Attachment B J.1.2 Automatic Transfer Switch (ATS) Specification 19AQMM19R0022.pdf
PDF 31 KB Posted
- Attached to
- World Wide Residential Generators Program Federal contract opportunity
- Solicitation number
- 19AQMM19R0022
About this file
This document package includes an automatic transfer switch specification and details of a related federal contract opportunity for residential generators. The specification outlines technical requirements for an automatic transfer switch to support generators between 25-1000kVA, including short circuit withstand ratings, self-test capabilities, and operational details. The related opportunity is a solicitation from the Department of State for pre-qualified vendors to provide generators and accessories on a global scale under an IDIQ contract worth up to $25 million over five years. Vendors must demonstrate the ability to meet standard product specifications while supporting delivery and maintenance worldwide. Proposals are due February 5th, 2020 with a small business set-aside and award of multiple IDIQ contracts expected.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A004 Resgen signed.pdf | ||
| A003 Resgen 19AQMM19R0022.pdf | ||
| A0002 Resgen 19AQMM19R0022.pdf | ||
| Attachment C J.1.3 US Department of State Worldwide Locations (1).docx | DOCX document | |
| Attachment A J.1.1 Packaged Generator Set Specification 19AQMM19R0022.pdf | ||
| A001 Resgen 19AQMM19R0022 solicitation.pdf | ||
| J.1.4 RGMS Vendor Service Interface 19 0408 (1).pdf | ||
| SF_33 resgen 19R0022.pdf | ||
| ResGen Solicitation 19AQMM19R022.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment J.1.2 Automatic Transfer Switch (ATS) Specification
Attachment B J.1.2 Automatic Transfer Switch (ATS) Specification
Overseas Building Operations
CFSM/FAC/PS
AUTOMATIC TRANSFER SWITCH
PART 1 GENERAL
1.1 DESCRIPTION
a. Provide Automatic Transfer Switch (ATS) as requested or required to support the required generator(s) identified in the Request for Proposal (RFP).
1.2 SUBMITTALS
Submit the following in electronic (PDF) format:
SD-02 Shop Drawings
Connection Diagrams Fabrication Drawings Installation Drawings
SD-03 Product Data Equipment and Performance Data Contacts Indicating Lights Terminal Board Enclosures Accessories
SD-06 Test Reports Qualification Testing Operation Tests
SD-07 Certificates Listing of Product Installations
SD-08 Manufacturer's Instructions Automatic Transfer Switch
1.3 QUALIFICATION TESTING
Provide certified independent laboratory test data for the furnished unit or an identical unit.
Ensure tests meet the general use requirements of UL 508, Table 22.1. Subject the complete automatic transfer switch to a test as outlined in NEMA ICS 1, paragraph 109.5. One cycle of operation tests under the UL 508 test requirements consists of a transfer of load from the normal source to the emergency source and reverse transfer to the normal source. After the required number of test cycles, ensure the temperature rise of the contacts has not exceeded 149 degrees F. Test the switch operating time and the sense relay pickup and dropout times.
PART 2 PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
Provide a complete automatic transfer switch assembly from one of the following manufacturers or approved equals:
a. ASCO
b. ATC
c. Cummins OTEC
2.2 SYSTEM DESCRIPTION
Provide a complete automatic transfer switch system for use with engine-generator sets for stand-by power rating and or ampacity requested. Submit the following:
a. Connection diagrams showing the relations and connections of contacts, indicating lights, and terminal board by showing the general physical layout of all controls, the interconnection of one system (or portion of system) with another.
b. Fabrication drawings for contacts, indicating lights, terminal board enclosures, and accessories consisting of fabrication and assembly details to be performed in the factory.
c. Installation drawings for automatic transfer equipment.
d. Equipment and performance data for automatic transfer equipment including test information, system functional flows, safety features, and mechanical automated details.
2.2.1 Design Requirements
Unless otherwise directed provide an automatic transfer switch of the four-pole type for three-phase application or three-pole for single phase applications based on the requests within the RFP. Provision for switched neutral pole will be included as a standard configuration.
2.2.2 Performance Requirements
Provide an industrial quality automatic transfer switch capable of transferring the load from the normal power source to emergency power source, and from an emergency source to the normal power source. Provide a switch that is solenoid-operated, mechanically held, double-throw, rated for continuous duty, capable of transferring in 300 milliseconds or less, and conforming to the applicable requirements of UL 1008 and NFPA 70, Article 700, except as herein modified.
Ensure the automatic transfer switch is capable of being placed in either the normal or the emergency position. Transfer switches are expected to incur frequent transitions between utility and generator power; potentially four times each day and seven days a week indefinitely. As such, there is a need to withstand operations where 10,000 or more transfer cycles can be expected during the lifecycle of the switch.
2.3 FABRICATION
2.3.1 Short Circuit Withstand Current Rating
Provide switch with short-circuit current rating of 30,000. Ensure switch is capable of withstanding 30,000 amperes for a period of 2 seconds without damage.
2.3.2 Self-Test Capability
Provide an automatic transfer switch with a control-circuit self-test feature capable of verifying the proper operation of the switch control circuit without moving the main contactor or causing discontinuity of service to the load. Include the following characteristics in the self-test circuit:
a. A key-operated switch that disconnects the main actuator and connects in its place, an indicator light. Design the key-operated switch to prevent removal of the key while the switch is in the self-test mode.
b. A power-failure simulator switch that removes voltage from the voltage-sensing devices so that emergency power activates the test light.
2.3.3 Enclosures
Provide automatic transfer switch enclosures with solid, unventilated, NEMA 3R, with manufacturer's standard finish.
2.4 COMPONENTS
2.4.1 Contacts
The switch shall insure an open transition operation and that at no time during the transition shall generator and utility power coexist on a common bus. Provide main contacts with wiping-action silver alloy that when rated for operation at 50 amperes or greater are protected against arcing.
Ensure auxiliary contacts and control transfer relay contacts have a minimum continuous current rating of not less than 10-amperes inductive at 120 volts ac. Provide the following auxiliary contacts:
a. Generator-control contacts, normally open, that close on under voltage or loss of normal power as specified, remaining closed until transfer back to normal power
b. Emergency-position contacts, normally open when the switch is in the normal position, that close when the switch is in the emergency position
c. Normal position contacts, normally closed when the switch is in the normal position, that open when the switch is in the emergency position
Use two pole auxiliary contacts.
2.4.2 Indicating Lights
Furnish automatic transfer switch with two indicating lamps. Provide one light to indicate that the switch is operating on normal power and the other light to indicate that the switch is operating on emergency power. Fuse each indicating circuit.
2.4.3 Terminal Board
Internally wire control devices, indicating lights, auxiliary contacts, and internal control devices or auxiliary switches to a common output terminal board. Wire the internal functions to facilitate remote connections or monitoring.
2.5 OPERATION
Monitor normal source voltage across phase lines by sensing devices. If the normal source voltage in phase drops to 90 percent or less for a timed period, the automatic transfer switch starts the emergency source and transfer the load to the emergency source when voltage and frequency reach rated values or, if the emergency source is on, verify voltage and frequency of the alternate source and transfer the load to the alternate source through an open transition process. Field adjustment shall be possible for a time period between 1 to 30 seconds. Provide a voltage and frequency sensor relay to monitor rated values on the emergency side to prohibit transfer until the emergency source voltage and frequency reach at least 95 percent of the required rating. Provide phase failure protection, with 65 to 70 percent drop and 92 to 95 percent voltage pickup ratings.
Furnish the automatic transfer switch with a time-delay feature, field adjustable from 2 to 30 minutes that operates to delay automatic transfer back to normal power until the normal source voltage and frequency reach at least 95 percent of the rated voltage. However, if the emergency power fails, and the normal source is again available at 90 percent of the rated voltage, bypass the time-delay circuitry, and the load immediately transferred back to the normal source.
Provide capability for manual transfer in either direction. Operate sensing relays without contact chatter or false response during voltage variations between dropout and pickup.
2.6 ACCESSORIES
Incorporate with the automatic transfer switch a 24-volt solid-state, high-and low-rate charger complete with rheostat and ammeter, to maintain the engine-generator cranking batteries in a fully charged condition.
Incorporate an engine-generator exerciser timer with the automatic transfer switch to permit weekly programming of engine-generator set test runs under load.
-- End of Section --
| PART 1 GENERAL |
| 1.1 DESCRIPTION |
| a. Provide Automatic Transfer Switch (ATS) as requested or required to support the required generator(s) identified in the Request for Proposal (RFP). |
| 1.2 SUBMITTALS |
| 1.3 QUALIFICATION TESTING |
| PART 2 PRODUCTS |
| 2.1 ACCEPTABLE MANUFACTURERS |
| 2.2 SYSTEM DESCRIPTION |
| 2.2.1 Design Requirements |
| 2.2.2 Performance Requirements |
| 2.3 FABRICATION |
| 2.3.1 Short Circuit Withstand Current Rating |
| 2.3.2 Self-Test Capability |
| 2.3.3 Enclosures |
| 2.4 COMPONENTS |
| 2.4.1 Contacts |
| 2.4.2 Indicating Lights |
| 2.4.3 Terminal Board |
| 2.5 OPERATION |
| 2.6 ACCESSORIES |