2-24.0112 PLUMB BID PERMIT 20260930.pdf

PDF 1 MB Posted

Attached to
Pocono Township Renovations to Police Wing 24-055
Solicitation number
US.257063
Issued by
Monroe County, Pittsburgh City, Pennsylvania

About this file

This is a plumbing bid permit set for the Pocono Township Municipal Complex Police Wing renovation project located in Tannersville, Pennsylvania. The plumbing scope of work encompasses the complete design and installation of sanitary drainage systems, domestic water supply systems, and vent piping for the police station renovation. The project requires the plumbing contractor to provide all necessary permits and approvals from authorities having jurisdiction and to furnish and install all equipment and materials in strict accordance with the Pennsylvania Uniform Construction Code and the 2021 International Plumbing Code. Key fixtures include multiple water closets, urinals, lavatories, kitchen sinks, showers, floor drains, and specialized equipment such as an oil/water separator, water cooler, ice maker box, and mop sinks. The drawings include a demolition plan identifying existing plumbing systems to be removed, sanitary and vent piping plans, domestic water supply plans, and riser diagrams showing fixture connections and pipe routing. The sealed bid submission deadline is November 12 at 1:00 PM through PennBid, with a mandatory pre-bid conference scheduled for October 14 at 10:00 AM at the Pocono Township Administration Building, followed by a site tour. Bid documents became available for download on October 7 at 9:00 AM.

The plumbing contractor must provide a one-year unconditional guarantee on all materials, equipment, and workmanship from the date of owner acceptance and is responsible for all permit fees, inspections, and utility company charges. Bid security in the amount of 10% of the base bid is required in the form of a certified check, bank cashier's check, letter of credit, or bid bond. The project is subject to the Pennsylvania Prevailing Wage Act and the Steel Products Procurement Act. All items of labor, material, and equipment necessary for completion of the work, whether specifically described or not, are considered included in the contract without extra cost. The contractor must coordinate plumbing work with all other trades, maintain safe work areas compliant with OSHA standards, carry appropriate liability and property damage insurance, and provide as-built drawings and operation and maintenance manuals upon project completion. No requests for information will be considered after seven days prior to the bid submission deadline.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A L

R

IG

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

P

LU

M B

IN

G

IN

FO

R M

A

TI

O N

S H

E E

T D

M R R A

S

P0.0

1. PLUMBING CONTRACTOR (PC) SHALL PROVIDE A COMPLETE AND WORKING SYSTEM WITH ALL

NECESSARY PERMITS AND APPROVALS FROM AUTHORITIES HAVING JURISDICTION.

2. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE

PENNSYLVANIA UNIFORM CONSTRUCTION CODE, 2021 INTERNATIONAL PLUMBING CODE, ALL

PERTINENT CODES, LAWS, ORDINANCES, REGULATIONS, AND RESPECTIVE MANUFACTURER'S WRITTEN

INSTRUCTIONS.

3. COORDINATE PLUMBING WORK WITH THE WORK OF ALL OTHER TRADES AND OWNER.

4. PLUMBING DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE DRAWINGS MUST BE FOLLOWED AS CLOSELY AS CIRCUMSTANCES PERMIT AND ACTUAL LINE LOCATIONS SHALL BE DETERMINED BY THE PC IN THE FIELD. HOWEVER, THE PC WILL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION OF ALL MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE INSTALLATION WITHIN THE INTENT AND

MEANING OF THE CONTRACT DOCUMENTS.

5. PC SHALL ARRANGE THE PROGRESS OF THEIR WORK SO AS TO CONFORM TO THE PROGRESS OF THE TRADES AND SHALL COMPLETE THE ENTIRE INSTALLATION AS SOON AS THE CONDITION OF THE

PROJECT WILL PERMIT.

6. ALL ITEMS OF LABOR, MATERIAL, AND EQUIPMENT NOT SPECIFICALLY DESCRIBED HEREIN NOR DETAILED ON THE DRAWINGS BUT INCIDENTAL TO OR NECESSARY FOR THE COMPLETION OF THE

WORK, SHALL BE CONSIDERED AS INCLUDED WITHOUT EXTRA COST.

7. PROVIDE NECESSARY SUPPORTS, HANGERS AND HARDWARE TO PROPERLY SECURE PIPING AND

EQUIPMENT TO BUILDING STRUCTURE.

8. FURNISH AND INSTALL ACCESS PANELS WHERE REQUIRED FOR ACCESS TO ALL CONCEALED VALVES, TRAPS OR EQUIPMENT WHERE NO OTHER MEANS IS PROVIDED. COORDINATE ACCESS LOCATIONS WITH

ARCHITECT AND GC.

9. DO NOT INSTALL PIPING OR ANY OTHER PLUMBING EQUIPMENT OVER ELECTRICAL PANELS. MAINTAIN

A MINIMUM OF 36" CLEAR IN FRONT OF ELECTRICAL PANELS. COORDINATE WITH EC.

10. PC SHALL PROVIDE INSTRUCTIONS TO THE OWNER FOR EACH SYSTEM INSTALLED AND THE OPERATION

OF ALL EQUIPMENT IN THEIR CONTRACT.

11. CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE SITE. FAILURE TO VISIT AND INSPECT THE EXISTING CONDITIONS SHALL NOT BE VALID REASON FOR AUTHORIZATION OF A CHANGE

ORDER.

12. PC SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS, EQUIPMENT, AND

WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE BY OWNER.

13. PROVIDE SHOCK ABSORBING DEVICES WHICH WILL PROTECT WATER SUPPLY PIPING FROM WATER HAMMER. REFER TO PLUMBING EQUIPMENT SCHEDULE FOR TYPES. LOCATE AT THE ENDS OF ALL

BRANCH PIPING RUNS.

14. PC SHALL SUBMIT TO THE ARCHITECT/ENGINEER AS-BUILT DRAWINGS AND OPERATION AND

MAINTENANCE MANUALS INCLUDING ALL NAME PLATE DATA, WIRING DIAGRAMS, MAINTENANCE

INSTRUCTIONS, AND PARTS LIST UPON PROJECT COMPLETION.

15. EXTERIOR BELOW GROUND PIPING SHALL BE BURIED BELOW THE LOCAL FROST LINE.

16. INTERIOR ABOVE GROUND DRAINAGE AND VENT PIPING SHALL BE CONCEALED IN WALLS AND ABOVE SUSPENDED CEILINGS WHERE POSSIBLE. VERTICAL STACKS AND RAIN WATER CONDUCTORS SHALL BE

PROVIDED WITH ACCESSIBLE CLEAN OUTS AT THEIR BASE.

17. PC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL TIMES. ALL SAFETY PROCEDURES AND ENFORCEMENT IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL CONFORM TO

ALL OSHA STANDARDS.

18. BACK FLOW PREVENTERS AND/OR VACUUM BREAKERS SHALL BE INSTALLED WHERE REQUIRED TO

PREVENT CONTAMINATION OF POTABLE WATER SYSTEM.

19. SUBMIT SHOP DRAWINGS AND PRODUCT DATA GROUPED TO INCLUDE COMPLETE SUBMITTALS OF

RELATED SYSTEMS, PRODUCTS, AND ACCESSORIES IN A SINGLE SUBMITTAL.

20. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL FEES, PERMITS AND INSPECTIONS. ALL CHARGES BY

UTILITY COMPANIES SHALL BE PAID BY THIS CONTRACTOR.

21. FOR ALL NEW AND EXISTING PEX, CPVC, PVC, DWV, AND ABS PIPING IN RETURN AIR PLENUMS, PROVIDE

3M FIRE BARRIER PLENUM WRAP 5A OR EQUAL. INSTALL PER MANUFACTURER'S WRITTEN

INSTRUCTIONS.

22. VISIBLE PATCHING IN FINISHED SPACES SHALL BE PERFORMED BY G.C. EXCEPT WHERE OTHERWISE INDICATED, ALL CUTTING, EXCAVATION, AND FILL REQUIRED FOR THE PLUMBING WORK SHALL BE BY

THE PC. DO NOT CUT STRUCTURAL MEMBERS.

23. PC SHALL CARRY AND DOCUMENT LIABILITY, ACCIDENT, AND PROPERTY DAMAGE INSURANCE IN

ACCORDANCE WITH THE OWNER'S REQUIREMENTS.

24. PC SHALL EXERCISE EXTREME CARE IN PROTECTING AREAS ADJACENT TO CONSTRUCTION AREAS, SHALL

FULLY PROTECT THE AREAS FROM ANY DAMAGE RESULTING FROM CONTRACTOR'S WORKMEN,

SUBCONTRACTORS OR AGENTS, AND SHALL BE RESPONSIBLE FOR REPAIRING, CLEANING OR REPLACING

AND SUCH DAMAGE.

25. ALL DIMENSIONS GIVEN ARE FINISH DIMENSIONS UNLESS OTHERWISE NOTED. DO NOT SCALE

DRAWINGS.

26. PC SHALL FOLLOW MANUFACTURERS DIRECTIONS, INSTRUCTIONS AND RECOMMENDATIONS FOR ALL MATERIALS AND PROCESSES USED IN THIS CONTRACT UNLESS SPECIFICALLY NOTED OTHERWISE.

27. UPON COMPLETION OF PROJECT, SUBMIT A COPY OF THE APPROVED PERMIT SET TO THE OWNER.

28. NOTIFY BUILDING OWNER AND TENANTS AT LEAST 48 HOURS PRIOR TO DEMOLITION WORK OR BUILDING SERVICE SHUT DOWNS. SHUT DOWNS SHALL BE PERFORMED AT DESIGNATED TIMES UNDER BUILDING OWNERS SUPERVISION AND ONLY WITH THEIR APPROVAL. ANY SHUT DOWN COSTS SHALL BE

INCLUDED IN THE PLUMBING CONTRACT.

29. ALL FIXTURES, EQUIPMENT, PIPING, ETC. TO BE REMOVED SHALL BE DISPOSED OF, RELOCATED, TURNED OVER TO THE OWNER OR SALVAGED AS DIRECTED BY THE ARCHITECT.

30. UPON COMPLETION OF NEW WORK ALL ABANDONED PIPING SHALL BE REMOVED.

31. EXISTING SYSTEMS SHALL BE LEFT IN PERFECT WORKING ORDER UPON COMPLETION OF ALL NEW

WORK.

32. LOCATIONS AND SIZES OF EXISTING PIPING ARE APPROXIMATE. FIELD VERIFY EXACT LOCATIONS AND

SIZES OF ALL EXISTING PIPING.

33. REMOVED PIPING, FITTINGS, VALVES, FIXTURES, ETC. SHALL NOT BE REUSED UNLESS SPECIFICALLY

NOTED OR APPROVED BY THE ENGINEER.

34. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING HEIGHTS.

PLUMBING GENERAL NOTES: MISCELLANEOUS SYMBOLS

DIRECTION OF VIEW

OR DETAIL IS SHOWN

OR DETAIL IS TAKEN

DRAWING FROM WHICH SECTION

DETAIL OR SECTION NUMBERX

X

SECTION NUMBER

DRAWING ON WHICH SECTION

X X

REVISION SYMBOLX

DRAWING NOTE SYMBOLX

POINT OF CONNECTION-NEW TO EXISTING

NOTE:

NOT ALL ABBREVIATIONS AND SYMBOLS

INDICATED MAY APPEAR ON THESE

CONTRACT DRAWINGS. THIS IS FOR

REFERENCE ONLY.

ABV ABOVE

ABV CLG ABOVE CEILING

AC AQUATICS CONTRACTOR

AD1 AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AMP AMPERE

AP ACCESS PANEL

APPROX. APPROXIMATE

AVG AVERAGE

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BFP1 REDUCED PRESSURE BACKFLOW PREVENTER

BOJ BOTTOM OF JOIST

BOP BOTTOM OF PIPE

BOS BOTTOM OF STEEL

BOT BOTTOM

BP BACK PRESSURE

BSMT BASEMENT

BTU BRITISH THERMAL UNITS

BWV1 BACK WATER VALVE

CFH CUBIC FEET PER HOUR

CI CAST IRON

CL CENTER LINE

CLG CEILING

CO CLEANOUT

COL COLUMN

CONC CONCRETE OR CONCENTRIC

CONN CONNECT

CONT CONTINUATION

CW COLD WATER

CF1 DRINKING FOUNTAIN

DEPT DEPARTMENT

DFU DRAINAGE FIXTURE UNIT

DIA, Ø DIAMETER

DIP DUCTILE IRON PIPE

DN DOWN

DN1 DOWN SPOUT NOZZLE

DW1 DISHWASHER

EC ELECTRICAL CONTRACTOR

ECO1 EXTERIOR CLEANOUT

ED1 EMERGENCY OVERFLOW DRAIN

EL ELEVATION

ABBREVIATIONS

ESP1 ELEVATOR SUMP PUMP

EX EXISTING

FCO1 FLOOR CLEANOUT

FD1 FLOOR DRAIN

FFD1 FUNNELED FLOOR DRAIN

FF ELEV FINISHED FLOOR ELEVATION

FSC FOOD SERVICE CONTRACTOR

FS1 FLOOR SINK

FLA FULL LOAD AMPS

FL FLOOR

FPM FOOT/FEET PER MINUTE

FPS FOOT/FEET PER SECOND

FRM FROM

FT FOOT/FEET

GAL GALLONS

GB1 GARBAGE DISPOSAL

GC GENERAL CONTRACTOR

GND GROUND

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR1 GAS PRESSURE REGULATOR

GPS GALLONS PER SECOND

GS1 GLASS FILLER

GSV GAS SOLENOID VALVE

GT1 GREASE TRAP

HB1 HOSE BIBB

HC HVAC CONTRACTOR

HEWC1 HANDICAP ELECTRIC WATER COOLER

HGT HEIGHT

HP HORSE POWER

HLAV1 HANDICAP LAVATORY

HS1 HAND SINK

HSH1 HANDICAP SHOWER

HUR1 HANDICAP URINAL

HWC1 HANDICAP WATER CLOSET

HW HOT WATER

HWR HOT WATER RETURN

IB1 ICE MAKER BOX

ID INSIDE DIAMETER

INV INVERT OF PIPE

KD1 KITCHEN DRAIN

KS1 KITCHEN SINK

KW KILOWATT

LAV1 LAVATORY

MAX MAXIMUM

MBH THOUSAND BTU'S PER HOUR

MH MANHOLE

MIN MINIMUM

MS1 MOP SINK

MTD MOUNTED

NA, N/A NOT APPLICABLE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OS&Y OUTSIDE STEM AND YOKE

PC PLUMBING CONTRACTOR

PRV PRESSURE REDUCING VALVE

PT1 PLASTER TRAP

PVC POLY VINYL CHLORIDE

RD1 ROOF DRAIN

RPM REVOLUTIONS PER MINUTE

RWC RAINWATER CONDUCTOR

SAN SANITARY

SE1 SEWAGE EJECTOR

SH1 SHOWER

SS1 SERVICE SINK

STM STORM

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP1 TRAP PRIMER

TUB1 TUB/SHOWER

TYP TYPICAL

UR1 URINAL

WB1 WASHER BOX

W WASTE

W/ WITH

W/O WITHOUT

WC1 WATER CLOSET

WCO1 WALL CLEAN OUT

WFSU WATER FIXTURE SUPPLY UNITS

WHA1 WATER HAMMER ARRESTER

WH1 NON-FREEZE WALL HYDRANT

WPV1 WHIRLPOOL VALVE

WSV WATER SOLENOID VALVE

V VENT

VTR VENT THROUGH ROOF

PLUMBING DRAWING LIST

P0.0 PLUMBING INFORMATION SHEET

P1.1 PLUMBING GROUND FLOOR POLICE WING DEMO PLAN

P2.1 PLUMBING GROUND FLOOR PLAN POLICE WING - SANITARY/VENT

P2.2 PLUMBING GROUND FLOOR PLAN POLICE WING - DOMESTIC WATER

P3.1 PLUMBING RISER DIAGRAM SHEET

P4.1 PLUMBING DETAILS SHEET

PLUMBING EQUIPMENT SCHEDULE

SYMBOL FIXTURE TYPE MANUFACTURER MODEL NO. FAUCET/

VALVE

ANSI/ASME

APPROVALS

MOUNTING/

SUPPORT

*MINIMUM BRANCH PIPE SIZES DFU

WSFU

ELECTRIC

**** NOTES

HW CW SAN TRAP VENT

AD1 AREA DRAIN JAY R. SMITH 2142 A112.6.3-2001 4" 4" 2" 0.0 PROVIDE WITH SEDIMENT BUCKET, DEEP SEAL TRAP AND

PROSET SURE SEAL TRAP GUARD

FD1 FLOOR DRAIN JAY R. SMITH 2005-A A112.6.3-2001 2" 2" 11

2" 0.0 PROVIDE WITH DEEP SEAL TRAP AND PROSET SURE SEAL

TRAP GUARD

FD2 LIGATURE RESISTANT

FLOOR DRAIN ZURN Z415LR A112.6.3-2001 2" 2" 11

2" 0.0 PROVIDE WITH DEEP SEAL TRAP AND PROSET SURE SEAL

TRAP GUARD

FCO1 FLOOR CLEAN OUT JAY R. SMITH 4031 A112.21.1M FLOOR 4" INSTALL FLUSH AND LEVEL WITH FLOOR

HB1 HOSE BIBB PRIER C-168NP.75 ASSE STD 1011 3

4"

PROVIDE COMPLETE WITH DOUBLE CHECK VACUUM

BREAKER, ANTI-SIPHON, CHROME PLATED. MOUNT 24"

ABOVE FINISHED FLOOR.

HEWC1 ADA WATER COOLER WITH

BOTTLE FILL STATION ELKAY LZSTL8WS NSF 61

SECTION 9 WALL BRACKET 1

2" 11

2" 11 2" 11

2" 1.0 0.5 115V, 5.0A INSTALL IN ACCORDANCE WITH MANUFACTURERS

INSTRUCTIONS FOR ADA COMPLIANCE

HKS1 ADA DOUBLE BOWL

KITCHEN SINK

ELKAY

"LUSTERTONE" LRAD25055

MOEN "ALDER"

87233

PULL DOWN FAUCET

A112.19.3M COUNTER 1

2" 1 2" 11

2" 11 2" 11

2" 2.0 1.4

1.5 GPM, PROVIDE WITH P-TRAP AND TAILPIECE, PULL

DOWN SWIVEL FAUCET, ELKAY MODEL LKPD1 PERFECT

DRAINS W/STRAINERS, LKADOS TAILPIECE CLIPS MODEL

LKUCLIP8. ADA COMPLIANT WHEN TOP OF BOWL IS

INSTALLED AT 34" AFF.

HLAV1 ADA COUNTERTOP SINK KOHLER "CAXTON" K-2209-0

SLOAN OPTIMA

ETF-880-4-BOX-ADM-C

P-0.5GPM-MLM-IR-FCT

A112.19.2M/

A117.1 UNDERMOUNT 1

2" 1 2" 11

2" 11 2" 11

2" 2.0 2.0 24 VAC BOX

TRANSFORMER

INSTALL IN ACCORDANCE WITH MANUFACTURERS

INSTRUCTIONS FOR ADA COMPLIANCE. PROVIDE

COMPLETE WITH P-TRAP, TAILPIECE, GRID STRAINER, 0.5

GPM, AND SENSOR OPERATED FAUCET.

HSH1 ADAPTABLE SHOWER REFER TO ARCHITECTURAL DRAWINGS FOR

ENCLOSURE

MOEN "DURA"

T8342EP15 A11.19.1M/A117.1 FLOOR 1

2" 1 2" 2" 2" 11

2" 2.0 1.4

PROVIDE WITH SIOUX CHIEF MODEL 825-29-PVC

SHOWER DRAIN STAINLESS STEEL STRAINER. BLOCKING,

1.5 GPM SHOWER HEAD, HAND HELD SHOWER, SINGLE

LEVER HANDLE CONTROLS. NOTE 7

HUR1 ADA URINAL KOHLER

"BARDON" K-4991-ET SLOAN "ROYAL"

186 ESS-0.5-TMO-HW

A112.19.2M/

A112.19.6M/A117.1

WALL/JAY R. SMITH

MODEL 0637

CARRIER

4" 2" 2" 2.0 5.0 24 VAC BOX

TRANSFORMER

0.5 GPF, VITREOUS CHINA, SENSOR OPERATED FLUSH

VALVE w/MANUAL OVERRIDE (MOUNT RIM 17-19" AFF)

HARD WIRED SENSOR FLUSH VALVE

HWC1 ADA WATER CLOSET KOHLER

"KINGSTON" K-4325 SLOAN "ROYAL II"

111 ESS-1.6-OR

A112.19.2M/

A112.19.6M/A117.1

WALL/JAY R SMITH

MODEL 0210

CARRIER

1" 4" 2" 4.0 10.0 24 VAC BOX

TRANSFORMER

1.28 GPF, VITREOUS CHINA, ELONGATED BOWL, SENSOR

OPERATED FLUSH VALVE w/MANUAL OVERRIDE (MOUNT

RIM 17-19" AFF FOR ADA INSTALLATION). BEMIS

1955-SSC ELONGATED OPEN FRONT SEAT.

HWC2 ADA ANTI-LIGATURE

COMBINATION FIXTURE

ACORN

"PENAL-WARE" 1418FA-CT-2-04-M-1.28-FV ADA PUSH BUTTON

FLUSH VALVE

A112.19.2M/

A112.19.6M/A117.1

FLOOR MOUNTED

BACK OUTLET 1" 4" 2" 4.0 10.0

1.28 GPF, STAINLESS STEEL, ELONGATED BOWL, MANUAL

ADA FLUSH VALVE TOILET WITH PUSH BUTTON

ACTIVATION (INTEGRAL SEAT RIM 18" AFF FOR ADA

INSTALLATION).

IB1 ICE MAKER BOX OATEY 38687 A112.18.1 RECESSED IN WALL 1

2"

MS1 MOLDED STONE

MOP SINK FIAT MSB2424

24"x24"x10"

MOEN

8124 FLOOR 3

4" 3

4" 3" 3" 2" 3.0 3.0 SEE NOTE 6

OW1 OIL/WATER SEPARATOR MONARCH

PRECAST

315 GAL. OIL/WATER

SEPARATOR 4" 2"

PROVIDE 315 GALLON OIL/WATER SEPARATOR,

EQUIPPED WITH INSPECTION PORTS AND VAPOR VENT.

PROVIDE EXTENSION COLLARS AS NECESSARY.

UR1 URINAL KOHLER

"BARDON" K-4991-ET SLOAN "ROYAL"

186 ESS-0.5-TMO-HW

A112.19.2M/

A112.19.6M/A117.1

WALL/JAY R. SMITH

MODEL 0637

CARRIER

4" 2" 2" 2.0 5.0 24 VAC BOX

TRANSFORMER

0.5 GPF, VITREOUS CHINA, SENSOR OPERATED FLUSH

VALVE w/MANUAL OVERRIDE (MOUNT RIM 15" AFF)

HARD WIRED SENSOR FLUSH VALVE

SS1 UTILITY SERVICE SINK AMERICAN STANDARD LAKEWALL

7692008.008

AMERICAN STANDARD

8340.243 A112.19.1 FLOOR 1

2" 1 2" 2" 2" 11

2" 2.0 3.0

PROVIDE WITH STANDARD 2" CAST IRON P-TRAP AND

STRAINER. INSTALL IN ACCORDANCE TO

MANUFACTURERS WRITTEN INSTRUCTIONS

WC1 WATER CLOSET KOHLER

"KINGSTON" K-4325-0 SLOAN "ROYAL II"

111 ESS-1.6-OR

A112.19.2M/

A112.19.6M/A117.1

WALL/JAY R SMITH

MODEL 0210

CARRIER

1" 4" 2" 4.0 10.0 24 VAC BOX

TRANSFORMER

1.6 GPF, VITREOUS CHINA, ELONGATED BOWL, SENSOR

OPERATED FLUSH VALVE w/MANUAL OVERRIDE (MOUNT

RIM 15" AFF). BEMIS 1955-SSC ELONGATED OPEN FRONT

SEAT.

WCO1 WALL CLEAN OUT JAY R. SMITH 4720 A112.36.2M WALL 4"

WH1 FREEZE PROOF

WALL HYDRANT JAY R. SMITH 5609QT A112.21.3M WALL 3

4" MOUNT MIN 24" AFG

WHA1 WATER HAMMER

ARRESTER JAY R. SMITH 5000 SERIES A112.26.1M

WSFU 1-11:PDI-A; WSFU 12-32:PDI-B;

WSFU 33-60:PDI-C; WSFU 61-113:PDI-D;

WSFU 114-154:PDI-E; WSFU 155-330:PDI-F

* MINIMUM SANITARY/VENT PIPE SIZE BELOW SLAB IS 2".

** VALUES TAKEN FROM TABLES 709.1 AND E103.3(2) FROM THE CURRENT ADOPTED IPC 2018.

*** PROVIDE TAILPIECE AND P-TRAP WITH GRID STRAINER AT ALL LAVATORY SINKS, MCGUIRE OR APPROVED EQUAL.

**** PLUMBING CONTRACTOR IS RESPONSIBLE TO PROVIDE THE TRANSFORMER AND ELECTRIC CONTRACTOR TO INSTALL, ALL LOW VOLTAGE WIRING FROM THE TRANSFORMER TO THE FIXTURE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR.

NOTES:

1. ALL FIXTURES TO BE SUPPLIED WHITE UNLESS OTHER WISE NOTED OR AS DIRECTED BY ARCHITECT.

2. ALL EXPOSED PIPING, P-TRAPS AND STOP VALVES TO BE CHROME PLATED BRASS 1/4 TURN LOCKABLE. PROVIDE MIXING VALVE POWER HYDROGAURD MODEL LFE480 OR EQUAL (SET TEMPERATURE TO 105°F)

3. PROVIDE "TRUEBRO" PRE-FORMED INSULATION KIT, WHITE IN COLOR ON ALL EXPOSED PIPING FOR HANDICAP FIXTURES INCLUDING IN THE BASE CABINETRY.

4. PROVIDE STOP VALVES AT EACH FIXTURE.

5. PROVIDE WITH 8" TRIM PLACE, BOX TRANSFORMER POWER SUPPLY, BELOW DECK THERMOSTATIC MIXING VALVE, POLISHED CHROME FINISH, 0.5 GPM, MULTI-LAMINAR SPRAY, INFRARED SENSOR, SMART FAUCET, OPTIMA HARDWIRED POWERED, DECK MOUNTED LOW INTEGRATED BASE BODY FAUCET.

6. PROVIDE WITH FIAT STAINLESS STEEL BUMPER GUARDS E-88-A AND MSG SERIES WALL GUARDS CAULKED WITH 833AA, HOSE AND BRACKET MODEL 832AA, MOP BRACKET MODEL 889CC MOUNTED ABOVE SINK.

7. PROVIDE COMPLETE WITH PRESSURE BALANCING CYCLE VALVE WITH 1/4 TURN STOPS, 3 FUNCTION TRANSFER VALVE, 1/2" CC CONNECTIONS, SHOWER ARM AND 1/2" IPS MALE THREAD, SHOWER HEAD, HAND-HELD SHOWER WITH NON-POSITIVE PAUSE , 69" METAL HOSE, 30" SLIDE BAR, DROP ELL, VACUUM BREAKER, MOUNTING HARDWARE, VANDAL RESISTANT SCREWS, QUICK CLEANING RUBBER NOZZLE, TEMPERATURE AND TRANSFER VALVE HAVE ADA COMPLIANT LEVER HANDLES, HANDLE OPERATES COUNTERCLOCKWISE THROUGH A 270°F ARC, ADJUSTABLE TEMPERATURE LIMIT STOP, PRESSURE BALANCING MECHANISM MAINTAINS SELECTED DISCHARGE TEMPERATURE TO ±2°F, TRANSFER VALVE OPERATES 3 DISTINCT FUNCTIONS, AND WATERSENSE CERTIFIED. ADA SHOWERS SHALL BE ADAPTABLE: SHOWER SEAT, GRAB BARS NOT REQUIRED AS PART OF INITAIL INSTALLATION, CURTAIN ROD, AND SOAP DISH BY G.C.

PLUMBING SYMBOLS

DOMESTIC COLD WATER

110°F HOT WATER

110°F HOT WATER RETURN

140°F HOT WATER

TEPID WATER (80°F-85°F)

SANITARY - ABOVE FLOOR

SANITARY - BELOW FLOOR

GREASE LADEN WASTE - ABOVE FLOOR

GREASE LADEN WASTE - BELOW FLOOR

RAINWATER CONDUCTOR - ABOVE FLOOR

RAINWATER CONDUCTOR - BELOW FLOOR

VENT

NATURAL GAS

EXISTING TO REMAIN

EXISTING TO BE REMOVED

GATE VALVE

BALL VALVE

BUTTERFLY VALVE

GAS VALVE

GAS PRESSURE REGULATOR

CHECK VALVE

MIXING VALVE

OS&Y VALVE

PRESSURE REDUCING VALVE

WATER HAMMER ARRESTER

BACKFLOW PREVENTER

SOLENOID VALVE

BALANCING VALVE

PRESSURE GAUGE WITH SHUT-OFF VALVE

WATER METER

PUMP

STRAINER WITH HOSE BIBB

PIPE CAP

PIPE RISE

PIPE DROP

PIPE THRU WITH BOTTOM TAP

UNION

ELBOW

TEE

ACCESS PANEL

ELECTRICAL PANEL BY EC

PRESSURE & TEMPERATURE RELIEF VALVE

THERMOMETER

VACUUM RELIEF VALVE

AQUASTAT

CW

HW

HWR

140HW

T

SAN

SAN

OW

OW

RWC

RWC

V

G

(E)

M

AP

lgamble Snapshot

2 2

4" SAN(E) 4" SAN(E)

2" SAN

4" SAN(E)

2" SAN

WH(E)

4" VTR(E)

3" V(E)

2" CW(E)

2" CW(E)2" CW(E)2" CW(E)

2" CW(E)

2" CW(E) UP

FRM CRAWL

SPACE BELOW

EWH(E), EX 80

GALLON ELECTRIC

WATER HEATER

(2) 4.5 KW ELEMENTS

CP(E), EX

RE-CIRC PUMP

4" HWR

1" HW125(E)

1" CW

4" HWR(E)

1" HW(E)

4" SAN(E)

1" CW(E)

4" HWR(E)

1" HW(E)

4" SAN(E)

1" CW(E)

FCO(E)

2" CW(E)

10 10 10

2" CW(E)

VTR(E)

4" SAN(E)

4" SAN(E)

4" SAN(E) U/G

EXISTING BILCO

DOORS TO WATER

UTILITY ROOM BELOW

14 15

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

KEY PLAN

PROJECT

NORTH

PROJECT

NORTH

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

P

LU

M B

IN

G

G R

O U

N D

F

LO

O R

D M

R R A

S

P1.1

PLUMBING GROUND FLOOR DEMO PLAN (POLICE WING)

SCALE: 1/8" = 1'-0"

P O

LI

C

E W

IN

G

D E

M O

P

LA

N

CONTRACTOR SHALL REMOVE EXISTING COLD WATER PIPING BACK TO POINT SHOWN. VALVE

AND TEMPORARILY CAPPED FOR FUTURE CONNECTION. CONTRACTOR SHALL FIELD VERIFY

EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING COLD WATER PIPING PRIOR TO

ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING WATER CLOSET, TOILET FLANGE, ASSOCIATED VALVES,

SANITARY PIPING, CW PIPING, ETC. REMOVE SANITARY AND CW PIPING BACK TO POINT

SHOWN ON PLAN AND CAP. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING,

INVERT, AND SIZE OF PIPING AND FIXTURE PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING VENT PIPING BACK TO POINT SHOWN BELOW ROOF

AND TEMPORARILY CAP FOR FUTURE CONNECTION. CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING VENT PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING URINAL, CARRIER, FLUSH VALVE, SANITARY PIPING, CW

PIPING, ETC. REMOVE SANITARY AND CW PIPING BACK TO POINT SHOWN ON PLAN AND CAP.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF PIPING

AND FIXTURE PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING THERMOSTATIC MIXING VALVE, COLD AND HOT

WATER PIPING IN IT'S ENTIRETY. CONTRACTOR SHALL FILED VERIFY EXACT LOCATION,

ROUTING, INVERT, AND SIZE OF VALVE AND PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING COLD WATER PIPING BACK TO POINT SHOWN. VALVE

AND CAP PIPING IN CRAW SPACE. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION,

ROUTING, INVERT, AND SIZE OF EXISTING COLD WATER PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING SANITARY PIPING BACK TO POINT SHOWN IN CRAWL

SPACE AND TEMPORARILY CAP. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING SANITARY PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING BI-LEVEL ELECTRIC WATER COOLER, ASSOCIATED

VALVES, COLD WATER PIPING, P-TRAP, TAILPIECE, COLD WATER PIPING, CARRIER, IN IT'S

ENTIRETY. CONTRACTOR SHALL REMOVE EXISTING SANITARY PIPING BACK TO POINT SHOWN

AND CAP. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF

EXISTING ELECTRIC WATER COOLER AND PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING LAUNDRY SERVICE SINK, ASSOCIATED VALVES, P-TRAP, TAILPIECE, FAUCET, VENT PIPING, COLD AND HOT WATER PIPING, ETC. IN IT'S ENTIRETY.

CONTRACTOR SHALL REMOVE EXISTING SANITARY PIPING BACK TO POINT SHOWN AND CAP.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING

LAUNDRY SERVICE SINK AND PIPING PRIOR TO ANY DEMOLITION.

EXISTING COLD WATER PIPING RUNNING IN CRAWL SPACE BELOW.

CONTRACTOR SHALL REMOVE EXISTING LAVATORY SERVICE SINK, ASSOCIATED VALVES, P-TRAP, TAILPIECE, FAUCET, VENT PIPING, COLD AND HOT WATER PIPING, ETC. IN IT'S ENTIRETY.

CONTRACTOR SHALL REMOVE EXISTING SANITARY PIPING BACK TO POINT SHOWN AND CAP.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING

LAVATORY SINK AND PIPING PRIOR TO ANY DEMOLITION.

CONTRACTOR SHALL FLUSH, CLEAN, AND/OR REPLACE ELEMENTS AS NECESSARY.

CONTRACTOR SHALL REMOVE EXISTING HAND SINK, ALL ASSOCIATED VALVES, P-TRAP,

TAILPIECE, FAUCET, VENT PIPING, COLD AND HOT WATER PIPING, ETC. IN IT'S ENTIRETY BACK

TO ADJACENT MAINS IN CEILING AND CAP. CONTRACTOR SHALL REMOVE EXISTING SANITARY

PIPING BACK TO MAIN UNDER SLAB AND CAP. CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING LAVATORY SINK AND PIPING PRIOR TO

ANY DEMOLITION. CONTRACTOR SHALL SAW CUT AND EXCAVATE EXISTING FLOOR SLAB AS

REQUIRED TO ACCESS EXISTING SANITARY PIPING, BACKFILL AND PATCH SLAB TO MATCH

EXISTING.

CONTRACTOR SHALL REMOVE EXISTING KITCHEN SINK, ALL ASSOCIATED VALVES, P-TRAP,

TAILPIECE, FAUCET, VENT PIPING, COLD AND HOT WATER PIPING, ETC. IN IT'S ENTIRETY BACK

TO WALL SPACE BEHIND SINK AND CAP IN WALL. CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING KITCHEN SINK AND PIPING PRIOR TO ANY

DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING THREE-COMPARTMENT SINK, ALL ASSOCIATED VALVES,

P-TRAP, TAILPIECE, FAUCET, VENT PIPING, COLD AND HOT WATER PIPING, ETC. IN IT'S ENTIRETY

BACK TO ADJACENT MAINS IN CEILING AND CAP. CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING LAVATORY SINK AND PIPING PRIOR TO

ANY DEMOLITION.

CONTRACTOR SHALL REMOVE EXISTING RECESSED GREASE TRAP, FLOOR SINK, ALL ASSOCIATED

SANITARY AND VENT PIPING BACK TO MAINS AND CAP. CONTRACTOR SHALL SAW CUT AND

EXCAVATE EXISTING FLOOR SLAB AS REQUIRED TO ACCESS EXISTING SANITARY PIPING,

BACKFILL AND PATCH SLAB TO MATCH EXISTING.

CONTRACTOR SHALL REMOVE EXISTING FLOOR SINK, ALL ASSOCIATED SANITARY AND VENT

PIPING BACK TO MAINS AND CAP. CONTRACTOR SHALL SAW CUT AND EXCAVATE EXISTING

FLOOR SLAB AS REQUIRED TO ACCESS EXISTING SANITARY PIPING, BACKFILL AND PATCH SLAB

TO MATCH EXISTING.

CONTRACTOR SHALL REMOVE ALL EXISTING PROPANE PIPING SERVING EXISTING COOKING

EQUIPMENT BACK TO MAIN IN CEILING SPACE AND PROVIDED VALVED AND CAPPED

CONNECTION FOR FUTURE USE. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING PROPANE PIPING PRIOR TO ANY DEMOLITION.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

N.I.C.

B F

D F

N.I.C.

4" VTR(E)

3" V(E)

4" SAN(E)

FCO(E)

VTR(E)

4" SAN(E)

4" SAN(E)

4" SAN(E) U/G

WCO2

HKS1

HKS1

4" VTR

3" V UP

HWC1HSH1

MS1

HLAV1

2" V UP,

2" W DN

2" V

2" SAN

4" SAN

3" V 3" V

2" V UP,

2" W DN

2" SAN

2" V

4" SAN

WCO1

FD1

HKS1

2" V

3" V

FD2

FD2

FD2

HWC2

HWC2

HWC2

SS1

4" SAN4" SAN(E)

FD1

HUR1 UR1

HLAV1

FD1

FD1

WC1

HWC1

WC1HSH1

2" SAN

1 1

HWC1

HLAV1

HEWC1

2" V

2" V 2" SAN

4" SAN

AD1 AD1 ECO1

MINIMUM

INVERT =

-3'-0' BFG

ECO1

OW1

OIL/WATER

SEPARATOR (OW1),

REFER TO DETAIL

REFER TO CIVIL

PLANS FOR

CONTINUATION

4" SAN

2" V

2" SAN

2" V

2" V

2" V

2" V

3" SAN

4" OW 4" OW

4" SAN

2" V U/G

2" V UP

TO 3" VTR

2" V UP

TO 3" VTR

2" V U/G

2" V U/G

SLAB ON GRADE CRAWL SPACE

SLAB ON GRADE CRAWL SPACE

2" V

WCO2

SALLY PORT

HALL

STORAGE

122B

H.C.

H.C.

H.C.

POLICE

LOBBY

INTERVIEW

INTERVIEW

HALL

GEAR

ROOM

TRAINING

ROOM

CORRIDOR

EVIDENCE

ROOM

L.T. STORAGE

EVIDENCE

INTK

ARMORY/

STORAGE

VEST.

DET

OFFICE

DET

OFFICE

HALL

CPL.

OFFICE

CPL.

OFFICE

CPL.

OFFICE

DET. SGT.

OFFICE

DET

OFFICE

CPL.

OFFICE

RECEP. SEC/

MAIL ROOM

STORAGE

FORENSIC

PROCESSING

PATROL

SGT.

CHIEF'S

OFFICE

HALL

PATROL

ROOM

MECH.

INTERVIEW

LOBBY

SECURITY

CORRIDOR

BREAK

ROOM

KITCHEN

TOILET

STORAGE

WOMENS

RESTROOM

WOMENS

LOCKERS

CLOSET

MENS

LOCKERS

MENS

RESTROOM

J/C

CORRIDOR

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

KEY PLAN

PROJECT

NORTH

PROJECT

NORTH

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

D M

R R A

S

P2.1

PLUMBING GROUND FLOOR PLAN (POLICE WING) - SANITARY/VENT

SCALE: 1/8" = 1'-0"

CONTRACTOR SHALL CONNECT NEW 4" SANITARY PIPING INTO EXISTING 4" SANITARY PIPING.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING

SANITARY PIPING PRIOR TO ANY NEW WORK. CONTRACTOR SHALL SAWCUT EXISTING SLAB

AND EXCAVATE AS REQUIRED TO ACCESS EXISTING PIPING. BACKFILL AND PATCH SLAB TO

MATCH EXISTING.

CONTRACTOR SHALL CONNECT NEW 3" VENT PIPING INTO EXISTING TEMPORARILY CAPPED 3"

VENT PIPING. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE

OF EXISTING VENT PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL CONNECT NEW SANITARY PIPING INTO EXISTING TEMPORARILY CAPPED

4" SANITARY PIPING. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING SANITARY PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL CONNECT NEW 2" VENT PIPING INTO EXISTING VENT PIPING IN THIS AREA.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING

VENT PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL SAWCUT EXISTING SLAB AND EXCAVATE AS REQUIRED TO ACCESS

EXISTING PIPING. BACKFILL AND PATCH SLAB TO MATCH EXISTING.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

P

LU

M B

IN

G

G R

O U

N D

F

LO

O R

P

LA

N P

O

LI

C E

W

IN

G

S A

N

IT

A R

Y /V

E N

T

N.I.C.

B F

D F

N.I.C.

WH(E)

2" CW(E)

2" CW(E)2" CW(E)

2" CW(E) UP

FRM CRAWL

SPACE BELOW

EWH(E), EX 80

GALLON ELECTRIC

WATER HEATER

(2) 4.5 KW ELEMENTS

CP(E), EX

RE-CIRC PUMP

4" HWR

1" HW125(E),

1" CW(E)

4" HWR(E)

1" HW(E)

1" CW(E)

4" HWR(E)

1" HW(E)

1" CW(E)

2" CW(E)

5 5

2" CW(E)

EXISTING BILCO

DOORS TO WATER

UTILITY ROOM BELOW

SS1HKS1

HKS1

MS1

TMV1

1" HW140

1" HW125

4" HWR110

4" HWR

4" HWR

1" HW

2" HW

2" CW

2" CW

2" HWR

4" HWR

1" HW

4" CW

4" HWR

1" HW

4" HWR

1" HW

HSH1

HWC2

WH1

WH1

4" CW

4" CW

4" CW

RUN 3 4" CW

DN ALONG

WALL w/SHUT-

OFF BALL VALVE

RUN 3 4" CW

DN ALONG

WALL w/SHUT-

OFF BALL VALVE

1" CW

4" HW

2" HWR

WH1

1" HW

2" CW

4" CW

HKS1

IB1

4" CW

HEWC1

HLAV1HWC1

HWC2

HWC2

HSH1

2" HWR

2" HW

4" CW

4" CW

2" CW

2" CW

SHUT-OFF VALVE (TYP)

BALANCING VALVE (TYP)

CHECK VALVE (TYP)

2" CW

2" HWR

2" CW

HUR1 UR1

HWC1

WC1

HLAV1

HLAV1HLAV1

WC1

4" CW

2" HW

1" HW

2" CW

HWC1

WHA1

WHA1

SALLY PORT

HALL

STORAGE

122B

H.C.

H.C.

H.C.

POLICE

LOBBY

INTERVIEW

INTERVIEW

HALL

GEAR

ROOM

TRAINING

ROOM

CORRIDOR

EVIDENCE

ROOM

L.T. STORAGE

EVIDENCE

INTK

ARMORY/

STORAGE

VEST.

DET

OFFICE

DET

OFFICE

HALL

CPL.

OFFICE

CPL.

OFFICE

CPL.

OFFICE

DET. SGT.

OFFICE

DET

OFFICE

CPL.

OFFICE

RECEP. SEC/

MAIL ROOM

STORAGE

FORENSIC

PROCESSING

PATROL

SGT.

CHIEF'S

OFFICE

HALL

PATROL

ROOM

MECH.

INTERVIEW

LOBBY

SECURITY

CORRIDOR

BREAK

ROOM

103KITCHEN

TOILET

STORAGE

WOMENS

RESTROOM

112WOMENS

LOCKERS

CLOSET

120 MENS

LOCKERS

MENS

RESTROOM

J/C

CORRIDOR

SLAB ON GRADE CRAWL SPACE

SLAB ON GRADE CRAWL SPACE

2" CW

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

KEY PLAN

PROJECT

NORTH

PROJECT

NORTH

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

D M

R R A

S

P2.2

PLUMBING GROUND FLOOR PLAN (POLICE WING) - DOMESTIC WATER

SCALE: 1/8" = 1'-0"

CONTRACTOR SHALL CONNECT NEW 3/4" HWR PIPING INTO EXISTING HWR PIPING PRIOR TO

EXISTING HOT WATER RE-CIRC PUMP. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION,

ROUTING, INVERT, AND SIZE OF EXISTING HWR PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL CONNECT NEW 1" HW PIPING INTO EXISTING HOT WATER PIPING FOR

EXISTING WATER HEATER AND PROVIDE SHUT-OFF VALVE. CONTRACTOR SHALL FIELD VERIFY

EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING HW PIPING PRIOR TO ANY NEW

WORK. CONTRACTOR SHALL VERIFY TEMPERATURE OF EXISTING WATER HEATER AND PROVIDE

NEW THERMOSTATIC MIXING VALVE TMV1.

CONTRACTOR SHALL CONNECT NEW 1" HW PIPING INTO EXISTING HOT WATER PIPING FOR

EXISTING WATER HEATER AND PROVIDE SHUT-OFF VALVE. CONTRACTOR SHALL FIELD VERIFY

EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING HW PIPING PRIOR TO ANY NEW

WORK.

CONTRACTOR SHALL CONNECT NEW 2" CW PIPING INTO EXISTING CW PIPING IN CRAWL

SPACE. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF

EXISTING CW PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL VERIFY THE LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING CW

PIPING IN CRAWL SPACE PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL CONNECT NEW 3/4" CW PIPING INTO EXISTING TEMPORARILY CAPPED

3/4" CW PIPING. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND

SIZE OF EXISTING CW PIPING PRIOR TO ANY NEW WORK.

CONTRACTOR SHALL DROP DOWN AND PROVIDE 2" CW AND 1" HW HEADER IN CHASE TO

SUPPLY EACH FIXTURE. PROVIDE WATER HAMMER ARRESTOR (WHA1) BETWEEN THE LAST

TWO FIXTURES.

PROVIDE HB1 MOUNTED UNDER SINK.

CONTRACTOR SHALL EXTEND 2" CW UP IN CHASE TO SUPPLY BATHROOM FIXTURES.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, ROUTING, INVERT, AND SIZE OF EXISTING

CW PIPING PRIOR TO ANY NEW WORK.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

P

LU

M B

IN

G

G R

O U

N D

F

LO

O R

P

LA

N P

O

LI

C E

W

IN

G

D O

M E

S

TI

C W

A

TE

R

FLOOR

ROOF

GROUND

SANITARY AND VENT RISER DIAGRAM

NO SCALE

-MINIMUM PIPE SIZE BELOW SLAB IS 2"

-DRAINAGE FIXTURE UNITS (0.0), SEE IPC TABLE 709.01

-ALL FIXTURES TO BE TRAPPED AND VENTED

-MINIMUM PIPE SLOPE:

3" PIPE SIZE OR MORE = 1 8"/FT

2" PIPE SIZE OR LESS = 1 4"/FT

-ALL VTR'S TO BE LOCATED A MINIMUM OF 10'

FROM ANY HVAC UNIT AND/OR FRESH AIR INTAKE

4"(E) (54.0)

4" VTR(E)

3"(E)

REFER TO FLOOR

PLAN FOR

CONTINUATION

2"

HKS1

(2.0)

2"

2" (1.0)

2"

HLAV1

(1.0)

2"

2" (1.0) 4" (4.0)

2"

HWC1

(4.0) 11

2"

HEWC1

(1.0)

2"

2" (1.0)

MS1

(2.0)

3" (2.0)

2"

2"

HKS1

(2.0)

2"

2" (2.0) 4" (4.0)

2"

HWC1

(4.0)

FD1

(0.0)

2" (0.0)

HSH1

(2.0)

2" (2.0) 4" (4.0)

2"

HWC1

(4.0)

FD1

(0.0)

2" (0.0)

2"

HLAV1

(1.0)

2"

2" (2.0)

HLAV1

(1.0)

2"

2" (2.0)

FD1

(0.0)

2" (0.0)

HSH1

(2.0)

2" (2.0)

2" (2.0)

2" (2.0)

2"

HUR1

(2.0)

2" (2.0)

2"

HUR1

(2.0)

2" (4.0) 4" (10.0)

4" (4.0)

2"

HWC1

(4.0)

4" (4.0)

2"

HWC1

(4.0)

FD1

(0.0)

2" (0.0)

2"

HLAV1

(1.0)

2"

2" (2.0)

HLAV1

(1.0)

2" 11

2"

HKS1

(2.0)

2"

2" (2.0)

FD1

(0.0)

2" (0.0) 4" (4.0)

2"

HWC2

(4.0)

FD1

(0.0)

2" (0.0) 4" (4.0)

2"

HWC2

(4.0)

WCO1

4"

2"

SS1

(2.0)

2"

2" (1.0)

FD1

(0.0)

2" (0.0) 4" (4.0)

2"

HWC2

(4.0) WCO1

4" 4"

FCO(E)

4" (7.0) 3" (2.0) 4" (10.0)

2" (2.0)

2"

4" (8.0)

WCO1

2"2"

2"

2"2"2"3"2"

4" VTR

3"

2" 2"3" 3"

4" (5.0)

4" (5.0)4" (13.0)4" (15.0)4" (25.0)4" (29.0)4" (31.0)4" (33.0)4" (43.0)4" (45.0)

4"(E)(47.0)

4"(E)(47.0)

EXISTING

80 GALLON

ELECTRIC

WATER

HEATER,

EWH(E)

1" CW(E)

1" HW(E)

2" CW(E)

2" CW(E)

4" HWR(E)

1" CW(E)

1" HW(E)

THERMOSTATIC

MIXING VALVE,

TMV1

1" HW140(E)

1" CW(E)

1" HW125

4" HWR

1" HW

RE-CIRC PUMP(E)

4" HWR(E)

2" CW(E)

IN CRAWL

SPACE

1" CW(E)

1" HW(E)

4" HWR(E)

WH1

4"

FLOOR

ROOF

GROUND HKS1

2"1

2"

HWC1

1"

HEWC1

2"

HKS1

2"1

2"

IB1

2"

HLAV1

UNDERSINK MIXING

VALVE, WATTS

MODEL LFM495 OR

EQUAL (TYP.)

2" HWR

2" HW

2" CW

SHUT-OFF VALVE (TYP)

BALANCING VALVE (TYP)

CHECK VALVE (TYP)

HWC1

1"

WC1

1"

HUR1

4"

HUR1

4"

HSH1 1

2"

2"HWC1

1"

WC1

1"

WHA1

HLAV1HLAV1

HSH1

2"1

2"

MS1

4"3

4"

HLAV1HLAV1

WH(E)

4"

HKS1

2"1

2"

HWC2

1"1 2" 1"1

2"

SS1

2"

HWC2

1"1 2"1

2"

4" 3

4"

REFER TO FLOOR PLAN

FOR CONTINUATION

DOMESTIC WATER RISER DIAGRAM

NO SCALE

2" CW(E)

IN CRAWL

SPACE

2" CW(E)

IN CRAWL

SPACE

2" CW(E)

IN CRAWL

SPACE

WH1 WH1HWC2

WHA1

1" 2" 3 4"3

4"

4"

4" HWR

1" HW

1" CW

2" CW

2" HW

4" HWR

1" HW

1" CW

2"

4" HWR

1" HW

4" CW

2" CW

2" CW HEADER

IN CHASE

2" CW HEADER,

1" HW HEADER

IN CHASE

4" HWR

1" HW

1" CW

4" HWR

1" HW

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

PL

UM

BI

NG

R

IS

ER

D

IA

G

RA

M

S

SH

EE

T

D M

R R A

S

P3.1

P ro gr es s P rin ts

R ev is io ns

C he ck ed

B y:

D ra w n

B y:

C on st ru ct io n Is su e

D at e:

S ca le : A

S N

O

TE

D

PO

C O

N O

T O

W N S H

IP

M U N

IC

IP

A L

C O

M

PL

EX

N C

C B

U

IL

D

IN

G O

LD

M

IL

L

R O

A D

TA

N N

ER

S V

IL

LE

P

A

BSEG Project No: 24.0112.000

4949 Liberty Lane, Suite 115, Allentown, PA 18106 P: 610-351-8225 F: 610-351-8210 www.bseg-ce.com

B u i l d i n g S y s t e m s E n g i n e e r i n g G r o u p

C O

P Y

R

IG

H T

K

IM

M

E L A

R C

H

IT

E C

T U

R E

IN

C c

A

H T

S R

E

SE

R V

E D

P H

O N

E .8

.7

P

IT

T S

B U

R G

H O

F F

IC

E

L

IB

E R

T Y

A V

E N

U E U

N

IT

P

IT

T

SB

U R

G H

P A

P H

IL

A

D E

L P

H

IA

O F

F

IC

E

N

O R

R

IS

T O

W N

R O

A D

SU

IT

E

B L U

E B

E L L P A

.2

4.

0%

S E

T

.3 0.

B

ID

/P

E R

M

IT

S E

T

P

LU

M B

IN

G

D E

TA

IL

S S

H E

E T

D M

R R A

S

P4.1

REDUCE IF REQUIRED (ANY

INCREASE IN THE SIZE OF THE

VENT SHALL BE MADE INSIDE

THE STRUCTURE A MIN. OF 1

FOOT BELOW THE ROOF

NO SCALE

VENT PIPE THROUGH FLAT ROOF DETAIL

NOTES:

1. AN OPEN VENT TERMINAL FROM A DRAINAGE SYSTEM SHALL NOT BE LOCATED

DIRECTLY BENEATH ANY DOOR, OPERABLE WINDOW, OR OTHER INTAKE OPENINGS

OF THE BUILDING OR OF AN ADJACENT BUILDING, AND ANY SUCH VENT TERMINAL

SHALL NOT BE WITHIN 10 FEET HORIZONTALLY OF SUCH AN OPENING UNLESS IT IS

AT LEAST 2 FEET ABOVE THE TOP OF SUCH OPENING.

2. FOLLOW ROOF MANUFACTURER'S FLASHING INSTRUCTIONS WHERE REQUIRED

MANUFACTURER'S WARRANTY.

" M

IN

IM

U M

, V

ER

IF

Y w /A

U

TH

O

RI

TY

H

AV

IN

G

JU

RI

SD

IC

TI

O N

E.P.D.M.

ROOF

VENT PIPE SIZE TO

BE A MIN. OF 3"Ø

(SEE DRAWINGS

FOR EXACT SIZE)

MAKE SEAL WATERTIGHT

BY AN APPROVED

FLASHING (BLACK FINISH)

FLASHING

COLLAR

INSULATION

REQUIRED SIZE

(SEE DRAWINGS

FOR EXACT SIZE)

WOOD JOIST

TRAP/SUPPLY GUARD FOR ADA ACCESSIBILITY - DETAIL

NO SCALE

FLANGE WITH

ESCUTCHEON

PLATE

SUPPLY TUBE

COVER WITH

INTERNAL TRIM

GROOVES

SUPPLY KIT WITH

BRASS STOPS

AND FULL TURN

BRASS STEMS

INTERNAL

FASTENER

(TYP.)

GRID DRAIN

WITH OVERFLOW

RUBBER WASHER

FRICTION WASHER

TAILPIECE

OFFSET

IF REQUIRED

TAILPIECE COVER

INTERNAL RIBS,

CUSHIONING AND

THERMAL RESISTANT

SLIP NUT (TYP.)

P-TRAP

J-BENT COVER

VENT HOLE

CLEANOUT

WASTE ARM

COVER WITH

INTERNAL TRIM

GROOVES

VENT

SLOTS

WHEEL

HANDLE OR

QUARTER

TURN BALL

VALVE

TYPICAL FLOOR DRAIN INSTALLED IN EXISTING FLOOR - DETAIL

NO SCALE

P-TRAP

THREADED, CAULKED

OR NO-HUB

CONNECTION

CAPPED TRAP PRIMER CONNECTION

PROVIDE SURE SEAL TRAP

GUARD OR EQUAL IN LIEU OF

TRAP PRIMER IF APPROVED

BY AUTHORITY HAVING JURISDICTION

OR APPROPRIATE CODE

PROVIDE A METAL SUPPORT PLATE

WHEN DRAIN IS INSTALLED IN AN

EXISTING FLOOR - CAULK

AROUND DRAIN PRIOR TO RE-GROUTING

FLASHING CLAMP w/WEEP HOLES

LOOSE GRAVEL AT

WEEP HOLESFINISHED FLOOR

CONCRETE

FLOOR

ADJUSTABLE STRAINER HEAD

REMOVE AND REPLACE CONCRETE

SLAB AS REQ'D TO INSTALL

NEW FLOOR DRAIN

CL

TYPICAL FLOOR CLEANOUT - DETAIL

NO SCALE

FLANGED WITH

FLASHING COLLAR

AS REQUIRED

FINISHED FLOOR

HEAVY DUTY TOP

FOR HIGH TRAFFIC

AREAS

CENTER

SECURING SCREW

THREADED

PLUG

FITTING TYPE

AS REQUIRED

TO SUIT

CL

JAY R SMITH FIG. 4500

CLEANOUT TEE WITH PLUG AND

COVER OR APPROVED EQUAL

NOTE: TYPICAL FOR CLEANOUT IN SOIL/WASTE/RAINWATER CONDUCTORS

FINISHED

FLOOR

AS

R

EQ

'D

BY

C

O

DE

ACCESS DOOR

INSULATION

AS SPECIFIED

SANITARY

PIPE

CASE

OR WALL

WALL CLEANOUT IN SANITARY - DETAIL

NO SCALE

HOSE

BRACKET

30" HOSE

NOTE: ALL FAUCETS SHALL BE PROVIDED WITH EITHER INTERNAL CHECK STOPS

OR CHECK VALVES ON WATER LINES TO PREVENT CROSSFLOW

MOP BASIN WITH FAUCET -DETAIL

NO SCALE

3" SANITARY DRAIN

FINISHED FLOOR

APPLY SILICONE SEALANT

AROUND TOP AND SIDES

OF BASIN AT WALLS AND

FLOOR

MOP BASIN

QUICK DRAIN

CONNECTOR

MOP (BY OTHERS)

SERVICE SINK FAUCET

w/INTERNAL CHECK STOPS

VACUUM BREAKER

MOP HANGER

4" HW

& CW

WALL

WATER HAMMER

ARRESTOR (TYP.)

NO SCALE

PIPE SLEEVE THRU WALL DETAIL

SHEET METAL SLEEVE

(MIN. 22 GAUGE)

ZERO CLEARANCE

CONTINUOUS FLANGE

FULL FORMED

FIBERGLASS ROPE (1000°F)

MIN. IF 3 WRAPS REQUIRED

FRICTION FIT BETWEEN

PIPE AND SLEEVE

SHEET METAL ANGLE

RING (MIN. 22 GAUGE)

SECURE TO SLEEVE

INSULATION

(WHERE REQ'D)

METAL STUD

ESCUTCHEON PLATE ON

BOTH SIDES WHERE

PIPING IS EXPOSED

PIPE

2A MODIFIED STONE

COMPACTED IN 8" LAYERS

2A MODIFIED

STONE COMPACTED

IN 4" LAYERS

UNDISTURBED

EARTH

12"

4" MIN TO

BARREL

TRENCH WIDTH AS

REQUIRED

#4 REINFORCING ROD 18" O.C.,

GROUTED MIN 6" INTO EXISTING SLAB

WITH NON-SHRIINK GROUT

NO SCALE

SANITARY PIPE IN EXISTING SLAB TRENCH DETAIL

TYPICAL FLOOR DRAIN IN WOOD FLOOR DETAIL

NO SCALE

DEEP SEAL TRAP

PROVIDE SURE SEAL TRAP

GUARD OR EQUAL IN LIEU OF

TRAP PRIMER IF APPROVED

OR APPROPRIATE CODE

ANCHOR FLANGE

ATTACHED TO FLOOR,

SEALED WATERTIGHT

ADJUSTABLE STRAINER

REFER TO DRAIN MANUFACTURER'S WRITTEN

INSTRUCTIONS FOR EXACT INSTALLATION REQUIREMENTS

WOOD SUPPORT

BLOCKING

WOOD SUBFLOOR

THREADED, CAULKED OR NO-HUB

CONNECTION

FINISHED FLOOR

CL

CLEVIS HANGER

NO VAPOR

BARRIER INSULATION

FOR STEEL

PIPE HANGER (WOOD) DETAIL

NO SCALE

WOOD BEAM

OR JOIST

MALLEABLE IRON

SIDE BEAM

CONNECTION

WOOD DRIVE SCREWS

NUT AND WASHER

ADJUST & POSITION

WITHIN SLOT

PIPE SIZES

2", 3 4", & 1"

SUSPENSION PIPE

CLAMP, TOP JOIST

MOUNT

WOOD BEAM

OR JOIST

SUSPENSION PIPE

CLAMP, TOP JOIST

MOUNT

PIPE SIZES

2", 3 4", & 1"

PIPE SIZES

2", 3 4", & 1"

SUSPENSION PIPE

CLAMP, TOP JOIST

MOUNT

WOOD BEAM

OR JOIST

MODEL #B-LINE FIG.

3100 STANDARD

CLEVIS HANGER OR

APPROVED EQUAL

ALL THREADED ROD

NOTES:

1. PIPE HANGERS AND ROD SHALL BE GALVANIZED STEEL EXCEPT

HANGERS FOR COPPER PIPING SHALL BE COPPER COATED.

2. FOR COPPER TUBING USE PLASTIC COATED B3100C OR APPROVED

EQUAL.

3. COORDINATE SLOT LOCATION WITH HANGERS.

PIPE RING

CROSS BRACE

PIPE

OPTION #1

OPTION #2

CAPPED TRAP PRIMER CONNECTION

6" 48" x 48" 6"

60" x 60

6"

8"

8"

4" INLET

4" OUTLET

MOLDED

POLYETHYLENE

BAFFLES (TYP.)

SEAL PIPE

WATERTIGHT

(TYP.)

4" INSPECTION PORTS

w/TRAFFIC RATED

CLEANOUTS FLUSH WITH

GRADE (TYP. OF 2)

FINISHED GRADE

24" DIA. HEAVY DUTY

TRAFFIC RATED

C.I. FRAME AND COVER

FLUSH WITH GRADE

24" DIA. CONCRETE

ADJUSTING RINGS

2" VAPOR VENT, INSTALL

ABOVE WATER LINE

SECTION VIEW

PLAN VIEW

OIL/WATER INTERCEPTOR (OW1) DETAIL

NO SCALE

Sheets and Views
24.0112_P0.0-P0.0
24.0112_P1.1-P1.1
24.0112_P2.1-P2.1
24.0112_P2.2-P2.1
24.0112_P3.1-P3.1
24.0112_P4.1-P4.1

File details come from the government source that posted it. Updated .