18051_Drawings 06 ELEC.pdf

PDF 3 MB Posted

Attached to
171/18051. TYC; Flint SOB; Parking Ramp Elevator Upgrades
Solicitation number
RFQ 171 190000000439 3
Issued by
Genesee County, Fife Lake Village, Michigan

About this file

This is a set of electrical drawings for the Flint State Office Building Parking Garage Elevator Renovation project located at 125 E. Union Street in Flint, Michigan. The drawings were prepared by CTR (Donn Rush & Associates) with elevator consulting services and are dated May 10, 2019, with project number 18-309.00. The scope of work encompasses electrical demolition and renovation work associated with elevator system upgrades across multiple levels of the parking garage. The work includes removal of existing elevator controller cabinets, cab lighting, pit lighting, receptacles, smoke and heat detectors, and phone lines, with corresponding installation of new electrical components including replacement panelboards, GFCI receptacles in weatherproof covers, heat and smoke detectors connected to the existing fire alarm system, and extended phone lines to new elevator controllers. The project includes multiple floor levels (1st, 2nd, and 3rd levels) with both standard and alternate electrical configurations. Key electrical installations specified include new 80-ampere fuses for elevator controllers, new duplex GFCI receptacles, elevator pit lights, and fire alarm control relays integrated with new elevator controllers for emergency recall functionality.

The electrical work must comply with the latest editions of applicable federal, state, and local codes including OSHA standards, NEC requirements, and state fire insurance regulations. All branch circuits require dedicated neutral and ground conductors with no shared neutrals permitted. All conduits in interior spaces must be recessed in walls or located in ceiling spaces above finished areas, with surface-mounted conduit prohibited unless otherwise noted. The electrical contractor must provide typed panel legends and label all receptacles and switches with their corresponding panelboard and branch circuit information. The specifications reference Section 16010 for additional requirements and note that the existing Honeywell fire alarm control panel is original to 1984 construction, requiring the contractor to provide all necessary components and modifications to integrate new heat detectors and elevator controllers. Standard outlet mounting heights are specified at 18 inches above finished floor in finished or shell spaces, with telecommunications outlets provided as extra deep double gang boxes with plastic bushings and rough-in connections to accessible ceiling space.

View the file

Other files

File Type Posted
18051_Drawings 03 ARCH.pdf PDF
Addendum 2 18051 (r).pdf PDF
18051_Drawings 07 ELEC.pdf PDF
18051_Drawings 02 ARCH.pdf PDF
18051_Drawings 05 MECH.pdf PDF
Advertisemnt 18051 (r).pdf PDF
Addendum 1 18051 (r).pdf PDF
Specifications 18051 (r).pdf PDF
18051_Drawings 01 STRUC_ARCH.pdf PDF
18051_Drawings 04 ARCH.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CIRCUIT DESIGNATIONS

LIGHTING

GENERAL NOTES

ABBREVIATIONS

GENERAL

POWER AND DIAGRAMS

DEMOLITION AND REMODEL

FIRE DETECTION AND ALARM

SECURITY

TELECOMMUNICATION

NOTE:

SYMBOLS SHOWN ARE FOR REFERENCE ONLY

AND DO NOT CONSTITUTE A CHECK LIST

OF DEVICES REQUIRED BY THE CONTRACT

J

S

OS

OS

PC

TC

LV

S

S D

TS

FS

M

F

F

F

FAA

H

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

1ST NUMBER INDICATES QUANTITY OF DATA CABLES

AutoCAD SHX Text

EX

AutoCAD SHX Text

EXISTING ELECTRICAL ITEM TO BE REMOVED

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text

EXISTING ELECTRICAL ITEM TO BE REMOVED AND RELOCATED

AutoCAD SHX Text

EXISTING ELECTRICAL ITEM RELOCATED. NEW LOCATION

AutoCAD SHX Text

EXISTING ELECTRICAL ITEM TO REMAIN

AutoCAD SHX Text B

AutoCAD SHX Text

EXISTING ELECTRICAL ITEM TO BE REMOVED AND PROVIDED WITH A BLANK COVERPLATE

AutoCAD SHX Text

EXISTING ELECTRICAL OR SYSTEMS CIRCUIT TO REMAIN

AutoCAD SHX Text EXISTING ELECTRICAL CIRCUIT TO BE REMOVED SHOWN ONLY WHERE CLARIFICATION BETWEEN EXISTING TO REMAIN AND REMOVED ITEMS IS REQUIRED

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

MAX QUANTITY OF CONDUCTORS PER CONDUIT

AutoCAD SHX Text

CONDUCTOR SIZE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NA

AutoCAD SHX Text

1 INCH

AutoCAD SHX Text

9 TO 13

AutoCAD SHX Text

7 TO 11

AutoCAD SHX Text

4 TO 5

AutoCAD SHX Text

CONDUIT RISER UP

AutoCAD SHX Text

CONDUIT RISER DOWN

AutoCAD SHX Text

INDICATES CIRCUIT CONTINUATION

AutoCAD SHX Text

STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS OTHERWISE NOTED

AutoCAD SHX Text

CONDUIT SEAL FITTING FOR HAZARDOUS AREAS

AutoCAD SHX Text

CONDUIT SLEEVE

AutoCAD SHX Text

CAP END OF CONDUIT

AutoCAD SHX Text

CABLE OR CORD CONNECTED

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

NOTE A: OUTLETS IN FINISHED OR SHELL SPACES SHALL BE MOUNTED AT +18" UON.

AutoCAD SHX Text NOTE B: OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18"AFF IN KNEE SPACE IF PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE SPACE IS PROVIDED UON.

AutoCAD SHX Text NOTE C: WHERE ASTERISK (*) IS INDICATED NEXT TO OUTLET AT WORK COUNTER, OUTLET SHALL BE LOCATED ABOVE COUNTER RATHER THAN IN KNEE SPACE.

AutoCAD SHX Text STANDARD TELECOMMUNICATIONS OUTLET - PROVIDE EXTRA DEEP DOUBLE GANG BOX WITH SINGLE GANG MUD RING AND (2) 3/4" CONDUITS TO ABOVE FINISHED CEILING. PROVIDE PLASTIC BUSHING AT THE ENDS OF THE CONDUITS. DATA DEVICES AND WIRING PROVIDED BY OTHERS U.O.N.

AutoCAD SHX Text THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS (NON-STANDARD) TYPES OF OUTLETS

AutoCAD SHX Text

2ND NUMBER INDICATES QUANTITY OF VOICE CABLES

AutoCAD SHX Text B

AutoCAD SHX Text

BLANK (ROUGH-IN TO ACCESSABLE CEILING SPACE)

AutoCAD SHX Text F

AutoCAD SHX Text

FIBER

AutoCAD SHX Text W

AutoCAD SHX Text

WALL PHONE OUTLET AT +48"

AutoCAD SHX Text C

AutoCAD SHX Text

CEILING PHONE OUTLET

AutoCAD SHX Text P

AutoCAD SHX Text

PUBLIC TELEPHONE AT +44"

AutoCAD SHX Text

FL

AutoCAD SHX Text

PEDESTAL FLOOR FITTING

AutoCAD SHX Text

FIXED VIDEO SURVEILANCE CAMERA

AutoCAD SHX Text

PAN/TILT/ZOOM VIDEO SURVEILANCE CAMERA

AutoCAD SHX Text

DOOR POSITION SWITCH

AutoCAD SHX Text

CONNECTION TO ELECTRIC OR PNEUMATIC DOOR LOCK

AutoCAD SHX Text

CARD READER AT +48"

AutoCAD SHX Text

1LN1-1

AutoCAD SHX Text BRANCH CIRCUIT HOMERUN. PROVIDE PHASE, NEUTRAL AND GROUND CONDUCTORS FOR EACH INDICATED CIRCUIT OR MULTI WIRE BRANCH AS REQUIRED. PROVIDE SWITCH LEGS FOR SWITCH CIRCUITING AS REQUIRED. PROVIDE EQUIPMENT GROUND WIRE IN ALL BRANCH CIRCUIT RACEWAYS/CIRCUITS. PROVIDE SEPARATE ISOLATED GROUND WIRE TO ALL ISOLATED GROUND DEVICES.

AutoCAD SHX Text

PANEL NAME

AutoCAD SHX Text

POLE NUMBERS

AutoCAD SHX Text

AMPERES

AutoCAD SHX Text

AMP FUSE OR AMP FRAME

AutoCAD SHX Text

AVAILABLE FAULT CURRENT (SYMMETRICAL)

AutoCAD SHX Text

ABOVE FINISHED FLOOR

AutoCAD SHX Text

AMPERE INTERRUPTING CAPACITY

AutoCAD SHX Text

ASYMMETRICAL

AutoCAD SHX Text

AMP TRIP

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text

AMERICAN WIRE GAUGE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

CAPACITY OR CAPACITOR

AutoCAD SHX Text

COMMUNITY ANTENNA TELEVISION

AutoCAD SHX Text

CIRCUIT BREAKER

AutoCAD SHX Text

CLOSED CIRCUIT TELEVISION

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

CONDUIT ONLY

AutoCAD SHX Text

CONNECT OR CONNECTION

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

DOUBLE POLE SINGLE THROW

AutoCAD SHX Text

ELECTRIC WATER COOLER

AutoCAD SHX Text

ELECTRIC OR ELECTRICAL

AutoCAD SHX Text

ELEVATION OR ELEVATOR

AutoCAD SHX Text

EMERGENCY

AutoCAD SHX Text

ELECTRICAL METAL TUBING

AutoCAD SHX Text

FIXTURE

AutoCAD SHX Text

FULL LOAD AMPERES

AutoCAD SHX Text

FLUORESCENT

AutoCAD SHX Text

FLUOR.

AutoCAD SHX Text

FLA

AutoCAD SHX Text

FIXT.

AutoCAD SHX Text

EMT

AutoCAD SHX Text

EMERG, EM

AutoCAD SHX Text

ELEV

AutoCAD SHX Text

ELEC

AutoCAD SHX Text

EWC

AutoCAD SHX Text

DPST

AutoCAD SHX Text

DISC.

AutoCAD SHX Text

CU

AutoCAD SHX Text

CONN.

AutoCAD SHX Text C.O.

AutoCAD SHX Text

CKT ,CCT

AutoCAD SHX Text

CCTV

AutoCAD SHX Text

CB

AutoCAD SHX Text

CATV

AutoCAD SHX Text

CAP.

AutoCAD SHX Text C

AutoCAD SHX Text

AWG

AutoCAD SHX Text

ATS

AutoCAD SHX Text

AT

AutoCAD SHX Text

ASYM.

AutoCAD SHX Text

AIC.

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text

AFC

AutoCAD SHX Text

AF

AutoCAD SHX Text

A, AMP

AutoCAD SHX Text

AMMETER

AutoCAD SHX Text

AM.

AutoCAD SHX Text

EC

AutoCAD SHX Text

ELECTRICAL CONTRACTOR

AutoCAD SHX Text

HIGH INTENSITY DISCHARGE

AutoCAD SHX Text

HAND-OFF-AUTO

AutoCAD SHX Text

HORSEPOWER

AutoCAD SHX Text

HIGH PRESSURE SODIUM

AutoCAD SHX Text

HERTZ

AutoCAD SHX Text

INTERMEDIATE METAL CONDUIT

AutoCAD SHX Text

ISOLATED GROUND

AutoCAD SHX Text

INCANDESCENT

AutoCAD SHX Text

KILOVOLT AMPERES

AutoCAD SHX Text

KILOWATT

AutoCAD SHX Text

KILOWATT HOUR

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

LOW VOLTAGE

AutoCAD SHX Text

MASTER ANTENNA TELEVISION

AutoCAD SHX Text

MAIN CIRCUIT BREAKER

AutoCAD SHX Text

MOTOR CONTROL CENTER

AutoCAD SHX Text

MANHOLE, METAL HALIDE OR MOUNTING HEIGHT

AutoCAD SHX Text

MAIN LUGS ONLY

AutoCAD SHX Text

NORMALLY CLOSED

AutoCAD SHX Text

NON FUSIBLE

AutoCAD SHX Text

NORMALLY OPEN

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

OVERLOADS

AutoCAD SHX Text

POLE

AutoCAD SHX Text

PULLBOX

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

PAIR

AutoCAD SHX Text

POWER

AutoCAD SHX Text

RECEPTACLE

AutoCAD SHX Text

RIGID GALVANIZED STEEL

AutoCAD SHX Text

RGS

AutoCAD SHX Text

REC

AutoCAD SHX Text

PWR.

AutoCAD SHX Text

PR

AutoCAD SHX Text

PNL

AutoCAD SHX Text

PB

AutoCAD SHX Text P

AutoCAD SHX Text

OL

AutoCAD SHX Text

NTS

AutoCAD SHX Text N.O.

AutoCAD SHX Text

NF

AutoCAD SHX Text N.C.

AutoCAD SHX Text

MLO

AutoCAD SHX Text

MH

AutoCAD SHX Text

MCC

AutoCAD SHX Text

MCB

AutoCAD SHX Text

MATV

AutoCAD SHX Text

LV

AutoCAD SHX Text

LTG

AutoCAD SHX Text

KWH

AutoCAD SHX Text

KW

AutoCAD SHX Text

KVA

AutoCAD SHX Text

KAIC

AutoCAD SHX Text

INCAND.

AutoCAD SHX Text I.G.

AutoCAD SHX Text

IMC

AutoCAD SHX Text

HZ.

AutoCAD SHX Text

HPS

AutoCAD SHX Text

HP

AutoCAD SHX Text

HOA

AutoCAD SHX Text

HID

AutoCAD SHX Text

GRC,GCR

AutoCAD SHX Text

GFCI

AutoCAD SHX Text

GFI

AutoCAD SHX Text

GALVANIZED RIGID CONDUIT

AutoCAD SHX Text

GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text

GROUND FAULT INTERRUPTER

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

JB

AutoCAD SHX Text

NATIONAL ELECTRICAL CODE

AutoCAD SHX Text N.E.C.

AutoCAD SHX Text N.I.C.

AutoCAD SHX Text

NOT IN CONTRACT

AutoCAD SHX Text

POLYVINYL CHLORIDE

AutoCAD SHX Text

PVC

AutoCAD SHX Text

GRD,GND,G

AutoCAD SHX Text

THOUSAND AMPERE INTERRUPTING CAPACITY

AutoCAD SHX Text

TELEPHONE

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

TELEPHONE TERMINAL BACKBOARD

AutoCAD SHX Text

TELEVISION

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text

UNDERGROUND

AutoCAD SHX Text

UNLESS OTHERWISE NOTED

AutoCAD SHX Text

VOLT

AutoCAD SHX Text

VOLT AMPERES

AutoCAD SHX Text

VOLTAGE DROP

AutoCAD SHX Text

VOLT METER

AutoCAD SHX Text

WATTS OR WIRE

AutoCAD SHX Text

WITH

AutoCAD SHX Text

WITHOUT

AutoCAD SHX Text

WEATHERPROOF

AutoCAD SHX Text

WP

AutoCAD SHX Text W/O

AutoCAD SHX Text W/

AutoCAD SHX Text W

AutoCAD SHX Text

VM

AutoCAD SHX Text

VD

AutoCAD SHX Text

VA

AutoCAD SHX Text V

AutoCAD SHX Text U.O.N.

AutoCAD SHX Text

UG

AutoCAD SHX Text

TYP

AutoCAD SHX Text

TV

AutoCAD SHX Text

TTB

AutoCAD SHX Text

XFMR

AutoCAD SHX Text

TEL

AutoCAD SHX Text

SOL

AutoCAD SHX Text

SPDT

AutoCAD SHX Text

SPKR

AutoCAD SHX Text

SPST

AutoCAD SHX Text

SOLENOID

AutoCAD SHX Text

SINGLE POLE DOUBLE THROW

AutoCAD SHX Text

SPEAKER

AutoCAD SHX Text

SINGLE POLE SINGLE THROW

AutoCAD SHX Text

SW.

AutoCAD SHX Text

SWBD

AutoCAD SHX Text

SYM

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

SWITCHBOARD

AutoCAD SHX Text

SYMMETRICAL

AutoCAD SHX Text

EXPLOSION PROOF

AutoCAD SHX Text

XP

AutoCAD SHX Text

EMERGENCY POWER OFF

AutoCAD SHX Text

EPO

AutoCAD SHX Text

DURESS ALARM

AutoCAD SHX Text

DOOR BELL

AutoCAD SHX Text

DB

AutoCAD SHX Text

DA

AutoCAD SHX Text

GEN

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text MOUNTING HEIGHTS TO BE AS INDICATED UON. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE FROM FINISHED FLOOR OR GRADE UON. SEE SPECIFICATION 16010 FOR ADDITIONAL REQUIREMENTS

AutoCAD SHX Text

KEY NOTE REFERENCE SYMBOL. DENOTES "SEE KEY NOTE NO. 2"

AutoCAD SHX Text

AutoCAD SHX Text

FOOT ON DEVICE INDICATES WALL MOUNTED

AutoCAD SHX Text SEE SPECIFICATONS FOR LIMITATIONS ON QUANTITY OF CURRENT CARRYING CONDUCTORS PER CONDUIT

AutoCAD SHX Text

PH OR

AutoCAD SHX Text

1 TO 3

AutoCAD SHX Text

5 TO 6

AutoCAD SHX Text

5 TO 8

AutoCAD SHX Text

3/4 INCH

AutoCAD SHX Text

1 TO 4

AutoCAD SHX Text

1 TO 4

AutoCAD SHX Text

1/2 INCH

AutoCAD SHX Text

NOTE A: UPPER CASE ALPHANUMERIC SUBSCRIPT DENOTES FIXTURE TYPE. SEE SCHEDULE(S)

AutoCAD SHX Text NOTE B: LOWER CASE LETTER SUBSCRIPT PROVIDED ADJACENT TO SWITCHING DEVICE AND ASSOCIATED LIGHT FIXTURE(S) WHERE REQUIRED FOR CLARIFICATION.

AutoCAD SHX Text

CEILING LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text

DIRECTIONAL AIMED FIXTURE AIM IN DIRECTION OF ARROW

AutoCAD SHX Text

WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text

FLUORESCENT LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text

FLUORESCENT WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text FLUORESCENT UNDER CABINET/COUNTER LIGHT OUTLET OR STRIP LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text EXIT LIGHT OUTLET WITH FIXTURE - SHADING INDICATES LOCATION OF FACE(S). ARROWS INDICATE DIRECTIONAL ARROWS WHERE REQUIRED. WALL MOUNTED SIGNS AT +90" CENTERED ABOVE DOOR WHERE APPLICABLE

AutoCAD SHX Text

EMERGENCY LIGHT FIXTURE WITH INTEGRAL BATTERY SOURCE AND ADJUSTABLE HEADS

AutoCAD SHX Text TRACK LIGHT OUTLET WITH FIXTURE. TYPE INDICATED, QUANTITY AND LENGTH AS SHOWN OR SCHEDULED

AutoCAD SHX Text

LIGHTING STANDARD WITH POST-TOP FIXTURE

AutoCAD SHX Text CEILING LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text FLUORESCENT LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text FLUORESCENT WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text FLUORESCENT STRIP LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text

NO SUBSCRIPT - SINGLE POLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TE

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text K

AutoCAD SHX Text

XP

AutoCAD SHX Text

DOUBLE POLE

AutoCAD SHX Text

THREE WAY

AutoCAD SHX Text

FOUR WAY

AutoCAD SHX Text

MANUAL STARTER WITH THERMAL ELEMENT

AutoCAD SHX Text

PILOT LIGHT

AutoCAD SHX Text

LIGHTED HANDLE

AutoCAD SHX Text

KEY OPERATED

AutoCAD SHX Text

EXPLOSION PROOF

AutoCAD SHX Text

LIGHTING DIMMER

AutoCAD SHX Text D

AutoCAD SHX Text M

AutoCAD SHX Text

MOTOR RATED

AutoCAD SHX Text

SWITCH AT +48" U.O.N.

AutoCAD SHX Text

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE VARIOUS TYPES OF SWITCHES.

AutoCAD SHX Text

PHOTOCELL

AutoCAD SHX Text

TIME CLOCK AT +48"

AutoCAD SHX Text

OCCUPANCY SENSOR WITH INTEGRAL SWITCH-WALL MOUNTED AT +48"

AutoCAD SHX Text

OCCUPANCY SENSOR - CEILING MOUNTED

AutoCAD SHX Text THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS TYPES OF OCCUPANCY SENSORS

AutoCAD SHX Text LIGHTING STANDARD POLE FIXTURE, PROVIDE QUANTITY OF HEADS AND ORIENTATION AS INDICATED

AutoCAD SHX Text

BOLLARD FIXTURE

AutoCAD SHX Text

LOW VOLTAGE SWITCH

AutoCAD SHX Text

NO SUBSCRIPT - COMBINATION INFRARED/ULTRASONIC SENSOR

AutoCAD SHX Text

INFRARED SENSOR

AutoCAD SHX Text

ULTRASONIC SENSOR

AutoCAD SHX Text I

AutoCAD SHX Text U

AutoCAD SHX Text

PENDANT LIGHT FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text

PENDANT LIGHT FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text

LINEAR PENDANT/SUSPENDED LIGHT FIXTURE CONNECTED TO NORMAL SOURCE

AutoCAD SHX Text LINEAR PENDANT/SUSPENDED LIGHT FIXTURE CONNECTED TO EMERGENCY SOURCE (LIFE SAFETY BRANCH)

AutoCAD SHX Text

GF

AutoCAD SHX Text

ST

AutoCAD SHX Text

XP

AutoCAD SHX Text

IG

AutoCAD SHX Text

WP

AutoCAD SHX Text

SAFETY TYPE RECEPTACLE

AutoCAD SHX Text

EXPLOSION PROOF RECEPTACLE

AutoCAD SHX Text

ISOLATED GROUND RECEPTACLE

AutoCAD SHX Text

WEATHERPROOF

AutoCAD SHX Text

SW

AutoCAD SHX Text

TOP HALF OF DUPLEX RECEPTACLE SWITCHED

AutoCAD SHX Text

CL

AutoCAD SHX Text

CLOCK RECEPTACLE AT +84"

AutoCAD SHX Text

HORIZONTAL MOUNTING

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE A: OUTLETS IN FINISHED OR SHELL SPACES SHALL BE MOUNTED AT +18" U.O.N.

AutoCAD SHX Text

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE DIFFERENT TYPES OF RECEPTACLES

AutoCAD SHX Text

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE AT +42" IN TOILETS

AutoCAD SHX Text

20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE, NEMA 5-20R

AutoCAD SHX Text

20A, 125V, 2 POLE, 3 WIRE GROUNDING SINGLE RECEPTACLE, NEMA 5-20R

AutoCAD SHX Text

20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R

AutoCAD SHX Text PEDESTAL TYPE, FLOOR OR COUNTER MOUNTED RECEPTACLE RECEPTACLE TYPE AS INDICATED ABOVE

AutoCAD SHX Text

FLUSH FLOOR BOX WITH RECEPTACLE, TYPE AS INDICATED ABOVE

AutoCAD SHX Text COMBINATION POWER/COMMUNICATIONS FLOOR BOX, SEE COMMUNICATIONS PLAN FOR SYSTEMS DEVICE

AutoCAD SHX Text

PIGTAIL DENOTES CONNECTION TO LIGHT SWITCH, LIGHT FIXTURE OR FIXED EQUIPMENT

AutoCAD SHX Text

SPECIAL PURPOSE RECEPTACLE SUBSCRIPT DENOTES NEMA TYPE, REFER TO SPECIFICATIONS

AutoCAD SHX Text

JUNCTION BOX, 4 INCH SQUARE UNLESS OTHERWISE NOTED

AutoCAD SHX Text

PLUG-IN RECEPTACLE STRIP (LENGTH AS INDICATED)

AutoCAD SHX Text

TELECOMMUNICATIONS/POWER POLE

AutoCAD SHX Text

208 VOLT PANELBOARD AT +72" TO TOP

AutoCAD SHX Text

480 VOLT PANELBOARD AT +72" TO TOP

AutoCAD SHX Text

CABLE TRAY OR WIREWAY

AutoCAD SHX Text

CIRCUIT BREAKER. AMP/POLES AS INDICATED

AutoCAD SHX Text

FUSE. SIZE AS INDICATED

AutoCAD SHX Text

FUSIBLE SWITCH. AMP/POLES/FUSE SIZE AS INDICATED

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH +72" TO TOP OR FLOOR MOUNTED.

AutoCAD SHX Text

DISCONNECT STABS FOR DRAWOUT TYPE EQUIPMENT

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

GROUND CONNECTION

AutoCAD SHX Text

MOTOR CONNECTION, HP AS INDICATED

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

START-STOP PUSHBUTTON STATION AT +48"

AutoCAD SHX Text

NO SUBSCRIPT - STANDARD FIRE ALARM PULL STATION

AutoCAD SHX Text

MANUAL STATION AT +48"

AutoCAD SHX Text THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS TYPE OF MANUAL STATIONS, FIRE SUPPRESSION SYSTEM CONTROL PANELS AND/OR ABORT SWITCHES

AutoCAD SHX Text

VISUAL NOTIFICATION APPLICANCE

AutoCAD SHX Text

WALL MOUNTED AUDIBLE NOTIFICATION APPLIANCE

AutoCAD SHX Text

MAGNETIC DOOR HOLDER/RELEASE. COORDINATE MOUNTING HEIGHT WITH DOOR MANUFACTURER.

AutoCAD SHX Text

SPRINKLER OR STANDPIPE FLOW ALARM SWITCH CONNECTION

AutoCAD SHX Text

VALVE TAMPER SWITCH

AutoCAD SHX Text

SOLENOID VALVE FOR PREACTION SPRINKLER SYSTEM

AutoCAD SHX Text

AIR PRESSURE MONITOR SWITCH FOR PRE-ACTION OR DRY PIPE SPRINKLER SYSTEM

AutoCAD SHX Text

SMOKE DETECTOR

AutoCAD SHX Text

AUTOMATIC HEAT DETECTOR

AutoCAD SHX Text

CONTROL PANEL AT +72" TO TOP

AutoCAD SHX Text

FIRE FIGHTERS TELEPHONE JACK AT +48"

AutoCAD SHX Text

FIRE FIGHTERS TELEPHONE HANDSET AT +48"

AutoCAD SHX Text

GROUNDING SYSTEM TEST WELL

AutoCAD SHX Text

GROUNDING CONNECTION

AutoCAD SHX Text NOTE B: RECEPTACLES LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE SPACE IS PROVIDED U.O.N.

AutoCAD SHX Text NOTE C: WHERE (AC) IS INDICATED NEXT TO RECPTACLES AT WORK COUNTER, RECEPTACLES SHALL BE LOCATED ABOVE COUNTER RATHER THAN IN KNEE SPACE.

AutoCAD SHX Text NOTE D: RECEPTACLES IN MECHANICAL AND ELECTRICAL SPACES SHALL BE MOUNTED AT +48" U.O.N.

AutoCAD SHX Text

RECEPTACLE SERVED BY UPS

AutoCAD SHX Text U

AutoCAD SHX Text

CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE

AutoCAD SHX Text

GROUND BUS ON STANDOFFS

AutoCAD SHX Text

FIRE ALARM ANNUNCIATOR PANEL AT +72" TO TOP

AutoCAD SHX Text

FIRE SUPPRESSION SYSTEM ABORT SWITCH STATION AT +48"

AutoCAD SHX Text THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS TYPE OF SMOKE DETECTORS

AutoCAD SHX Text

NO SUBSCRIPT - PHOTO ELECTRIC AREA BEAM

AutoCAD SHX Text

DUCT SMOKE DETECTOR

AutoCAD SHX Text

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS TYPE OF HEAT DETECTORS

AutoCAD SHX Text

NO SUBSCRIPT - FIXED TEMPERATURE (155 DEGREE U.O.N.)

AutoCAD SHX Text R/F

AutoCAD SHX Text

COMBINATION RATE OF RISE FIXED TEMPERATURE (135 DEGREE U.O.N.)

AutoCAD SHX Text

XP

AutoCAD SHX Text

EXPLOSION PROOF, FIXED TEMPERATURE (135 DEGREE U.O.N.) CLASS 1, GROUP C

AutoCAD SHX Text NOTE: WALL MOUNT VISUAL AND COMBINATION AUDIO/VISUAL NOTIFICATION APPLIANCES AT +80" AFF TO BOTTOM OF FACE PLATE U.O.N.

AutoCAD SHX Text

WALL MOUNTED COMBINATION AUDIBLE/VISUAL NOTIFICATION APPLIANCE

AutoCAD SHX Text

CEILING MOUNTED VISUAL NOTIFICATION APPLIANCE

AutoCAD SHX Text

CEILING MOUNTED COMBINATION AUDIBLE/VISUAL NOTIFICATION APPLIANCE

AutoCAD SHX Text V

AutoCAD SHX Text

CEILING MOUNTED REMOTE ALARM INDICATOR

AutoCAD SHX Text

WALL MOUNTED REMOTE ALARM INDICATOR AND TEST STATION AT +48"

AutoCAD SHX Text

CONTROL PANEL: INTEGRAL PART OF, OR FURNISHED BY OTHER THAN DIVISION 16

AutoCAD SHX Text

EQUIPMENT OR TERMINAL CABINET AT +72" TO TOP

AutoCAD SHX Text

POWER SUPPLY

AutoCAD SHX Text

PUSHBUTTON STATION AT +48"

AutoCAD SHX Text

SAFETY SWITCH AT +54". CHARACTERISTICS AS INDICATED BY FRAME/POLES.

AutoCAD SHX Text MAGNETIC MOTOR STARTER AT +54". CHARACTERISTICS AS INDICATED BY FRAME SIZE/POLES/NEMA SIZE.

AutoCAD SHX Text COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT AT +54". CHARACTERISTICS AS INDICATED BY FRAME/FUSE/POLES/NEMA SIZE

AutoCAD SHX Text

ADJUSTABLE FREQUENCY DRIVE

AutoCAD SHX Text

MAGNETIC CONTACTOR AT +54". AMPS/POLES/CONTACT VOLTS/ COIL VOLTS AS INDICATED.

AutoCAD SHX Text SEPARATELY MOUNTED, ENCLOSED MOLDED CASE CIRCUIT BREAKER AT +48". FLUSH MOUNTED IN FINISHED AREAS. AMP/POLES AS INDICATED.

AutoCAD SHX Text FUSED SAFETY SWITCH AT +54". CHARACTERISTICS AS INDICATED BY FRAME/FUSESIZE/POLES.

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text E-001

AutoCAD SHX Text

ELECTRICAL SYMBOLS SHEET

AutoCAD SHX Text

RCH

AutoCAD SHX Text

JAS

GENERAL NOTES

KEYED NOTES

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uFIRST LEVEL ELECTRICAL DEMOLITION FLOOR PLAN

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

ED-101 1ST LEVEL - ELECTRICAL DEMOLITION

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING MAIN SWITCHBOARD 'MDP'

AutoCAD SHX Text

EXISTING XFMR 'TLPD'

AutoCAD SHX Text

EXISTING PANEL 'LPD'

AutoCAD SHX Text

EXISTING PANEL 'LPC'

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR CONTROLLER CABINETS BACK TO THE DISCONNECT SWITCH FOR THE ASSOCIATED ELEVATOR CAR. MAINTAIN FEEDER FOR EXTENSION TO NEW. 2. REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO DISCONNECT. MAINTAIN BRANCH CIRCUIT FOR EXTENSION TO NEW FUSED SWITCH. 3. DISCONNECT AND REMOVE EXISTING PIT LIGHTING. MAINTAIN BRANCH CIRCUIT FOR DISCONNECT AND REMOVE EXISTING PIT LIGHTING. MAINTAIN BRANCH CIRCUIT FOR CONNECTION/EXTENSION TO NEW LIGHTING. EXISTING SWITCH TO REMAIN. 4. REMOVE AND REPLACE EXISTING ELEVATOR PIT RECEPTACLE WITH NEW GFCI RECEPTACLE. REMOVE AND REPLACE EXISTING ELEVATOR PIT RECEPTACLE WITH NEW GFCI RECEPTACLE. 5. REMOVE EXISTING ELEVATOR SMOKE/HEAT DETECTOR. REMOVE ALL WIRING BACK TO REMOVE EXISTING ELEVATOR SMOKE/HEAT DETECTOR. REMOVE ALL WIRING BACK TO SOURCE. TYPICAL FOR ALL FLOORS. 6. REMOVE EXISTING ELEVATOR MACHINE ROOM SMOKE/HEAT DETECTOR. REMOVE EXISTING ELEVATOR MACHINE ROOM SMOKE/HEAT DETECTOR. 7. DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. MAINTAIN FOR DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. MAINTAIN FOR CONNECTION TO NEW ELEVATOR CONTROLLERS. 8. REMOVE AND REPLACE EXISTING 200A, 42P, PANELBOARD 'LPD'. SEE NEW PANEL REMOVE AND REPLACE EXISTING 200A, 42P, PANELBOARD 'LPD'. SEE NEW PANEL SCHEDULES. RE-TERMINATE ALL EXISTING CONDUCTORS TO NEW PANEL. 9. REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR CONTROLLER CABINETS BACK TO SOURCE. 10. DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. REMOVE ALL DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. REMOVE ALL CONDUIT AND WIRE BACK TO SOURCE. 11. REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO SOURCE. 12. DISCONNECT AND REMOVE EXISTING PIT LIGHTING, RECEPTACLE, AND SWITCH. REMOVE ALL DISCONNECT AND REMOVE EXISTING PIT LIGHTING, RECEPTACLE, AND SWITCH. REMOVE ALL CONDUIT AND WIRE BACK TO SOURCE.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text

ED-101

1ST LEVEL - ELECTRICAL DEMOLITION

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uFIRST LEVEL ELECTRICAL DEMOLITION FLOOR PLAN

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

ED-101A 1ST LEVEL - ELECTRICAL DEMOLITION - ALTERNATE

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING MAIN SWITCHBOARD 'MDP'

AutoCAD SHX Text

EXISTING XFMR 'TLPD'

AutoCAD SHX Text

EXISTING PANEL 'LPD'

AutoCAD SHX Text

EXISTING PANEL 'LPC'

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR REMOVE ALL EQUIPMENT, SWITCHES, CONDUIT AND CIRCUITING ASSOCIATED WITH ELEVATOR CONTROLLER CABINETS BACK TO THE DISCONNECT SWITCH FOR THE ASSOCIATED ELEVATOR CAR. MAINTAIN FEEDER FOR EXTENSION TO NEW. 2. REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO REMOVE CONNECTION TO ELEVATOR CAB LIGHTS. REMOVE CONDUIT AND WIRE BACK TO DISCONNECT. MAINTAIN BRANCH CIRCUIT FOR EXTENSION TO NEW FUSED SWITCH. 3. DISCONNECT AND REMOVE EXISTING PIT LIGHTING. MAINTAIN BRANCH CIRCUIT FOR DISCONNECT AND REMOVE EXISTING PIT LIGHTING. MAINTAIN BRANCH CIRCUIT FOR CONNECTION/EXTENSION TO NEW LIGHTING. EXISTING SWITCH TO REMAIN. 4. REMOVE AND REPLACE EXISTING ELEVATOR PIT RECEPTACLE WITH NEW GFCI RECEPTACLE. REMOVE AND REPLACE EXISTING ELEVATOR PIT RECEPTACLE WITH NEW GFCI RECEPTACLE. 5. REMOVE EXISTING ELEVATOR SMOKE/HEAT DETECTOR. REMOVE ALL WIRING BACK TO REMOVE EXISTING ELEVATOR SMOKE/HEAT DETECTOR. REMOVE ALL WIRING BACK TO SOURCE. TYPICAL FOR ALL FLOORS. 6. REMOVE EXISTING ELEVATOR MACHINE ROOM SMOKE/HEAT DETECTOR. REMOVE EXISTING ELEVATOR MACHINE ROOM SMOKE/HEAT DETECTOR. 7. DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. MAINTAIN FOR DISCONNECT EXISTING PHONE LINES FROM ELEVATORS TO BE REMOVED. MAINTAIN FOR CONNECTION TO NEW ELEVATOR CONTROLLERS. 8. REMOVE AND REPLACE EXISTING 200A, 42P, PANELBOARD 'LPD'. SEE NEW PANEL REMOVE AND REPLACE EXISTING 200A, 42P, PANELBOARD 'LPD'. SEE NEW PANEL SCHEDULES. RE-TERMINATE ALL EXISTING CONDUCTORS TO NEW PANEL.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text

ED-101A

1ST LEVEL - ELECTRICAL DEMOLITION - ALTERNATE

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uFIRST LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-101 1ST AND 2ND LEVEL - ELECTRICAL

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uSECOND LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-101 1ST AND 2ND LEVEL - ELECTRICAL

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING MAIN SWITCHBOARD 'MDP'

AutoCAD SHX Text

EXISTING XFMR 'TLPD'

AutoCAD SHX Text

NEW PANEL 'LPD'

AutoCAD SHX Text

EXISTING PANEL 'LPC'

AutoCAD SHX Text E

AutoCAD SHX Text C1

AutoCAD SHX Text C1

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

LPD-43/45 #10W

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

LPD-55/57 #10W

AutoCAD SHX Text

LPD-59

AutoCAD SHX Text

WP

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. PROVIDE NEW CONNECTION TO NEW ELEVATOR CONTROLLER. REPLACE EXISTING FUSES WITH PROVIDE NEW CONNECTION TO NEW ELEVATOR CONTROLLER. REPLACE EXISTING FUSES WITH NEW 80A FUSES. 2. PROVIDE NEW CONNECTION TO ELEVATOR CAB LIGHTS. EXTEND EXISTING CIRCUIT TO NEW PROVIDE NEW CONNECTION TO ELEVATOR CAB LIGHTS. EXTEND EXISTING CIRCUIT TO NEW ELEVATOR CONTROLLER. 3. PROVIDE NEW ELEVATOR PIT LIGHT. CONNECT TO EXISTING SWITCH AND CIRCUIT. EXTEND PROVIDE NEW ELEVATOR PIT LIGHT. CONNECT TO EXISTING SWITCH AND CIRCUIT. EXTEND TO NEW LOCATION. COORDINATE EXACT LOCATION WITH ELEVATOR MANUFACTURER PRIOR TO INSTALLATION. 4. PROVIDE NEW DUPLEX GFCI RECEPTACLE IN WEATHERPROOF WHILE IN USE COVER. PROVIDE NEW DUPLEX GFCI RECEPTACLE IN WEATHERPROOF WHILE IN USE COVER. CONNECT TO EXISTING CIRCUIT. COORDINATE EXACT LOCATION WITH ELEVATOR MANUFACTURER AND EXTEND CIRCUIT AS REQUIRED. 5. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER FOR ELEVATOR RECALL. 6. REMOVE NEW HEAT AND SMOKE DETECTOR IN ELEVATOR MACHINE ROOM. CONNECT TO REMOVE NEW HEAT AND SMOKE DETECTOR IN ELEVATOR MACHINE ROOM. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER. 7. EXTEND EXISTING PHONE LINES TO NEW ELEVATOR CONTROLLER.EXTEND EXISTING PHONE LINES TO NEW ELEVATOR CONTROLLER.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text E-101

1ST AND 2ND LEVEL - ELECTRICAL

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uFIRST LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-101A 1ST AND 2ND LEVEL - ELECTRICAL - ALTERNATE

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uSECOND LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-101A 1ST AND 2ND LEVEL - ELECTRICAL - ALTERNATE

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING MAIN SWITCHBOARD 'MDP'

AutoCAD SHX Text

EXISTING XFMR 'TLPD'

AutoCAD SHX Text

NEW PANEL 'LPD'

AutoCAD SHX Text

EXISTING PANEL 'LPC'

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text C1

AutoCAD SHX Text C1

AutoCAD SHX Text C1

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

LPD-43/45 #10W

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

LPD-47/49 #10W

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

LPD-55/57 #10W

AutoCAD SHX Text

LPD-51/53 #10W

AutoCAD SHX Text

30/25/3 NEMA 3R

AutoCAD SHX Text

LPD-59

AutoCAD SHX Text

WP

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. PROVIDE NEW CONNECTION TO NEW ELEVATOR CONTROLLER. REPLACE EXISTING FUSES WITH PROVIDE NEW CONNECTION TO NEW ELEVATOR CONTROLLER. REPLACE EXISTING FUSES WITH NEW 80A FUSES. 2. PROVIDE NEW CONNECTION TO ELEVATOR CAB LIGHTS. EXTEND EXISTING CIRCUIT TO NEW PROVIDE NEW CONNECTION TO ELEVATOR CAB LIGHTS. EXTEND EXISTING CIRCUIT TO NEW ELEVATOR CONTROLLER. 3. PROVIDE NEW ELEVATOR PIT LIGHT. CONNECT TO EXISTING SWITCH AND CIRCUIT. EXTEND PROVIDE NEW ELEVATOR PIT LIGHT. CONNECT TO EXISTING SWITCH AND CIRCUIT. EXTEND TO NEW LOCATION. COORDINATE EXACT LOCATION WITH ELEVATOR MANUFACTURER PRIOR TO INSTALLATION. 4. PROVIDE NEW DUPLEX GFCI RECEPTACLE IN WEATHERPROOF WHILE IN USE COVER. PROVIDE NEW DUPLEX GFCI RECEPTACLE IN WEATHERPROOF WHILE IN USE COVER. CONNECT TO EXISTING CIRCUIT. COORDINATE EXACT LOCATION WITH ELEVATOR MANUFACTURER AND EXTEND CIRCUIT AS REQUIRED. 5. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER FOR ELEVATOR RECALL. 6. REMOVE NEW HEAT AND SMOKE DETECTOR IN ELEVATOR MACHINE ROOM. CONNECT TO REMOVE NEW HEAT AND SMOKE DETECTOR IN ELEVATOR MACHINE ROOM. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER. 7. EXTEND EXISTING PHONE LINES TO NEW ELEVATOR CONTROLLER.EXTEND EXISTING PHONE LINES TO NEW ELEVATOR CONTROLLER.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text E-101A

1ST AND 2ND LEVEL - ELECTRICAL - ALTERNATE

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uTHIRD LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-102 3RD LEVEL - ELECTRICAL

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING PANEL 'LPE'

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER FOR ELEVATOR RECALL. 2. EXISTING HONEYWELL FIRE ALARM CONTROL PANEL. PANEL IS ORIGINAL TO 1984 EXISTING HONEYWELL FIRE ALARM CONTROL PANEL. PANEL IS ORIGINAL TO 1984 CONSTRUCTION. CONTRACTOR SHALL PROVIDE ALL NECESSARY COMPONENTS AND MODIFICATIONS TO CONNECT TO NEW HEAT DETECTORS AND ELEVATOR CONTROLLERS.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text E-102

3RD LEVEL - ELECTRICAL

C

TR

J o b N o . 1 .0

W

W W

.C

TR

M E P .C

O M

D on n R us h

A ss oc ia te s

P ea rw oo d D r D ew itt

, M I 4

(5

) 3

-0

E le va to r C on su lti ng

FLINT STATE

OFFICE BUILDING

PARKING

GARAGE

ELEVATOR

RENOVATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

SCALE -

AutoCAD SHX Text %%uTHIRD LEVEL FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

E-102A 3RD LEVEL - ELECTRICAL - ALTERNATE

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

EXISTING PANEL 'LPE'

AutoCAD SHX Text A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. B. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, NEC OR OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING AND SPECIFICATIONS. C. ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH ALL CONDUITS LOCATED IN INTERIOR SPACE MUST BE RECESSED IN WALLS OR LOCATED HIGH UP IN CEILING SPACE ABOVE. SURFACE MOUNTED CONDUIT WILL NOT BE ALLOWED UNLESS NOTED OTHERWISE. D. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E.C. TO PROVIDE TYPE WRITTEN PANEL LEGENDS. E. ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND ALL BRANCH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE NOT PERMITTED. F. ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME ALL BATTERY OPERATED FIXTURES SHALL BE PROVIDED A DEDICATED HOT FROM THE SAME CIRCUIT SERVING THE ADJACENT NORMAL LIGHTING FIXTURES. G. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT. LABEL ALL RECEPTACLES AND SWITCHES WITH PANELBOARD AND BRANCH CIRCUIT.

AutoCAD SHX Text

1. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE NEW HEAT AND SMOKE DETECTOR. CONNECT TO EXISTING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED FIRE ALARM CONTROL RELAYS AND CONNECT TO NEW ELEVATOR CONTROLLER FOR ELEVATOR RECALL. 2. EXISTING HONEYWELL FIRE ALARM CONTROL PANEL. PANEL IS ORIGINAL TO 1984 EXISTING HONEYWELL FIRE ALARM CONTROL PANEL. PANEL IS ORIGINAL TO 1984 CONSTRUCTION. CONTRACTOR SHALL PROVIDE ALL NECESSARY COMPONENTS AND MODIFICATIONS TO CONNECT TO NEW HEAT DETECTORS AND ELEVATOR CONTROLLERS.

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text Sheet Size - 24x36

AutoCAD SHX Text

CONSULTANT

AutoCAD SHX Text 18-309.00

AutoCAD SHX Text 05-10-2019

AutoCAD SHX Text

PLAN REVIEW

AutoCAD SHX Text 125 E. Union St. Flint, MI

AutoCAD SHX Text File No.: 071/18051.TYC Index No.: 171CODTMB7188

AutoCAD SHX Text E-102A

3RD LEVEL - ELECTRICAL - ALTERNATE

E-001
ED-101
ED-101A
E-101
E-101A
E-102
E-102A