18.3 B130_131 Annual FS Inspection PreDel Supplement (05 May 22).pdf
PDF 331 KB Posted
- Attached to
- 174 CES Fire Alarm Panel Replacement Federal contract opportunity
- Solicitation number
- W50S8N-22-Q-0019
- Issued by
- Department of the Army National Guard
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| WD - SAM.gov.pdf | ||
| Fire Panel Combined Synopsitation.docx | DOCX document | |
| 18.1 B130_131 Annual FA Supplement(05 May 22).pdf | ||
| SOW_HAAW222009 Repair FA Bldg 130_131_FINAL.docx | DOCX document | |
| 18.4 B130_131 Annual Fire Alarm Inspection (05 May 22).pdf | ||
| 18.2 B130_131 Annual Fire Suppression Inspection(05 May 22).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION
OUR BUSINESS IS
PROTECTING YOURS
CONTACT US TODAY FOR A QUOTE
Phone: 315-451-0971
Online: davisulmer.com/rfq
INSPECTION
CAPABILITIES
FIRE
ALARM
FIRE
EXTINGUISHER
FIRE ALARM
MONITORING
FIRE
SPRINKLER
FIRE
SUPPRESSION
EXIT
EM/EXIT
LIGHTING
Pre-Action/Deluge Fire Sprinkler System Inspection Report
Location Code: DTJARRG
Contact: Tim Stagner
Contact Address: BLD# 130, EAST MOLLOY ROAD
SYRACUSE, NY 13213
Phone:
Email: timothy.g.stagner.nfg@mail.mil
Property Evaluated: U.S. NEW YORK ANG/HANGAR - 174TH - BLD# 130/131 (Not Specified)
BLD# 130/131, 6001 EAST MOLLOY
ROAD
SYRACUSE, NY 13213
Description: Pre/Del (1Deluge System )
Work Order: SV2103170412/1
Company: Davis Ulmer Sprinkler Co
NYS FIRE ALARM 12000259060,
Expires: 2/22/2022
Address: 7633 Edgecomb Drive Liverpool, NY 13088
Company Phone: 315-451-0971
Inspector: John Manwaring
NOT REQUIRED
Date of Work: 5/5/2021
Frequency: Annual
Tag: Na
Attached Files
Terms and Limitations.pdf 0.2MB NFPA 25 - 2014 PreAction & Deluge.pdf 80.9kB
Deficiency Summary
There are no reported deficiencies for this submission
General Comments
These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
There are no general comments for this submission
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 1 of 8
Davis Ulmer Sprinkler Co 7633 Edgecomb Drive Liverpool, NY 13088 Phone: 315-451-0971
Pre-Action/Deluge Fire Sprinkler System Inspection Report
Tag Na Inspection Frequency: Annual Property Being Evaluated:
U.S. NEW YORK ANG/HANGAR - 174TH - BLD# 130/131 (Not Specified) Owner:
Tim Stagner Owner's Phone Number:
Property Address:
BLD# 130/131, 6001 EAST MOLLOY ROAD, SYRACUSE, NY, 13213
1. General A. (To be filled out by the Owner or Owner's Representative) Has the Owners section been answered on another inspection report that will be submitted with this inspection report? Yes No
Answers to the following questions should be for all fire and life safety systems and not limited to the scope of the present inspection form.
1. Has the occupancy, machinery, or operations remained the same since the last inspection? Yes No
2. Has the system(s) remained in service without modifications or repairs since the last inspection? Yes No
3. If a fire has occurred since the last inspection, have all damaged sprinkler system components been replaced? Yes No N/A
4. Has there been an internal inspection of the piping within the last 5 years? Yes No N/A 4a. Date last checked (Checking is recommended at least every 5 years) 06/2017
5. Have fire pumps had a curve test completed in the past 12 months? Yes No N/A
6. Are gravity, surface, or pressure tanks protected from freezing? Yes No N/A
7. Are any sprinkler heads or other sprinkler system components exposed to harsh conditions (ie.
Corrosive atmospheres, extreme temperatures, etc.) Yes No N/A
8. Do any systems contain low-point drains, excluding wet systems? (Please note - Low point drains should be emptied of condensation on a regular basis) Yes No N/A
9. Does the valve room have adequate heat to maintain a minimum of 40 F? Yes No N/A The above answers are verified as accurate and current by the undersigned Owner or Owner’s Representative for all fire and life safety systems.
Owner Signature
Printed Jeff Chrissley Title Fire Chief Date 5/5/2021 B. (To be answered by the inspector)
a. Is System in service upon arrival? Yes No
b. Was the alarm panel free of alarm and trouble signals upon arrival? (If no, please explain in comments) Yes No N/A
c. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes No
2. Control Valves
a. Do Control Valves appear to be free of damage/leaks? Yes No
b. Are all control valves sealed, secured, or supervised in the open position? Yes No
Control Valves:
No. of Valves: Type: Additional Info:
Easily Accessible?
Signs? Valve in proper position?
Secured? Supervision Operational?
System 1 BFV Yes No Yes No N/A Yes No Yes No
N/A Yes No N/A
Other 1(manual release) BFV Yes No Yes No
N/A Yes No Yes No N/A
Yes No N/A
3. Water Supplies
a. Water Supply Source City Private
Pressure Fire Pump & Tank Pressure Fire Pump & City Pressure Fire Pump & Pond
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 2 of 8
Liverpool, NY 13088 Phone: 315-451-0971
Main Drain Test Pipe Size
Static Pressure Before
Flow Pressure
Static Pressure
After
Test Pipe Location Time to Restore Pressure
Results
System #1 3/4” 75 55 75 Main Drain 5s Pass Fail N/A
4. Tanks, Pumps, Fire Dept. Connections
a. Appears that the F.D.C. is in satisfactory condition, couplings free, caps or plugs in place and check valves tight? Yes No N/A
b. Are fire department connections visible, accessible, and identification sign(s) in place? Yes No N/A
5. Pre-Action and Deluge Systems
a. No. of Pre-Action Systems 1
b. No. of Deluge Systems 0
c. Are the air and priming water pressures adequate? Yes No N/A
d. Does Valve and Trim appear to be free of damage/leaks and in good condition? Yes No N/A
e. Does Valve and Trim appear to be in its appropriate open or closed positions at time of inspection? Yes No N/A
f. Did the supervisory devices operate properly during testing? Yes No N/A
g. Did the deluge or pre-action valves operate properly during testing? Yes No N/A
h. Does the valve operate from the manual trip or remote control station? Yes No N/A
6. Trip Test
System: Make, Model, Size, and Location
Test Type Air (psi) Water (psi) Trip (psi) Trip Time (sec) Water Delivery (sec)
1.5” Reliable H in outside mechanical room
Partial Full N/A 15 75 1s Na Na
7. After Tests
a. Was partial trip test of the Preaction valve conducted with control valve partially opened? Yes No N/A
b. Was a full flow trip test of Preaction valve conducted with control valve opened fully? Yes No N/A
c. Date of last full trip test Unknown
d. Does the air pressure maintained appear to be at proper setting for system? Yes No N/A
e. Have all known drum drip/low point drains been drained and inspected during the inspection? Yes No N/A
8. Alarms
a. Did the water motor(s) and gong(s) test satisfactory? Yes No N/A
b. Did the electric alarm(s) test satisfactory? Yes No N/A
c. Did the supervisory alarms operate during testing? Yes No N/A
d. Was the alarm panel clear of alarm and trouble signals upon departure? (If no, please explain in comments) Yes No N/A
9. Systems, Sprinklers, and Piping (inspected from the ground level)
a. Is the hydraulic design information sign provided, legible, and attached securely to the sprinkler riser? Yes No N/A
b. Do all gauges appear to be in good condition and read within normal range? Yes No N/A
c. Are all of the gauges dated within 5 years or compared to a calibrated gauge? Yes No N/A
d. Does the hand hose valve(s) on the sprinkler system appear to be in satisfactory condition? Yes No N/A
e. Do sprinkler heads generally appear to be free of damage, corrosion, paint, loading and visible obstruction, and appear to be installed in the correct orientation? Yes No N/A
f. Do escutcheons and cover plates for recessed, flush, and concealed sprinklers generally appear to be installed? Yes No N/A
g. Are extra sprinklers heads available on the premises in a head cabinet, along with the appropriate head wrench? Yes No N/A
h. Is a list of the installed sprinkler heads kept in the spare head cabinet? Yes No N/A Make/Model of Heads:
i. Does the exterior condition of fire sprinkler system appear to be satisfactory? Yes No N/A
j. Have all dry heads known to be more than 10 years old been replaced or a sample tested? Yes No N/A
k. Have all QR heads known to be more than 20 years old been replaced or a sample tested? Yes No N/A
l. Have all SR heads known to be more than 50 years old been replaced or a sample tested? Yes No N/A
m. Have all heads known to be more than 75 Years old been replaced or sample tested? Yes No N/A
n. Do all known high-temp and sprinklers subject to harsh conditions appear to be less than 5 years old? Yes No N/A
o. Do all visible pipe supports/hangers and seismic bracing appear to be in good condition? Yes No N/A
10. Observations These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
Please see the summary section at the top of the form for the comments.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 3 of 8
Liverpool, NY 13088 Phone: 315-451-0971
11. Adjustments or Corrections Made:
12. List Changes in the Occupancy Hazard or Fire Protection Equipment, as Advised by the Owner in Section 1A
13. Inspector Information:
Test Verification:
Inspected By John Manwaring Inspector Signature
Inspector License: NOT REQUIRED Date of Work 5/5/2021 Inspection Notes
Pulled manual release to perform trip test
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 4 of 8
Liverpool, NY 13088 Phone: 315-451-0971
SECTION IV - OTHER TERMS AND LIMITATIONS
1. This Agreement is for inspection services only. If Customer wants Company to make any repairs, alterations or replacements as a result of the inspection services performed pursuant to this Agreement, such work and the additional compensation to Company must be specified in a separate written agreement between Company and Customer.
2. Any additional system equipment added to the Property after the date of this Agreement or not otherwise specified in Section II of this Agreement is not included in the inspection services to be provided pursuant to this Agreement. Inclusion of any such other equipment will require execution of an amendment to this agreement and adjustment of the inspection fee.
3. The inspection services provided by Company pursuant to this Agreement are limited to an evaluation of the functionality of the equipment identified in Section II above. Company will not evaluate or express any opinion as to whether the design and/or installation of the system are suitable for the Property or the operations at the Property.
4. Company’s inspection is limited to a visual inspection of external readily accessible parts of the system and will not include every component including but not limited to sprinkler heads, pipe, fittings, hangers, pull stations, smoke detectors, conduit wire or other parts of the system being inspected. Company will only inspect a representative number or sample of the sprinkler heads, pipes, hangers, valves or other devices and equipment in their current position. THEREFORE, BY CONDUCTING ITS INSPECTION UNDER THIS AGREEMENT, COMPANY DOES NOT GUARANTEE OR WARRANT THE CONDITION OR OPERATION OF EVERY PIPE, SPRINKLER HEAD OR OTHER PART OF
THE FIRE PROTECTION AND/OR FIRE ALARM/SECURITY SYSTEM ON THE PROPERTY.
5. AS A MATERIAL INDUCEMENT FOR COMPANY TO PROVIDE THE SERVICES SPECIFIED IN THIS AGREEMENT AT THE INSPECTION FEE QUOTED IN THIS AGREEMENT, CUSTOMER AGREES THAT COMPANY’S LIABILITY TO CUSTOMER AND ALL THIRD PARTIES WITH RESPECT TO ANY CLAIM UNDER THIS AGREEMENT, OR ARISING FROM THE SERVICES FURNISHED BY COMPANY, SHALL BE LIMITED TO THE LESSER OF $1,000.00 OR THE TOTAL CONSIDERATION ACTUALLY RECEIVED BY COMPANY UNDER THIS AGREEMENT. THE FOREGOING LIMITATION SHALL APPLY TO ALL CLAIMS REGARDLESS OF THE NATURE THEREOF, INCLUDING CLAIMS ASSERTED AS A BREACH OF CONTRACT, A BREACH OF WARRANTY, NEGLIGENCE, STRICT LIABILITY OR OTHERWISE. IN NO EVENT SHALL COMPANY BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, SPECIAL, AND INDIRECT OR PUNITIVE DAMAGES, OR DAMAGES FOR LOST PROFITS. If Customer desires Company to accept an increased limit of liability for the services provided under this Agreement, Company will provide an alternate inspection fee quote reflecting such increased limit, provided, however, that the increased limit shall be effective only upon Company’s and Customer’s execution of a replacement agreement confirming the same and Customer’s payment of the alternate fee.
6. Company, following each inspection, will provide to Customer a written “Report of Inspection” (“Report”). If required and/or with prior written authorization, Company will provide copies of the Report to the local or state authority having jurisdiction on behalf of Customer. If requested by Customer, a copy of the Report will also be forwarded to Customer’s insurance company. The Report and recommendations, if any, by Company are only advisory in nature and are intended to assist Customer in reducing the possibility of loss to the Property by indicating obvious defects or impairments to the system(s) which were discovered by Company’s inspection and which should receive prompt attention.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 5 of 8
Liverpool, NY 13088 Phone: 315-451-0971
7. Customer agrees to obtain and shall be solely responsible to maintain property and casualty insurance for the Property, all contents therein, and operations performed within or around the Property. No insurance company, insurer or bonding company or their successors or assigns shall have any right of subrogation or otherwise against Company arising out of this Agreement or the services provided by Company pursuant to this Agreement.
8. Customer agrees to indemnify, defend and hold harmless Company, its agents, and employees from and against any and all claims, demands, suits, liabilities, damages, judgments, losses and expenses (including, without limitation, attorneys’ fees) which may be asserted against or incurred by Company by any third party arising out of or related to this Agreement or the services provided by Company pursuant to this Agreement.
9. Company will make every reasonable effort to prevent the discharge of water into or onto areas of landscaping, decorative pavement, etc., at the Property, however it is Customer’s responsibility to provide sufficient and readily accessible means to accept the full flow of water that may be required by tests as determined by the type of inspection and to take measures to eliminate the formation of ice in any area where a slip and fall hazard could occur.
10. This Agreement may not be assigned by Customer without the written consent of Company.
11. This Agreement may be signed in counterparts; a signed facsimile, photocopy, and/or electronic mail of this Agreement shall be as binding on both parties just as though this Agreement were executed in its original, pre-printed form.
12. This Agreement constitutes the entire Agreement between Company and Customer regarding the subject matter hereof and supersedes all prior agreements and understandings relating thereto. Although Customer for its convenience or in furtherance of its internal procedures may issue to Company a purchase order, order acknowledgement or similar form in connection with the services provided by Company pursuant to this Agreement, no term or condition in any such form that is different from or in addition to the terms set forth in this Agreement shall be applicable, and all such different or additional terms shall be ineffective and void. This Agreement cannot be amended or modified except by a writing signed by Customer and Company.
13. Customer acknowledges Company is relying upon the accuracy of the information regarding Customer and the Property set forth in Sections I of this Agreement. Customer represents that all such information is complete and accurate as of the date on which this Agreement is signed by Customer. Customer will promptly advise Company in writing of any change to such information.
14. Other inclusions, exclusions, or attachments (if any) we exclude fire alarm.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 6 of 8
Liverpool, NY 13088 Phone: 315-451-0971
5.2.1.1.1 Sprinklers shall not show signs of leakage; shall be free of corrosion, foreign materials, paint, and physical damage; and shall be installed in the correct orientation (e.g., upright, pendent, or sidewall).
5.3.1.1.2 Where sprinklers are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, on a 5 year basis, either sprinklers shall be replaced or representative sprinkler samples shall be tested.
5.2.1.1.6 Escutcheons and coverplates for recessed, flush, and concealed sprinklers shall be replaced if found missing during the inspection.
5.2.2.1 Pipe and fittings shall be in good condition and free of mechanical damage, leakage, and corrosion.
5.2.3.2 Hangers and seismic braces that are damaged or loose shall be replaced or refastened.
5.2.6 The hydraulic design information sign for hydraulically designed systems shall be inspected quarterly to verify that it is attached securely to the sprinkler riser and is legible.
5.3.1.1.1 Where sprinklers have been in service for 50 years, they shall be replaced or representative samples from one or more sample areas shall be tested.
5.3.1.1.1.3 Sprinklers manufactured using fast response elements that have been in service for 20 years shall be replaced, or representative samples shall be tested and then retested at 10 year
5.3.1.1.1.6 Dry sprinklers that have been in service for 10 years shall be replaced or representative samples shall be tested and then retested at 10 year intervals.
5.3.2.1 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.
5.3.2.2 Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced.
5.4.1.5.4 The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: (1) For protected facilities having under 300 sprinklers — no fewer than 6 sprinklers
(2) For protected facilities having 300 to 1000 sprinklers — no fewer than 12 sprinklers (3) For protected facilities having over 1000 sprinklers — no fewer than 24 sprinklers
5.4.1.5.5 One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system.
5.4.1.5.6 A list of the sprinklers installed in the property shall be posted in the sprinkler cabinet.
13.2.6.1 Mechanical waterflow devices, including but not limited to water motor gongs, shall be tested quarterly.
13.2.6.2 Vane type and pressure switch–type waterflow devices shall be tested semiannually.
13.3.2.2 Valves should be kept free of snow, ice, storage, or other obstructions so that access is ensured.
13.3.3.5.2 A distinctive signal shall indicate movement from the valve's normal position during either the first two revolutions of a hand wheel or when the stem of the valve has moved one fifth of the distance from it's normal position.
13.4.3.1.4 The gauge monitoring the preaction system supervisory air pressure, if provided, shall be inspected monthly to verify that it indicates that normal pressure is being maintained.
13.4.3.1.6 The preaction or deluge valve shall be externally inspected monthly to verify the following:
13.4.3.1.6, 1 The valve is free from physical damage.
NFPA 25 2014 Preaction/Deluge
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 7 of 8
Liverpool, NY 13088 Phone: 315-451-0971
13.4.3.1.6, 2 All trim valves are in the appropriate open or closed position.
13.4.3.1.6, 3 The valve seat is not leaking.
13.4.3.1.6, 4 Electrical components are in service.
13.4.3.2.1 The priming water level in supervised preaction systems shall be tested quarterly for compliance with the manufacturer's instructions.
13.4.3.2.2 Each deluge valve shall be trip tested annually at full flow in warm weather and in accordance with the manufacturer’s instructions.
13.4.3.2.2.1 Full flow tests shal incorporate full functionality of the system as a unit, including automatic and manual activation.
13.4.3.2.4 During those years when full flow testing in accordance with 13.4.3.2.3 is not required, the preaction valve shall be trip tested with the control valve partially open.
13.4.3.3.3 Auxiliary drains in preaction or deluge systems shall be operated after each system operation and before the onset of freezing conditions (and thereafter as needed).
13.5.6.1, 1 Hose caps are in place and not damaged.
13.5.6.1, 2 Hose threads are not damaged.
13.5.6.1, 3 Valve handles are present and not damaged.
13.5.6.1, 4 Gaskets are not damaged or showing signs of deterioration.
13.5.6.1, 5 No leaks are present.
13.5.6.1, 6 Valves are not obstructed or otherwise not capable of normal operation.
13.7.1 Fire department connections shall be inspected quarterly to verify the following:
13.7.1, 1 The fire department connections are visible and accessible.
13.7.1, 2 Couplings or swivels are not damaged and rotate smoothly.
13.7.1, 3 Plugs or caps are in place and undamaged.
13.7.1, 4 Gaskets are in place and in good condition.
13.7.1, 5 Identification signs are in place.
13.7.1, 6 The check valve is not leaking.
13.7.1, 7 The automatic drain valve is in place and operating properly.
13.7.1, 8 The fire department connection clapper(s) is in place and operating properly.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 8 of 8