19UK5626Q0031 - Attachment 1.pdf
PDF 37 MB Posted
- Attached to
- Fuel Distribution Systems
- Solicitation number
- 19UK5626Q0031
- Issued by
-
Department of State US Embassy London
About this file
This is a Solicitation for preventive maintenance services for the Fuel Distribution Systems at the U.S. Embassy London. The U.S. Department of State, through the U.S. Embassy London, is seeking a contractor to provide all necessary managerial, administrative, and direct labor personnel, along with transportation, equipment, tools, repair parts, supplies, and materials required to perform the work. The contract will be awarded as a firm fixed price agreement to the lowest priced, technically acceptable offeror who is a responsible contractor. Payment will be made by electronic funds transfer following full completion of services, based on quantities and unit prices as specified in the contract.
Key dates and submission requirements include a mandatory site visit at the U.S. Embassy London on June 18, 2026 at 10:00 AM BST, with attendance confirmation required by email to procurement_box3@state.gov by COB June 15, 2026. All questions regarding the solicitation must be submitted by COB June 22, 2026. Quotes are due by 5:00 PM BST on July 7, 2026 and must be submitted via email to procurement_box3@state.gov with the subject line "19UK5626Q0031 - Fuel Distribution." The Government may award a Purchase Order or Contract based on the initial offer without discussion. Solicitation number is 19UK5626Q0031.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| QAs - Fuel Distribution - 19UK5626Q0031.pdf | ||
| SF 18 - 19UK5626Q0031.docx | DOCX document | |
| 19UK5626Q0031 - SOW - Fuel Management.pdf | ||
| FAR Clauses FAC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE&OF&CONTENTS:&
1. Datasheet&
2. Notes&And&Exceptions&
3. 231113>2.5,&2.7,&2.8,&2.9,&2.14&&10,000Gallon&Vertical&Storage&Tanks&and&Accessories&
4. 231113>2.17&Remote&Fill&and&Accessories&
5. 231113>2.1.C&Flexible&Connectors&
6. 231113>2.3&Valves&
7. 231113>2.6&Boiler&Daytank&and&Generator&Daytank&Fittings&(Gen.&Day&Tanks&by&Others)&
8. 231113>2.10,&2.11&Pneumercator&Leak&and&Level&Monitoring&System&Datasheets&
9. 231113>2.10,&2.11&Pneumercator&Leak&and&Level&Monitoring&System&Main&Drawings&
10. 231113>2.10,&2.11&Pneumercator&Leak&and&Level&Monitoring&System&NOB&Drawings&
11. 231113>2.16&Phillips&Fuel&Oil&Pumps&and&Control&System&Main&System&
12. 231113>2.16&Phillips&Fuel&Oil&Pumps&and&Control&System&NOB&System&
13. 231113&Phillips&Fill&System&and&Diversion&Controller&
14. 231113>2.15&RCI&&Fuel&Maintenance&System&
15. 231113&FRP>1&Phillips&Manual&Fuel&Removal&Pump& 16.
17.
18.
19.
20.
Datasheet#
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
LI DESCRIPTION MFTR/PART0N0. QTY U/M
1 Aboveground+Storage+Tanks 2 100000Gallon0VERTICAL0Storage0Tank
Application:0ABOVEGROUND0Type:0SINGLE0WALL Material:0Mild0Carbon0Steel0Diameter:010'/0Height:017' 1/4"0Shell01/4"0Head Each0Tank0Includes:
*0(1)018"DIA0Emergency0Vent0Manway *0(1)02"FNPT0Threaded0Opening *0(5)04"FNPT0Threaded0Openings *0(1)04"FNPT0Threaded0Opening0(Fill)0with0an0internal0drop0tube0 extending0to06"0of0bottom0of0tank *0Striker0Plates *0Lifting0Lugs *0Grounding0Lug *0(1)0Set0Hold0Down0Lugs *0UL^1420Label
4 ea
3 Epoxy0Primer0/0White0Urethane0Top0Coat.0SP^60Blast0Included 4 ea 4 EXTERNAL0VERTICAL0STRAIGHT0LADDER0^0PAINTED 2 ea 5 EXTERNAL0SAFETY0CAGE0^0PAINTED 2 ea 6 PAINTED024"W0x036"L0CATWALK0W/HANDRAIL0BOTH0SIDES0F/GLASS0
GRATING0
2 ea
7 TANK0TOP0PERIMETER0SAFETY0RAILING0^0PAINTED 4 ea 8 Special030^year0limited0warranty0^0requries0internal0seal0welding0for0 tanks0 4 ea
9 Box0of0accessoried0needed0to0accommodate0ladders,0railings,0platforms0 and0safety0cages
1 ea
10 Internal0Seal0Welding0for0each0tank 4 ea 11 Delivery0^010,0000gallon0vertical0tank0to0Baltimore,0MD0Offloading0and0 preparation0for0export0by0others.
FRT 1 lot
10"0Flanged0Emergency0Vent0^0808,3500CFH0@02.50psi,080oz/sq0in Morrison0244F^^0400AV 4 ea 151 Crating:WPM/1SPM0150Heat0Treated0Wooden0Crate/18'L0x0120"W0x0
120"H
CRATING0TANKS0FOR0SHIPMENT0OVERSEAS
4 ea
152 Crating0and0Freight0for0ladders,0safety0cages,0platforms0and0railings 1 ea 12 Remote+Fill+ 13 Custom0Remote0Grade0Fill0Assembly0with:
^14GA0SS0Secondary0Containment,0horizontal0discharge ^3/8""0diamond0plate0H200Load0rating ^5ea00spill0bucket0 ^5ea0hand0pump ^5ea0entry0boot0(mounted)
Fairfield0RFTC^Custom 1 ea
14 Drybreak0Adapter,0FNPT,0Al,04"0NPTFPM0VITON0SEAL0(@remote0fill) TODO07476^1107 4 ea 15 Drybreak0Cap,0Al,04"0FPM0SEAL0(@remote0fill) TODO05635B^1407 4 ea 16 4"0Butterfly0Valve0^0ductile0iron0body;0lug0style;0for0fuel0service.0255#0DI,0
SS,0BUNA.0ADD0Lockable0handle0per0drawing00(isolate0in0fuel0storage0 room0since0single0wall)
DixBFVL400 4 ea
17 Tank+Accessories 18 4"0x015"0Flex0connector,0male0x0male,0stainless0steel0(fill) Flexing0FFUL40X15MxM 4 ea 19 4"0Updraft0Vent Morrison0354^0400AV 4 ea 20 Ball0Valve,02"0Lockable0(FOS/FOR) Morrison0691B008001V0or0equal 12 ea
21 Flex0Connector,02"x018",0MxM0swivel0(FOS/FOR) FF20X18HMXM346 16 ea 22 2"0x02"0Internal0Emergency0Valve Morrison0272HO^0100AV0or0equal 8 ea 23 Misc0Tank0Fittings0and0Ports 1 ea 24 Building+Occupied 25 Flex0Connector,02"x018",0MxM0swivel0(Tank0FOS/FOR,0Polisher0and0Pump0
Connections) FF20X18HMXM346 16 ea
26 Safety0Valve0at0bulding0entry,02"0(FOS0where0it0enters0the0MER's) Morrison0346DI^05000AV0or0equal 3 ea 27 Ball0Valve,02"0Lockable0(if0needed0for0isolation0of0sections) Morrison0691B008001V0or0equal 10 ea 28 Day+Tank+Fittings 29 Vacuum0Breaker,01"MNPT0x03/4"FNPT,0SS0ball0w/viton0o^ring0for0fuel0oil0
(day0tank0return0line) 5 ea
30 2"0Flame0Arrestor 4 ea 31 Pneumercator+>+Main+ 32 TMS04000000w/0Display0&0Push0Buttons0^0Includes:000000000000000000000000000000000000000000
*040Mag0Inventory0Probe/80Leak0Sensor0Card,0(Probes0and0Sensors0 Separate) 0*0Two0RS^2320Ports 0*0One0RS^4850Port
KJ024A02580
ProtectoSeal06672
TMS04000 1 ea
33 Console0Adders 34 At^Factory0Programming 1 ea 35 Internal040Mag0Probe/80Leak0Sensor0Interface0Card 1 ea 36 Internal0160Leak0Sensor0Interface0Card 1 ea 37 Internal080Relay/80Non0I.S.0Input0I/O0Card0 1 ea 38 Internal04^200Mili^amp0Card0^0120Channels 1 ea 39 Internal0Mod0Bus0Card0for0BAS 1 ea 40 External0Relays 41 TX01064^10^0Extrenal0Relay0Expansion0Panel00 1 ea 42 Internal0160Relay0Card 1 ea 43 Mag0Probes 44 MP^461^xxx^21^Series0Flexible0Kynar0Inventory0Probe0for017'00tall0AST 4 ea 45 B4Xx^Kx0^0Extended0Buna^N0Float0Kit0^04"0Dia.0^0Standard0Product0and0
Extended0Water 4 ea
46 ***Probe0Installation0Kit0included0in0Flex0Probe0Price*** 47 MP^450S^xxx^110Rigid0Inventory0Probes0for010Boiler0Day0Tank 1 ea 48 S2K20^0Dual0Float0Kits^0Include:0Product0and0Water0Floats0for0Diesel 1 ea 49 PK020DM10^03/4"0S.S./Teflon0Probe0Installation0Compression0Fitting0Kit0for0
Direct0Mounting 1 ea
50 MP^450S^xxx^110Rigid0Inventory0Probes0for030UTL0Gen0Sub^base0Day0 Tanks
3 ea
51 S2x0^0Standard0Stainless0Steel0Float0^000000000000002"0Dia.0^0Product0Only 3 ea 52 PK020DM10^03/4"0S.S./Teflon0Probe0Installation0Compression0Fitting0Kit0for0
Direct0Mounting 000*NOTE:080of080Probe0Inputs0Used
3 ea
53 Leak0Sensors 54 SK20^02"0Leak0Sensor0Installation0Cap0Kit0for0Day0Tanks 4 ea 55 ES^825^200^F0Discriminating,0Optic0Leak0Sensor,0Fuels
40^0Remote0Fill0Sump0Sensor0 40^0Low0Point0DW0Fill0Pipe0Sensor0 120^0Low0Point0DW0Supply0Pipe0Sensor00(best0guess) 40^0Day0Tank0Leak0Sensors0(30gen,010boiler)
24 ea
56 LS^6000LD^BN^1F00Non^Discriminating,0Buna^n0Float,0Liquid0Leak0Sensor,0
Sumps,0Disp.0Pans,0Steel0Tanks
10^0Fuel0Polisher0Cabinet0Leak0Sensor
10^0Pump0Set0Skid0#10Leak0Sensor
20^0Fuel0Tank0Room0Leak0Sensor
000*NOTE:0280of0320Sensor0Inputs0Used
4 ea
57 Remote0Alarms 58 RA04000Remote0Alarm0Panel
00*0Audible0Alarm0w/0Digital0Display,0Test0&0Silence0Buttons
00*0Utilizes0RS04850Port0for0Communications0with0TMS0Console
00*00Switchable0Power0115/2300VAC0(50/600Hz)
00*00NEMA04X0Enclosure
4 ea
59 Remote0Alarm0w/0Digital0Level0Display 60 ETD010000remote0digital0level0display0and0level0alarm0panel000000000000000000000000000000000000000000000
Audible0alarm0w/digital0display,0test0and0silence0buttons00000000000000000000000000000000000000000000000000000
Utilizes0RS4850port0for0communications0with0TMS0console000000000000000000000000000000000000000000
Switchable0power0115/2300VAC(50/60HZ)00000000000000000000000000000000000000000000000000000000000000000000000000000
NEMA04X0enclosure
2 ea
61 Other 62 Auto0Cad0Wiring0Diagrams0for0Pneumercator 1 ea 63 Pneumercator+>+NOB 64 TMS04000000w/0Display0&0Push0Buttons0^0Includes:0
0*040Mag0Inventory0Probe/80Leak0Sensor0Card,0(Probes0and0Sensors0 Separate)0
0*0Two0RS^2320Ports0
0*0One0RS^4850Port0
0*0NEMA0120Case0
0*0TMS0COMM0Remote0communication0software0
TMS04000 1 ea
65 Console0Adders 66 At^Factory0Programming 1 ea 67 Internal080Relay/80Non0I.S.0Input0I/O0Card0 1 ea 68 Internal04^200Mili^amp0Card0^060Channels 1 ea 69 Internal0Mod0Bus0Card0for0BAS 1 ea 70 Mag0Probes 71 MP^461^xxx^21^Series0Flexible0Kynar0Inventory0Probe0for017'00tall0AST 1 ea 72 B4Xx^Kx0^0Extended0Buna^N0Float0Kit0^04"0Dia.0^0Standard0Product0and0
Extended0Water
1 ea
73 ***Probe0Installation0Kit0included0in0Flex0Probe0Price*** 74 MP^450S^xxx^110Rigid0Inventory0Probes0for010NOB0Gen0Sub^base0Day0
Tank
1 ea
75 S2x0^0Standard0Stainless0Steel0Float0^000000000000002"0Dia.0^0Product0Only 1 ea 76 PK020DM10^03/4"0S.S./Teflon0Probe0Installation0Compression0Fitting0Kit0for0
Direct0Mounting
000*0NOTE:020of040Probe0Inputs0Used
1 ea
77 Leak0Sensors 78 SK20^02"0Leak0Sensor0Installation0Cap0Kit0for0Day0Tanks 1 ea 79 ES^825^200^F0Discriminating,0Optic0Leak0Sensor,0Fuels
10^0NOB0Day0Tank0Leak0Sensors
2 ea
80 LS^6000LD^BN^1F00Non^Discriminating,0Buna^n0Float,0Liquid0Leak0Sensor,0
Sumps,0Disp.0Pans,0Steel0Tanks
10^0Pump0Set0Skid0#20Leak0Sensor
000*NOTE:060of080Sensor0Inputs0Used
1 ea
81 Remote0Alarm0w/0Digital0Level0Display
82 ETD010000remote0digital0level0display0and0level0alarm0panel000000000000000000000000000000000000000000000 Audible0alarm0w/digital0display,0test0and0silence0buttons00000000000000000000000000000000000000000000000000000 Utilizes0RS4850port0for0communications0with0TMS0console000000000000000000000000000000000000000000 Switchable0power0115/2300VAC(50/60HZ)00000000000000000000000000000000000000000000000000000000000000000000000000000 NEMA04X0enclosure
2 ea
83 Other 84 Auto0Cad0Wiring0Diagrams0for0Pneumercator 1 ea 85 Fuel+Polishing+System 86 FRS0660^25^MTU^4^UL00Recirulating0Unit0includes:
0*0PLC0based,0FOUR0TANK0System 0*0UL05080Listed00 0*0NEMA040Locakable0Weatherproof0Enclosure0(48"0x042"0x012") 0*0250GPM0positive0displacement0pump0@01000PSI0capacity0@018000rpm 0*0RCI0Fuel0Purifier:0Primary0Particulate0Removal0^098%0(to100microns) 0000000000000000000000000000000000000000000000Free0Water0Removal0^099.9% 0*0Water0detector0with0Alarm0and0ball0drain0valve 0*0Pre^engineered0for0Class0II0or0III0Combustible0liquids 0*02.00hp0pump0motor0 0*0Pump0Motor0Starter0^0200amp0single0pole0circuit0breaker 0*0Pump0Control0Touch0Commands0^0Auto,0Off,0Manual 0*0Catch0basin0leak0detector 0*06"0Weatherproof0Operator0Touch0panel0Interface 0*0Alarm0conditions:0Leak,0High0Water,0Pump0Fail 0*0Factory0Assembled,0pre^plumbed0and0pre^wired 0*0Isolated0compartments0for0mechanical0and0electrical0devices 0*0External01.5"0dia.0Ports0(w/0Ball0Valves)0for0connection0of0field0 plumbing 0*01.5"0dia.0Automatic0Ball0Valves0(8)
FS0Choice 1 ea
ADD:0Upgrade0to01.5"0Valves0and0System 1 lot 87 Adders 88 Up^Grade0to030Phase0Power0^03800VAC050hz0w/0Rotory0Disconnect 1 ea 89 MODBUS0RTU0Communications 1 ea 90 Custom0Programming0to0include:
40Additional0Inputs0for0signals0from0Pump0Sets Larger0PLC
1 ea
91 30Micron0Spin^on0Filter0w/0Pressure0Alarm0Sensor0(Stage02)0^01"0NPT 1 ea 92 Automatic0Water0drain0into0150gal0container0w/high0level0alarm 1 ea 155 Automatic0Chemical0Feed0(chemicals0separate) 1 ea 93 Other 94 International0Crating0Charge 1 ea 95 Freight 1 ea
96 PUMP+AND+PUMP+CONTROLLERS
97 FUEL0FILL0POINT0PANEL0&0TANK0FILL0MOTORIZED0BALL0VALVES0PER0
SECTION02.17
98 Fill0Point0remote0control0panel,0with0selector0switches0and0alarm0lights,0
NEMA
40lockable0panel0with0deadfront0(Note:0Main0controls0to0be0located0in0 main0panel)
FPC^1^460 1 ea
99 Note:&Panel&cannot&be&located&in&pit 100 Note:&Fill&point&controller&will&interface&with&Pneumacator&via&4920&mA& signal&for&tank&level&and&dry&contact&for&tank&leak.
101 MAIN0CONTROL0PANEL0FOR0MAIN0TANKS01,2,03
&04;0PUMP0SET0A;0GEN0BELLY0TANKS01,020&03,0BOILER0DAY0TANK
102 Pumping0System0Control0Panel:0NEMA03R0enclosure;0fused0disconnect0 switch,0motor0starters0/overload,0pump0HOA,0system0status0display
PC0System0 1 ea
103 Main0tank0supply0&0return0valves,02"carbon0steel0motorized0ball0 valve,#1500lb0flanged0with0electric0actuator0&0end0switches
XX066231^XX066232C2 6 ea
104 Main0tank0fill0valves,04"carbon0steel0motorized0ball0valve,#1500lb0flanged0 with0electric0actuator0&0position0end0switches.
XX070937^XX070938C2 4 ea
105 Note:&Controller&will&interface&with&Pneumacator&via&4920&mA&signal&for& tank&level&and&dry&contact&for&tank&leak.&System&will&be&400VAC/3PH/50& Hz.&Price&includes&mounting&&&wiring&Pneumacator&to&control&panel.
106 DUPLEX0PUMP0SET0A
107 #200Duplex0oil0pump0set,0120GPM0@01500PSI0with0(2)020HP0motors,04000
VAC/3PH/50Hz D20^4^020^F^X 1 ea
108 Pump0discharge0flow0switch0with0flow0loss0alarm0indication0and0 automatic0lag0pump0start0(factory0installed0on0pump0set0discharge)
Option01258G0 1 ea
109 Controls&to&be&located&in&main&control&panel.&System&shall&be&set&with& BRPV&in&lieu&of&standard&relief&valves.
Pump&set&flow&rate&per&pump&schedule&and¬&drawing.
Exception0
110 GEN0DAY0TANKS01,020&030ACCESSORIES
111 1"0Flow0control0manifold:0(1)0solenoid0valve0with0isloation0valves;0manual0 bypass0tee0with0shut0off0valve;0strainer0&0flow0restrictor Option01082C 3 ea
112 #240gear0pump,0cast0iron,0viton0seal,0101/2"0NPT0ports,0CW0rotation,0 internal0relief0valve,0101/20HP,022/380/4400VAC0500hertz,0TEFC0motor,0170
GPM0@0200PSI
GP24V01543TCW^R^50 3 ea
113 Push0Button0Station,0Day0Tank0Return SQ^9001XALD101 3 ea 114 Note:&Manifold&flow&restrictors&field&set&to&be&4&GPM&as&to¬& overwhelm&the&return&pumps 115 Factory0Integration0of0Pneumercator0Panel 1 ea 116 Factory0Witness0Test 1 ea
117 BOILER0DAY0TANK0&0ACCESSORIES
118 5000Gallon0daytank0v12,0closed0top0basin0per0UL0142,0visual0level0gauge,0 generator0supply0&0return0ports0with0drop0tubes PDWT^500.12 1 ea
119 #240gear0pump,0cast0iron,0viton0seal,0101/2"0NPT0ports,0CW0rotation,0 internal0relief0valve,0101/20HP,022/380/4400VAC0500hertz,0TEFC0motor,0170
GPM0@0200PSI
GP24V01543TCW^R^50 1 ea
120 1"0Flow0control0manifold:0(1)0solenoid0valve0with0isloation0valves;0manual0 bypass0tee0with0shut0off0valve;0strainer0&0flow0restrictor
Option01082C 1 ea
121 Daytank0Hand0Pump,0piston0type0rated0200gallons0per01000strokes0with0 check0&0manual0shut0off0valve
Option01015 1 ea
122 Outdoor0weather0proof0vent0cap,02"0(shipped0loose) OEM^4025 1 ea 123 4"0Emergency0Vent0(shipped0loose) U48^40 2 ea 124 Push0Button0Station Q^9001XALD101 1 ea 125 Exception:&Day&tank&shall&be&UL&142&only.&Pump,&level&control,&monitoring& panel&and&all&accessories&shall&be&per&Phillips&standard.
126 Exception:&Phillips&take&exception&to&Section&2.6c.&Pump,&level&control,& monitoring&panel&and&all&accessories&shall&be&per&Phillips&standards.
127 NOB+GEN+SET+CONTROLLER+&+PUMP+SET
128 NOB0daytank0level0controller:0NEMA012,0fused0disconnect,0motor0 starter/overload,0alarm0&0status0display,0reset0&0test0pushbuttons PTC0Special0 1 ea
129 1"0Flow0control0manifold:0(1)0solenoid0valve0with0isloation0valves;0manual0 bypass0tee0with0shut0off0valve;0strainer0&0flow0restrictor
Option01082C 1 ea
130 Main0tank0supply0&0return0valves,02"carbon0steel0motorized0ball0 valve,#1500lb0flanged0with0electric0actuator0&0end0switches
XX066231^XX066232C2 2 ea
131 Pump0Set0B:0#80Duplex0oil0pump0set,04.60GPM0@01500PSI0with0(2)01.50HP0 TEFC0motors,04000VAC/3PH/50Hz
D8^4^010^F^X 1 ea
132 Pump0set0discharge0flow0switch0with0flow0loss0alarm0indication0and0 automatic0lag0pump0start0(factory0installed0on0pump0set0discharge)
Option01258G 1 ea
133 #240gear0pump,0cast0iron,0viton0seal,0101/2"0NPT0ports,0CW0rotation,0 internal0relief0valve,0101/20HP,022/380/4400VAC0500hertz,0TEFC0motor,0170
GPM0@0200PSI
GP24V01543TCW^R^50 1 ea
134 1"0NPT0Back0pressure0regulating0valve,03030stainless0steel0body0with0 viton0 diaphragm,050to0750PSI0pressure0range0(for0pressure0relief0@0pumpsets)
RVI2010T^SS^5/75 2 ea
135 Note:&Controls&and&motor&starters&for&pump&set&B&shall&be&located&in&NOB& day&tank&control&panel.&Return&pump&is"e&as&a&single&pump&unit, ¬&duplex.
136 System&will&be&400VAC/3PH/50&Hz.
137 System&to&be&as&per&Phillips&standard&components&and&manufacturing& practices.&Submittals&3&9&4&weeks,¤t&production&is&12&weeks.
138 Factory0Integration0of0Pneumercator0Panel 1 ea 139 Factory0Witness0Test 1 ea
FRP>1
Manual0Fuel0Removal0Pump0as0per0submittal0documents #0240Return0Pump0&0Accessories0170GPM0@0500PSI,011⁄20HP0motors,04000 VAC/03Ø/050Hz0with0loose0manual0controller.
SP24^130062 1 ea
Foot0Valve EBW^150^202^01 1 ea
Notes#And#Exceptions!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
200 NOTES&AND&EXCEPTIONS
201 General 206 Fire-Pump-is-not-indicated-and-no-controls-or-manifolds-are-provided-for-fire-pump-connection.- 209 Overfill-prevention-valves-are-excluded-as-below-grade-style-valves-would-be-required-but-the-head-room-for-installation-and-maintenance-is-too-small.-Instead-the-motorized-valves-for-security-isolation-will-also-be-used-for-overfill-prevention.-This-is-acceptable-as-per-NFPA-30I21.7.1.5
210 Drawing-Exceptions 211 Drawing-NOBM6.03:-Polishing-system-was-scheduled-in-the-IFC-set-as-
50GPM.-We-believe-this-is-unnecessary-and-recommend-staying-with- 25GPM-and-using-1"-supply-and-return-lines-as-per-the-above-proposal.
212 Drawing-NOBM6.03:-Return-Pump-flowrate-was-increased-to-17.6GPM-and-the-pressure-was-reduced-to-20PSI.
213 Drawing-NOB-M9.4.1:-Fill-Box-with-removable-cover-is-excluded--in-this-proposal.-Fill-buckets-with-secondary-containment-are-offered-and-remote-fill-alarms-are-NEMA-4-and-can-be-mounted-on-a-outside-wall-or-inside-a-wall-box.-Remote-fill-display-includes-an-audioIvisual-alarm-but-does-not-include-a-level-display-as-per-standard-OBO-specifications.Wall-box-is-not-included-in-this-proposal.-Tank-4-return-valve-is-excluded.-Back-pressure-valves-are-excluded-as-it-is-assumed-day-tanks-do-not-need-to-loop.-Pressure-relief-valve-at-boiler-day-tank-is-excluded-as-it-is-not-needed-and-will-not-work-in-this-location.--Fuel-Polishing-system-will-require-to-pull-from-the-each-tank-individually-and-cannot-pull-from-the-common-supply-as-shown.-Mechanical-overfill-prevention-valves-are-not-included-since-we-have-motorizes-isolation-valves.Sump-Pump-system-assembly-is-excluded.
214 Drawing-NOB-MP1.000.BA:-Fill-lines-are-shown-as-50mm.-4"-is-assumed-when-sizing-accessories.-
215 Drawing-NOB-MC9.3.0-/-NOB-MC9.3.1:-Does-not-show-the-correct-valves-and-is-therefore-excluded.-Position-indicators-only-provided-on-the-fill-and-return-valve-per-standard-OBO-design.-Not-on-fuel-supply-manifolds.- Sequence-will-be-Philipps-standard-as-submitted.-Remote-Alarm-for-fill-does-not-include-a-tank-level-display.-Service-Court-motorized-valves-are-not-necessary-and-are-excluded.
216 Specification-231113 218 1.4:-Phillips-control-system-is-offered.
222 2.2:-Excluded-in-this-proposal.
223 2.4:-Excluded-in-this-proposal-as-these-are-shear-valves-for-dispensers 224 2.5:-Standard-Highland-UL-construction-provided.
225 2.8:-Section-assumed-to-be-only-for-10k-tanks.-C:-Overfill-prevention-by-motorized-valve.-G:-Standard-highland-catwalk,-rails-etc.-.-.-are-offered.- Specialty-catwalk-as-shown-in-the-drawings-is-by-others.-I/J:-remote-fill-of-this-system-so-fill-boxes-are-not-included-on-the-tank.-L.-Flame-arrestors-are-excluded..
226 2.11:-Section-is-excluded-as-all-leak-monitoring-is-provided-within-section- 2.10.
228 Specification-231113I2.15:-Polishing-system-specification-is-written-around-a-different-manufacturer-therefore-we-do-not-meet-all-of-the-requirements.-We-do-meet-the-polishing-requirement-but-exclude-the-chemical-additives-from-the-base-bid-as-we-do-nto-recommend-these.
229 2.16:-Based-on-Phillips-Pump.
230 2.17:-Custom-grade-fill-provided.
231113I2.5,#2.7,#2.8,#2.9,#2.14##10,000Gallon#Vertical#Storage#Tanks#and#Accessories!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
Highland Vertical Storage Tanks
UL-142 Vertical Storage Tanks Highland Vertical Storage Tanks are ideal for the stor-age of a wide variety of liquids. Available in carbon and stainless steel, Highland Vertical Tanks for the
VWRUDJH�RI�ÀDPPDEOH�DQG�FRPEXVWLEOH�OLTXLGV�EHDU�
the Underwriters Laboratories UL-142 label. Tanks
FDQ�DOVR�EH�PDQXIDFWXUHG�WR�$3,�����$SSHQGL[�-�IRU�
VKRS�EXLOW�WDQNV�
Highland UL-142 tanks are available in single-wall, GRXEOH�ERWWRP��RU�GRXEOH�ZDOO��VLGHV� �ERWWRP��
FRQVWUXFWLRQ��9HUWLFDO�8/�����WDQNV�RYHU�����GLDPHWHU�
DUH�SURYLGHG�ZLWK�D�FRQHG�WRS�WR�VKHG�UDLQZDWHU�DQG�
VQRZ��8/�����VSHFL¿FDWLRQV�OLPLW�FRQVWUXFWLRQ�WR�D�
PD[LPXP�YHUWLFDO�VKHOO�KHLJKW�RI���¶�´���
%HFDXVH�SLSLQJ�LQVWDOODWLRQV�YDU\�ZLWK�HDFK�WDQN��WKH�
VL]H�DQG�ORFDWLRQ�RI�¿WWLQJV�FDQ�EH�VSHFL¿HG�E\�WKH�
HQG�XVHU��8S�WR���´�RI�WKUHDGHG�¿WWLQJV�DUH�JHQHUDOO\�
LQFOXGHG�ZLWK�WKH�WDQN��1RUPDO�DQG�HPHUJHQF\�YHQW-
ing is required on all UL-142 Aboveground Vertical tanks.
7DQNV�DUH�SURYLGHG�ZLWK�D�FRDW�RI�SULPHU��6SHFLDO�
VXUIDFH�SUHSDUDWLRQ�DQG�SULPHUV�DUH�DYDLODEOH�WR�
DFFRPRGDWH�\RXU�¿HOG�¿QLVK�FRDW�VSHFL¿FDWLRQV��
+LJKODQG�FDQ�DOVR�SURYLGH�FRPSOHWH�92&�FRPSOLDQW�
¿QLVK�V\VWHPV��)LHOG�WRXFK�XS�ZLOO�EH�UHTXLUHG�GXH�WR�
WDQN�VKLSSLQJ�DQG�KDQGOLQJ��DQG�SLSLQJ�DQG�DFFHV-
sory installation.
6SHFLDO�OLQLQJV�DUH�DYDLODEOH�IRU�VWRUDJH�RI�IHUWLOL]HUV��
SRWDEOH�ZDWHU��FKHPLFDOV��HWF��2WKHU�RSWLRQV�LQFOXGH��
FRQHG�ERWWRP��OHJV��ODGGHUV��FDJHV��KDQGUDLOV��JDXJ-
LQJ�V\VWHPV��KHDWHUV��ÀDPH�DUUHVWRUV��VXPSV��VLJKW�
JODVVHV�DQG�ÀDQJHV��
2XU�&RPPLWPHQW�WR�,QGXVWU\
6HUYLFH��4XDOLW\�DQG�'HOLYHU\�DW�&RPSHWLWLYH�3ULFHV
+LJKODQG�LV�FRPPLWWHG�WR�SURGXFLQJ�KLJK�TXDOLW\�VWHHO�WDQN�
SURGXFWV��:H
YH�EHHQ�PDQXIDFWXULQJ�WDQNV�IRU�PRUH�WKDQ�
���\HDUV��DOZD\V�VWULYLQJ�IRU�H[FHOOHQFH��)RU�LQIRUPDWLRQ�RQ�
RWKHU�SURGXFWV��SOHDVH�FDOO�RQH�RI�RXU�RI¿FHV�RU�FRQWDFW�\RXU�
ORFDO�+LJKODQG�UHSUHVHQWDWLYH�
Highland TankTANK
HIG
HLAND
MFG. CO
HT-1145
Emergency Vent (18" Loose-bolt Manway) Standard on 3,000 - 29,600 gallon tanks
Optional Clean-out Manway
Threaded Fitting
Threaded Fittings
Diameter
Straight Shell Height
General Arrangement - Single-wall
*XLGH�6SHFLÀFDWLRQ
)XUQLVK�DQG�LQVWDOO�D�BBBBBBBBBB�JDOORQ�DERYHJURXQG�YHUWL-
FDO���VLQJOH�ZDOO��GRXEOH�ERWWRP��GRXEOH�ZDOO��VWHHO�VWRUDJH�
WDQN�BBBBBBBBBB�LQFKHV�LQ�GLDPHWHU�E\�BBBBBBBBBB�KLJK���
7DQN�VKDOO�EH�IDEULFDWHG�IURP�PLOG�FDUERQ�VWHHO�ZLWK�D�ÀDW�
ERWWRP�KHDG�DQG�D�FRQHG�WRS�RYHU�����GLDPHWHU�RQO\���7DQN�
JDXJH��ERWWRP�KHDG�DQG�VKHOO�JDXJH�BBBBB��7RS�JDXJH�
BBBBB���$OO�LWHPV�LQFOXGHG�LQ�WDQN�XQLW�VKDOO�EH�FRDWHG�ZLWK�
SULPHU���7KH�WDQN�XQLW�VKDOO�EH�PDQXIDFWXUHG�LQ�FRQIRUPDQFH�
ZLWK�8QGHUZULWHUV�/DERUDWRULHV¶�8/�����VSHFL¿FDWLRQV�DQG�
so labeled.
3URYLGH�WKUHDGHG�¿WWLQJV�DV�SHU�DWWDFKHG�GUDZLQJ��$OO�¿WWLQJV�
LQ�FRQHG�WRS�VKDOO�EH�IXOO�FRXSOLQJV��$OO�8/�����DERYHJ-
URXQG�VLQJOH�ZDOO�WDQNV�VKDOO�LQFOXGH�¿WWLQJV�IRU�QRUPDO�DQG�
HPHUJHQF\�YHQWLQJ���
Tanks shall be fabricated with the following threaded
FRQQHFWLRQV���BBBBB���LQFK��BBBBB���LQFK��BBBBB���LQFK�DV�
ORFDWHG�RQ�DWWDFKHG�GUDZLQJ��$1'�25�BBBBB�
�����ÀDQJHG�FRQQHFWLRQV�ZLWK�ÀDQJH�SURWHFWRUV���)ODQJH�
VL]HV�DV�IROORZV��TW\�VL]H���BBBBBBBBBBBB��
BBBBBBBBBBBB��BBBBBBBBBBBB��ZLWK�ORFDWLRQV�DOVR�LQGL-
FDWHG�RQ�GUDZLQJ���7KUHDG�SURWHFWRUV�VKDOO�EH�
LQVHUWHG�LQ�DOO�WKUHDGHG�RSHQLQJV�SULRU�WR�VKLSPHQW�
Highland tanks are air tested at the factory but MUST be
UHWHVWHG�DW�WKH�MREVLWH�E\�WKH�LQVWDOOHU�SULRU�WR�
installation.
� 9ROXPH� � 'LPHQVLRQV
� *DOORQV� 'LDPHWHU� � 6KHOO�+HLJKW
185� �¶�´� �¶�´ 240� �¶�´� �¶�´ 300� �¶�´� �¶�´ 500� �¶�´� �¶�´ 1,000� �¶�´� ��¶�´ 1,000� �¶�´� �¶�´ 1,500� �¶�´� �¶�´ 2,000� �¶�´� ��¶�´ 3,000� �¶�´� �¶�´ 4,000� �¶�´� ��¶�´ 5,000� �¶�´� ��¶�´ 6,000� �¶�´� ��¶�´ 8,000� ��¶�´� ��¶�´
2SWLRQV� �$FFHVVRULHV�
� BBBB� 0DQZD\�BBBBB�LQFKHV�LQ�GLDPHWHU�ZLWK�EROWHG�
and gasketed lid
� BBBB� /RRVH�EROW�PDQZD\�BBBBB�LQFKHV�LQ�GLDPHWHU�
with bolted and gasketed lid
� BBBB� (PHUJHQF\�9HQW
� BBBB� ([WHUQDO�/DGGHU�ZLWK�&DJH
� BBBB� ([WHUQDO�/DGGHU� �3ODWIRUP
� BBBB� ([WHUQDO�6WDLUZD\
� BBBB� :DONZD\�V��ZLWK�KDQGUDLOV
� BBBB� ���[����[������&OLS�$QJOH�IRU�DQFKRULQJ
� BBBB�&RQHG�ERWWRP�ZLWK�/HJV��BBBBB���FOHDUDQFH�
� BBBB� &RPPHUFLDO�JULW�EODVW��663&�����HSR[\�SULPHU�FRDW
� BBBB� 2WKHU�H[WHULRU�FRDWLQJ�BBBBBBBBBBBBB
� BBBB� ,QWHUQDO�/DGGHU�V�
� BBBB� ,QWHUQDO�&RDWLQJ�BBBBBBBBBBBBBBB��0XVW�LQFOXGH�
� � LQWHULRU�ZHOG���0LQLPXP�VL]H�����JDOORQ��
� BBBB� /HYHO�6HQVLQJ�6\VWHP�V�
� BBBB� 3XPS�3ODWIRUP
Double-bottom Double-wall
��+LJKODQG�7DQN���+7���������������
Please visit us at www.highlandtank.com
2QH�+LJKODQG�5RDG
6WR\VWRZQ��3$������
�����3DWWHUVRQ�6WUHHW
*UHHQVERUR��1&������
�����&KHVWQXW�6WUHHW
/HEDQRQ��3$������
������WK�6WUHHW
:DWHUYOLHW��1<������
�����(OL]DEHWKWRZQ�5RDG
0DQKHLP��3$������
�����6WR\VWRZQ�5RDG
)ULHGHQV��3$������
TANK
HIG
HLAND
MFG. CO
� 9ROXPH� � 'LPHQVLRQV
� *DOORQV� 'LDPHWHU� � 6KHOO�+HLJKW
10,000� ��¶�´� ��¶�´ 12,000� ��¶�´� ��¶�´ 15,000� ��¶�´� ��¶�´ 20,000� ��¶�´� ��¶�´ 20,000� ��¶�´� ��¶�´ 25,000� ��¶�´� ��¶�´ 30,000� ��¶�´� ��¶�´ 30,000� ��¶�´� ��¶�´ 40,000� ��¶�´� ��¶�´ 40,000� ��¶�´� ��¶�´ 40,000� ��¶�´� ��¶�´ 49,500� ��¶�´� ��¶�´
SEE ATTACHED DRAWING FOR SPECIFICS
Thomas Goodwin 28 January 2014
Search
ENGLISHESPAÑOL
Features Ordering Instructions Downloads Related Products
Updraft Vent
FIG 354, 354T
Atmospheric updraft vents are installed on the top of storage tank vent pipes on underground and aboveground fuel storage tanks.
Note: Open vents will allow unrestricted evaporation of product.
WARNING: DO NOT FILL OR UNLOAD FUEL FROM A STORAGE
TANK UNLESS IT IS CERTAIN THAT THE TANK VENTS WILL
OPERATE PROPERLY. Morrison tank vents are designed only for use on shop fabricated atmospheric tanks which have been built and tested in accordance with UL 142, NFPA 30 & 30A, and API 650 and in accordance with all applicable local, state, and federal laws. In normal operation, dust and debris can accumulate in vent openings and block air passages. Certain atmospheric conditions such as a sudden drop in temperature, below freezing temperatures, and freezing rain can cause moisture to enter the vent and freeze which can restrict internal movement of vent mechnisms and block air passages. All storage tank vent air passages must be completely free of restriction and all vent mechanisms must have free movement in order to insure proper operation. Any restriction of airflow can cause excessive pressure or vacuum to build up in the storage tank, which can result in structural damage to the tank, fuel spillage, property damage, fire, injury, and death. Monthly inspection, and immediate inspection during freezing conditions, by someone familiar with the proper operation of storage tank vents, is required to insure venting devices are functioning properly before filling or unloading a tank.
Fig Suffix Size Description Weight
354 0100 AV 1.5" Updraft Vent 0.75
354 0200 AV 2" Updraft Vent 0.75
354 0300 AV 3" Updraft Vent 1.5
354 0400 AV 4" Updraft Vent 2.25
354T 0200 AV 2" Updraft Vent, Slip-on, Teflon Coated Aluminum, w/ss Screen 0.75
354T 0300AV 3" Updraft Vent, Slip-on, Teflon Coated Aluminum, w/ss Screen 1.5
Copyright © 2013 Morrison Bros. Co. ® - All Rights Reserved.
Home Products Resources Sales Contacts About Morrison Bros. Co Contact Us Order Tracking CARB Certification http://www.morbros.com/ http://www.morbros.com/products/vents/updraft-vents/updraft-vent http://www.morbros.com/es/node/475 http://www.morbros.com/products/vents/updraft-vents/updraft-vent# http://www.morbros.com/products/vents/updraft-vents/updraft-vent# http://www.morbros.com/products/vents/updraft-vents/updraft-vent# http://www.morbros.com/products/vents/updraft-vents/updraft-vent# http://www.morbros.com/ http://www.morbros.com/products http://www.morbros.com/resources http://www.morbros.com/sales-contacts http://www.morbros.com/about-morrison-bros-co http://www.morbros.com/contact-us http://www.morbros.com/order-tracking http://www.morbros.com/carb-certification/certification-exam
The Morrison Fig. 272 Internal Emergency Valve is for installation at the outlet of an A.S.T. where product fl ow must be stopped at the connection to the tank in the event of a fi re. Fig. 272 Flanged Internal Emergency Valves conform to ANSI B16.42 specifi cations for Class 150 raised face ductile iron fl anges. The Fig. 272 is offered with an optional shear section and/or locking mechanism.
Model 272 Internal Emergency Valves
SPECIFICATION SHEET
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
Model 272HDI
Model 272HO
Model 272HLS
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
SPECIFICATION OPTIONS:
A - Size: In inches - (Inlet) x (Outlet) B - Tank Connection: Flanged (F) or Male (Blank) C - Body / Cap Material: Ductile Iron (DI) or Brass (B) D - O-ring/ Packing: General Packing w/ Flourocarbon Elastomer O-ring (GEN) PTFE packing w/ TFE Encapsulated O-ring (TFE) Fig. 272DI-0400 AV-(Packing only) E - Plunger Material: Ductile Iron (DI) or Brass (B) F - Shaft Material: Plated Steel (S) or Brass (B) G - Lifting Rod: Steel (S) or Brass (B) Handle: Iron Fulcrum Lever: Iron Spring: Stainless Steel Fuselink: 212oF Hold Open Rod: Steel H - Shear Section: Yes (Y) / No (N) I - Locking Mechanism Yes (Y) / No (N) J - Length of Valve (inches) K - Shipping Weight (lbs.)
272HDI0500 AV 3 X 3 DI TFE DI ST ST N N 10.62 10
272DLS0500 AV 3 X 3 DI TFE DI ST ST Y Y 10.62 11.5
272HDS0500 AV 3 X 3 DI TFE DI ST ST Y N 10.62 10
272HO-0500 AV 3 X 3 B GEN B B B N N 10.62 11.5
272HOL0500 AV 3 X 3 B GEN B B B N Y 10.62 13
272HLS0500 AV 3 X 3 B GEN B B B Y Y 10.62 13
272HOS0500 AV 3 X 3 B GEN B B B Y N 10.62 11.5
272HDL0500 AV 3 X 3 DI TFE DI ST ST N Y 10.62 10
272HO-0600 AV 4 X 3 B GEN B B B N N 12.31 17
272HOL0600 AV 4 X 3 B GEN B B B N Y 12.31 18
272HLS0600 AV 4 X 3 B GEN B B B Y Y 12.31 18
272HOS0600 AV 4 X 3 B GEN B B B Y N 12.31 17
272HDI0700 AV 4 X 4 DI TFE DI ST ST N N 12.37 21
272HDS0700 AV 4 X 4 DI TFE DI ST ST Y N 12.37 21
272HO-0700 AV 4 X 4 B GEN B B B N N 12.37 20.25
272HOS0700 AV 4 X 4 B GEN B B B Y N 12.37 20.25
I.D. Number A B C D E F G H I J K
272DI-0300 AV 4 X 3 F DI TFE DI ST ST N N 16.81 34
272DI-0400 AV 6 X 4 F DI TFE DI ST ST N N 13.5 42
272HDI0100 AV 2 X 2 DI TFE DI ST ST N N 8.75 7
272DLS0100 AV 2 X 2 DI TFE DI ST ST Y Y 8.75 6.5
272HDS0100 AV 2 X 2 DI TFE DI ST ST Y N 8.75 7
272HO-0100 AV 2 X 2 B GEN B B B N N 8.75 6.5
272HOL0100 AV 2 X 2 B GEN B B B N Y 8.75 7
272HLS0100 AV 2 X 2 B GEN B B B Y Y 8.75 7
272HOS0100 AV 2 X 2 B GEN B B B Y N 8.75 6.5
272HDL0100 AV 2 X 2 DI TFE DI ST ST N Y 8.75 7
Model 272 Internal Emergency Valves (continued)
231113I2.17#Remote#Fill#and#Accessories!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
FAIRFIELD INDUSTRIES, INC
827 NORTH 6TH STREET, NEWARK, NJ 07107
PHONE: 973-483-0100 FAX: 973-483-5333
RFTC/CUSTOM
A NTS RFTC3111 - -
A.CONKLIN 1/2/14 1 OF 2
FEATURES:
· REMOVABLE 1/2" THICK DIAMOND PLATE COVER; H-20 TRUCK LOAD
RATING; BOLTED AND SEALED WITH GASKET
· 14 GA. STAINLESS STEEL SECONDARY CONTAINMENT/TERMINATION
CHAMBER
· FOUR (4) SCM-5 4"
· FOUR (4) FOUR INCH FLANGES
· ONE (1) SCM-5 2"
· ONE (1) TWO INCH FLANGE
· CHANNEL-STYLE CONCRETE ANCHORS
· 1
8" THICK BUNA-N GASKET
· MADE IN USA
SIDE
RFTC/CUSTOM
DETAIL A
DETAIL A
EXPLODED
BUNA-N GASKET
1/2" DIAMOND PLATE
NYLON WASHER
8 X 1 14" SS. HEX BOLT
14 GA. STEEL
TOP
20.38
Page Technical information 4 Material & sealing. Standard sealing is FKM, others on request. / Werkstoff & dichtung. Standard-Dichtungswerkstoff ist FKM, andere auf Anfrage. / Material & tätning. Standardtätning är FKM, andra på förfrågan.
5 Dimension, diameter, thread. / DN, durchmesser, gewinde. / Dimension, diameter, gänga.
7 Thread measurement / Gewindemasse / Gängmått
Page Option / Zuwahl / Tillval 10-12 Selectivity to prevent cross contamination of media / Codierung gegen Produktvermischung.
/ Selektivitet för att undvika mediablandning.
Dimen-sion
D.Ø Connection Material Seal Weight Fig. Code no.
Werkstoff Dichtung Gewicht Abb. Bestellnummer
DN mm Material Tätning Vikt Bild Beställningsnr
BSP
DN 100 164 4" female SS FKM 6,9 kg 2 5830A-4407 DN 100 164 4" female Al FKM 3,3 kg 1 5631-1107 DN 100 164 4" female Brass FKM 7,4 kg 2 5631-2207
NPT
-- 164 4" female SS FKM 7,3 kg 2 7480A-4407 -- 164 4" female Al FKM 3,3 kg 1 7476-1107 -- 164 4" female Brass FKM 7,4 kg 2 7476-2207
TODO-MATIC®
For industrial process plant, Road and rail tankers, ISO containers, Aviation fuel bunkering, Offshore, Pharmaceutical and Petrochemical industries. Media: Butadiene, Drilling Mud, Barite, Methanol, Potable Water, Waste Water, Base Oil, Oil Based Mud etc.
TODO-MATIC® Tankkupplung (Vaterteilkupplung) Gewinde. Fϋr Anlagen, Tankwagen und Kesselwagen, Container, Flugzeugtreibstoff-Tankläger, Offshore, pharmazeutische und petrochemische Industrie. Medien: Butadien, Bohrschlamm, Barite, Diesel, Methanol, Schmutzwasser, ölhaltiger Schlamm.
TODO-MATIC® tankdel med gänga. För fabriker, tankbilar, tankvagnar (järnväg), container, bunkring flygbränsle, skepp, plattformar. Media: Buta-dien, borrslam, baryt, diesel, metanol, dricksvatten, avfallsvatten, oljebaserat slam etc.
TODO-MATIC® Tank Unit 4" (DN100, Ø 164 mm) threaded
1.
T O D O A B . D es ig n m ay c ha ng e w ith ou t n ot ic e
- K on st ru kt iv e än de ru ng en v or be ha lte n
- K on st ru kt io ns än dr in ga r f ör be hå lle s.
BSP threads according to ISO 228-G. NPT threads according to ANSI B 2.1. / BSPGewinde gemäß ISO 228-G.
NPT Gewinde gemäß ANSI B 2.1. / BSP gängor enligt ISO 228-G. NPT gängor enligt ANSI B 2.1.
Figure Abbildung
Bild
2.
Dimension D.Ø Material Seal Weight Fig. Code no.
Werkstoff Dichtung Gewicht Abb. Bestellnummer
DN mm Material Tätning Vikt Bild Beställningsnr
DN 20-40 (¾”-1½”) 56 Al - 0,2 kg 1 4915-1400 DN 20-40 (¾”-1½”) 56 Brass - 0,4 kg 1 4915-2400 DN 20-40 (¾”-1½”) 56 SS - 0,4 kg 1 4915-4400 DN 20-40 (¾”-1½”) 56 CR - 0,1 kg 4 3664-10 DN 20-40 (¾”-1½”) 56 Al FKM 0,4 kg - 5659-1407 DN 40-50 (1½”-2”) 70 Al FKM 0,3 kg 2 6070B-1407 DN 40-50 (1½”-2”) 70 Brass FKM 0,7 kg 2 6070B-2407 DN 40-50 (1½”-2”) 70 SS FKM 0,6 kg 2 6070B-4407 DN 40-50 (1½”-2”) 70 CR - 0,15 kg 4 3666-10
DN 65 (2½”) 105 Al FKM 0,5 kg 3 5435C-1407 DN 65 (2½”) 105 Brass FKM 1,4 kg 3 5435C-2407 DN 65 (2½”) 105 SS FKM 1,2 kg 3 5435C-4407 DN 80 (3”) 119 Al FKM 0,6 kg 3 5535C-1407 DN 80 (3”) 119 Brass FKM 1,6 kg 3 5535C-2407 DN 80 (3”) 119 SS FKM 1,4 kg 3 5535C-4407 DN 80 (3”) 119 Al FKM 1,3 kg 5 5662-1407 DN 100 (4”) 164 Al FKM 1,6 kg 2 5635B-1407 DN 100 (4”) 164 Brass FKM 3,6 kg 2 5635B-2407 DN 100 (4”) 164 SS FKM 3,1 kg 2 5635B-4407 DN 100 (4”) 164 Al FKM 2,2 kg 5 5663-1407 DN 150 (6”) 238 Al FKM 3,5 kg 6 7219-1407
Kappen für TODO-MATIC® Vaterteil.
Skyddskåpa för TODO-MATIC® tankdel.
Dust cap for TODO-MATIC® Tank Unit ¾" - 6"
Figure Abbildung
Bild
1.
T O D O A B . D es ig n m ay c ha ng e w ith ou t n ot ic e
- K on st ru kt iv e än de ru ng en v or be ha lte n
- K on st ru kt io ns än dr in ga r f ör be hå lle s.
TODO-MATIC®
5.
2.
3.
4.
6.
522 DPL410877.963.4966 • www.dixonvalve.com
Valves
N Valves
Ductile Iron Butterfl y Valves
• for use between two 150 lb. fl anges
• will lock "open" or "closed"
• rated to 200 PSI at ambient temperature (70°F)
Size with Buna-N liner with EPDM liner Part # Price/E Part # Price/E
2" 3" 4" 6"
BFVL200
BFVL300
BFVL400
BFVL600
$145.00 181.25 270.00 475.00
BFVL200E
BFVL300E
BFVL400E
BFVL600E
$145.00 181.25 270.00 475.00 threaded lug style with bronze disc
• ductile iron body, ASTM A536
• aluminum bronze disc, ASTM B148, ALY.954
• Buna-N seal and stem seals
• PTFE bushing
• stainless steel top and bottom stems
• The number of holes on the valve should match the number of holes for the specifi c fl ange size listed in the Pipe and Flange dimensions chart on page 619.
Size with Buna-N liner with EPDM liner Part # Price/E Part # Price/E
2" 3" 4" 6"
BBFVW200
BBFVW300
BBFVW400
BBFVW600
$133.00 170.00 240.00 420.00
BBFVW200E
BBFVW300E
BBFVW400E
BBFVW600E
$133.00 170.00 240.00 420.00 wafer style with bronze disc
• ductile iron body, ASTM A536
• aluminum bronze disc, ASTM B148, ALY.954
• Buna-N seal and stem seals
• PTFE bushing
• stainless steel top and bottom stems
• The number of holes on the valve depends on the body size.
Size with Buna-N liner Part # Price/E
2" 3" 4" 6"
BFVW200
BFVW300
BFVW400
BFVW600
$150.00 185.00 250.00 440.00 wafer style with stainless disc
• ductile iron body, ASTM A536
• stainless steel disc, ASTM A351, GR. CF-8M
• Buna-N seal and stem seals
• PTFE bushing
• stainless steel top and bottom stems
• The number of holes on the valve depends on the body size.
NOT RECOMMENDED FOR STEAM SERVICE
231113I2.1.C#Flexible#Connectors!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
FLEX-ING’s premiere above and below ground fi re rated fl ex connector.
),5()/(;� )/(;,%/(�&211(&7256�
'HVFULSWLRQ�³
$SSOLFDWLRQ�³
)HDWXUHV�³
Connects the shear valve with primary piping in a fuel dispenser sump system.
www.fl ex-ing.com
SB 989 Compliant Successful Praxair/Tracer Testing
Metal construction All metal construction means one fl ex-connector for both above and below ground applications.
Full Vacuum Testable under full vacuum.
UL Listed UL Listed for above and below ground installation.
Long service life An 18-8 alloy with titanium, 321 Stainless Steel inner core provides a long service life.
Greater fl exibility Standard wall thickness with close pitch corrugations gives more fl exibility.
Multi-seal design The 346 Integral Male Swivel* ensures ease of installation with a multi-seal design.
Schedule 80 construction
Thick, schedule 80 hex end fi ttings protect against deformation of the ends.
Quality tested 100% pressure tested to assure quality.
Superior working pressure
350 psi working pressure assembly exceeds UL 50 psi requirement on 3/4” - 3”. 225 psi on 4”
Minimum Bend Radius from Centerline of Hose 6” - Hose up to 2” 9” - Hose up to 3” 13” - Hose up to 4”
6HH�5HTXLUHPHQWV�DQG�,QVWDOODWLRQ�,QVWUXFWLRQV�RQ�3DJH���
2828 Fallon Drive Sherman, Texas 75090 Phone: 1.800.333.3599 / 1.903.892.8983 Fax: 1.800.765.4801 / 1.903.893.9576
15"
(67$%/,6+('�����
1-1/2” HEX MALE X 2” FEMALE FFUL15X18HMX2F
FFUL15X24HMX2F
FFUL15X30HMX2F
1-1/2” MALE 346 SWIVEL X 2” FEMALE FF15X18M346X2F
FF15X24M346X2F
FF15X30M346X2F
2” HEX MALE X 2” HEX MALE FFUL20X18HMXHM
FFUL20X24HMXHM
FFUL20X30HMXHM
2” HEX MALE X 2” MALE 346 SWIVEL FF20X18HMXM346
FF20X24HMXM346
FF20X30HMXM346
2” HEX MALE X 2” FEMALE FFUL20X18HMXF
FFUL20X24HMXF
FFUL20X30HMXF
2” FEMALE X 2” MALE 346 SWIVEL FF20X18M346XF
FF20X24M346XF
FF20X30M346XF
)/(;�&211(&725�6<67(0
2” FIREFLEX
1-1/2” FIREFLEX
1( &7
�6< (0
231113I2.3#Valves!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
Ball valves are used throughout fuel piping systems where a shut-off is required or desired.
Features
• Quarter turn operation
• Full port for maximum fl ow and minimum pressure drop
• Can be operated in partial open position for fl ow control
• Double seal allows the valve to be operated in both directions
• Blowout proof stem
• 600 PSIG non-shock cold working pressure rating for ¼″ to 2″ size
• 450 PSIG non-shock cold working pressure rating for 2½″ to 4″ size
• Can be used for air service
• 691B is lockable with a padlock
Construction Details
• Forged brass body
• Hard chrome plated ball
• Tefl on® seal
Certifi cations & Listings UL 842 listed for fl ammable liquids, UL 125 listed for LP gas shut-off, FM approval ¼″ to 2″, CSA approved
Model 691 & 691B Full Port Brass Ball Valve
SPECIFICATION SHEET
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
I.D. Number Size A B C Port Size Weight (lbs)
691---0100 1V ¼″ 1.771 1.496 3.228 0.314 0.30
691---0200 1V ⅜″ 1.771 1.496 3.228 0.393 0.30
691---0300 1V ½″ 2.32 1.69 3.94 0.59 0.50
691---0400 1V ¾″ 2.519 1.968 4.724 0.787 0.80
691---0500 1V 1″ 3.188 2.125 4.724 0.984 1.17
691---0600 1V 1¼″ 3.661 2.874 6.22 1.259 1.93
691---0700 1V 1½″ 4.015 3.11 6.22 1.574 2.40
691---0800 1V 2″ 4.763 3.385 6.22 1.968 4.02
691---0900 1V 2½″ 6.141 5.196 10.04 2.559 10.0
691---1000 1V 3″ 6.968 5.551 10.04 3.149 13.65
691---1100 1V 4″ 8.504 6.062 10.04 3.937 22.0
691B--0100 1V ¼″ 1.771 1.496 3.228 0.314 0.30
691B--0200 1V 3/8″ 1.771 1.496 3.228 0.393 0.30
691B--0300 1V ½″ 2.32 1.69 3.94 0.59 0.50
691B--0400 1V ¾″ 2.519 1.968 4.724 0.787 0.80
691B--0500 1V 1″ 3.188 2.125 4.724 0.984 1.17
691B--0600 1V 1¼″ 3.661 2.874 6.22 1.259 1.93
691B--0700 1V 1½″ 4.015 3.11 6.22 1.574 2.40
691B--0800 1V 2″ 4.763 3.385 6.22 1.968 4.02
691B--0900 1V 2½″ 6.141 5.196 10.04 2.559 10.0
691B--1000 1V 3″ 6.968 5.551 10.04 3.149 13.65
691B--1100 1V 4″ 8.504 6.062 10.04 3.937 22.0
691 (¼″)
691B (1″)
NOTE: All dimensions are in inches.
The Morrison Fig. 346 Series External Emergency Valve is designed for installation at the outlet of an AST or in a liquid transfer line where product fl ow must be stopped in the event of a fi re. The fl anges on the 346FDI models conform to ANSI B16.42 specifi cations for class 150 raised face ductile iron fl anges. Cold non-shock pressure rating is 200 P.S.I. W.O.G. for sizes ¾” to 3” and 250 P.S.I. W.O.G. for the 4”.
Ductile iron valves are painted green.
Model 346 External Emergency Valves
SPECIFICATION SHEET
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
I.D Number A B C D E F G H I J K L
346FDI0200 AV 2 F DI TFE DI DI 165 4 6.25 6.5 15.0
346FDI0300 AV 3 F DI TFE DI DI 165 4 8.53 8.63 29.40
346FDI0400 AV 4 F DI TFE DI DI 165 8 11.75 11.5 72.0
346DI-1000 AV ¾ DI TFE DI DI 165 5 6.94 I 7.30
346DI-1100 AV 1 DI TFE DI DI 165 5 6.94 I 7.30
346DI-1200 AV 1¼ DI TFE DI DI 165 5 6.94 I 7.0
346DI-0400 AV 1½ DI TFE DI DI 165 5 5.44 6.80
346DI-0500 AV 2 DI TFE DI DI 165 5 5.44 6.20
346DI-0600 AV 3 DI TFE DI DI 165 7 8.32 15.50
346SS-1000 AV ¾ SS TFE SS SS 165 5 6.94 SS 8.60
346SS-1100 AV 1 SS TFE SS SS 165 5 6.94 SS 8.60
346SS-1200 AV 1¼ SS TFE SS SS 165 5 6.94 SS 8.50
346SS-0100 AV 1½ SS TFE SS SS 165 5 5.44 8.0
346SS-0200 AV 2 SS TFE SS SS 165 5 5.44 7.0
SPECIFICATION OPTIONS:
A—Size: In Inches B—Mounting Connection: Flanged (F) or Female NPT (Blank) C—Body / Cap Material: Ductile Iron (DI) or 316 Stainless Steel (SS) D—Gasket Material: Tefl on (TFE) E—Poppet: Ductile Iron (DI) or 316 Stainless Steel (SS) O-ring: Tefl on Encapsulated Flourocarbon Elastomer Spring: 302 Stainless Steel Seal Nut/Plug: 303 Stainless Steel Handle: Brass Fulcrum Shaft: 303 Stainless Steel Groove Pin: Steel Hold Open Hook: Stainless Steel F—Lever Arm: Ductile Iron (DI) or 316 Stainless Steel (SS) G—Fuse Link: 165° F STD. (212°F Optional); Fuse Link is UL Listed & Factory Mutual Listed H—Number of Bolt Holes I—Height of Valve (Inches) J—Length of Valve (Inches) K—Reducing Bushings: Iron (I) or 316SS (SS) L—Shipping Weight (lbs.)
Companion fl anges, fl ange gaskets, nuts, bolts and washers available.
Model 346DI
Model 346FDI
Model 346SS
109 Holland Ave • Bridgeport, Connecticut 06605 USA • Phone: 203-908-3323 Fax: 203-908-3325 www.phillipfuelsystems.com
PHILLIPS FUEL SYSTEMS
Back Pressure Regulating Valves Phillip’s RVI & BPS series back pressure regulating valves are self-contained units designed to handle the most critical upstream pressure requirements typically found in fuel oil loop applications. Our industrial duty back pressure regulating valve automatically maintains the desired set pressure in the loop system by relieving excess pressure into the lower pressure return side of the loop. With a fast response and available in two separate spring ranges, these adjustable valves are ideally suited for continuous operation.
Features Include:
• Fast Response
• 303 Stainless steel body, viton piston seals
• 300 PSIG Maximum Pressure
• 200 Degrees F Max Temperature
• Adjustable pressure ranges
Size Part Pressure Size Part Pressure Number Range Number Range
1/2" RVI2005T-SS-2/25 2-25 PSI 1 1/2" BPS0515T-SS-15/60 15-60 PSI
NPT RVI2005T-SS-5/75 5-75 PSI NPT BPS0515T-SS-25/150 25-150 PSI
3/4" RVI2007T-SS-0/50 2-25 PSI 1 1/2” BPS0515A-SS-15/60 15-60 PSI
NPT RVI2007T-SS-50/150 5-75 PSI Flanged BPS0515A-SS-25/150 25-150 PSI
1" RVI2010T-SS-0/50 2-25 PSI 2” BPS0520T-SS-15/60 15-60 PSI
NPT RVI2010T-SS-50/150 5-75 PSI NPT BPS0520T-SS-25/150 25-150 PSI
1 1/4" BPS0511T-SS-15/60 15-60 PSI 2" BPS0520A-SS-15/60 15-60 PSI
NPT BPS0511T-SS-25/150 25-150 PSI Flanged BPS0520A-SS-25/150 25-150 PSI
1 1/4” BPS0512A-SS-15/60 15-60 PSI 3" BPS0530A-SS-15/60 15-60 PSI
Flanged BPS0512A-SS-25/150 25-150 PSI Flanged BPS0530A-SS-25/150 25-150 PSI
1 1/2" BPS0515T-SS-15/60 15-60 PSI 4" BPS0540A-SS-15/60 15-40 PSI
NPT BPS0515T-SS-25/150 25-150 PSI Flanged BPS0540A-SS-25/150 25-195 PSI
HOW IT WORKS
By sensing the upstream pressure acting on the underside of the diaphragm through a port in the bottom of the diaphragm case, an increase in up-stream pressure pass the set pressure will compress the spring and allow the valve to open. The spring will close as the upstream pressure decreases.
The higher the system pressure above the set point, the more flow the valve will pass.
Fuel Oil Accessories Back Pressure Valves
7 Other Items [RVI - BPS Back Pressure Reg Valve London Submittals].pdf Page 1 of 2
109 Holland Ave • Bridgeport, Connecticut 06605 USA • Phone: 203-908-3323 Fax: 203-908-3325 www.phillipfuelsystems.com
PHILLIPS FUEL SYSTEMS Fuel Oil Accessories Back Pressure Valves
Size Dimension (in) Cv Max
NPT A B C GPM
1/2 2.50 0.63 5.62 4.5 15 3/4 3.00 0.75 6.17 6.7 25 1 4.00 1.00 9.25 13.7 40
RVI-20 SERIES INLINE VALVE
BPS-05 SERIES- NPT
RIGHT ANGLE PORTING
Size Dimension (in) Flow NPT A B C Cv 1 1/4 2.0 2.5 11.0 15.9 1 1/2 2.0 2.5 12.3 27.7 2 2.4 3.0 12.5 49.5
BPS-05 SERIES- FLANGED
RIGHT ANGLE PORTING
Size Dimension (in) Flow NPT A B C Cv 1 1/4 3.0 3.5 12.3 15.9 1 1/2 3.0 4.0 13.5 27.7 2 3.5 4.5 15.5 49.5 3 5.5 5.5 21.0 79.7 4 6.0 6.0 23.0 104.6
7 Other Items [RVI - BPS Back Pressure Reg Valve London Submittals].pdf Page 2 of 2
231113I2.6#Boiler#Daytank#and#Generator#Daytank#Fittings#(Gen.#Day#Tanks#by#Others)!
US#Embassy#London!
Fuel#Oil#Submittal!
231113!
BL#Harbert#International!
120080!
PDWT500-130062
500 gallon closed dike daytank, per UL 142
London
D
C
B
A
B
C
D
345678
8 7 6 5 4 3 2 1
Phillips Fuel Systems 109 Holland Ave Bridgeport CT, USA 06605 Phone: (203)-908-3323 Fax: (203)-908-3325
All rights Reserved. No portion of this package or any part herein shall not be reproduced in any form without the written permission of Phillips Fuel System Inc
By acceptance of this package, it is understood that Phillips Fuel System Inc shall be responsible for only those items indicated herein and unless otherwise noted.
The signatory whose signature appears is duly authorized by all necessary and appropriate action to execute approval and will all abide by Phillips Fuel Systems Inc standard sales terms and conditions and be responsible for verifying correctness of the type, size, location, operation, electrical requirements, piping, accessories or any other requirements for successful operation. It is further understood that by acceptance of this package, Phillips Fuel System Inc will not be held liable for any deviation or omission from any quotation and/or specification. Phillips Fuel System Inc reserves the right, without approval, to rearrange components or substitute, due to lack of availability, quality and/or performance, any component indicated herein with a compatible component, as long as that component is of the same quality and general design.
Approved __________________________ Date ___________
Approved __________________________ Date ___________
Approved __________________________ Date ___________
PHILLIPS FUEL SYSTEMS INC LIMITED WARRANTY FOR NEW PUMPS OR PUMPING SYSTEMS
MANUFACTURED BY PHILLIPS FUEL SYSTEMS INC
A. PRODUCTS WARRANTED - Phillips Fuel System Inc, subject to the limitations contained below, will at its option, repair or replace, without charge for parts or labor only, any part or parts of a new pump or system manufactured by PHILLIPS FUEL SYSTEMS which is found, upon examination by PHILLIPS FUEL SYSTEMS INC at it's factory in Bridgeport, Ct. or by its designated affiliate, to be DEFECTIVE IN MATERIAL AND/OR WORKMANSHIP if determined by such examination within twelve months from the date of sale to the original consumer purchaser.
B. PRODUCTS AND ITEMS NOT WARRANTED - The provisions of this warranty shall not apply to any equipment, part or accessory which:
(a) has been improperly specified by buyer;;
(b) has been improperly stored or handled prior to placing in service;;
(c) has been improperly mounted, installed or connected, altered or modified in any way.
(d) has not been operated within specifications as stated on its nameplate, label, placard, or within its operating manual;;
(e) has not been properly maintained;;
(f) parts supplied by buyer for inclusion in finished equipment are not covered by this warranty;;
(g) components or assemblies specified by buyer with no substitution permissible that are not normally used by Phillips Fuel System Inc are not covered by this warranty;;
(h) that interfaces with, controls or is controlled by any device that has not been approved by Phillips Fuel System Inc
Phillips Fuel System Inc reserves the right to reject warranty claims of any kind against assembled equipment, parts or material for which Phillips Fuel System Inc has not received payment in full and for any system which was not authorized for start up and use by Phillips Fuel System Inc or by its designated affiliate. Should buyer, at his own risk, elect to replace failed equipment or parts in the field rather than obtain start up service under this warranty, Phillips will supply and invoice parts at normal prices upon receipt of buyer’s bonafide purchase order. Failed equipment or parts returned for in-warranty crediting in exchange for replacement parts must be returned within 45 days from date of shipment of replacement in order to qualify for warranty consideration.
This warranty is extended to the original buyer only and is not transferable to subsequent buyers. This warranty is available for installations in the forty-eight contiguous U.S. states only.
C. SECURING WARRANTY SERVICE - Warranty service can be arranged by contacting PHILLIPS FUEL SYSTEMS INC, c/o Service Manager, 109 Holland Ave, Bridgeport, Ct 06605. Warranty service can only be performed by Phillips Fuel System Inc at its factory in Bridgeport, Ct or by its designated affiliate. At the time of requesting warranty service, evidence must be presented of the date of sale to the original consumer purchaser. The purchaser shall pay any charges for making service calls and/or for transporting the product to and from the place where the inspection and/or warranty work is performed. The purchaser shall be responsible for any damage or loss incurred in connection with the transportation of the system and/or of part or parts of the system, submitted for inspection and/or warranty work.
D. NO ADDITIONAL WARRANTIES OR REPRESENTATIONS - The foregoing EXPRESSED WARRANTY IS IN LIEU OF ALL OTHER EXPRESSED WARRANTIES. Neither Phillips Fuel System Inc nor any of its affiliates make any warranties, representations or promises, written or verbal, as to the quality of the system or its parts other than those set forth herein.
ANY IMPLIED WARRANTIES (INCLUDING, BUT NOT LIMITED TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE) TO THE EXTENT EITHER APPLIES TO PART OR PARTS OF A SYSTEM SHALL BE
LIMITED IN DURATION TO THE PERIODS OF THE EXPRESSED WARRANTIES AS DEFINED IN
PARAGRAPH A. Some states do not allow limitations on how long an implied warranty lasts, so the above limitations may not apply.
E. DAMAGES - IN NO EVENT WILL PHILLIPS PUMPS BE LIABLE FOR ANY INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES AND/OR EXPENSES.