199-B3199-004 Kitchen Dependency Repairs - Drawings 2023_06_06.pdf
PDF 1023 KB Posted
- Solicitation number
- 20155
- Issued by
- Isle of Wight County, Virginia
About this file
This document is a set of drawings for a state and local government contract opportunity for masonry repairs to the historic kitchen dependency of the Belle Isle Residence in Lancaster County, Virginia. The project scope includes exterior repairs such as partial replacement of masonry walls, masonry repointing, and other miscellaneous repairs. A pre-bid conference is scheduled for 11:00 AM on Thursday, July 20, 2023. The contract is being managed by the Virginia Department of Conservation and Recreation, with the project manager being Erich Thomas.
The drawings provide details on the required repairs, including underpinning the brick foundation, removing and rebuilding sections of the masonry walls, repointing mortar joints, replacing window and door assemblies, and repairing the roof and exterior trim. The project is classified as a Level 1 alteration under the Virginia Existing Building Code, with the building being of Type VB construction. The contract requires the use of historic lime mortar and matching brick for the masonry repairs.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D A
T E
D E
S I G
N
A P
P R
O V
E D
Q C
R
E V
I E
W
J O
B
N
O
D A
T E
D R
A W
N C
L I E
N T
N O
R
E V
I S
I O
N S
SHEET OF
S C
A L E
F I L E
N
M
E
G
J o b s
K i t c h e n
M a s o n r y
R e p a i r s
B e l l e
I s l e C
A D
G
G
C
O V
R
S
H E
E T d w g
Y O
U T
M
E
G
C
O V
H E
P
O
T T
E D
T u e s d a y
J u n e a m
E
R s k w a k
C
B
A
D
21 3 4 5
D C
R
O T
E D
P W
S
K I T
C H
P
E N
D E
N C
Y
M A
S O
N R
Y
R
E P
A I R
S
D E
B
P
R O
J E
C
D
E
B
V I R
G I N
I A
L A
N C
A S
T E
R
B o u l d e r
S p r i n g s
D r i v e
S u i t e i c h m o n d
V m a n f a x w w w b r o c k e n b r o u g h c o m
D C
R
P
R O
J E
D
E
G-001
C O
V E
R
S
H E
E T
A
B B
R E
V I A
T I O
N S
L E
G E
N D
A
N D
N O
T E
S
K W
H
S J K
S J K
BELLE ISLE STATE PARK
1632 BELLE ISLE ROAD
LANCASTER, VIRGINIA 22503
DEB PROJECT CODE: 199-B3199-004
DCR PROJECT CODE: 199-16646 (B20)
KITCHEN DEPENDENCY MASONRY REPAIRS
DIMENSIONAL LUMBER
MASONRY
WOODEN BOARDS &
GYPSUM DRYWALL
PLASTER AND GROUT
MATERIALS LEGEND
ARCHITECTURAL ABBREVIATIONS
ACM ASBESTOS CONTAINING MATERIALS
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
BD BOARD
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS, CONTINUES
COORD COORDINATE
DEMO DEMOLITION, DEMOLISH
DIA DIAMETER
DWG(S) DRAWING(S)
EXIST EXISTING
FF FINISHED FLOOR
FT FEET, FOOT
GALV GALVANIZED
GSF GROSS SQUARE FEET
GYP GYPSUM
INSUL INSULATION
MANUF MANUFACTURER
MAX MAXIMUM
MIN MINIMUM
MTL METAL
OC ON CENTER
PT PRESSURE TREATED
PTD PAINTED
REINF REINFORCING, REINFORCE
REQ'D REQUIRED
SF SQUARE FEET
SIM SIMILAR
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VERT VERTICAL, VERTICALLY
W/ WITH
WD WOOD
NUMBERED NOTE
BREAK LINE
CONCEALED LINE
REFLECTED OR
BOUNDARY LINE
PROPERTY LINE OR
OR PROJECTED LINE
CENTERLINE, FLOOR LINE
LEVEL LINE
REVISION
SYMBOLS LEGEND
NUMBERED NOTE
NEW WORK
DEMOLITION
OWNER
VA DEPT. OF CONSERVATION & RECREATION
ATTN: ERICH THOMAS
600 EAST MAIN STREET, 24TH FLOOR
RICHMOND VA, 23219
PHONE: 804-659-3012
EMAIL: erich.thomas@dcr.virginia.gov
ENGINEER
AUSTIN BROCKENBROUGH & ASSOCIATES, LLC
ATTN: SE JIN KWAK
1011 BOULDER SPRINGS DRIVE, SUITE 200
RICHMOND, VIRGINIA 23225
PHONE: 804-592-3900 FAX: 804-592-3901
EMAIL: skwak@brockenbrough.com
GENERAL INFORMATIONPROJECT DESCRIPTION
THE SCOPE OF THIS PROJECT INCLUDES EXTERIOR REPAIRS TO THE HISTORIC KITCHEN
DEPENDENCY OF THE BELLE ISLE RESIDENCE. REPAIRS INCLUDE PARTIAL REPLACEMENT OF
MASONRY WALLS, UNDERPINNING, MASONRY REPOINTING, AND OTHER MISCELLANEOUS REPAIRS.
SCALE: NONE
LOCATION MAP
RICHMOND
FARMVILLE
CHARLOTTESVILLE
LEXINGTON
STAUNTON
WINCHESTER
PROJECT LOCATION
DETAIL SECTION INTERIOR
ELEVATION
DETAIL/SECTION
TITLE
PHOTOGRAPH/
NUMBER INDICATES "SECTION"
LETTER INDICATES "ELEVATION"
OR "DETAIL"
DRAWING(S) ON WHICH DETAIL/
SECTION/ELEVATION IS TAKEN
DRAWING(S) ON WHICH DETAIL/
SECTION/ELEVATION IS DRAWN
ELEVATION
A2
A3
A4
A-3
A1
BUBBLE SYMBOLS
BUILDING CODE INFORMATION
APPLICABLE CODES FOR NEW WORK:
VIRGINIA EXISTING BUILDING CODE 2018 EDITION
PROJECT CONSTITUTES A LEVEL 1 ALTERATION
VIRGINIA CONSTRUCTION & PROFESSIONAL SERVICES MANUAL (CPSM) 2022 EDITION, REV 1
USE GROUP: R-5 (RESIDENTIAL)
OCCUPANT LOAD: 3 PEOPLE (BASED ON GROSS AREA)
BUILDING AREA: 544 GSF
BUILDING HEIGHT: 1 STORY (15 FEET)
CONSTRUCTION TYPE: VB (UNSPRINKLERED, UNPROTECTED)
LEAD PAINT DISCLOSURE STATEMENT
ASBESTOS DISCLOSURE STATEMENT
AN ASBESTOS INSPECTION WAS PERFORMED AND ACM WAS FOUND GENERALLY IN THE AREAS INDICATED.
HOWEVER, THE WORK IN THIS PROJECT IS NOT INTENDED TO DISTURB THE EXISTING ACM. THE ASBESTOS
INSPECTION REPORT IS INCLUDED AS AN APPENDIX TO THE PROJECT SPECIFICATIONS.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS BEEN
CONDUCTED AND CAN BE FOUND IN THE PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE
CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN
TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL BE
RECYCLED TO THE EXTENT POSSIBLE.
INDEX OF DRAWINGS
SHEET
NUMBER
DRAWING
NUMBER
DRAWING TITLE
GENERAL
1 G-001
COVER SHEET, ABBREVIATIONS, LEGEND AND NOTES
ARCHITECTURAL
2 A-101 FLOOR & ROOF PLANS
3 A-201 EXTERIOR ELEVATIONS
4 A-501 DETAILS
SCALE: NONE
VICINITY MAP
PROJECT SITE
EXISTING FRAMING
B
E
L
I d
C d e g k inn
L a d
B e l
A r r e
R
A
P
P
A
H
A
N
N
O
K
I
V
E
R
MULBERRY CREEK
5 S-101 UNDERPINNING FOUNDATION PLAN & STRUCTURAL NOTES
GENERAL NOTES
1. CONTACT VIRGINIA 811 AT 811, 1-800-552-7001, OR https://www.va811.com NO LESS THAN 72 HOURS
PRIOR TO EXCAVATION AND DO NOT DISTURB THE SOIL UNTIL DIG TICKET HAS BEEN PROCESSED.
A-101 A-501
C
A-101 A-201
A
A-101 A-201
B
A-101 A-201
D
A-101 A-201
28'-4"± (VIF)
V
I F
EXISTING WOOD FLOOR
& JOISTS TO REMAIN
EXISTING
PARTITIONS TO
REMAIN, TYP
REBUILD DAMAGED
MASONRY WALL
INDICATED BY HATCH
A
A-101 A-501
EXISTING METAL ROOF
TO REMAIN, TYP
S L
O P
E
S
L O
D A
T E
D E
S I G
N
A P
P R
O V
E D
Q C
R
E V
I E
W
J O
B
N
O
D A
T E
D R
A W
N C
L I E
N T
N O
R
E V
I S
I O
N S
SHEET OF
S C
A L E
F I
M
E
G
J o b s
K i t c h e n
M a s o n r y
R e p a i r s
B e l l e
I s l e C
A D
A
A
F
L O
O
F
P
L A
N S d
Y O
M
E
A
F
L O
O
F
P
L A
O
T T
E D
T u e s d a y
J u n e
E
R s k w a k
C
B
A
D
21 3 4 5
D C
R
T
E D
P W
S
K I T
C H
P
E N
D E
N C
Y
M A
S O
N R
Y
R
E P
A I R
S
D E
B
P
R O
J E
D
E
B
V I R
G I N
I A
L A
N C
A S
T E
R u l d e r
S p r i n g s
D r i v e
S u i c h m o n d m a f a x w w w b r o c k e n b r o u g h c o m
D C
R
P
R O
J E
D
E
A-101
F L O
O
F
P
L A
N S
K W
H
S J K
S J K
7'5'4'3'2'0'
3/8"=1'-0"
1' 6' 8'
SCALE:
PLAN
NORTH
3/8" = 1'-0"
FLOOR PLAN
01 UNDERPIN BRICK FOUNDATION AS INDICATED WITH NEW REINFORCED CONCRETE FOOTING.
CONTRACTOR MUST PROVIDE TEMPORARY SUPPORT OF EXISTING WALL(S) AND ROOF. SEE
WALL SECTION 1/A-501 AND SHEET S-101.
02 CAREFULLY REMOVE EXISTING DOOR AND WINDOW ASSEMBLIES, CLEAN ASSEMBLIES, AND
PROVIDE STORAGE. REINSTALL DOOR AND WINDOW ASSEMBLIES AFTER MASONRY REPAIR AND
PROVIDE NEW STEEL HEADER. SEE DETAILS A/A-501, B/A-501 & C/A-501. REPLACE DRYWALL AND
WOOD FURRING AROUND OPENINGS AS NEEDED.
03 AFTER UNDERPINNING IS COMPLETE, REMOVE OUTER TWO WYTHES OF SOUTH WALL (SEE
LEGEND). REBUILD OUTER WYTHES OF WALL USING HISTORIC LIME MORTAR & BRICK AS
SPECIFIED. LAY BRICK IN FLEMISH BOND TO MATCH EXISTING.
04 REPLACE WINDOW BRICKMOLD AND SILL AT LOWER WINDOW TO MATCH EXISTING SIZE AND
PROFILE.
05 REPLACE EAVE FASCIA, SOFFIT & FRIEZE BOARD TO MATCH EXISTING SIZE AND PROFILE. SEE
WALL SECTION 1/A-501.
06 REPLACE WOOD THRESHOLD AT BOTH DOORS TO MATCH EXISTING SIZE. SEE DETAIL A/A-501.
1. TRIM VEGETATION AROUND BUILDING AND CLEAN EXTERIOR
MASONRY WALL USING LOW-PRESSURE WATER SPRAY & BRUSH
PRIOR TO MATCHING BRICK AND MORTAR COLOR RANGE.
2. CONTRACTOR TO PROVIDE TEMPORARY SUPPORT AND BRACING
FOR ROOF AND WALLS DURING MASONRY REPAIR AND FOOTING
WORK.
3. PAINT ALL EXTERIOR DOORS, WINDOWS, FASCIA, SOFFIT, AND
TRIM. MATCH EXISTING COLOR.
4. REPOINT BRICK MASONRY WALLS AND FOUNDATION USING
HISTORIC LIME MORTAR AS SPECIFIED & INDICATED ON A-201.
PROVIDE INTEGRATED EXTERIOR MOCK-UP FOR REVIEW. SEE
APPENDIX A OF THE PROJECT MANUAL FOR ADDITIONAL
INFORMATION ON EXISTING MORTAR.
5. REPAIR BRICK MASONRY WALLS AND FOUNDATION USING
HISTORIC LIME MORTAR & BRICK AS SPECIFIED & INDICATED ON
A-501 & S-101. REPLACEMENT BRICK TO MATCH SIZE, COLOR, AND
TEXTURE OF ADJACENT BRICK AT THREE AREAS AS SELECTED BY
ARCHITECT. PROVIDE INTEGRATED EXTERIOR MOCK-UP FOR
REVIEW SEPARATE FROM REPOINTING MOCK-UP. ALL BRICK TO BE
LAID IN FLEMISH BOND.
6. CLEAN EXTERIOR MASONRY USING LOW-PRESSURE WATER
SPRAY & BRUSH AFTER REPOINTING & REPAIR WORK.
SHEET NOTESGENERAL NOTES
SCALE:
PLAN
NORTH
3/8" = 1'-0"
ROOF PLAN
FINISH FLOOR
0'-0"
EAVE
9'-7"+/-
FINISH FLOOR
0'-0"
EAVE
9'-7"+/-
PRESERVE EXISTING
WINDOW, TYP
PRESERVE EXISTING
DOOR
PRESERVE EXISTING
WINDOW, TYP
REPOINT
INAPPROPRIATE
MORTAR
CRACKED MASONRY
POORLY LAID
MASONRY
RE-LAY SECTIONS OF
COMMON BOND BRICK
AS INDICATED
POORLY LAID
MASONRY
EXISTING VENT TO
REMAIN, DO NOT FILL
EXISTING VENT TO
REMAIN, DO NOT FILL
MISSING BRICK
CHIMNEY SHOWN ON
HABS PHOTOS
EXISTING
STANDING-SEAM
METAL ROOF TO
REMAIN
EXIST WOOD RAKE
TO REMAIN
FINISH FLOOR
0'-0"
EAVE
9'-7"+/-
FINISH FLOOR
0'-0"
EAVE
9'-7"+/-
PRESERVE EXISTING
WINDOW, TYP
CRACKED MASONRY
BETWEEN WINDOWS
CRACKED MASONRY
DETERIORATED
MORTAR
EXISTING VENT TO
REMAIN, DO NOT FILL
MISSING BRICK
CHIMNEY SHOWN ON
HABS PHOTOS
03 03
EXISTING
STANDING-SEAM
METAL ROOF TO
REMAIN
EXIST WOOD RAKE
TO REMAIN
D A
T E
D E
S I G
N
A P
P R
O V
E D
Q C
R
E V
I E
W
J O
B
N
O
D A
T E
D R
A W
N C
L I E
N T
N O
R
E V
I S
I O
N S
SHEET OF
S C
A L E
F I
M
E
G
J o b s
K i t c h e n
M a s o n r y
R e p a i r s
B e l l e
I s l e C
A D
A
A
E
X T
E R
I O
R
E
L E
V A
T I O
N S d
Y O
M
E
A
E
X T
E R
I O
R
E
L E
V A
T I O
O
T T
E D
T u e s d a y
J u n e
E
R s k w a k
C
B
A
D
21 3 4 5
D C
R
T
E D
P W
S
K I T
C H
P
E N
D E
N C
Y
M A
S O
N R
Y
R
E P
A I R
S
D E
B
P
R O
J E
D
E
B
V I R
G I N
I A
L A
N C
A S
T E
R u l d e r
S p r i n g s
D r i v e
S u i c h m o n d m a f a x w w w b r o c k e n b r o u g h c o m
D C
R
P
R O
J E
D
E
A-201
E X
T E
R I O
R
E
L E
V A
T I O
N S
K W
H
S J K
S J K
1/4"=1'-0"
0' 4' 12'1' 8'
SCALE: 1/4"=1'-0"
NORTH ELEVATION
A
A-101 A-201 SCALE: 1/4"=1'-0"
EAST ELEVATION
B
A-101 A-201
SCALE: 1/4"=1'-0"
SOUTH ELEVATION
C
A-101 A-201 SCALE: 1/4"=1'-0"
WEST ELEVATION
D
A-101 A-201
1. PAINT ALL EXTERIOR DOORS, WINDOWS, FASCIA, SOFFIT, AND TRIM.
MATCH EXISTING COLOR.
2. BRICK PATTERNS ON EXTERIOR ELEVATIONS ARE REPRESENTATIVE
AND DOES NOT REFLECT ACTUAL BRICK BOND ON WALLS. VERIFY
ACTUAL BRICK BOND IN THE FIELD.
3. COLORED DIAGONAL SHADING ON ELEVATIONS REPRESENTS
GENERAL AREAS IN NEED OF REPAIR AS DESCRIBED IN THE LEGEND
BELOW.
4. PROTECT EXISTING DOORS, WINDOWS, AND EXTERIOR FINISH TRIM
DURING MASONRY WORK.
REPOINT MORTAR JOINTS WITH
APPROPRIATE MORTAR, MATCH EXISTING
LEGEND
REPLACE BRICK IN FLEMISH BOND &
REPOINT MORTAR JOINTS IN HATCHED
AREA WITH APPROPRIATE BRICK & MORTAR
GENERAL NOTES
01 UNDERPIN BRICK FOUNDATION AS INDICATED WITH NEW REINFORCED
CONCRETE FOOTING. INSTALL TEMPORARY LATERAL SHORTING
AND/OR BRACING BEFORE BEGINNING UNDERPINNING. SEE WALL
SECTION 1/A-501 AND SHEET S-101.
02 CAREFULLY REMOVE EXISTING DOOR AND WINDOW ASSEMBLIES,
CLEAN ASSEMBLIES, AND PROVIDE STORAGE. REINSTALL DOOR AND
WINDOW ASSEMBLIES AFTER MASONRY REPAIR AND PROVIDE NEW
STEEL HEADER.
03 AFTER UNDERPINNING IS COMPLETE, REMOVE OUTER TWO WYTHES
OF SOUTH WALL (SEE LEGEND). REBUILD OUTER WYTHES OF WALL
USING HISTORIC LIME MORTAR & BRICK AS SPECIFIED. LAY BRICK IN
FLEMISH BOND TO MATCH EXISTING.
04 REPLACE WINDOW BRICKMOLD AND SILL AT LOWER WINDOW TO
MATCH EXISTING SIZE AND PROFILE. SEE PHOTO BELOW.
05 REPLACE EAVE FASCIA, SOFFIT & FRIEZE BOARD TO MATCH
EXISTING SIZE AND PROFILE. SEE WALL SECTION 1/A-501.
06 REPLACE WOOD THRESHOLD AT BOTH DOORS TO MATCH EXISTING
SIZE. SEE DETAIL A/A-501.
SHEET NOTES
REBUILD OUTER TWO WYTHES OF BRICK
WALL WITH APPROPRIATE BRICK AND
MORTAR
2'-6"
REPLACE WINDOW
BRICKMOLD AND SILL,
MATCH EXISTING
1" SOFFIT BOARD,
MATCH EXISTING
EXIST METAL ROOF
& WD BOARDS TO
REMAIN
WD CROWN
MOULDING, MATCH
EXISTING SIZE &
PROFILE
EXIST WD NAILER
TO REMAIN
EXIST INNER
WYTHE OF WALL TO
REMAIN
EXIST WALL &
CEILING FINISHES
TO REMAIN
1" FASCIA BOARD &
UPPER MOLDING,
MATCH EXIST
SHEET METAL
COVERING TO
REMAIN
1/2" DIA GALV
ANCHOR BOLTS W/
WASHERS AT 48" OC,
8" EMBED INTO BRICK
PT 2x8 SILL, SLOTTED
TO SLIDE ONTO
ANCHORS, OVER
NON-SHRINK GROUT,
TOENAIL EACH EXIST
RAFTER TO SILL W/
(4) 10d NAILS
NEW BRICK, MATCH
EXIST
EXIST WD WALL &
BASE TO REMAIN
EXIST WD FLOOR
JOISTS TO REMAIN
6"
NEW OUTER TWO
WYTHES OF BRICK,
MATCH EXIST,
MORTAR SOLID
AGAINST EXIST WALL.
GROUT SOLID ANY
EXISTING WALL VOIDS
FINISH GRADE
COLD FLUID APPLIED
DAMPPROOFING
BELOW GRADE
AFTER CASTING
FOOTING, PROVIDE
NON-SHRINK
"FLOWABLE" GROUT
UNDER FULL AREA OF
WALL
#4 AT 12" OC
3-#4 CONT, LAP 12"
MIN AT SEGMENT
JOINTS
UNDERPINNING
FOOTING, CAST IN
SEGMENTS AS SHOWN
ON S-101
UNDISTURBED
SUBGRADE, OWNER'S
GEOTECH ENGINEER
TO INSPECT &
APPROVE SUBGRADE
FOR 2,000 PSF BEARING
V
I F
EXIST INNER WYTHE
OF WALL TO REMAIN
1'-7"+/-
PT SOUTHERN PINE
NO 2, WD NAILER,
MATCH EXISTING
SIZE
EXIST INNER
WYTHE OF WALL TO
REMAIN
EXIST WALL FURRING
& FINISHES TO REMAIN
REMOVE AND
REINSTALL EXIST WD
WINDOW ASSEMBLY
NEW OUTER TWO
WYTHES OF BRICK,
MATCH EXIST
MASONRY SCREW
ANCHORS AT 12"
OC, 4" FROM BOTH
ENDS
SEALANT
SEALANT
PT SOUTHERN PINE
NO 2, WD NAILER,
MATCH EXISTING
SIZE
EXIST INNER
WYTHE OF WALL TO
REMAIN
EXIST WALL FURRING
& FINISHES TO REMAIN
REMOVE AND
REINSTALL EXIST WD
DOOR ASSEMBLY
PT WOOD SILL,
MATCH EXISTING,
SLOPE TO EXT
NEW OUTER TWO
WYTHES OF BRICK,
MATCH EXIST
V
I F
MASONRY SCREW
ANCHORS AT 12"
OC, 4" FROM BOTH
ENDS
SEALANT
SEALANT
PT WOOD SILL,
MATCH EXISTING,
SLOPE TO EXT
EXIST WD WALL &
BASE TO REMAIN
EXIST WD FLOOR
JOISTS TO REMAINNEW OUTER TWO
WYTHES OF BRICK,
MATCH EXIST
1 1/2"
V
I F
CONT 1/2" DRIP
EDGE
1/4" SLOPE
ALIGN SILL TO TOP
OF EXIST WOOD
FLOORING
(2) L2x3x3/8 GALV
SHELF ANGLE, EXTEND
8" MIN PAST JAMB ON
BOTH SIDES
PT SOUTHERN PINE
NO 2, WD NAILER,
MATCH EXISTING
SIZE
EXIST INNER
WYTHE OF WALL TO
REMAIN
EXIST WALL
FURRING &
FINISHES TO
REMAIN
NEW OUTER TWO
WYTHES OF BRICK,
MATCH EXIST,
MORTAR SOLID
AGAINST EXIST WALL
REMOVE AND
REINSTALL EXIST WD
DOOR ASSEMBLY
D A
T E
D E
S I G
N
A P
P R
O V
E D
Q C
R
E V
I E
W
J O
B
N
O
D A
T E
D R
A W
N C
L I E
N T
N O
R
E V
I S
I O
N S
SHEET OF
S C
A L E
F I
M
E
G
J o b s
K i t c h e n
M a s o n r y
R e p a i r s
B e l l e
I s l e C
A D
A
A
D
E T
A I L S d
Y O
M
E
A
D
E T
A I
O
T T
E D
T u e s d a y
J u n e
E
R s k w a k
C
B
A
D
21 3 4 5
D C
R
T
E D
P W
S
K I T
C H
P
E N
D E
N C
Y
M A
S O
N R
Y
R
E P
A I R
S
D E
B
P
R O
J E
D
E
B
V I R
G I N
I A
L A
N C
A S
T E
R u l d e r
S p r i n g s
D r i v e
S u i c h m o n d m a f a x w w w b r o c k e n b r o u g h c o m
D C
R
P
R O
J E
D
E
A-501
D E
T A
I L S
K W
H
S J K
S J K
2'1'0'
1 1/2"=1'-0"
3"=1'-0"
1'0' 3" 6" 9"
SCALE: 1-1/2"=1'-0"
WALL SECTION
A-101 A-501
SCALE: 3"=1'-0"
WINDOW DETAIL
C
A-101 A-501
SCALE: 3"=1'-0"
DOOR JAMB DETAIL
B
A-101 A-501
SCALE: 3"=1'-0"
DOOR SILL DETAIL
A-101 A-501
10" MIN.
3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"
30'-0"
A B C D E
EXISTING WOOD-
FRAMED FLOOR
EXISTING 4-WYTHE BRICK
MASONRY EXTERIOR WALL,
BEARING DIRECTLY ON
SUBGRADE (TYP)
28'-3 3/4"±
10" MIN.
A B C D E
A1
S-101 S-101
A1
S-101 S-101
B1
S-101 S-101
EXCAVATE BENEATH
WALL FOR 3'-0" LONG
UNDERPINNING
SEGMENT, SEE PLAN
GEOTECHNICAL ENGINEER MUST
INSPECT SUBGRADE FOR 2000
PSF SUITABILITY. EXTEND
EXCAVATION DEPTH IF DIRECTED
3'-0" LONG FOUNDATION
SEGMENT, SEE PLAN
NONSHRINK "FLOWABLE"
GROUT UNDER FULL AREA
OF WALL, EACH SEGMENT
STEP 1
EXCAVATION
STEP 2
FOUNDATION AND GROUT
GRADE
UNDERPINNING
FOOTING OUTLINE
6" 1'-7"±
(2) #4 x2'-6" LONG
(3) #4 x1'-6" LONG
3" CLR (TYP)
OVERPOUR
(CONTRACTOR OPTION)
AFTER UNDERPINNIGN IS
COMPLETE, BACKFILL
EXCAVATION TO DRAIN
AWAY FROM BUILDING
AFTER
UNDERPINNING
IS COMPLETE,
REBUILD OUTER
TWO BRICK
WYTHES (SEE
ARCH DWGS).
PLACE FIRST
MORTAR BED
ON GROUT PAD.
ALIGN
EXCAVATION
WITH INNER
FACE OF
EXISTING
WALL
CHIP OR
REMOVE BRICK
AS REQUIRED
TO INSTALL
GROUT.
M
I N
M
A X
CARVE FOUNDATION KEY INTO
EXCAVATED EARTH FACE OF
MINIMUM DIMENSIONS SHOWN (TYP)
2" MIN
PREVIOUS SEGMENT NEW SEGMENT
M
I N
M
I N
D A
T E
D E
S I G
N
A P
P R
O V
E D
Q C
R
E V
I E
W
J O
B
N
O
D A
T E
D R
A W
N C
L I E
N T
N O
R
E V
I S
I O
N S
SHEET OF
S C
A L E
F I
M
E
G
J o b s
K i t c h e n
M a s o n r y
R e p a i r s
B e l l e
I s l e C
A D
S
S
U
N D
E R
P I N
N I N
G
F
O U
N D
A T
I O
N
P
L A
N d
Y O
M
E
S
U
N D
E R
P I N
N I N
G
F
O U
N D
A T
I O
N
P
L
O
T T
E D
T u e s d a y
J u n e p
E
R d c l a r k
C
B
A
D
21 3 4 5
D C
R
T
E D
P W
S
K I T
C H
P
E N
D E
N C
Y
M A
S O
N R
Y
R
E P
A I R
S
D E
B
P
R O
J E
D
E
B
V I R
G I N
I A
L A
N C
A S
T E
R
B o u l d e r
S p r i n g s
D r i v e
S u i t e c h m o n d m a f a x w w w b r o c k e n b r o u g h c o m
D C
R
P
R O
J E
D
E
B
S-101
U N
D E
R P
I N
N I N
G
F
O U
N D
A T
I O
N
P
L A
N
A C
S
D S
C
S A
D
3/4"=1'-0"
0 1' 2' 3' 4'
SCALE: 3/4"=1'-0"
UNDERPINNING FOUNDATION SECTION
A1
S-101S-101
1. EXISTING FOUNDATION IS ASSUMED TO CONSIST OF MULTI-WYTHE BRICK WALLS BEARING
DIRECTLY ON SUBGRADE.
2. PRIOR TO MOBILIZATION, CONTRACTOR MUST HOLD AN UNDERPINNING
PRE-CONSTRUCTION MEETING WITH TELECONFERENCE OPTION. INCLUDE THE OWNER'S
REPRESENTATIVE, THE RELEVANT SUBCONTRACTORS, AND THE STRUCTURAL ENGINEER
OF RECORD, AT MINIMUM.
3. PRIOR TO BEGINNING UNDERPINNING, INSTALL TEMPORARY SHORING OF THE ROOF ATTIC
FRAMING INTERIOR OF THE SOUTH WALL. ALSO INSTALL TEMPORARY LATERAL BRACING
OF THE SOUTH WALL. MAINTAIN SHORING/BRACING UNTIL THE SOUTH WALL IS REBUILT.
SHORING AND BRACING SELECTION, DESIGN, AND INSTALLATION IS THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
4. UNDERPIN SOUTH WALL IN FIVE (5) CONSTRUCTION SEQUENCES OF TWO (2) SEGMENTS
EACH. SEQUENCES ARE LABELED A, B, C, D, E.
5. COMPLETE THE EXCAVATION, CONCRETE CONSTRUCTION, AND GROUT FOR EACH
SEQUENCE BEFORE PROCEEDING TO THE NEXT. TO MAINTAIN WALL SUPPORT, AT NO TIME
MAY MULTIPLE SEQUENCES BE UNDER EXCAVATION.
6. AFTER ALL UNDERPINNING IS COMPLETE, PROCEED TO REMOVE AND REBUILD EXTERIOR
WYTHES OF SOUTH WALL AS SHOWN IN ARCH DRAWINGS.
UNDERPINNING FOUNDATION PLAN NOTES
1. SELECTION AND APPLICATION OF FOUNDATION REPAIRS HAVE BEEN PERFORMED IN
ACCORDANCE WITH THE 2018 VIRGINIA EXISTING BUILDING CODE, AND ASCE 7-16 "MINIMUM
DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES".
2. THE CONTRACT DOCUMENTS INCLUDE DRAWINGS AND SPECIFICATIONS TO BE USED IN
CONJUNCTION. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3. THERE ARE NO EXISTING DRAWINGS. INFORMATION REGARDING THE EXISTING STRUCTURE
WAS OBTAINED FROM LIMITED VISUAL FIELD INVESTIGATION BY THE A/E.
4. CONTRACTOR MUST VERIFY EXISTING CONDITIONS. COORDINATE THESE CONDITIONS WITH
THE CONTRACT DOCUMENTS. NOTIFY THE A/E OF EXISTING CONDITIONS DIFFERING FROM
WHAT IS SHOWN THAT PREVENT ACCOMPLISHING THE WORK.
5. CONTRACTOR MUST PROVIDE TEMPORARY SHORING OF ROOF AND LATERAL SUPPORT OF
WALLS AS REQUIRED TO SUCCESSFULLY PERFORM FOUNDATION UNDERPINNING SHOWN.
6. IF STRUCTURE IS OBSERVED TO SETTLE, MOVE, OR CRACK DURING REPAIR WORK, HALT
WORK AND IMMEDIATELY CONTACT THE A/E FOR DIRECTION.
7. LOADS AND DESIGN CRITERIA
A. RISK CATEGORY II
B. LIVE LOADS
FLOOR 100 PSF
ROOF 20 PSF
1. NO GEOTECHNICAL INVESTIGATION WAS PERFORMED FOR THE PROJECT.
2. UNDERPINNING FOUNDATIONS MUST BEAR ON SUBGRADE HAVING A MINIMUM ALLOWABLE
SOIL BEARING PRESSURE OF 2000 PSF.
3. THE SPECIAL INSPECTOR OR GEOTECHNICAL ENGINEER MUST INSPECT AND APPROVE
UNDERPINNING FOUNDATION SUBGRADES PRIOR TO CONCRETE PLACEMENT. UNDERCUT
ANY UNACCEPTABLE AREAS IDENTIFIED BY THE SPECIAL INSPECTOR, AND BACKFILL WITH
LEAN CONCRETE OR FLOWABLE FILL AS DIRECTED.
CONCRETE NOTES
1. CONCRETE WORK MUST CONFORM TO THE REQUIREMENTS OF ACI 318-14 "BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE".
2. CONCRETE MATERIAL AND MIX DESIGN PROPERTIES MUST BE:
MINIMUM 28 DAY CONCRETE COMPRESSIVE STRENGTH (f'c):
UNDERPINNING FOUNDATIONS 3000 PSI
NON-SHRINK "FLOWABLE" GROUT ASTM C1107, 3000 PSI
WATER/CEMENT RATIO, AIR CONTENT, AND SLUMP SEE SPECIFICATIONS
REINFORCING STEEL ASTM A615, GRADE 60
1. MASONRY WORK MUST CONFORM TO THE REQUIREMENTS OF TMS 402-16 "BUILDING CODE
REQUIREMENTS FOR MASONRY STRUCTURES" AND TMS 602-16 "SPECIFICATION FOR
MASONRY STRUCTURES".
2. MASONRY MATERIAL PROPERTIES MUST BE:
CLAY FACE BRICK ASTM C216
MORTAR ASTM C270
MINIMUM BRICK NET AREA COMPRESSIVE STRENGTH f'm = 3350 PSI
MINIMUM MORTAR COMPRESSIVE STRENGTH f'c = 2000 PSI
MASONRY NOTES
STRUCTURAL LEGEND
CAST-IN-PLACE CONCRETE
BRICK
EARTH
GROUT, OR CONCRETE (PLAN)
ABBREVIATION DESCRIPTION
STRUCTURAL ABBREVIATIONS
ACI AMERICAN CONCRETE INSTITUTE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
CLR, CLEAR CLEAR(ANCE)
CONT CONTINUOUS
DWGS DRAWINGS
(E), EX, EXST EXISTING
GALV GALVANIZED
MAX MAXIMUM
MIN MINIUMUM; MINUTE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
REINF REINFORCEMENT
TMS THE MASONRY SOCIETY
TOF TOP OF FOOTING, TOP OF FOUNDATION
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VUSBC VIRGINIA UNIFORM STATEWIDE BUILDING
CODE
WWF WELDED WIRE FABRIC
W/ WITH
± PLUS OR MINUS
SCALE:
PLAN
NORTH
3/8"=1'-0"
SOUTH WALL UNDERPINNING FOUNDATION PLAN
C1
S-101
GENERAL STRUCTURAL NOTES
7'5'4'3'2'0'
3/8"=1'-0"
1' 6' 8'
1. STRUCTURAL STEEL SCOPE CONSISTS OF LOOSE
LINTELS USED IN EXTERIOR MASONRY WALLS.
2. STRUCTURAL STEEL ANGLES MUST CONFORM TO
ASTM A36, Fy = 36 KSI
3. HOT-DIP GALVANIZE STEEL LINTELS IN EXTERIOR
WALLS.
SCALE: 3/4"=1'-0"
UNDERPINNING SEGMENT JOINT DETAIL
B1
S-101S-101
FOUNDATION NOTES
STRUCTURAL STEEL NOTES
| Sheets and Views |
| G-001 COVER SHEET, ABBREVIATIONS, LEGEND, AND NOTES |
| A-101 FLOOR & ROOF PLANS |
| A-201 EXTERIOR ELEVATIONS |
| A-501 DETAILS |
| S-101 UNDERPINNING FOUNDATION PLAN |
2023-06-06T13:41:46-0400
2023-06-06T13:42:01-0400
2023-06-06T13:47:23-0400
2023-06-06T13:47:40-0400
2023-06-06T13:47:34-0400
2023-06-06T13:47:34-0400
2023-06-06T13:47:35-0400
2023-06-06T13:47:51-0400
2023-06-06T13:47:51-0400
2023-06-06T13:47:52-0400
File details come from the government source that posted it. Updated .