY NOT APPEAR ON THIS

DETAIL. ALL ITEMS SHOWN ON THIS DETAIL

MAY NOT BE REQUIRED FOR THIS

PROJECT.

4. FIRE ALARM NORN/STROBES ARE TO BE

MOUNTED NO HIGHER THAN 96" AND NO

LOWER THAN 80" TO CENTER OF DEVICE.

STRUCTURE

STRUCTURE

STRUCTURE STRUCTURE

ALL THREAD (SIZE AS

REQUIRED) 3/8" MIN.

BEAM CLAMPS OR

HANGER CLAMPS (AS

REQUIRED BY WEIGHT

SUPPORTED)

RACEWAY. (3/4" - 6")

CONDUIT HANGER

BEAM CLAMPS OR

HANGER CLAMPS

(AS

REQUIRED BY

WEIGHT

SUPPORTED)

RACEWAY. (3/4" - 6")

NOTES:

1. WIRE SHALL NOT BE USED AS A

COMPONENT OF ANY RACEWAY

HANGER SYSTEM.

2. DO NOT NOT SUPPORT ANY

RACEWAY THAN THAN 1" FROM

BOTTOM CORD OF STEEL

TRUSSES.

CL

6"

LC

5 4

(TYP.)

EMT

(TYP.)

EMT

EMT

EMT

NOTES:

1. TYP. FOR WOOD AND METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOWN. COORDINATE RING DEPTH TO BE

FLUSH WITH FINISHED SURFACE, UNLESS NOTED OTHERWISE.

3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCH. AND

MECH. DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.

4. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN

THE SAME STUD SPACEMUST BE SEPARATED BY A MIN. OF 6"

HORIZONTAL DISTANCE.

5. ELECTRICAL BOXES INSTALLED IN FIRE RESISTANT WALLS OR

PARTITIONS SHALL COMPLY WITH IBC 714.3.2.

6. INSULATED THOAT EMT CONNECTOR.

7. CADDY FASTENER, THROUGH STUD CABLE/CONDUIT SUPPORT

'FB12P'.

8. ADUSTABLE BAR HANGER.

9. TYPICAL DEVICE JUNCTION BOX.

REFER TO SECTION

FOR ATTACHMENT OF

ALL THREAD ROD TO

KINDORF CHANNEL

1 1/2"x1 1/2"-12GA. KINDORF

CHANNEL OR APPROVED

SUBSTITUTE

3/8" ALL THREAD,

MINIMUM. INCREASE

ROD SIZE IF WEIGHT

REQUIRES PER ROD

MANUFACTURERS

RECOMMENDATIONS.SUPPORT CONDUIT

WITH KINDORF STRAP

OR APPROVED

SUBSTITUTE.

BEAM CLAMPS OR

HANGER CLAMPS AS

REQUIRED BY WEIGHT

SUPPORTED

PROVIDE 25% SPACE CAPACITY

NUT

WASHER

WASHER

NUT

E

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:4

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

E L

E C

T R

IC

A

L D

E T

A

IL

S

E-501

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

NO SCALEE-501

1 MOUNTING HEIGHT DETAIL

NO SCALEE-501

2 RACEWAY SUPPORT METHODS DIAGRAM

NO SCALEE-501

3 ROUGH-IN DETAIL

NO SCALEE-501

4 TRAPEZE SUPPORT DETAIL

E

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:4

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

E L

E C

T R

IC

A

L S

C H

E D

U L

E S

E-601

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

TNotes:

Total Est. Demand: 30.0 A

Total Conn.: 30.0 A

Total Est. Demand: 10806 VA

Total Conn. Load: 10806 VA

Motor 10806 VA 100.00% 10806 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 30.0 A 30.0 A 30.0 A

Total Load: 3602 VA 3602 VA 3602 VA

17 SPARE 5 20 A 1 - 0 0 18

15 OUTLET UNDER PANEL A 2 20 A 1 - 0 0

- 2 20 A 2 AIR HANDLER

13 OFFICE 2 20 A 1 - 0 0 14

11 GARAGE DOOR / OUTLET ON COLUMN 2 20 A 1 - 0 0

- 2 50 A 2 CONDENSER

9 0 3602 10

7 0 3602 8

SPARE 5 40 A 3 -

0 3602

- 3 40 A 1,2 SOUTH FREEZER - WEST UNIT (CU-3)

3 SPACE 4 -- 1 - -- 0 - 1 20 A 2 CONDESER RECEPTACLE 4

1 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 2

CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 200.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A

Supply From: Phases: 3 Mains Type: MAIN CB

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL

Branch Panel: B EXISTING

Notes:

Total Est. Demand: 0.0 A

Total Conn.: 0.0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Motor 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 0.0 A 0.0 A 0.0 A

Total Load: 0 VA 0 VA 0 VA

11 0 0 12

220V OUTLET 2 20 A 2 -

0 0 10

7 SOUTH FREEZER LIGHTS 2 20 A 1 - 0 0

- 3 40 A 1,2 SOUTH FREEZER - EAST UNIT (CU-4)

5 SOUTH FREEZER HEAT TAPE 2 20 A 1 - 0 0 6

3 OUTLET BY PANEL 2 20 A 1 - 0 0 4

1 FREEZER ALARM 2 20 A 1 - 0 0

- 3 30 A 5 SPARE

CKT Circuit Description Code BRK P Size A (VA) B (VA) C (VA) Size P BRK Code Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 200.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A

Supply From: MD Phases: 3 Mains Type: MLO

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL

Branch Panel: C EXISTING

Notes:

Total Est. Demand: 0.0 A

Total Conn.: 0.0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Motor 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 0.0 A 0.0 A 0.0 A

Total Load: 0 VA 0 VA 0 VA

11 0 0 12

9 0 0 10

NORTHWEST FREEZER UNIT (CU-1) 1,3 50 A 3 -

0 0

- 3 100 A 2 PANEL 'B'

5 0 0 - 1 20 A 5 SPARE 6

3 0 0 - 1 20 A 5 SPARE 4

SOUTHWEST FREEZER UNIT (CU-2) 1,3 40 A 3 -

0 0 - 1 20 A 5 SPARE 2

CKT Circuit Description Code BRK P Size A (VA) B (VA) C (VA) Size P BRK Code Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 200.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A

Supply From: MD Phases: 3 Mains Type: MAIN CB

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL

Branch Panel: A EXISTING

BY THE EXTERNAL FORMATION OF ICE ON THE ENCLOSURE.

INGRESS OF WATER (RAIN, SLEET, SNOW); AND THAT WILL BE UNDAMAGED

WITH RESPECT TO HARMFUL EFFECTS ON THE EQUIPMENT DUE TO THE

OBJECTS (FALLING DIRT), AND THAT PROVIDE A DEGREE OF PROTECTION

EQUIPMENT INSIDE THE ENCLOSURE AGAINST INGRESS OF SOLID FOREIGN

HAZARDOUS PARTS, THAT PROVIDE A DEGREE OF PROTECTION OF THE

PROVIDE A DEGREE OF PROTECTION TO PERSONNEL AGAINST ACCESS TO

3R ENCLOSURES CONSTRUCTED FOR EITHER INDOOR OR OUTDOOR USE THAT

ENCLOSURE AGAINST INGRESS OF SOLID FOREIGN OBJECTS (FALLING DIRT).

THAT PROVIDE A DEGREE OF PROTECTION OF THE EQUIPMENT INSIDE THE

PROTECTION TO PERSONNEL AGAINST ACCESS TO HAZARDOUS PARTS AND

1 ENCLOSURES CONSTRUCTED FOR INDOOR USE THAT PROVIDE A DEGREE OF

RATING NEMA STANDARDS / DEFINITIONS

NEMA ENCLOSURES

K2 = 12.9 x [ 1 + 0.00323 x [T2 - 75] ]

CALCULATION USED TO ADJUST K FACTORS FOR 60 °C AND 90 °C CONDUCTORS:

K FACTORS USED: 60 °C = 12.275, 75 °C = 12.9, 90 °C = 13.525

SECTION 8.4.1 [ADDENDUM C] AND IECC C405.9.

BRANCH VOLTAGE DROP MUST NOT EXCEED 5 PERCENT PER ASHRAE 90.1,

PERCENT, THESE TABLES CANNOT BE USED. THE COMBINED FEEDER PLUS

WHERE FEEDER CIRCUIT VOLTAGE DROP [AT DESIGN LOAD] EXCEEDS 2

MAINTAIN A TARGET MAXIMUM OF 3 PERCENT VOLTAGE DROP.

1-WAY DISTANCES IN FEET FOR BRANCH CIRCUITS [AT DESIGN LOAD] THAT

THE PURPOSE OF THESE TABLES IS TO DISPLAY THE MAXIMUM ALLOWABLE

1 PH VD CALCULATION USED: 2 x K x Q x I x [D / ECM] 3 PH VD CALCULATION USED: 1.732 x K x Q x I x [D / ECM]

VOLTAGE DROP NOTES

Notes:

Total Est. Demand: 141.9 A

Largest Motor 10950 VA 125.00% 13688 VA Total Conn.: 134.3 A

Receptacle 180 VA 100.00% 180 VA Total Est. Demand: 51124 VA

Other 500 VA 100.00% 500 VA Total Conn. Load: 48386 VA

Motor 36756 VA 100.00% 36756 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Conn. Load: 48386 VA

10 SPARE 3 100.0 A 100.0 A 0 VA --

9 SPARE 3 100.0 A 100.0 A 0 VA --

8 PANEL 'D' 3 250.0 A 250.0 A 21900 VA CIRCUIT 11,13,15

7 SPACE 1 -- -- -- --

6 PANEL 'A' 3 200.0 A 200.0 A 0 VA CIRCUIT 10,12,14

5 SPACE 1 -- -- -- --

4 PANEL 'C' 3 200.0 A 200.0 A 0 VA CIRCUIT 4,6,8

3 SPACE 1 -- -- -- --

2 PANEL 'L' 3 200.0 A 200.0 A 0 VA CIRCUIT 2

1 PANEL 'F' 3 200.0 A 200.0 A 26486 VA CIRCUIT 1

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 400.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 400.0 A

Supply From: Phases: 3 Mains Type: MLO

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating:

Switchboard: MD Existing

TOTAL ESTIMATED DEMAND ADDITION = 141.9 AMPS.

400 AMP EXISTING SERVICE - 151.3 AMPS = 248.7 AMPS REMAINING

121.02 AMPS X 125% = 151.3 AMPS

CURRENT DEMAND : 43.6kW @ 208 VOLT 3 PHASE = 121.02 AMPS

23-May-2023 THROUGH 24-MAY-2024

AT 125% OF MAXIMUM DEMAND IN RECENT 12 MONTH PERIOD.

AT 125% OF MAXIMUM DEMAND IN RECENT 12 MONTH PERIOD.

PER 2020 NEC 200.87, EXISTING LOAD CAN BE DETERMINED

ESTIMATED DEMAND

60 7.20 - - - - - - - - - - - 58

57.5 6.90 - - - - - - - - - - - 60 55 6.60 - - - - - - - - - - - 63

52.5 6.30 - - - - - - - - - - - 66 50 6.00 - - - - - - - - - - 73 69

47.5 5.70 - - - - - - - - - - 77 73 45 5.40 - - - - - - - - - - 81 77

42.5 5.10 - - - - - - - - 51 90 86 82 40 4.80 - - - - - - - 57 54 96 91 87

37.5 4.50 - - - - - - - 61 58 102 97 93 35 4.20 - - - - - - - 65 62 109 104 99

32.5 3.90 - - - - - - - 70 67 118 112 107 30 3.60 - - - - - 46 80 76 73 128 122 116

27.5 3.30 - - - - 52 50 88 83 79 139 133 127 25 3.00 - - - - 57 55 96 92 87 153 146 139

22.5 2.70 - - 38 67 64 61 107 102 97 171 162 155 20 2.40 - 45 43 76 72 69 121 115 109 192 183 174

17.5 2.10 - 52 49 87 82 78 138 131 125 219 209 199 15 1.80 63 60 57 101 96 92 161 153 146 256 244 232

12.5 1.50 76 72 69 121 115 110 193 184 175 307 293 279 10 1.20 95 91 86 152 144 138 242 230 219 384 366 349

7.5 0.90 127 121 115 203 193 184 322 307 292 513 488 465 5 0.60 191 182 173 304 289 276 484 460 439 769 732 698 A kVA 20 25 30 30 35 40 40 50 55 55 65 75

°C 60 75 90 60 75 90 60 75 90 60 75 90

WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU

VOLTAGE DROP - 120/1

60 12.48 - - - - - - - - - - - 100

57.5 11.96 - - - - - - - - - - - 105 55 11.44 - - - - - - - - - - - 110

52.5 10.92 - - - - - - - - - - - 115 50 10.40 - - - - - - - - - - 126 121

47.5 9.88 - - - - - - - - - - 133 127 45 9.36 - - - - - - - - - - 141 134

42.5 8.84 - - - - - - - - 89 156 149 142 40 8.32 - - - - - - - 99 95 166 158 151

37.5 7.80 - - - - - - - 106 101 177 169 161 35 7.28 - - - - - - - 114 108 190 181 173

32.5 6.76 - - - - - - - 122 117 205 195 186 30 6.24 - - - - - 79 139 133 126 222 211 201

27.5 5.72 - - - - 91 87 152 145 138 242 230 220 25 5.20 - - - - 100 95 167 159 152 266 253 242

22.5 4.68 - - 66 117 111 106 186 177 169 296 282 269 20 4.16 - 78 75 131 125 119 209 199 190 333 317 302

17.5 3.64 - 90 86 150 143 136 239 228 217 381 362 346 15 3.12 110 105 100 175 167 159 279 266 253 444 423 403

12.5 2.60 132 126 120 211 200 191 335 319 304 533 507 484 10 2.08 165 157 150 263 251 239 419 399 380 667 634 605

7.5 1.56 221 210 200 351 334 319 559 532 507 889 846 807 5 1.04 331 315 301 527 502 479 839 798 761 1334 1269 1211 A kVA 20 25 30 30 35 40 40 50 55 55 65 75

°C 60 75 90 60 75 90 60 75 90 60 75 90

WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU

VOLTAGE DROP - 208/1

60 21.62 - - - - - - - - - - - 116

57.5 20.71 - - - - - - - - - - - 121 55 19.81 - - - - - - - - - - - 127

52.5 18.91 - - - - - - - - - - - 133 50 18.01 - - - - - - - - - - 146 139

47.5 17.11 - - - - - - - - - - 154 147 45 16.21 - - - - - - - - - - 162 155

42.5 15.31 - - - - - - - - 103 181 172 164 40 14.41 - - - - - - - 115 109 192 183 174

37.5 13.51 - - - - - - - 122 117 205 195 186 35 12.61 - - - - - - - 131 125 220 209 199

32.5 11.71 - - - - - - - 141 135 237 225 215 30 10.81 - - - - - 92 161 153 146 256 244 233

27.5 9.91 - - - - 105 100 176 167 159 280 266 254 25 9.01 - - - - 115 110 193 184 175 308 293 279

22.5 8.11 - - 77 135 128 122 215 204 195 342 325 310 20 7.21 - 91 86 152 144 138 242 230 219 385 366 349

17.5 6.30 - 104 99 174 165 158 276 263 251 440 418 399 15 5.40 127 121 115 203 193 184 323 307 293 513 488 466

12.5 4.50 153 145 139 243 231 221 387 368 351 616 586 559 10 3.60 191 182 173 304 289 276 484 461 439 770 733 699

7.5 2.70 255 243 231 406 386 368 646 614 586 1027 977 932 5 1.80 383 364 347 609 579 553 969 922 879 1540 1466 1398 A kVA 20 25 30 30 35 40 40 50 55 55 65 75

°C 60 75 90 60 75 90 60 75 90 60 75 90

WIRE SIZE #12 AWG CU #10 AWG CU #8 AWG CU #6 AWG CU

VOLTAGE DROP - 208/3

AT

TS

NE

TUFO

HA

R E

I G

E N

F P

R O

IS

S

E

O LAN

JAMES BRIAN

KORHORN, JR

#13060801-2202

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:2

:4

A M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

E L

E C

T R

IC

A

L S

C H

E D

U L

E S

E-602

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

Notes:

Total Est. Demand: 0.0 A

Total Conn.: 0.0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 0.0 A 0.0 A 0.0 A

Total Load: 0 VA 0 VA 0 VA

41 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 42

39 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 40

37 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 38

35 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 36

33 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 34

31 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 32

29 RADIANT HEATER CONTROL 2 20 A 1 - 0 0 30

27 SOUTH RANDIANT GAS HEATER 2 20 A 1 - 0 0 28

25 EAST RADIANT GAS HEATER 2 20 A 1 - 0 0

- 3 60 A 2 PANEL 'C'

23 WEST RADIANT GAS HEATER 2 20 A 1 - 0 0 - 1 20 A 5 SPARE 24

21 NORTH RADIANT GAS HEATER 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 22

19 EXIT SIGN EAST WALL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 20

17 SOUTH OUTLET BY MAIN PANEL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 18

15 NORTH OUTLET BY MAIN PANEL 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 16

13 CENTER LIGHTS 2 20 A 1 - 0 0 - 1 20 A 6 SPARE 14

11 SOUTH MIDDLE LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 WATER HEATER 12

9 SOUTH LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 WATER HEATER 10

7 LTG CONTACT / DOCK LVLR / GARAGE... 2 20 A 1 - 0 0 - 1 20 A 2 EXTERIOR LIGHTS 8

5 NORTH MIDDLE LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 OFFICE BASE BOARD HEATERS 6

3 NORTH LIGHTS 2 20 A 1 - 0 0 - 1 20 A 2 OFFICE BASE BOARD HEATERS 4

1 GARAGE UNIT HEATER 2 20 A 1 - 0 0 - 1 20 A 2 RESTROOMS 2

CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT

Enclosure: NEMA1 MCB Rating: 200.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A

Supply From: MD Phases: 3 Mains Type: MCB

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: L EXISTING

Notes:

Total Est. Demand: 73.5 A

Total Conn.: 73.5 A

Receptacle 180 VA 100.00% 180 VA Total Est. Demand: 26486 VA

Other 500 VA 100.00% 500 VA Total Conn. Load: 26486 VA

Motor 25806 VA 100.00% 25806 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings for Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 78.7 A 78.7 A 66.5 A

Total Load: 9253 VA 9253 VA 7980 VA

41 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 42

39 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 40

37 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 38

35 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 36

33 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 34

31 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 32

29 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 30

27 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 28

25 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 26

23 SPACE 4 -- 1 - -- 180 12 1 20 A 3 CONVENIENCE OUTLET BY DHP-1 24

21 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 22

19 SPACE 4 -- 1 - -- -- - 1 -- 4 SPACE 20

17 0 500 12 1 20 A 3 CONTROL PANEL - ATC 18

FREEZER LIGHTS 2 20 A 2 -

0 1953 16

13 FREEZER OUTLETS / DOOR HEATER 2 20 A 1 - 0 1953

- 2 20 A 1,3 DHP-1 / DFC-1

11 3650 0 12

9 3650 0 10

RTU-4 1,3 50 A 3 -

3650 0

- 3 40 A 1,2 SOUTHEAST FREEZER UNIT (CU-6)

5 3650 0 6

3 3650 0 4

RTU-3 1,2 50 A 3 -

3650 0

- 3 50 A 1,2 NORTHEAST FREEZER UNIT (CU-5)

CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT

Enclosure: NEMA1 MCB Rating: 200.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 200.0 A

Supply From: MD Phases: 3 Mains Type: MCB

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: F EXISTING

Notes:

Total Est. Demand: 68.4 A

Total Conn.: 60.8 A

Total Est. Demand: 24638 VA

Largest Motor 10950 VA 125.00% 13688 VA Total Conn. Load: 21900 VA

Motor 10950 VA 100.00% 10950 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

5 = Existing Breaker to Remain as Spare 6 = Demo Circuit Leave Breaker as Spare

3 = Provide New Breaker for New Load 4 = Space to Remain

1 = See Drawings For Conduit & Conductor Sizes 2 = Existing Breaker and Load to Remain

Code:

Total Amps: 60.8 A 60.8 A 60.8 A

Total Load: 7300 VA 7300 VA 7300 VA

17 SPACE 4 -- 1 - -- 0 - 1 20 A 2 FREEZER LIGHTS 18

15 3650 0 - 1 20 A 2 FANS / CONDENSORS 16

13 3650 0 - 1 20 A 2 WORK PLUGS 14

RTU-2 1,3 50 A 3 -

3650 0 12

9 3650 0 10

7 3650 0

- 3 20 A 2 COMPRESSOR RIGHT

RTU-1 1,3 50 A 3 -

3650 0 6

3 GARAGE DOOR OPENERS 2 20 A 1 - 0 0 4

1 SPARE 5 20 A 1 - 0 0

- 3 20 A 2 COMPRESSOR LEFT

CKT Circuit Description Code BRK P Size A B C Size P BRK Code Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 250.0 A

Mounting: SURFACE Wires: 4 Mains Rating: 250.0 A

Supply From: MD Phases: 3 Mains Type: MLO

Location: WAREHOUSE 217 Volts: 208Y/120 A.I.C. Rating: 14,000 AMPS SYMMETRICAL

Branch Panel: D EXISTING

SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN.

GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/

16. INDOOR UNIT POWERED FROM OUTDOOR UNIT WITH LINE VOLTAGE

15. CONTROLLED WITH LIGHTS

14. DUCT DETECTOR IN RETURN AIR DUCT

13. DIRECT CONNECTION SIZE TO FACILITATE INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.

12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL

11. VARIABLE FREQUENCY DRIVE NOTES:

10. NEMA 3R NON-FUSED DISCONNECT SWITCH

9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER F2 = NON-INDUCTIVE FUSE (CLASS RK1)

8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER F1 = INDUCTIVE FUSE (CLASS RK5)

7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:

6. MAGNETIC STARTER

5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.

4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.

3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.

2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.

1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.

REMARKS: REMARKS:

HP = HORSEPOWER FLA = FULL LOAD AMPERES MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)

W = WATTS MCA = MINIMUM CIRCUIT AMPACITY STR = STARTER PL = POLE

KW = KILOWATTS VA = VOLT AMPERES DISC = DISCONNECT OCPD = OVERCURRENT PROTECTIVE DEVICE

V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT

ABBREVIATIONS:

RTU-4 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B

RTU-3 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B

RTU-2 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B

RTU-1 ROOF-TOP UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 50 C1 - - - 10B,12B

DHP-1 DCTLS HEAT PUMP 208/1 9 MCA 7.2 1 2 12 12 3/4" 20 C1 20/2 15 - 9A

DFC-1 DCTLS FAN COIL 208/1 1 MCA 0.8 1 2 12 12 3/4" 15 C1 - - - 16A

SETS QTY SIZE GND SIZE MOCP SIZE/PL SIZE SIZE

V/PH LOAD FLA

WIRE COND OCPD/

TYPE

DISC FUSE NEMATYPE DESCRIPTION

ELECTRICAL OVER CURRENT PROTECTION STR

REMARKS

EQUIPMENT SCHEDULE

SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN.

GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/

16. INDOOR UNIT POWERED FROM OUTDOOR UNIT WITH LINE VOLTAGE

15. CONTROLLED WITH LIGHTS

14. DUCT DETECTOR IN RETURN AIR DUCT

13. DIRECT CONNECTION SIZE TO FACILITATE INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.

12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL

11. VARIABLE FREQUENCY DRIVE NOTES:

10. NEMA 3R NON-FUSED DISCONNECT SWITCH

9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER F2 = NON-INDUCTIVE FUSE (CLASS RK1)

8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER F1 = INDUCTIVE FUSE (CLASS RK5)

7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:

6. MAGNETIC STARTER

5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.

4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.

3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.

2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.

1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.

REMARKS: REMARKS:

HP = HORSEPOWER FLA = FULL LOAD AMPERES MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)

W = WATTS MCA = MINIMUM CIRCUIT AMPACITY STR = STARTER PL = POLE

KW = KILOWATTS VA = VOLT AMPERES DISC = DISCONNECT OCPD = OVERCURRENT PROTECTIVE DEVICE

V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT

ABBREVIATIONS:

CU-6 SOUTHEAST FREEZER UNIT 208/3 30.3 MCA 24.2 1 3 8 10 3/4" 40 C1 - - - -

CU-5 NORTHEAST FREEZER UNIT 208/3 44 MCA 35.2 1 3 6 10 1" 50 C1 - - - -

CU-4 SOUTH FREEZER - EAST UNIT 208/3 37.5 MCA 30.0 1 3 8 10 3/4" 40 C1 - - - -

CU-3 SOUTH FREEZER - WEST UNIT 208/3 37.5 MCA 30.0 1 3 8 10 3/4" 40 C1 - - - -

CU-2 SOUTHWEST FREEZER UNIT 208/3 38 MCA 30.4 1 3 8 10 3/4" 40 C1 - - - -

CU-1 NORTHWEST FREEZER UNIT 208/3 44 MCA 35.2 1 3 6 10 1" 50 C1 - - - -

SETS QTY SIZE GND SIZE MOCP SIZE/PL SIZE SIZE

V/PH LOAD FLA

WIRE COND OCPD/

TYPE

DISC FUSE NEMATYPE DESCRIPTION

ELECTRICAL OVER CURRENT PROTECTION STR

REMARKS

EQUIPMENT SCHEDULE

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

20"x8"

20"/8"FO

(E)

FD

SD

MD

MBD

BD

CD

20"Ø

EA

OA

TA

RLA

RA

SA

EXHAUST AIR

OUTSIDE AIR

RELIEF AIR

RETURN AIR

SUPPLY AIR - LOW PRESSURE

TRANSFER AIR

GRILLES, REGISTERS & DIFFUSERS SYMBOLS AND TAGS

CFMID

NECK SIZE

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

CFMTYPE (SEE SCHEDULE)

NUMBER OF SLOTS / SLOT WIDTH /

ACTIVE SLOT LENGTH (PLENUM LENGTH)

/ NECK SIZE

DUCT BEING DEMOLISHED

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

GEA GREASE EXHAUST AIR

SEA SMOKE EXHAUST AIR

EQUIPMENT BY OTHERS

(REFER TO OTHER DISCIPLINE

FOR ADDITIONAL INFORMATION)

EXISTING EQUIPMENT

TO REMAIN

FLUE EXHAUST GAS FLUE

CA COMBUSTION AIR

OA CONDITIONED OUTSIDE AIR

VAV-XX

10' - 0"

(E)VAV-XX

VAV-XX

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

D DEGREE

DB DRY BULB

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

EA EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FL FLOOR

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

MA MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MUA MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

OA OUTSIDE AIR

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

RA RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

RDO ROOF DRAIN OVERFLOW

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

SA SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TRENCH DRAIN

TDR TEMPERATURE DROP

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

SECTION TOTAL TRACK LENGTH

BOTTOM OF EQUIPMENT

ELEVATION

590 lb

RTU-XX

4.0 ton

RTU-XX

115000 Btu/h

115 CFH

RTU-XX

Htg: 3.7 GPM

VAV-XX

HEATING

COIL

FLOW OPERATING WEIGHT

NOT INCLUDING CURB

FUEL INPUT

GAS PIPE FLOW

NOMINAL COOLING

CAPACITY

VAV BOX

ROOFTOP UNIT

DATA DEVICE TAGS

DAMPER TAGS

VAV-XX

RTU-XX

EQUIPMENT ID

SYMBOL

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE

DAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

SENSOR

MANUAL SWITCH

THERMOSTAT

TEMPERATURE SENSOR

TEMPERATURE & HUMIDITY SENSOR

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

HUMIDISTAT

EXISTING RELOCATED

EQUIPMENT (R)VAV-XX

POINT WHERE EXISTING IS TO BE DEMOLISHED

Room

EXISTING PIPE TAG

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

1/8" / 12" SLOPE

INVERT: -105' - 1"

(E)

HVAC SYMBOLS

SQUARE

SUPPLY DIFFUSER

RECTANGULAR

SUPPLY DIFFUSER

RECTANGULAR

RETURN GRILLE

SQUARE

RETURN GRILLE

ROUND SUPPLY

DIFFUSER

RECTANGULAR

EXHAUST GRILLE

SQUARE

EXHAUST GRILLE

SA SUPPLY AIR - MEDIUM PRESSURE

6"Ø

CD1 /100

8"x8"

CD1 /200

12"x12"

RG1 /500

8"Ø

RG2 /180

12"Ø

EG2 /300

8"x8"

EG3 /150

BLOW PATTERNS

3-WAY

4-WAY

2-WAY

2-WAY

CORNER

1-WAY

CEILING

SIDEWALL

14"x14"

SWS1 /300

16"x16"

SWE1 /400

28"x12"

SWR1 /600

LS1 /200

2/1.00"/5'-0"/10"Ø

5' - 0"

LINEAR SLOT

24"x24"

RG4 /800

PLENUM RETURN GRILLE

WITH SOUND BOOT

12"Ø

CD5 /400

LINEAR BAR GRILLES

48"x6"

LB1 /300

2"

PIPING SYMBOLS

* NOTE *

THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN

THIS SET OF DRAWINGS.

CHWS

CWV

CA

CD

LPCR

CWR

CWS

DCW

FCW

SCW

DHW

DHW140°

DHWR

DHWR140°

GV

GW

HWR

HWS

NG

OV

OW

PD

V

W

SHWR

SHWS

LPS

RD

RDO

CHWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

COMBINATION WASTE & VENT

COMPRESSED AIR

CONDENSATE DRAINAGE

LOW PRESSURE CONDENSATE RETURN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

DOMESTIC COLD WATER

FILTERED COLD WATER

SOFT COLD WATER

HOT WATER

HOT WATER 140°

HOT WATER RECIRCULATION

HOT WATER RECIRCULATION 140°

GREASE VENT

GREASE WASTE

HEATING WATER RETURN

HEATING WATER SUPPLY

NATURAL GAS

OIL VENT

OIL WASTE

PUMP DISCHARGE

SANITARY VENT

SANITARY SEWER

SOLAR HOT WATER RETURN

SOLAR HOT WATER SUPPLY

LOW PRESSURE STEAM

ROOF DRAIN

ROOF DRAIN OVERFLOW

REFL

REFS

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

4"

4"

REFHG REFRIGERANT-HOT GAS DRAIN SIZE

PIPE RISE

PIPE DROP

PIPE TEE REDUCING 45

DEGREE TEE

45 DEGREE TEE

PG PROPANE GAS

TYPE (SEE SCHEDULE)

RO REVERSE OSMOSIS WATER

IW INDIRECT WASTE

4000 SF

6" RD-1

4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN

4" FS-4FLOOR SINK

4" DD-29 DECK DRAIN4" FD-3PFLOOR DRAIN

8 WFU

4" FD-13

HUB DRAIN

DRAIN TAGS

"P" - INDICATES

PRIMER CONNECTION

FIXTURE UNITS

FLOW CONTROL

DRAIN

4" RD-12

COMBINATION

DRAINS

ROOF DRAIN4" RD-15

ROOF AREA

SERVED BY DRAIN

2" DOM. WM

PIPE ACCESSORY TAGS

DOMESTIC WATER METER

BALANCING VALVE

1/4 TURN BALL VALVE

CHECK VALVE

3-WAY MIXING VALVE

MOTORIZED CONTROL VALVE

3 WAY MOTORIZED CONTROL

VALVE

PRESSURE REDUCING VALVE

REFRIGERANT SOLENOID VALVE

BUTTERFLY VALVE

2" BALANCING

2" SHUTOFF

2" CHECK

2" TMV

2" M-CNTRL

2" 3-WAY CNTRL

2" PRV

3/8" SOLENOID

2" BUTTERFLY

WATER CLOSET -

WALL HUNG - ADA WC-1

U-1

1 WFU

LAV-1A

1.5 CWFU

1.5 HWFU

LAV-1A

FIXTURE UNITS

4" WCO

PIPE ACCESORY

TAG

PLUMBING FIXTURE TAGS

4" WCO

TYPE (SEE SCHEDULE)

WC-1A

CAP

PLUG

GWR

GWS

GROUND LOOP WATER RETURN

GROUND LOOP WATER SUPPLY

NPCW NON-POTABLE COLD WATER

NPHW NON-POTABLE HOT WATER

8" COTG CLEANOUT TO GRADE

PIPE CONNECTION SIZE

NER NET ENERGY LOOP RETURN

NES NET ENERGY LOOP SUPPLY

HPCR

HPS

HIGH PRESSURE CONDENSATE RETURN

HIGH PRESSURE STEAM

CO2 MEDICAL GAS - CARBON DIOXIDE (CO2)

HE MEDICAL GAS - HELIUM (HE)

IA MEDICAL GAS - INSTRUMENT AIR

MA MEDICAL GAS - MEDICAL AIR

MV MEDICAL GAS – MEDICAL VACUUM

N2 MEDICAL GAS – NITROGEN (N2)

N2O MEDICAL GAS – NITROUS OXIDE (N2O)

O2 MEDICAL GAS – OXYGEN (O2)

WAGD WASTE ANESTHESIA GAS DISPOSAL

GHWR GLYCOL HEATING WATER RETURN

GHWS GLYCOL HEATING WATER SUPPLY

VALVE SIZE

R E

G I S

T E R

E

D

PROFESSIONA

L

E N

G I N

E E

R

No. 353492

S

T A

TE OF UTA

H

LADD M.

BIRCH

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A

B

C

D

E

F

G

H

J

K

L

M

REVISIONS

SUBMITTAL:

SHEET NO.

STAMP:

PROJECT NUMBER

F ile

P a th

P ri n t D a te

REVIEW - NOT FOR

CONSTRUCTION

230 N. 1680 E.

Building V St. George, Utah 84107 O: (435)674-5800 www.vbfa.com VBFA Project #: 240255

10.18.2024

A u to d e s k D o c s /C

A R

B O

N S

C H

O O

L D

IS

T

R

IC

T F

O O

D D

IS

T

R

IB

U T

IO

N

W A

R E

H O

U S

E A

IR

C

O N

D

IT

IO

N

IN

G

/2

C a rb o n S c h o o l D is tr ic t F o o d D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

P v

.r v t

/1

/2

:5

:5

P

M

240255

C a rb o n S c h o o l D is tr ic t

F o o d

D is tr ib u ti o n W a re h o u s e

A ir

C o n d it io n in g

M E

C H

A N

IC

A

L T

IT

L

E S

H E

E T

M-000

C A

R B

O N

C O

U N

T Y

S C

H O

O L

D

IS

T R

IC

T

MECHANICAL SHEET INDEX

M-000 MECHANICAL TITLE SHEET

M-001 MECHANICAL GENERAL NOTES

MD-101 MECHANICAL DEMO PLAN

M-101 MECHANICAL FLOOR PLAN

M-501 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

P-001 PLUMBING ABBREVIATION & NOTES

PD-101 PLUMBING DEMO PLAN

P-101 PLUMBING FLOOR PLAN

P-501 PLUMBING DETAILS & SCHEDULES

MECHANICAL GENERAL NOTES

1. COORDINATE EXACT PLACEMENT OF DIFFUSERS, GRILLES AND REGISTERS WITH ARCHITECTURAL

REFLECTED CEILING PLAN, TYPICAL.

2. SEE DETAIL FOR DIFFUSER CONNECTIONS TO DUCTWORK, TYPICAL.

3. BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE NECK INLET SIZE OF THE DIFFUSERS,

REGISTER OR GRILLE IT SERVES UNLESS NOTED OTHERWISE, TYPICAL.

4. COORDINATE EXACT MOUNTING LOCATION OF ALL THERMOSTATS WITH LATEST REVISION OF

ARCHITECTURAL ELEVATION AND FURNISHINGS PLANS, TYPICAL.

5. THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE OR COMBINATION FIRE/SMOKE

DAMPERS AT ALL LOCATIONS SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO MEET

THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION LOCATIONS.

DAMPERS ARE TO BE PROVIDED WITH SHUTOFF/TEST SWITCH AT EACH LOCATION.

6. PROVIDE AND INSTALL TURNING VANES IN ALL SQUARE LOW PRESSURE DUCTWORK AT ELBOWS OR

TEES, TYPICAL.

7. INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND SERVICEABLE LOCATIONS, MEETING ALL

MANUFACTURERS REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.

8. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. REFER TO MECHANICAL SPECIFICATIONS

FOR EXTENT OF DUCT INSULATION AND LINER AND ADJUST SHEET METAL DIMENSION.

9. PROVIDE AND INSTALL REMOTE DAMPER OPERATORS FOR ALL DAMPERS INSTALLED ABOVE

INACCESSIBLE CEILING, SEE MECHANICAL SPECIFICATIONS FOR EQUIPMENT REQUIREMENTS,

TYPICAL.

10. PROVIDE AND INSTALL HIGH EFFICIENCY TAKE-OFF FITTINGS AND BALANCING DAMPER AT ALL

BRANCH CONNECTIONS TO LOW PRESSURE DUCTWORK. PROVIDE BALANCING DAMPERS AT EACH

BRANCH TAKE OFF TO SERVE DIFFUSER OR GRILLE AS WELL AS WHERE INDICATED.

11. PROVIDE AND INSTALL HIGH EFFICIENCY OR CONICAL TAKE-OFFS AT ALL BRANCH CONNECTIONS TO

MEDIUM PRESSURE DUCTWORK.

12. WHERE DUCTWORK CROSSES, SUPPLY DUCTWORK IS USUALLY BELOW RETURN AND EXHAUST

DUCT. RETURN DUCTWORK IS USUALLY BELOW EXHAUST DUCTS.

13. AT LOCATIONS WHERE DIFFUSERS OR GRILLES ARE UNDER DUCTWORK, CONTRACTOR TO

FABRICATE TRANSITION BOOT FROM FLEX CONNECTION TO DIFFUSER OR GRILLE WITH BALANCING

DAMPER, TYPICAL.

14. THE MECHANICAL CONTRACTOR SHALL PROVIDE CEILING MOUNTED ACCESS DOORS FOR ALL FIRE, SMOKE AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED ABOVE INACCESSIBLE CEILING. FIELD

VERIFY EXACT INSTALLATION LOCATIONS PRIOR TO COMMENCING WORK AND COORDINATE

INSTALLATIONS WITH LATEST ARCHITECTURAL REFLECTED CEILING PLANS.

15. ALL VAV BOXES TO HAVE REHEAT COILS, EXCEPT AS NOTED. PROVIDE EQUIPMENT TAG TO MATCH SCHEDULE. PROVIDE A MINIMUM OF TWO DUCT DIAMETERS OF STRAIGHT ROUND DUCT TO INLET OF

VAV BOX. BOX SHALL BE HARD CONNECTED (CONICAL) TO MEDIUM PRESSURE DUCT, TYPICAL.

16. PROVIDE ACCESS DOORS TO ACCESS VAV BOX CONTROLS ABOVE HARD CEILINGS. PROVIDE

MINIMUM 24" X 24".

17. FLEX DUCT IS REQUIRED FOR ALL DIFFUSERS AND GRILLES INSTALLED IN LAY-IN CEILINGS. FOR DIFFUSERS AND GRILLES IN HARD LID CEILINGS, THE DUCTWORK SHALL BE EXTENDED ALL THE WAY

TO THE DIFFUSER AND SHALL BE CONNECTED WITH A HARD CONNECTION OR A FLEX DUCT

CONNECTION WITH A MUD RING AND LAY-IN DIFFUSER AS SHOWN ON PLANS.

18. THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE

CONTRACT DOCUMENTS.

19. PROVIDE ACCESS TO ALL TEMPERATURE CONTROLS ABOVE CEILING. LOCATE IN ACCESSIBLE LOCATION. WHERE THERE ARE HARD CEILINGS THE CONTRACTOR SHALL PROVIDE 24" X 24" ACCESS

DOOR.

20. SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.

21. CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE SENSORS AT 5'-0" AFF, A MINIMUM

OF 8" FROM LIGHT SWITCH,…