18.2 B130_131 Annual Fire Suppression Inspection(05 May 22).pdf
PDF 354 KB Posted
- Attached to
- 174 CES Fire Alarm Panel Replacement Federal contract opportunity
- Solicitation number
- W50S8N-22-Q-0019
- Issued by
- Department of the Army National Guard
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SOW_HAAW222009 Repair FA Bldg 130_131_FINAL.docx | DOCX document | |
| 18.4 B130_131 Annual Fire Alarm Inspection (05 May 22).pdf | ||
| 18.3 B130_131 Annual FS Inspection PreDel Supplement (05 May 22).pdf | ||
| 18.1 B130_131 Annual FA Supplement(05 May 22).pdf | ||
| WD - SAM.gov.pdf | ||
| Fire Panel Combined Synopsitation.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION
OUR BUSINESS IS
PROTECTING YOURS
CONTACT US TODAY FOR A QUOTE
Phone: 315-451-0971
Online: davisulmer.com/rfq
INSPECTION
CAPABILITIES
FIRE
ALARM
FIRE
EXTINGUISHER
FIRE ALARM
MONITORING
FIRE
SPRINKLER
FIRE
SUPPRESSION
EXIT
EM/EXIT
LIGHTING
Wet Fire Sprinkler System Inspection Report
Location Code: DTJARRG
Contact: Tim Stagner
Contact Address: BLD# 130, EAST MOLLOY ROAD
SYRACUSE, NY 13213
Phone:
Email: timothy.g.stagner.nfg@mail.mil
Property Evaluated: U.S. NEW YORK ANG/HANGAR - 174TH - BLD# 130/131 (Not Specified)
BLD# 130/131, 6001 EAST MOLLOY
ROAD
SYRACUSE, NY 13213
Description: Wet (2- WET SYSTEMS)
Work Order: SV2103170412/1
Company: Davis Ulmer Sprinkler Co
NYS FIRE ALARM 12000259060,
Expires: 2/22/2022
Address: 7633 Edgecomb Drive Liverpool, NY 13088
Company Phone: 315-451-0971
Inspector: John Manwaring
NOT REQUIRED
Date of Work: 5/5/2021
Frequency: Annual
Tag: Na
Attached Files
Terms and Limitations.pdf 0.2MB NFPA 25 - 2014 WET SYSTEM.pdf 0.1MB
Deficiency Summary
There are no reported deficiencies for this submission
General Comments
These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
There are no general comments for this submission
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 1 of 13
Davis Ulmer Sprinkler Co 7633 Edgecomb Drive Liverpool, NY 13088 Phone: 315-451-0971
Wet Fire Sprinkler System Inspection Report
Tag Na Inspection Frequency: Annual Property Being Evaluated:
U.S. NEW YORK ANG/HANGAR - 174TH - BLD# 130/131 (Not Specified) Owner:
Tim Stagner Owner's Phone Number:
Property Address:
BLD# 130/131, 6001 EAST MOLLOY ROAD, SYRACUSE, NY, 13213
1. General A. (To be filled out by the Owner or Owner's Representative) Has the Owners section been answered on another inspection report that will be submitted with this inspection report? Yes No
Answers to the following questions should be for all fire and life safety systems and not limited to the scope of the present inspection form.
1. Has the occupancy, machinery, or operations remained the same since the last inspection? Yes No
2. Has the system(s) remained in service without modifications or repairs since the last inspection? Yes No
3. If a fire has occurred since the last inspection, have all damaged sprinkler system components been replaced? Yes No N/A
4. Has there been an internal inspection of the piping within the last 5 years? Yes No N/A 4a. Date last checked (Checking is recommended at least every 5 years) 5/2017
5. Have fire pumps had a curve test completed in the past 12 months? Yes No N/A
6. Are gravity, surface, or pressure tanks protected from freezing? Yes No N/A
7. Are any sprinkler heads or other sprinkler system components exposed to harsh conditions (ie.
Corrosive atmospheres, extreme temperatures, etc.) Yes No N/A
8. Do any systems contain low-point drains, excluding wet systems? (Please note - Low point drains should be emptied of condensation on a regular basis) Yes No N/A
9. Does the valve room have adequate heat to maintain a minimum of 40 F? Yes No N/A The above answers are verified as accurate and current by the undersigned Owner or Owner’s Representative for all fire and life safety systems.
Owner Signature
Printed Jeff Chrissley Title Fire Chief Date 5/5/2021 B. (To be answered by the inspector)
a. Is System in service upon arrival? Yes No
b. Was the alarm panel free of alarm and trouble signals upon arrival? (If no, please explain in comments) Yes No N/A
c. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes No N/A
d. Does it appear that visible exterior openings are protected against the entrance of cold air? Yes No N/A
2. Control Valves
a. Do Control Valves appear to be free of damage/leaks? Yes No
b. Are all control valves sealed, secured, or supervised in the open position? Yes No
Control Valves:
No. of Valves: Type: Additional Info:
Easily Accessible?
Signs? Valve in proper position?
Secured? Supervision Operational?
Backflow 2 OS&Y Yes No Yes No N/A Yes No Yes No
N/A Yes No N/A
Backflow 2- (131) BFV Yes No Yes No N/A Yes No Yes No
N/A Yes No N/A
City Connection 2 PIV Yes No Yes No
N/A Yes No Yes No N/A
Yes No N/A
3. Water Supplies
a. Water Supply Source City Private
Pressure Fire Pump & Tank Pressure Fire Pump & City Pressure Fire Pump & Pond
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 2 of 13
Liverpool, NY 13088 Phone: 315-451-0971
Main Drain Test Pipe Size
Static Pressure Before
Flow Pressure
Static Pressure
After
Test Pipe Location Time to Restore Pressure
Results
Bldg 130 2" 80 50 80 Sprinkler Room 5s Pass Fail N/A
Bldg 131 2" 75 50 75 Outside Sprinkler Room 5s Pass Fail N/A
4. Tanks, Pumps, Fire Dept. Connections
a. Appears that the F.D.C. is in satisfactory condition, couplings free, caps or plugs in place and check valves tight? Yes No N/A
b. Are fire department connections visible, accessible, and identification sign(s) in place? Yes No N/A
c. Do fire pumps, gravity, surface and pressure tanks appear to be in good external condition and properly maintained? Yes No N/A
5. Wet Systems
System # Make Model Size (inches) Location/Description
130 Viking J-1 6" Sprinkler Room
131 Direct Feed N/A 4" Outside Sprinkler Room
a. Do Valve and Trim appear to be free of damage/leaks and in good condition? Yes No N/A
d. Is the Hydraulic Name Plate, if required, securely attached and legible? Yes No N/A
e. Are all known and accessible cold weather valves in the appropriate open or closed position? Yes No N/A
f. Are there anti-freeze system(s) at this location? Yes No N/A
6. Alarms
a. Did the water motor gong operate during testing? Yes No N/A
b. Did the electric alarms operate during testing? Yes No N/A
c. Did alarms activate within appropriate time? Yes No N/A
System Time
Bldg 130 Pressure Switch 3s
Bldg 131 Flow Switch 37s
d. Did the supervisory alarms operate during testing? Yes No N/A
e. Was the alarm panel clear of alarm and trouble signals upon departure? (If no, please explain in comments) Yes No N/A
7. Systems, Sprinklers, and Piping (Inspected at the ground level)
a. Do all gauges appear to be in good condition and read within normal range? Yes No N/A
b. Are all of the gauges dated within 5 years or compared to a calibrated gauge? Yes No N/A
c. Do sprinkler heads generally appear to be free of damage, corrosion, paint, loading and visible obstruction, and appear to be installed in the correct orientation? Yes No N/A
d. Do escutcheons and cover plates for recessed, flush, and concealed sprinklers generally appear to be installed? Yes No N/A
e. Are extra sprinklers heads available on the premises in a head cabinet, along with the appropriate head wrench? Yes No N/A
f. Is a list of the installed sprinkler heads kept in the spare head cabinet? Yes No N/A Make/Model of Heads:
g. Does the exterior condition of fire sprinkler system appear to be satisfactory? Yes No N/A
h. Have all dry heads known to be more than 10 years old been replaced or a sample tested? Yes No N/A
i. Have all QR heads known to be more than 20 years old been replaced or a sample tested? Yes No N/A
j. Have all SR heads known to be more than 50 years old been replaced or a sample tested? Yes No N/A
k. Have all heads known to be more than 75 Years old been replaced or sample tested? Yes No N/A
l. Do all known high-temp and sprinklers subject to harsh conditions appear to be less than 5 years old? Yes No N/A
m. Does the hand hose valve(s) on the sprinkler system appear to be in satisfactory condition? Yes No N/A
n. Do all visible pipe supports/hangers and seismic bracing appear to be in good condition? Yes No N/A
8. Observations These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
Please see the summary section at the top of the form for the comments.
9. Adjustments or Corrections Made:
10. List Changes in the Occupancy Hazard or Fire Protection Equipment, as Advised by the Owner in Section 1A
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 3 of 13
Liverpool, NY 13088 Phone: 315-451-0971
11. Inspector Information:
Test Verification:
Inspected By John Manwaring Inspector Signature
Inspector License: NOT REQUIRED Date of Work 5/5/2021 Inspection Notes
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 4 of 13
Liverpool, NY 13088 Phone: 315-451-0971
SECTION IV - OTHER TERMS AND LIMITATIONS
1. This Agreement is for inspection services only. If Customer wants Company to make any repairs, alterations or replacements as a result of the inspection services performed pursuant to this Agreement, such work and the additional compensation to Company must be specified in a separate written agreement between Company and Customer.
2. Any additional system equipment added to the Property after the date of this Agreement or not otherwise specified in Section II of this Agreement is not included in the inspection services to be provided pursuant to this Agreement. Inclusion of any such other equipment will require execution of an amendment to this agreement and adjustment of the inspection fee.
3. The inspection services provided by Company pursuant to this Agreement are limited to an evaluation of the functionality of the equipment identified in Section II above. Company will not evaluate or express any opinion as to whether the design and/or installation of the system are suitable for the Property or the operations at the Property.
4. Company’s inspection is limited to a visual inspection of external readily accessible parts of the system and will not include every component including but not limited to sprinkler heads, pipe, fittings, hangers, pull stations, smoke detectors, conduit wire or other parts of the system being inspected. Company will only inspect a representative number or sample of the sprinkler heads, pipes, hangers, valves or other devices and equipment in their current position. THEREFORE, BY CONDUCTING ITS INSPECTION UNDER THIS AGREEMENT, COMPANY DOES NOT GUARANTEE OR WARRANT THE CONDITION OR OPERATION OF EVERY PIPE, SPRINKLER HEAD OR OTHER PART OF
THE FIRE PROTECTION AND/OR FIRE ALARM/SECURITY SYSTEM ON THE PROPERTY.
5. AS A MATERIAL INDUCEMENT FOR COMPANY TO PROVIDE THE SERVICES SPECIFIED IN THIS AGREEMENT AT THE INSPECTION FEE QUOTED IN THIS AGREEMENT, CUSTOMER AGREES THAT COMPANY’S LIABILITY TO CUSTOMER AND ALL THIRD PARTIES WITH RESPECT TO ANY CLAIM UNDER THIS AGREEMENT, OR ARISING FROM THE SERVICES FURNISHED BY COMPANY, SHALL BE LIMITED TO THE LESSER OF $1,000.00 OR THE TOTAL CONSIDERATION ACTUALLY RECEIVED BY COMPANY UNDER THIS AGREEMENT. THE FOREGOING LIMITATION SHALL APPLY TO ALL CLAIMS REGARDLESS OF THE NATURE THEREOF, INCLUDING CLAIMS ASSERTED AS A BREACH OF CONTRACT, A BREACH OF WARRANTY, NEGLIGENCE, STRICT LIABILITY OR OTHERWISE. IN NO EVENT SHALL COMPANY BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, SPECIAL, AND INDIRECT OR PUNITIVE DAMAGES, OR DAMAGES FOR LOST PROFITS. If Customer desires Company to accept an increased limit of liability for the services provided under this Agreement, Company will provide an alternate inspection fee quote reflecting such increased limit, provided, however, that the increased limit shall be effective only upon Company’s and Customer’s execution of a replacement agreement confirming the same and Customer’s payment of the alternate fee.
6. Company, following each inspection, will provide to Customer a written “Report of Inspection” (“Report”). If required and/or with prior written authorization, Company will provide copies of the Report to the local or state authority having jurisdiction on behalf of Customer. If requested by Customer, a copy of the Report will also be forwarded to Customer’s insurance company. The Report and recommendations, if any, by Company are only advisory in nature and are intended to assist Customer in reducing the possibility of loss to the Property by indicating obvious defects or impairments to the system(s) which were discovered by Company’s inspection and which should receive prompt attention.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 5 of 13
Liverpool, NY 13088 Phone: 315-451-0971
7. Customer agrees to obtain and shall be solely responsible to maintain property and casualty insurance for the Property, all contents therein, and operations performed within or around the Property. No insurance company, insurer or bonding company or their successors or assigns shall have any right of subrogation or otherwise against Company arising out of this Agreement or the services provided by Company pursuant to this Agreement.
8. Customer agrees to indemnify, defend and hold harmless Company, its agents, and employees from and against any and all claims, demands, suits, liabilities, damages, judgments, losses and expenses (including, without limitation, attorneys’ fees) which may be asserted against or incurred by Company by any third party arising out of or related to this Agreement or the services provided by Company pursuant to this Agreement.
9. Company will make every reasonable effort to prevent the discharge of water into or onto areas of landscaping, decorative pavement, etc., at the Property, however it is Customer’s responsibility to provide sufficient and readily accessible means to accept the full flow of water that may be required by tests as determined by the type of inspection and to take measures to eliminate the formation of ice in any area where a slip and fall hazard could occur.
10. This Agreement may not be assigned by Customer without the written consent of Company.
11. This Agreement may be signed in counterparts; a signed facsimile, photocopy, and/or electronic mail of this Agreement shall be as binding on both parties just as though this Agreement were executed in its original, pre-printed form.
12. This Agreement constitutes the entire Agreement between Company and Customer regarding the subject matter hereof and supersedes all prior agreements and understandings relating thereto. Although Customer for its convenience or in furtherance of its internal procedures may issue to Company a purchase order, order acknowledgement or similar form in connection with the services provided by Company pursuant to this Agreement, no term or condition in any such form that is different from or in addition to the terms set forth in this Agreement shall be applicable, and all such different or additional terms shall be ineffective and void. This Agreement cannot be amended or modified except by a writing signed by Customer and Company.
13. Customer acknowledges Company is relying upon the accuracy of the information regarding Customer and the Property set forth in Sections I of this Agreement. Customer represents that all such information is complete and accurate as of the date on which this Agreement is signed by Customer. Customer will promptly advise Company in writing of any change to such information.
14. Other inclusions, exclusions, or attachments (if any) we exclude fire alarm.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 6 of 13
NFPA 25-2014 WET SYSTEM
3.3.23 Inspection. A visual examination of a system or portion thereof to verify that it appears to be in operating condition and is free of physical damage.
4.1.2 Freeze Protection. The property owner or designated representative shall ensure that water-approved antifreeze solution is utilized.
4.1.2.1 All areas of the building containing water-filled piping that does not have another means
4.1.2.2 Aboveground water-filled pipes that pass through open areas, cold rooms, against freezing by insulating coverings, frost proof casings, listed heat tracing
5.2.1.1 Sprinklers shall be inspected from the floor level annually.
5.2.1.1.1 Sprinklers shall not show signs of leakage; shall be free of corrosion, foreign materials, paint, and physical damage; and shall be installed in the correct up-right,
5.2.1.1.2 Any sprinkler that shows signs of any of the following shall be replaced:
5.2.1.1.2, 1 Leakage
5.2.1.1.2, 2
5.2.1.1.2, 3 Physical damage
5.2.1.1.2, 4 Loss of fluid in the glass bulb heat-responsive element
5.2.1.1.2, 5 Loading
5.2.1.1.2, 6 Painting unless painted by the sprinkler manufacturer
5.2.1.1.3 Any sprinkler that has been installed in the incorrect orientation shall be corrected by repositioning the branch line, drop, or sprig, or shall be replaced.
5.2.1.1.6 Escutcheons and cover plates for recessed, flush, and concealed sprinklers shall be replaced if found missing during the inspection.
5.2.1.1.7 Escutcheons for pendent sprinklers that are not recessed, flush, or concealed shall not be required to be replaced if found missing during the inspection.
5.2.1.2 The minimum clearance to storage as described in 5.2.1.2.1 through 5.2.1.2.6 shall be maintained below all sprinkler deflectors.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 7 of 13
5.2.1.2.1 Unless greater distances are required by 5.2.1.2.2, 5.2.1.2.3, or 5.2.1.2.4, or lesser distances are permitted by 5.2.1.2.6, clearance between the deflector and the top
5.2.1.2.2 Where standards other than NFPA 13, Standard for the Installation of Sprinkler
Systems, specify greater clearance to storage minimums, they shall be followed.
5.2.1.2.3 greater for special sprinklers.
5.2.1.2.4 or greater where rubber tires are stored.
5.2.1.2.5 In-rack sprinklers shall not be required to meet the obstruction criteria and clearance from storage requirements.
5.2.1.2.6 to be permitted by the installation standard.
5.2.1.3 Storage closer to the sprinkler deflector than permitted by the clearance rules of the installation standard described in 5.2.1.2.1 through 5.2.1.2.4 shall be corrected.
5.2.1.4 The supply of spare sprinklers shall be inspected annually for the following:
5.2.1.4, 1 The correct number and type of sprinklers as required by 5.4.1.5
5.2.1.4, 2 A sprinkler wrench for each type of sprinkler as required by 5.4.1.5.5
5.2.1.4, 3 The list of spare sprinklers as required by 5.4.1.5.6
5.2.3 Hangers and Seismic Braces. Sprinkler pipe hangers and seismic braces shall be inspected annually from the floor level.
5.2.3.1 Hangers and seismic braces shall not be damaged, loose, or unattached.
5.2.3.2 Hangers and seismic braces that are damaged, loose, or unattached shall be replaced or refastened.
5.2.3.3 Hangers and seismic braces installed in concealed spaces such as above suspended ceilings shall not require inspection.
5.2.3.4 Hangers and seismic bracing installed in areas that are inaccessible for safety considerations due to process operations shall be inspected during each scheduled shutdown.
5.2.4.1 Gauges on wet pipe and deluge sprinkler systems shall be inspected quarterly to ensure that they are in good condition and that normal water supply pressure is being maintained.
5.2.6 Hydraulic Design Information Sign. The hydraulic design information sign shall be inspected quarterly to verify that it is provided, attached securely to the sprinkler riser, and is legible.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 8 of 13
5.2.6.1 A hydraulic design information sign that is missing or illegible shall be replaced.
5.2.6.2 A pipe schedule system shall have a hydraulic design information sign that reads “Pipe Schedule System.”
5.3.1.1 Where required by this section, sample sprinklers shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing.
5.3.1.1.1 Where sprinklers have been in service for 50 years, they shall be replaced or representative samples from one or more sample areas shall be tested.
5.3.1.1.1.1 Test procedures shall be repeated at 10-year intervals.
5.3.1.1.1.3 Sprinklers manufactured using fast-response elements that have been in service for
20 years shall be replaced or representative samples shall be tested and then retested at 10-year intervals.
5.3.1.1.1.4 Representative samples of solder-type sprinklers with a temperature classification of extra high [325°F or greater that are exposed to semi continuous to continuous maximum allowable ambient temperature conditions shall be tested at 5-year intervals.
5.3.1.1.1.6 Dry sprinklers that have been in service for 10 years shall be replaced or representative samples shall be tested and then retested at 10-year intervals.
5.3.1.1.2 Where sprinklers are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, on a 5-year basis, either sprinklers shall be replaced or representative sprinkler samples shall be tested.
5.3.2.1 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.
5.3.2.2 Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced.
5.3.3.1 Mechanical waterflow alarm devices including, but not limited to, water motor gongs, shall be tested quarterly.
5.3.3.2 Vane-type and pressure switch–type waterflow alarm devices shall be tested semiannually.
5.3.3.3 Testing waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector’s test connection.
5.3.3.3.1 Where freezing weather conditions or other circumstances prohibit use of the inspector’s test connection, the bypass connection shall be permitted to be used.
5.4.1.4 A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 9 of 13
5.4.1.5.1 The sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property.
5.4.1.5.2 The sprinklers shall be kept in a cabinet located where the temperature in which they are subjected will at no time exceed 100
5.4.1.5.3 Where dry sprinklers of different lengths are installed, spare dry sprinklers shall not be required, provided that a means of returning the system to service is furnished.
5.4.1.5.4 The stock of spare sprinklers shall include all types and ratings installed and shall be as follows:
5.4.1.5.4, 1 For protected facilities having under 300 sprinklers – no fewer than 6 sprinklers.
5.4.1.5.4, 2 For protected facilities having 300 to 1000 sprinklers – no fewer than 12 sprinklers.
5.4.1.5.4, 3 For protected facilities having over 1000 sprinklers – no fewer than 24 sprinklers.
5.4.1.5.5 One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system.
5.4.1.5.6 A list of the sprinklers installed in the property shall be posted in the sprinkler cabinet.
5.4.1.5.6.1 The list shall include the following:
5.4.1.5.6.1, 1 ipped; or the manufacturer, model, orifice, deflector type, thermal sensitivity, and pressure rating.
5.4.1.5.6.1, 2 General description
5.4.1.5.6.1, 3 Quantity of each time to be contained in the cabinet
5.4.1.5.6.1, 4 Issue or revision date of the list
The purpose of inspection shall be to verify that the pump assembly appears to be in operating condition and is free from physical damage.
The exterior of the tank, supporting structure, vents, foundation, and catwalks or ladders, where provided, shall be inspected quarterly for signs of obvious damage or weakening.
13.2.5 Main Drain Test. A main drain test shall be conducted annually at each water supply lead-in to a building water-based fire protection system to deter-mine whether there has been a change in the condition of the water supply.
13.2.5.1 Where the lead-in to a building supplies a header or manifold serving multiple systems, a single main drain test shall be permitted.
13.2.5.2 In systems where the sole water supply is through a backflow preventer and/or pressure-reducing valves, the main drain test of at least one system downstream of the device shall be conducted on a quarterly basis.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 10 of 13
13.2.5.3 When there is a 10 percent reduction in full flow pressure when compared to the original acceptance test or previously performed tests, the cause of the reduction shall be identified and corrected if necessary.
13.3.1 Each control valve shall be identified and have a sign indicating the system or portion of the system it controls.
13.3.1.1 Systems that have more than one control valve that
must be closed to work on a system shall have a sign on each affected valve referring to the existence and location of other valves.
13.3.1.3 Each normally open valve shall be secured by means
of a seal or a lock or shall be electrically supervised in accordance with the applicable NFPA standards.
13.3.1.4 Normally closed valves shall be secured by means of a seal or shall be electrically supervised in accordance with the applicable NFPA standard.
13.3.2.2 The valve inspection shall verify that the valves are in the following condition:
13.3.2.2, 1 In the normal open or closed position
13.3.2.2, 2 Sealed, locked, or supervised
13.3.2.2, 3 Accessible
13.3.2.2, 4 P rovided with correct wrenches
13.3.2.2, 5 Free from external leaks
13.3.2.2, 6 Provided with applicable identification
13.3.3.5.1 Valve supervisory switches shall be tested semiannually.
13.3.3.5.2 A distinctive signal shall indicate movement from the valve’s normal position during either the first two revolutions of a hand wheel or when the stem of the valve has moved one-fifth of the distance from its normal position.
13.3.3.5.3 The signal shall not be restored at any valve position except the normal position.
13.4.1.1 Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following:
13.4.1.1, 1 The gauges indicate normal supply water pressure is being maintained.
13.4.1.1, 2 The valve is free of physical damage.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 11 of 13
13.4.1.1, 3 All valves are in the appropriate open or closed position.
13.4.1.1, 4 The retarding chamber or alarm drains are not leaking.
13.5.6.1.1 Hose valves shall be inspected quarterly to verify that the valves are in the following condition:
13.5.6.1.1, 1 Hose caps are in place and not damaged.
13.5.6.1.1, 2 Hose threads are not damaged.
13.5.6.1.1, 3 Valve handles are present and not damaged.
13.5.6.1.1, 4 Gaskets are not damaged or showing signs of deterioration.
13.5.6.1.1, 5 No leaks are present.
13.5.6.1.1, 6 Valves are not obstructed or otherwise not capable of normal operation.
13.5.6.1.2 Hose valves shall be inspected to ensure that hose caps are in place and not damaged.
13.5.6.1.3 Hose threads shall be inspected for damage.
13.5.6.1.4 Valve handles shall be present and not damaged.
13.5.6.1.5 Gaskets shall be inspected for damage or deterioration.
13.5.6.1.6 Hose valves shall be inspected for leaks.
13.5.6.1.7 Hose valves shall be inspected to ensure no obstructions are present.
Hose valves shall be inspected to ensure that restricting devices are present.
13.7.1 Fire department connections shall be inspected quarterly to verify the following:
13.7.1, 1 The fire department connections are visible and accessible.
13.7.1, 2 or swivels are not damaged and rotate smoothly.
13.7.1, 3 Plugs or caps are in place and undamaged.
13.7.1, 4 Gaskets are in place and in good condition.
13.7.1, 5 Identification signs are in place.
13.7.1, 6 The check valve is not leaking.
13.7.1, 7 The automatic drain valve is in place and operating properly.
The fire department connection is in place and operating properly.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 12 of 13
Interior of the connection is inspected for obstructions.
13.7.2 manufacturer’s instructions.
13.7.3 Any obstructions that are present shall be removed.
Davis Ulmer Sprinkler Co, 7633 Edgecomb Drive, Liverpool, NY, 13088 Phone: 315-451-0971 Page 13 of 13