This document summarizes a solicitation for water storage tank remediation services. The Bureau of Overseas Buildings Operations within the U.S. Department of State is seeking multiple vendors to provide assessment, repair, and interior coating of concrete water storage tanks at U.S. diplomatic missions worldwide over the course of a five-year IDIQ contract period. The solicitation will result in at least three IDIQ contract awards, with one being set aside for a woman-owned small business, one for a small business, and one unrestricted. The maximum total contract value is $100 million. Interested offerors must submit proposals by March 27, 2020. The question submission period closes on March 12, 2020, with responses posted as an amendment. Technical considerations are more important than cost in the best value determination for award.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2020 OBO FIRE CODE UNCLASSIFIED FIRE SERVICE FEATURES
Chapter 5
OBO-ICS 2020 OBO-International Codes Supplements JANUARY 2020 Amendments to the International Fire Code
United States Department of State UNCLASSIFIED IFC 5 - 2
SECTION 507
FIRE PROTECTION WATER SUPPLIES
Add the following subparagraph:
507.1.1 Fire protection water distribution treatment. Where on-compound treatment of water is provided for the potable water system a chlorine residual of 0.5 mg/l shall be maintained within the fire protection water distribution system.
Delete Paragraph 507.2 and replace with the following:
507.2 Type of water supply. Compound fire protection systems shall be supplied from a compound fire protection water storage tank. That tank shall be supplied an receive make-up from the compound raw water inlet tank after that water has passed through the potable water treatment systems to the compound potable water storage tank.; refer to OBO-ICS IPC Chapter 6 for those systems.
Delete Subparagraph 507.2.2.1 and replace with the following:
507.2.2.1 Water tanks. Compound fire protection water storage tanks shall be installed in accordance with
NFPA 22.
1. Capacity. Calculated fire protection water supply capacity for the largest demand of an automatic sprinkler system presented by any one compound building based on the requirements of OBO-ICS IFC Chapter 9.
Capacity shall include the total combined inside and outside hose allowances required by NFPA 13. The duration of the water supply shall use the higher duration value in NFPA 13.
2. Fire protection water distribution system. Where the general water storage is supplied from the municipal source, and where the municipal source water has been treated by the municipality, the fire protection water distribution system shall be designed to maintain a minimum chlorine residual of 0.5 mg/L
3. Split tank. The fire protection water storage tank shall be designed to as a split tank with two approximately equal tanks in order to facilitate maintenance of a portion of the tanks without removing all of the system capacity. The combined size of both tanks shall provide the required capacity. Both portions of the split tank shall function independently, with both fed from the compound potable water storage tank, and both feeding the site fire protection distribution system.
4. Configuration with compound fire pump. The compound fire protection water storage tank shall be located for use of a horizontally-mounted split case fire pump.
5. Access to tank interior. Provide two manholes in the top of each raw water tank, minimum of 1000mm by 1000 mm, for maintenance, ventilation and rescue access. Manholes shall be locked except when in use.
Insert the following subparagraph:
507.2.3 Fire Pumps. Where fire pumps are not located in standalone structures, openings within exterior walls, floors, or roofs shall be provided that allow a 2300mm (90 in.) long by 4450mm (175 in.) wide skid to pass through.
Doors, hatches, or removable louvers are all acceptable openings.