17820 Plans.pdf
PDF 8 MB Posted
- Solicitation number
- S-29100-00017820
- Issued by
- Oregon
About this file
This is a plans document related to the Snake River Correctional Institution Complex One Water Heater Replacement project in Oregon. The document appears to contain technical specifications and design drawings for the replacement of water heating equipment at the correctional facility. The project involves the removal and replacement of existing water heater units to improve facility infrastructure and operational efficiency. Specific quantities, response deadlines, site visit schedules, and bidder meeting information would be detailed in the associated bid solicitation documents rather than in the plans themselves.
The plans document serves as the technical reference material for contractors preparing bids on this rebid opportunity. Pricing, set-aside provisions, funding sources, and contractual terms would be established in the main solicitation documentation. Contractors should review these plans in conjunction with the bid documents to understand the full scope of work, material specifications, installation requirements, and any performance standards applicable to the water heater replacement project at this Oregon Department of Corrections facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 17820 ITB GTC SC.pdf | ||
| 17820 Addenda 1.pdf | ||
| 17820 Scope Specs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
25107
A
M E
C H
A N
I C
L
C
O N
S U
L T
I N
G
F I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
SNAKE RIVER CORRECTIONAL INSTITUTE (SRCI)
OREGON DEPARTMENT OF CORRECTIONS
777 STANTON BLVD, ONTARIO, OREGON 97914
INMATE HOUSING - COMPLEX #1 BUILDINGS A, B AND C
HOT WATER HEATER REPLACEMENT
SRCI
SCOPE OF WORK
G1.0
C O
VE
R
S H
EE
T
AN
D
G
EN
ER
AL
IN
FO
R M
AT
IO
N
GENERAL SCOPE
1. The six each roof mounted hot water heaters at Inmate Housing Complex #1 at Buildings A, B, and C on the SRCI campus are desired to be replaced. Existing hot water heaters are 80% efficient and include a 250 gallon storage tank with 400 MBH gas fired power burner with fire tube heaters inside the storage tank.
2. Hot water heaters are desired to be replaced with larger hot water heaters with 800 MBH of gas heating with 250 gallons of storage.
3. Weight of new hot water heater weights are equivalent to the existing hot water heater weights. No structural upgrades are anticipated for the one for one replacement of hot water heaters on the roof.
4. New tempering valves are desired to be added to the project to maintain 105°F to 110°F tempered water supply to all showers and lavatories.
5. The entire scope on this project is responsible of the Contractor.
6. All hot water heater controls shall be provided and installed by the Contractor.
7. Heat tracing of all domestic cold water and hot water supply lines above roof is desired to be added to this project.
8. Hot water heater shall be equipped with a BACnet controller
9. Shut down of domestic water systems is required for this hot water heater replacement project. Contractor shall coordinate with SRCI on shut down requirements with SRCI.
10. Fully integrate all devices into building automation system for monitoring and control.
BUILDING C
BUILDING B
BUILDING A
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
NORTH
AutoCAD SHX Text ARCHITECTURAL G1.0 COVER SHEET AND GENERAL INFORMATION COVER SHEET AND GENERAL INFORMATION PLUMBING P1.0 PLUMBING COVER SHEET PLUMBING COVER SHEET P1.1 ENLARGED SITE PLAN ENLARGED SITE PLAN P2.1 PLUMBING PLAN - BLDG A PLUMBING PLAN - BLDG A P2.2 PLUMBING PLAN - BLDG B PLUMBING PLAN - BLDG B P2.3 PLUMBING PLAN - BLDG C PLUMBING PLAN - BLDG C P3.1 HOT WATER HEATER TANK AND BURNER - DEMOLITION SCHEMATIC HOT WATER HEATER TANK AND BURNER - DEMOLITION SCHEMATIC P4.1 HOT WATER HEATER TANK AND BURNER - NEW SCHEMATIC HOT WATER HEATER TANK AND BURNER - NEW SCHEMATIC P5.1 CONTROLS SCHEMATIC - CONFIGURATION 1 CONTROLS SCHEMATIC - CONFIGURATION 1 P5.2 CONTROLS SCHEMATIC - CONFIGURATION 2 CONTROLS SCHEMATIC - CONFIGURATION 2 ELECTRIC E0.0 ELECTRICAL SYMBOLS AND SHEET INDEX ELECTRICAL SYMBOLS AND SHEET INDEX E2.0D BUILDING 'A' ELECTRICAL DEMOLITION PLAN BUILDING 'A' ELECTRICAL DEMOLITION PLAN E2.0E BUILDING 'A' ELECTRICAL PLAN BUILDING 'A' ELECTRICAL PLAN E2.1D BUILDING 'B' ELECTRICAL DEMOLITION PLAN BUILDING 'B' ELECTRICAL DEMOLITION PLAN E2.1E BUILDING 'B' ELECTRICAL PLAN BUILDING 'B' ELECTRICAL PLAN E2.2D BUILDING 'C' ELECTRICAL DEMOLITION PLAN BUILDING 'C' ELECTRICAL DEMOLITION PLAN E2.2E BUILDING 'C' ELECTRICAL PLAN BUILDING 'C' ELECTRICAL PLAN E3.0 ONE LINE DIAGRAM ONE LINE DIAGRAM E3.1 ELECTRICAL SCHEDULESELECTRICAL SCHEDULES
AutoCAD SHX Text
BUILDING DATA INFORMATION:
AutoCAD SHX Text THERE IS NO CHANGE IN USE OR OCCUPANCY FOR THIS MECHANICAL EQUIPMENT UPGRADE PROJECT
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
BUILDING DATA
AutoCAD SHX Text
DRAWING INDEX
AutoCAD SHX Text
SITE PLAN
AutoCAD SHX Text
DISCIPLINE INDEX
AutoCAD SHX Text
DISCIPLINES P PLUMBING PLUMBING E ELECTRICAL ELECTRICAL
AutoCAD SHX Text
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P1.0
PL
U
M
BI
N G
C O
VE
R
S H
EE
T
PLUMBING LEGEND
CW
HW
HWR
NP
C
G
MPG
P- #
GW
X
X
PLUMBING ABBREVIATIONS
TW
DOMESTIC HOT WATER HEATER SCHEDULE - EXISTING
NO. TYPE MANUFACTURER
GPH
RECOVERYEWT LWT
NORMAL
OPERATING
PRESSURE
HWH
BOILER
RELIEF
PRESSURE
INPUT MBH OUTPUT MBH EFF TYPE SHIPPING
WEIGHT STORAGE
(1ST HOUR)
GPH
RECOVERY
(CONTINUOUS)
DOMESTIC HOT WATER HEATER SCHEDULE
NO. TYPE MANUFACTURER
GPH
RECOVERYEWT LWT
NORMAL
OPERATING
PRESSURE
HWH
BOILER
RELIEF
PRESSURE
INPUT MBH OUTPUT MBH EFF TYPE SHIPPING
WEIGHT STORAGE
(1ST HOUR)
GPH
RECOVERY
(CONTINUOUS)
HW
HWR
CW
TW TW
TWTW
SCALE:
A
P1.0
TEMPERING VALVE REPLACEMENT
NTS
KEY NOTES:
EXISTING THERMOSTATIC MIXING VALVE SHALL BE REPLACED WITH DIGITALLY
CONTROLLED MIXING VALVE. VALVE IS A 'POWERS' INTELLISTATION 2 -
DIGITAL WATER MIXING VALVE MODEL IS2075VL WITH THE FOLLOWING
CHARACTERISTICS:
· 3/4" COLD WATER AND HOT WATER INLET
· 1" TEMPERED WATER OUTLET
· CV 17.3
· 54.8 GPM AT 10PSIG PRESSURE DROP
· 3 GPM MINIMUM FLOW RATE
· BACNET CONTROL INTERFACE
· 120/240 POWER SUPPLY
· VALVE TO FAIL IN COLD WATER POSITION
COMPLEX A, B, AND C EACH HAVE 6 TEMPERING VALVES LOCATED WITHIN 3
CHASES. A TOTAL OF 18 TEMPERING VALVES ARE REQUIRED TO BE REPLACED
ON THIS PROJECT.
1.
2ND FLOOR
1ST FLOOR
2ND FLOOR
1ST FLOOR
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
COLD WATER PIPING
AutoCAD SHX Text
HOT WATER PIPING
AutoCAD SHX Text
HOT WATER RETURN PIPING
AutoCAD SHX Text
NON POTABLE WATER PIPING
AutoCAD SHX Text
WASTE PIPING
AutoCAD SHX Text
VENT PIPING
AutoCAD SHX Text
LOW PRESSURE GAS PIPING
AutoCAD SHX Text
PLUMBING FIXTURE IDENTIFICATION
AutoCAD SHX Text
PIPE BREAK
AutoCAD SHX Text
PIPE RISE
AutoCAD SHX Text
PIPE DROP
AutoCAD SHX Text
PIPE END CAP
AutoCAD SHX Text
REDUCER
AutoCAD SHX Text
VENT THROUGH ROOF
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
FLOOR SINK
AutoCAD SHX Text
STRAINER
AutoCAD SHX Text
UNION
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
PRESSURE RELIEF VALVE
AutoCAD SHX Text
DOUBLE CHECK BACKFLOW PREVENTER
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
CIRCUIT SETTER
AutoCAD SHX Text
WATER METER
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
CONDENSATE PIPING
AutoCAD SHX Text
POINT OF CONNECTION EXISTING TO NEW
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTER
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
TEMPERATURE GAUGE
AutoCAD SHX Text
PT PLUG
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
MEDIUM PRESSURE GAS PIPING
AutoCAD SHX Text
GREASE WASTE PIPING
AutoCAD SHX Text
EQUIPMENT CALLOUT
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
BRITISH THERMAL UNITS
AutoCAD SHX Text
BTU
AutoCAD SHX Text
EVAPORATIVE
AutoCAD SHX Text
EVAP
AutoCAD SHX Text
HORSE POWER
AutoCAD SHX Text
HP
AutoCAD SHX Text
KILOWATT
AutoCAD SHX Text kW
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
MAX
AutoCAD SHX Text
BTU'S IN THOUSANDS
AutoCAD SHX Text
MBH
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
MIN
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
NO
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
SPE
AutoCAD SHX Text
STATIC PRESSURE EXTERNAL
AutoCAD SHX Text S/T
AutoCAD SHX Text
SENSIBLE TO TOTAL COOLING RATIO
AutoCAD SHX Text
RPM
AutoCAD SHX Text
REVOLUTIONS PER MINUTE
AutoCAD SHX Text
HOUR
AutoCAD SHX Text
HR
AutoCAD SHX Text
MINIMUM CIRCUIT AMPS
AutoCAD SHX Text
MCA
AutoCAD SHX Text
CHARACTERISTICS
AutoCAD SHX Text
CHAR
AutoCAD SHX Text
FEET
AutoCAD SHX Text
FT
AutoCAD SHX Text
ENTERING
AutoCAD SHX Text
ENT
AutoCAD SHX Text
LEAVING
AutoCAD SHX Text
LVG
AutoCAD SHX Text
SEASONAL ENERGY EFFICIENCY RATIO
AutoCAD SHX Text
SEER
AutoCAD SHX Text
ENERGY EFFICIENCY RATIO
AutoCAD SHX Text
EER
AutoCAD SHX Text
STATIC PRESSURE
AutoCAD SHX Text
SP
AutoCAD SHX Text
POUNDS
AutoCAD SHX Text
LB
AutoCAD SHX Text
SQUARE FEET
AutoCAD SHX Text
SF
AutoCAD SHX Text
CFM
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
TEMPERED WATER PIPING
AutoCAD SHX Text
PUMP
AutoCAD SHX Text A1
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text A1
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text A2
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text B1
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text A2
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text B1
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text B2
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text C1
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text C2
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,100#
AutoCAD SHX Text
'PVI' 500 LHE 250A
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text
250 GAL
AutoCAD SHX Text B2
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text C1
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text C2
AutoCAD SHX Text
NON CONDENSING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 80%
AutoCAD SHX Text
FIRE-TUBE
AutoCAD SHX Text 60%%D
AutoCAD SHX Text 140%%D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
65-PSI
AutoCAD SHX Text
100-PSI
AutoCAD SHX Text 1,380#
AutoCAD SHX Text
'PVI' 800 LHE 250A
AutoCAD SHX Text REPLACE HOT WATER HEATER - REFERENCE SHEET P3.1 AND P4.1. CONTRACTOR TO DELIVER HOT WATER HEATER TO SRCI.
AutoCAD SHX Text
REPLACE HOT WATER HEATER - REFERENCE SHEET P3.1 AND P4.1.
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P1.1
EN
LA
R G
ED
S
IT
E
PL
AN
Enlarged Site Plan Scale: 1/8" = 1'-0"
N.
8 6 24 0 8 16 24
BUILDING C BUILDING B
BUILDING A
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
Plumbing Plan - Building A Scale: 1/12" = 1'-0"
N.
12 9 36 0 12 24 36
KEY NOTES:
REPLACE HOT WATER HEATER TANK AND BURNER. REPLACE ALL INSULATION
AND PROVIDE NEW HEARTRACE INSIDE OF INSULATION.
CONTRACTOR SHALL REPLACE 2 EACH EXISTING THERMOSTATIC MIXING
VALVES LOCATED WITHIN CHASES BELOW ROOF ACCESS HATCH WITH
DIGITALLY CONTROLLED MIXING VALVES. REFERENCE DETAIL A SHEET P1.0.
1.
P2.1
PL
U
M
BI
N G
P
LA
N
BU
IL
D
IN
G A
HWH
A2 HWH
A1
A P3.1
A P4.1
A P3.1
A P4.1
KEY PLAN
NORTH
CW
HW
(EXISTING AIR
HANDLING
UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT) (EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
MPG MPG
2.
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
A P5.1
A P5.2
A P5.2
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P2.2
PL
U
M
BI
N G
P
LA
N
BU
IL
D
IN
G B
Plumbing Plan - Building B Scale: 1/12" = 1'-0"
N.
12 9 36 0 12 24 36
KEY NOTES:
REPLACE HOT WATER HEATER TANK AND BURNER. REPLACE ALL INSULATION
AND PROVIDE NEW HEARTRACE INSIDE OF INSULATION.
CONTRACTOR SHALL REPLACE 2 EACH EXISTING THERMOSTATIC MIXING
VALVES LOCATED WITHIN CHASES BELOW ROOF ACCESS HATCH WITH
DIGITALLY CONTROLLED MIXING VALVES. REFERENCE DETAIL A SHEET P1.0.
1.
HWH
B2
HWH
B1
A P3.1
A P4.1
A P3.1
A P4.1
KEY PLAN
NORTH
H W C
W
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
M P
G M
P G
2.
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
A P5.1
A P5.2
A P5.2
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P2.3
PL
U
M
BI
N G
P
LA
N
BU
IL
D
IN
G C
Plumbing Plan - Building C Scale: 1/12" = 1'-0"
N.
12 9 36 0 12 24 36
KEY NOTES:
REPLACE HOT WATER HEATER TANK AND BURNER. REPLACE ALL INSULATION
AND PROVIDE NEW HEARTRACE INSIDE OF INSULATION.
CONTRACTOR SHALL REPLACE 2 EACH EXISTING THERMOSTATIC MIXING
VALVES LOCATED WITHIN CHASES BELOW ROOF ACCESS HATCH WITH
DIGITALLY CONTROLLED MIXING VALVES. REFERENCE DETAIL A SHEET P1.0.
1.
HWH
C2
A P3.1
A P4.1
HWH
C1
A P3.1
A P4.1
CW
HW
KEY PLAN
NORTH
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
(EXISTING AIR
HANDLING UNIT)
MPG
2.
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
A P5.1
A P5.2
A P5.2
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P3.1
SCALE:
G
KEY NOTES:
REMOVE GAS PIPING SUPPLY.
REMOVE GAS FLUE.
REMOVE HOT WATER HEATER.
EXISTING ROOF CURBS TO REMAIN.
REMOVE CW & HW LINE TO BELOW ROOF INSULATION.
REMOVE GATE VALVES ON BUILDING A ONLY. KEEP GATE VALVES ON
BUILDING B AND C.
REMOVE EXISTING BALL VALVE.
1.
2.
3.
4.
5.
250 GALLON WATER HEATER
400 MBH HOT WATER HEATER
RELIEF VALVE
ROOF CURBS
NEMA RATED CONTROL ENCLOSURE
5"Ø FLUE
POWER BURNER
4"
HWR
CW
HW
6.
2"
2"
3"
3"
2"
2"
TO ADJACENT ROOF
MOUNTED HOT WATER
HEATER
H O
T W
A
TE
R H
EA
TE
R T
A N
K A
N D
B U
R N
ER
D
EM
O
LI
TI
O
N S
C H
EM
A
TI
C
7.
A
P3.1
HOT WATER HEATER - DEMOLITION SCHEMATIC
NTS
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
P4.1
SCALE:
G
4"
HWR
CW
HW
CW
HW
250 GALLON WATER HEATER
800 MBH HOT WATER HEATER
RELIEF VALVE
ROOF CURBS
SB-92747 NEMA RATED CONTROL ENCLOSURE
GAS FLUE
POWER BURNER
2 12"
2 12"
KEY NOTES:
PROVIDE SB-92747 NEMA RATED CONTROL ENCLOSURE ON SB-91833 BASIS
OF DESIGN.
CONNECT NEW CW LINE TO EXISTING CW LINE. PLUMBING CONTRACTOR TO
VERIFY SIZE AND LOCATION OF EXISTING CW LINE PRIOR TO WORK
COMMENCING.
CONNECT NEW GAS LINE TO EXISTING GAS LINE SERVICING HOT WATER
HEATER. PLUMBING/MECHANICAL CONTRACTOR TO VERIFY SIZE AND TIE-IN
LOCATION TO EXISTING GAS LINE PRIOR TO WORK COMMENCING.
CONNECT NEW HW LINE TO EXISTING HW LINE. PLUMBING CONTRACTOR TO
VERIFY SIZE AND LOCATION OF EXISTING HW LINE PRIOR TO WORK
COMMENCING.
NEW CHECK VALVE.
POINT OF CONNECTION FOR 3/4" LINE TO BLADDER EXPANSION TANK.
NEW BUTTERFLY ISOLATION VALVES FOR BUILDING A ONLY.
PROVIDE SIZE AND INSTALL GAS FLUE IN ACCORDANCE WITH
MANUFACTURERS INSTALLATION INSTRUCTIONS.
REPLACE EXISTING BALL VALVE WITH 2" BALL VALVE.
1.
2.
3.
4.
2 4
3"
2"
TO ADJACENT ROOF
MOUNTED HOT WATER
HEATER
2"
2"
2"
5.
6.
7.
H O
T W
A
TE
R H
EA
TE
R T
A N
K A
N D
B U
R N
ER
N
EW
S C
H
EM
A
TI
C
7 7
3"
3"
4"
B & G PTA-125V ASME RATED
60 GALLON TOTAL VOLUME
40 GALLON ACCEPTANCE VOLUME
UNION (TYP.)
BALL
ISOLATION
VALVE (TYP.)
8.
9.
A
P4.1
HOT WATER HEATER TANK AND BURNER - NEW SCHEMATIC
NTS
SB-92747 NEMA RATED CONTROL ENCLOSURE
B P4.1
SCALE:
B
P4.1
HOT WATER HEATER TANK
AND BURNER - SECTION
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
TV MPC
AI
T
AI
T
AI
AI
CW
HW
HW
CWTW
TW
CW
HW HW
CONTROL NOTES:#
250 GALLON WATER HEATER 250 GALLON WATER HEATER
P5.1
C O
N
TR
O
LS
S C
H
EM
A
TI
C
C O
N
FI
G U
R A
TI
O
N
TV MPCIO084
1. LOCATE HOFFMAN ENCLOSURE WITH TV MPC AND TV MPCIO084
CONTROLLER INSIDE MECHANICAL CHASE. CONTROLLER HAS 90 WATT
POWER SUPPLY. CONTROLLER WILL HAVE A PROGRAM FOR THE HOT WATER
TEMPERATURE SENSORS SERVING WATER HEATERS AND FOR THE
INTEGRATION FOR EACH OF THE MIXING VALVES.
EACH MIXING VALVE WILL HAVE ITS OWN TEMPERATURE AND SETPOINT
ADJUSTMENTS WITH A GRAPHIC. MIXING VALVE IS HAS 17 W POWER SUPPLY.
BREAK COMMUNICATION AT EXISTING ROOFTOP UNIT AND RUN NEW LOW
VOLT WIRING (DAISY CHAIN CONFIGURATION) TO BOTH MIXING VALVES AND
THEN BACK. MIXING VALVES LOCATED IN MECHANICAL CHASE BELOW
ROOFTOP UNIT.
2.
3.
HOFFMAN ENCLOSURE
AI
AI
AI
AI
SCALE:
A
P5.0
CONTROL SCHEMATIC - CONFIGURATION 1
NTS
90 W
EXISTING ROOFTOP UNIT
UPC CONTROLLER
TEMPERING
VALVE
CONTROLLER
120 V 17 W
120 V
TEMPERING
VALVE
CONTROLLER
120 V 17 W
HW
CW
ROOF
FLOOR 2
FLOOR 1
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
DRAWN BY:
CHECKED BY:
Ti kk er E ng in ee rin g In c.
W
. O ve rla nd
R d.
, S ui te
Bo is e, ID
Ph on e (2
) 6
-0
F ax
(2
) 6
-0 tik ke r@ tik ke re ng in ee rin g.
co m
SHEET NO.
SHEET DATA
D
AT
E N
O
R E
V
IS
IO
N
S
D
ES
C R
IP
TI
O N
CB
BT
03-05-26
C H
A N
I C
N
S U
L T
I
R M
TI
K K
ER
EN
G
IN
EE
R
IN
G
SN
A
K E
R
IV
ER
C
O R
R
EC
TI
O
N A
L
IN
ST
IT
U
TI
O N
C om pl ex
H ot
W at er H ea te r R ep la ce m en t O nt ar io , O
R
AI
AI
CW
HW
HW
CWTW
TW
HW
CONTROL NOTES:#
EXISTING ROOFTOP UNIT
P5.2
C O
N
TR
O
LS
S C
H
EM
A
TI
C
C O
N
FI
G U
R A
TI
O
N
1. BREAK COMMUNICATION AT EXISTING ROOFTOP UNIT AND RUN NEW LOW
VOLT WIRING (DAISY CHAIN CONFIGURATION) TO BOTH MIXING VALVES IN
MECHANICAL CHASE BELOW ROOFTOP UNIT AND THEN BACK.
EACH MIXING VALVE WILL HAVE ITS OWN TEMPERATURE AND SETPOINT
ADJUSTMENTS WITH A GRAPHIC.
2.
UPC CONTROLLER
CW
TEMPERING
VALVE
CONTROLLER
120/240 V
17 W
HW
CW
SCALE:
A
P5.1
CONTROL SCHEMATIC - CONFIGURATION 2
NTS
TEMPERING
VALVE
CONTROLLER
120/240 V
17 W
FLOOR 2
FLOOR 1
ROOF
7-
-2
M
IX
IN
G
V
AL
VE
M
O D
IF
IC
AT
IO
N S
HEREPULL
PULL STATION
5:00
COUNTER OR
BACKSPLASH
ABOVE COUNTER OR BACKSPLASH
TELEPHONE/DATA OUTLET
ABOVE COUNTER RECEPTACLE
REMOTE
EMERGENCY HEAD
EMERGENCY LIGHT
EXIT
EXIT SIGN
CENTERED OVER DOOR
(WHERE APPLICABLE)
DOOR OPENING
CLOCK OUTLET
DIGITAL CLOCK/
SPEAKER COMBO
(ABOVE WHITEBOARD)
FIRE ALARM
PULL STATION
(TO MECHANISM)
TELEVISION
OUTLET
TELEPHONE/DATA
OUTLET
DUPLEX RECEPTACLE
FLOOR
INTERCOM BUTTON
WALL
SPEAKER
MOUNTING HEIGHT DETAIL
UNLESS NOTED OTHERWISE
LIGHT SWITCH
FIRE
FIRE ALARM NOTIFICATION DEVICE
(ENTIRE LENS OF STROBE MUST BE ABOVE 80" AFF)
E0.0 ELECTRICAL SYMBOLS AND SHEET INDEX
E2.0D BUILDING 'A' - ELECTRICAL DEMOLITION PLAN
E2.0E BUILDING 'A' - ELECTRICAL PLAN
E2.1D BUILDING 'B' - ELECTRICAL DEMOLITION PLAN
E2.1E BUILDING 'B' - ELECTRICAL PLAN
E2.2D BUILDING 'C' - ELECTRICAL DEMOLITION PLAN
E2.2E BUILDING 'C' - ELECTRICAL PLAN
E3.0 ONE LINE DIAGRAM
E3.1 ELECTRICAL SCHEDULES
ELECTRICAL DRAWING SHEET INDEXELECTRICAL ABBREVIATIONS
CIRCUITING SYMBOLS
see electrical specifications for further information
ONE LINE SYMBOLS
see electrical specifications for further information
ELECTRICAL DEVICE SYMBOLS
see electrical specifications for further information
LIGHTING SYMBOLS
see luminaire schedule for mounting and fixture type
LINE TYPES
T T# or
T#
TC
P
OC
VS
ALL
X XX
UNO
T
A
J
PANEL
M
J
A AMPERES
AC 6" ABOVE BACKSPLASH
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AF AMP FRAME
AIC AMPS INTERRUPTING CAPACITY
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CO CONDUIT ONLY, PROVIDE PULL-LINE
CT CURRENT TRANSFORMER
CTL CONTROL
DC DIRECT CURRENT
DEMO DEMOLITION
DET DETAIL
E EMPTY/EMERGENCY
(E) EXISTING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EL EMERGENCY LIGHT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXG EXISTING
F FUSE
FVNR FULL VOLTAGE NON-REVERSING
FYR FULL VOLTAGE REVERSING
G/GND GROUND
GFI GROUND FAULT INTERRUPTION
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HPS HIGH PRESSURE SODIUM
HT HEIGHT
HVAC HEATING, VENTILATING, & AIR CONDITIONING
HACR HEATING, AIR CONDITIONING, REFRIGERATION
IBT INTERSYSTEM BONDING TERMINATION
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IPCO IDAHO POWER COMPANY
J/JB JUNCTION BOX
KA KILOAMP
KW KILOWATT
KWH KILOWATT HOUR
LTE LONG TERM EVALUATION
M MAGNETIC CONTACTOR COIL
MB MAIN BREAKER
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MH MANHOLE
MH METAL HALIDE
MTG MOUNTING
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
PC PHOTOCELL
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PWR POWER
PIR PASSIVE INFARED
REC RECEPTACLE
(R) RELOCATED
SF SQUARE FEET
T TELEPHONE
TB TERMINAL BOARD
TBD TO BE DETERMINED
TC TIME CLOCK
TDR TIME DELAY RELAY
TJB TERMINAL JUNCTION BOX
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLT-AMPERE
WP WEATHER PROOF/NEMA 3R
XFMR TRANSFORMER
X EXPLOSION PROOF
XFR TRANSFER
2'x4' ARCHITECTURAL LUMINAIRE
2'x4' PARABOLIC LUMINAIRE
2'x4' LUMINAIRE
2'x4' LUMINAIRE WITH EMERGENCY POWER SOURCE AS
NOTED
1'x4' LUMINAIRE
1'x4' LUMINAIRE WITH EMERGENCY POWER SOURCE AS
NOTED
2'x2' PARABOLIC LUMINAIRE
2'x2' LUMINAIRE
SURFACE CABLE DOWN LUMINAIRE
SURFACE CABLE DOWN LUMINAIRE
SURFACE PENDANT LUMINAIRE
SURFACE UPLIGHT LUMINAIRE
STEP LUMINAIRE
RECESSED WALLWASH LUMINAIRE
RECESSED SLOPED CEILING LUMINAIRE
RECESSED ACCENT LUMINAIRE
RECESSED LUMINAIRE
RECESSED LUMINAIRE WITH EMERGENCY POWER SOURCE
AS NOTED
INDIRECT LUMINAIRE (LENGTH AS INDICATED ON DWGS)
GRID CEILINGS: PROVIDE WITH UL LISTED GRID JUNCTION
BOX. EXCESS AIRCRAFT CABLE TO BE COILED AND
CONCEALED IN FIXTURE, DO NOT CUT OFF EXCESS
AIRCRAFT CABLE; VERIFY FINAL MOUNTING HEIGHT WITH
OWNER; SEE DETAIL ON DETAIL SHEET(S)
INDIRECT LUMINAIRES WITH EMERGENCY POWER SOURCE
AS NOTED (LENGTH AS INDICATED ON DWGS)
GRID CEILINGS: PROVIDE WITH UL LISTED GRID JUNCTION
BOX. EXCESS AIRCRAFT CABLE TO BE COILED AND
CONCEALED IN FIXTURE, DO NOT CUT OFF EXCESS
AIRCRAFT CABLE; VERIFY FINAL MOUNTING HEIGHT WITH
OWNER; SEE DETAIL ON DETAIL SHEET(S)
4' WALL FIXTURE
4' WALL FIXTURE WITH EMERGENCY POWER SOURCE AS
NOTED
2' WALL FIXTURE
2' WALL FIXTURE WITH EMERGENCY POWER SOURCE AS
NOTED
3' WALL FIXTURE
EMERGENCY LUMINAIRE
SURFACE/WALL MOUNTED FLOOD LIGHT
TRACK LUMINAIRE HEAD MOUNTED AS INDICATED
ROUND LUMINAIRE
WALL MOUNTED LUMINAIRE
TIMECLOCK
PHOTOCELL
OCCUPANCY SENSOR. OCCUPANCY SENSOR TO BE
INSTALLED NO LESS THAN 6FT FROM ANY HVAC
DIFFUSERS.
CEILING MOUNTED VACANCY SENSOR. VACANCY SENSOR
TO BE INSTALLED NO LESS THAN 6FT FROM ANY HVAC
DIFFUSERS. PROVIDE WITH LOW VOLTAGE MOMENTARY
WALL SWITCH FOR MANUAL 'ON' CONTROL.
POLE LIGHT WITH ONE HEAD ARM MOUNTED
POLE LIGHT WITH TWO HEADS ARM MOUNTED
WALLPACK LUMINAIRE
WALLPACK LUMINAIRE WITH EMERGENCY POWER SOURCE
AS NOTED
LIGHTING CONTACTOR TO BE NEMA 1 UNLESS OTHERWISE
NOTED. SIZE, POLES, AND TYPE AS INDICATED ON
DRAWING
CEILING MOUNTED EXIT SIGN, DOUBLE FACE
WALL MOUNTED EXIT SIGN, DOUBLE FACE
CEILING MOUNTED EXIT SIGN, SINGLE FACE
WALL MOUNTED EXIT SIGN, SINGLE FACE
WALL MOUNTED EXIT SIGN/ EMERGENCY LIGHT COMBO
UNIT, SINGLE FACE
ARROW INDICATES DIRECTION TO BE SHOWN ON SIGN
LAMP TYPE AND NUMBER TO DIFFERENT
LUMINAIRE
E-DESIGNATES FIXTURE WITH EMERGENCY
BATTERY
FIXTURES WITH AN 'E' DESIGNATION ARE TO BE SUPPLIED WITH BODINE 90
MINUTE EMERGENCY BATTERY PACK (OR EQUAL) SUITABLE FOR THAT
FIXTURES LAMP TYPE AND TO PRODUCE 50% OF THE ORIGINAL OUTPUT.
DUAL LEVEL SWITCHING, INSIDE AND OUTSIDE LAMPS OF
FIXTURE TO BE SWITCHED SEPARATELY.
SINGLE RECEPTACLE. MOUNT AT +18" AFF UNLESS
OTHERWISE NOTED.
SINGLE RECEPTACLE MOUNTED IN FLOOR. TYPE OF BOX
AS INDICATED.
DUPLEX RECEPTACLE. MOUNT AT +18" AFF UNLESS
OTHERWISE NOTED.
C CEILING MOUNTED
DUPLEX RECEPTACLE, HALF OF RECEPTACLE SHALL BE
SWITCHED. MOUNT AT +18" AFF UNLESS NOTED
OTHERWISE.
DUPLEX RECEPTACLE. MOUNTED IN FLOOR. TYPE OF BOX
AS INDICATED.
FOURPLEX RECEPTACLE. MOUNT AT +18" AFF UNLESS
OTHERWISE NOTED.
FOURPLEX RECEPTACLE. MOUNTED IN FLOOR. TYPE OF
BOX AS INDICATED.
SWITCH SUBSCRIPT INICATES TYPE OF SWITCH. MOUNT AT
+46" AFF UNLESS NOTED OTHERWISE
D DIMMER
K KEYED
LV LOW VOLTAGE
M MOMENTARY CONTACT
OV OVERRIDE
OC OCCUPANCY SENSOR; SEE DRAWINGS FOR
ADDITIONAL INFORMATION. FOR 2-POLE, LINE
VOLTAGE OCCUPANCY SENSOR, FURNISH AND
INSTALL DUAL LEVEL SWITCHING. SENSORS MUST BE
DUAL TECHNOLOGY AND A MINIMUM OF 1,000
SQUARE FEET OF COVERAGE.
VS VACANCY SENSOR; SEE DRAWINGS FOR ADDITIONAL
INFORMATION. FOR SENSORS MUST BE DUAL
TECHNOLOGY AND A MINIMUM OF 1,000 SQUARE
FEET OF COVERAGE. VACANCY SENSOR TO BE
PROVIDED WITH MANUAL 'ON' OPERATION.
P PILOT LIGHT
TO THERMAL OVERLOAD
(THE NUMBER OF POLES TO MATCH CIRCUIT
REQUIREMENTS AND BE SIZED FOR ASSOCIATED
MOTOR LOAD.)
2 DOUBLE POLE
3 THREE WAY
4 FOUR WAY
a SUPERSCRIPT INDICATES LIGHTS TO BE SWITCHED
MOTOR STARTER/CONTACTOR TO BE NEMA 1 UNLESS
NOTED OTHERWISE. SIZE AND TYPE AS INDICATED ON
DRAWING.
COMBINATION MOTOR STARTER AND DISCONNECT TO BE
NEMA 1 UNLESS NOTED OTHERWISE. SIZE AND TYPE AS
INDICATED ON DRAWING.
FUSED DISCONNECT SWITCH TO BE NEMA 1 UNLESS
NOTED OTHERWISE. SIZE AND POLES AS INDICATED.
NON-FUSED DISCONNECT SWITCH TO BE NEMA 1 UNLESS
NOTED OTHERWISE. SIZE AND POLES AS INDICATED.
THERMOSTAT MOUNTED AT +48" AFF UNLESS NOTED
OTHERWISE. MECHANICAL UNIT TO BE CONTROLLED AS
INDICATED.
AQUASTAT
EQUIPMENT CONNECTION POINT. VERIFY TYPE OF
CONNECTION WITH EQUIPMENT SUPPLIER. ELECTRICAL
CONTRACTOR TO SUPPLY ALL RACEWAY AND
CONDUCTORS UNLESS NOTED OTHERWISE.
EQUIPMENT CONNECTION POINT MOUNTED IN FLOOR.
TYPE OF BOX AS INDICATED. VERIFY TYPE OF CONNECTION
WITH EQUIPMENT SUPPLIER. ELECTRICAL CONTRACTOR
TO SUPPLY ALL RACEWAY AND CONDUCTORS UNLESS
NOTED OTHERWISE
GROUND ROD; 5/8" BY 10' MINIMUM, COPPER-CLAD
JUNCTION BOX
WALL MOUNTED PUSHBUTTON. MOUNT AT +46" AFF
UNLESS NOTED OTHERWISE
3 BUTTON DOOR CONTROLLER
2 BUTTON DOOR CONTROLLER
TRANSFORMER. SIZE AND TYPE AS INDICATED
# = TRANSFORMER DESIGNATION
MOTOR WITH THERMAL OVERLOAD
MOTOR
or PANELBOARD. SEE ELECTRICAL SCHEDULES FOR TYPE, SIZE AND MOUNTING
# = PANELBOARD DESIGNATION
EQUIPMENT CABINET, SURFACE MOUNTED
EQUIPMENT CABINET, FLUSH MOUNTED
WALL MOUNTED CIRCUITBREAKER. TYPE AND SIZE AS
INDICATED
WM
WIREMOLD - POWER AND DATA
RACEWAY MOUNT RECEPTACLES AS SHOWN.
MOUNTING OF RACEWAY AS INDICATED
PLUGMOLD - POWER ONLYPM
MECHANICAL EQUIPMENT CALLOUT
POWER POLE
TWO COMPARTMENT POWER POLE
ATS
#A
#P
AUTOMATIC TRANSFER SWITCH, SIZE AND POLES AS
INDICATED ON DRAWING
#A
#P
CIRCUIT BREAKER; SIZE AND POLES AS INDICATED ON
DRAWING
PANELBOARD; NAME, SIZE, TYPE AS INDICATED ON
DRAWINGS
PAD MOUNTED TRANSFORMER BY LOCAL UTILITY
METER
GROUND BAR
SECTOR SWITCH
CURRENT CARRYING
CONDUCTORS
A-2,4,6
3/4" MIN. PANEL HOMERUN
ISOLATED GROUND
NEUTRAL
MOUNTING TYPE
GROUNDING CONDUCTOR
EM
EMERGENCY POWER SOURCE
CONDUIT SIZE
QUANTITY AND SIZE
OF GROUNDING
CONDUCTOR
QUANTITY AND SIZE OF CONDUCTORS
BEGINNING OF CIRCUIT AND
NUMBER OF CIRCUIT
CONDUIT UP
CONDUIT DOWN
UNDERGROUND OR CONCEALED
CONDUIT
EXISTING CONDUIT
CONDUIT STUBBED, CAPPED,
MARKED, AND PROVIDED WITH
PULLSTRING
FUTURE CONDUIT
EXISTING
DEMOLITION
FUTURE
NEW
CIRCUIT CONCEALED IN WALL
OR CEILING TYPICALLY TO BE
3#12-1#12G,3/4"C (UNO)
S
TO
M
M
F
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
D A
T E
N O
D
E S
C R
I P
T I O
N
MR
JWVS
03-04-26
25107 electricalengineeringcompany engineering � tomorrow
800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:
world wide web: e2co.com
25105
T i k k e r
E n g i n e e r i n g
I n c
W
O v e r l a n d
R d
S u i t e
B o i s e
D
P h o n e a x t i k k e r t i k k e r e n g i n e e r i n g c o m
SHEET NO.
SHEET DATA
R E
V
IS
IO
N
S
H
U
T
R
TI
K K
ER
EN
G
IN
EE
R
IN
G
S N
A K
E
R
I V
R
R E
C T
I O
N A
L
I N
S T
I T
U T
I O
N
C o m p l e x
H o t
W a t e r
H e a t e r
R e p l a c e m e n t
O n t a r i o
O
R
M I X
I N
G
V
A L V
E
M
O D
I F
I C
A T
I O
N S
E L
E C
T R
I C
Y M
B O
E
D E
X
E0.0
SCALE: NO SCALE
ELECTRICAL SYMBOLS AND SHEET INDEX
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
HWH
A2
120/1
HWH
A1
120/1
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAINTAINING AND
RESTORING; IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING
THROUGH RENOVATED AREAS THAT SERVE EQUIPMENT IN UNDISTURBED
AREAS.
2. EXISTING CONDUIT MAY BE UTILIZED FOR NEW INSTALLATION IF IT IS
CURRENTLY INSTALLED PER THE INSTALLATION REQUIREMENTS INDICATED
IN THESE CONTRACT DOCUMENTS (DRAWING AND SPECIFICATIONS).
3. PROVIDE BLANK COVERS FOR ALL JUNCTION BOXES THAT CANNOT BE
REMOVED DUE TO EXISTING INSTALLATION CONDITIONS.
4. CONTRACTOR TO COORDINATE ALL CONSTRUCTION ACTIVITY WITH OWNER
TO MINIMIZE ASSOCIATED DOWN TIME AND/OR POWER OUTAGES. ALL POWER
OUTAGES ARE TO BE COORDINATED WITH OWNER IN TERMS OF LENGTH OF
OUTAGE, AREA EFFECTED, AND ALTERNATIVE OPTIONS FOR TEMPORARY
POWER PRIOR TO BEGINNING WORK IN THE AREA EFFECTED BY OUTAGE.
5. ANY EXISTING ITEM TO BE REMOVED ON EXISTING WALLS THAT ARE TO
REMAIN, SHALL BE REMOVED OR ABANDONED WHERE REMOVAL IS NOT
POSSIBLE WITHOUT DAMAGE TO THOSE WALLS. ANY DAMAGE TO EXISTING
REMAINING WALLS AS A RESULT OF REMOVING THE ITEM SHALL BE REPAIRED
AT NO ADDITIONAL COST TO OWNER.
6. ELECTRICAL CONTRACTOR TO IDENTIFY NEW SPARE CIRCUITS AS A RESULT
OF REMOVAL OF ELECTRICAL EQUIPMENT AND REUSE NEW SPARE CIRCUIT
BREAKERS FOR NEW CIRCUITS.
7. ANY EXISTING ITEMS TO BE REMOVED AND REINSTALLED SHALL BE REMOVED
WITHOUT DAMAGING THE DEVICE. ANY DAMAGE TO THE ASSOCIATED
ELECTRICAL DEVICE AS A RESULT OF REMOVING AND REINSTALLATION SHALL
BE REPAIRED OR REPLACED AT NO COST TO OWNER.
KEYED NOTES:
1. DISCONNECT EXISTING 120V BRANCH CIRCUIT AT THE TURBO POWER WATER
HEATER BLOWER.
2. DISCONNECT EXISTING BRANCH CIRCUIT HOMERUN TO PANEL ASSOCIATED
WITH THE WATER HEATER. THE HOME RUN IS TO REMAIN AND BE REUSED
FOR (1) WATER HEATER AND A NEW HOMERUN IS TO BE INSTALLED FOR THE
OTHER WATER HEATER. THE EXISTING BRANCH CIRCUIT CAN ONLY
ACCOMODATE 1 OF THE NEW HEATERS. THE EXISTING BRANCH PANEL IS A
SQUARE D QOC342MQS LOAD CENTER, 208Y/120, 3Ø,125A MAIN BREAKER
THAT HAS 30 POSITIONS. THE EXISTING PANEL THAT THE BRANCH CIRCUIT IS
TERMINATED AT IS TO BE DISCONNECTED AND REMOVED. A NEW PANEL
SHALL BE INSTALLED IN THE SAME LOCATION THAT HAS THE SAME RATINGS
BUT IS A 42 CIRCUIT PANEL TO ALLOW BOTH WATER HEATERS TO BE
POWERED. SEE SHEET E2.0E FOR ADDITIONAL INFORMATION.
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
D A
T E
N O
D
E S
C R
I P
T I O
N
MR
JWVS
03-04-26
25107 electricalengineeringcompany engineering 4 tomorrow
800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:
world wide web: e2co.com
25105
L N N e U Q J L Q e e U L Q J Q c
W
O v e r l a n d
R d
S u i t e
B o i s e
P h o n e x t i k k e r t i k k e r e n g i n e e r i n g c o m
SHEET NO.
SHEET DATA
R E
V
IS
IO
N
K K
ER
EN
G
IN
EE
R
IN
G o P S O e o W D W e U e D W e U e S O D c e P e Q W
Q W D U L o
M I X
I N
G
V
A L V
E
M
O D
I F
I C
A T
I O
N S
E
E
B
U I L
D I N
G
A
E
L E
C T
R I C
M
O L
I T
I O
N
P
L A
N
E2.0D
SCALE: 1" = 10'-0"
BUILDING 'A' - ELECTRICAL DEMOLITION PLAN
A2
120/1
10 MCA
HWH
A1
120/1
10 MCA
1-8
#10'S
1-31
#10'S
T
K
V
A
'1'
1-33
ENCLOSURE
BELOW THE
ROOF DECK
BY OTHERS
1-39
HOFFMAN
1-35
1-37
#10'S
#10'S
#10'S
#10'S
GENERAL NOTES:
1. COORDINATE ALL WORK ON HVAC SYSTEMS WITH DIVISION 15.
2. ALL BREAKERS SUPPLYING MECHANICAL EQUIPMENT SHALL BE HACR RATED.
KEYED NOTES:
1. CONNECTION FOR 120V CONTROL POWER AND BLOWER POWER AT HOT
WATER HEATER. BRANCH CIRCUIT IS CONNECTED AT CONTROL PANEL AND
ROUTED FROM CONTROL PANEL TO BLOWER AT UNIT. THE WATER HEATER IS
MOUNTED ON THE ROOF - ALL FITTINGS AND CONNECTIONS SHALL BE
WEATHER TIGHT.
2. UTILIZE THE EXITING BRANCH CIRCUIT WHERE POSSIBLE ROUTED TO NEW
PANEL 1 THAT WAS PREVIOUSLY UTILIZED TO POWER BOTH WATER HEATERS
AND THE HEAT TRACE. (PANEL 1 IS BEING REPLACED WITH A NEW PANEL IN
THE SAME LOCATION.) UTILIZE THE BREAKER AT POSITION 1-6. THIS BREAKER
SHALL BE A GFEP TYPE BREAKER. FIELD VERIFY EXISTING CONDITIONS.
3. FURNISH AND INSTALL NEW BRANCH CIRCUIT TO NEW BREAKER IN NEW
PANEL AT POSITION 1-31. THIS BREAKER SHALL BE A GFEP TYPE BREAKER.
4. UTILIZE EXISTING RACEWAY SYSTEM AND THE EXISTING BRANCH CIRCUIT FOR
THIS WATER HEATER BRANCH CIRCUIT. EXISTING RECEPTACLES SHALL
REMAIN CONNECTED TO THIS BRANCH CIRCUIT- FIELD VERIFY EXISTING
CONDITIONS.
5. FURNISH AND INSTALL NEW CONDUIT AND CONDUCTORS ROUTED ON ROOF
TOP ADJACENT TO THE EXISTING BRANCH CIRCUIT CONDUITS ALREADY
ROUTED ON ROOF SUPPORTS - FIELD VERIFY EXISTING CONDITIONS.
6. LOCATION OF THE HOT WATER AND COLD WATER PIPING STUB DOWN INTO
THE FACILITY. COORDINATE WITH THE PLUMBING PLANS FOR THE EXACT
LOCATIONS FOR COLD AND HOT WATER STUB LOCATIONS.
7. FURNISH AND INSTALL HEAT TRACE ON THE COLD WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-A1. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
8. FURNISH AND INSTALL HEAT TRACE ON THE HOT WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-A1. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
9. FURNISH AND INSTALL HEAT TRACE ON THE COLD WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-A2. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
10. FURNISH AND INSTALL HEAT TRACE ON THE HOT WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-A2. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
11. ROUTE CONDUIT AND CONDUCTORS TO THE NEW PANEL THAT IS REPLACING
THE EXISTING PANEL IN THE SAME LOCATION IN THE ELECTRICAL ROOM.
CONDUITS SHALL FOLLOW THE EXISTING CONDUIT ROUTING ALONG THE
ROOF UTILIZING THE EXISTING STAND OFF BLOCKS WHERE POSSIBLE. FIELD
VERIFY EXISTING ROUTE.
12. LOCATION OF THE EXISTING ELECTRICAL ROOM INSIDE THE BUILDING ON THE
FLOOR BELOW THE ROOF - FIELD VERIFY THE PANEL LAYOUT IN THE ROOM.
SEE THE PARTIAL ONELINE DIAGRAM FOR ADDITIONAL INFORMATION.
13. FURNISH AND INSTALL A HARD WIRED CONNECTION TO THE NEW DIGITAL
WATER MIXING VALVES INSTALLED WITHIN THE EXISTING MECHANICAL CHASE.
COORDINATE THE MOUNTING LOCATION AND CONNECTION AT THE
TERMINATIONS INSIDE OF THE VALVE CONTROL BOX (FURNISHED WITH THE
VALVE). COORDINATE WITH THE PLUMBING CONTRACTOR FOR LOCATIONS
AND WITH EXISTING CONDITIONS FOR CONDUIT ROUTING.
14. FURNISH AND INSTALL CONDUIT AND CONDUCTORS FOR MONITORING AND
CONTROL FOR THE MIXING VALVES AND SENSORS FROM A TV MPC
CONTROLLER LOCATED IN THE NEW ENCLOSURE TO THE UPC AT THE
MECHANICAL ROOF TOP UNIT. PROVIDE A BACNET CONNECTION FROM THE
VALVES TO THE UPC FOR EACH DIGITAL MIXING VALVE AND SENSOR.
COORDINATE THE BACNET SYSTEM CABLING REQUIREMENTS WITH THE
OWNER, FOR BACNET MS/TP THE CONDUCTORS SHALL BE RS-485 CABLES IN
3/4" CONDUIT.
15. CONNECTION FOR POWER SUPPLY FOR THE DIGITAL CONTROLLER THAT IS
BEING INSTALLED IN THE NEW ENCLOSURE. COORDINATE ALL CONNECTION
REQUIREMENTS WITH THE EQUIPMENT SUPPLIER.
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
D A
T E
N O
D
E S
C R
I P
T I O
N
MR
JWVS
03-04-26
25107 electricalengineeringcompany engineering 4 tomorrow
800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:
world wide web: e2co.com
25105
L N N e U Q J L Q e e U L Q J Q c
W
O v e r l a n d
R d
S u i t e
B o i s e
P h o n e x t i k k e r t i k k e r e n g i n e e r i n g c o m
SHEET NO.
SHEET DATA
R E
V
IS
IO
N
K K
ER
EN
G
IN
EE
R
IN
G o P S O e o W D W e U e D W e U e S O D c e P e Q W
Q W D U L o
M I X
I N
G
V
A L V
E
M
O D
I F
I C
A T
I O
N S
E
E
B
U I L
D I N
G
A
E
L E
C T
R I C
P
A
N
E2.0E
SCALE: 1" = 10'-0"
BUILDING 'A' - ELECTRICAL PLAN
B1
120/1
HWH
B2
120/1
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAINTAINING AND
RESTORING; IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING
THROUGH RENOVATED AREAS THAT SERVE EQUIPMENT IN UNDISTURBED
AREAS.
2. EXISTING CONDUIT MAY BE UTILIZED FOR NEW INSTALLATION IF IT IS
CURRENTLY INSTALLED PER THE INSTALLATION REQUIREMENTS INDICATED
IN THESE CONTRACT DOCUMENTS (DRAWING AND SPECIFICATIONS).
3. PROVIDE BLANK COVERS FOR ALL JUNCTION BOXES THAT CANNOT BE
REMOVED DUE TO EXISTING INSTALLATION CONDITIONS.
4. CONTRACTOR TO COORDINATE ALL CONSTRUCTION ACTIVITY WITH OWNER
TO MINIMIZE ASSOCIATED DOWN TIME AND/OR POWER OUTAGES. ALL POWER
OUTAGES ARE TO BE COORDINATED WITH OWNER IN TERMS OF LENGTH OF
OUTAGE, AREA EFFECTED, AND ALTERNATIVE OPTIONS FOR TEMPORARY
POWER PRIOR TO BEGINNING WORK IN THE AREA EFFECTED BY OUTAGE.
5. ANY EXISTING ITEM TO BE REMOVED ON EXISTING WALLS THAT ARE TO
REMAIN, SHALL BE REMOVED OR ABANDONED WHERE REMOVAL IS NOT
POSSIBLE WITHOUT DAMAGE TO THOSE WALLS. ANY DAMAGE TO EXISTING
REMAINING WALLS AS A RESULT OF REMOVING THE ITEM SHALL BE REPAIRED
AT NO ADDITIONAL COST TO OWNER.
6. ELECTRICAL CONTRACTOR TO IDENTIFY NEW SPARE CIRCUITS AS A RESULT
OF REMOVAL OF ELECTRICAL EQUIPMENT AND REUSE NEW SPARE CIRCUIT
BREAKERS FOR NEW CIRCUITS.
7. ANY EXISTING ITEMS TO BE REMOVED AND REINSTALLED SHALL BE REMOVED
WITHOUT DAMAGING THE DEVICE. ANY DAMAGE TO THE ASSOCIATED
ELECTRICAL DEVICE AS A RESULT OF REMOVING AND REINSTALLATION SHALL
BE REPAIRED OR REPLACED AT NO COST TO OWNER.
KEYED NOTES:
1. DISCONNECT EXISTING 120V BRANCH CIRCUIT AT THE TURBO POWER WATER
HEATER BLOWER.
2. DISCONNECT EXISTING BRANCH CIRCUIT HOMERUN TO PANEL ASSOCIATED
WITH THE WATER HEATER. THE HOME RUN IS TO REMAIN AND BE REUSED
FOR (1) WATER HEATER AND A NEW HOMERUN IS TO BE INSTALLED FOR THE
OTHER WATER HEATER. THE EXISTING BRANCH CIRCUIT CAN ONLY
ACCOMODATE 1 OF THE NEW HEATERS. THE EXISTING BRANCH PANEL IS A
SQUARE D QOC342MQS LOAD CENTER, 208Y/120, 3Ø,125A MAIN BREAKER
THAT HAS 30 POSITIONS. THE EXISTING PANEL THAT THE BRANCH CIRCUIT IS
TERMINATED AT IS TO BE DISCONNECTED AND REMOVED. A NEW PANEL
SHALL BE INSTALLED IN THE SAME LOCATION THAT HAS THE SAME RATINGS
BUT IS A 42 CIRCUIT PANEL TO ALLOW BOTH WATER HEATERS TO BE
POWERED. SEE SHEET E2.1E FOR ADDITIONAL INFORMATION.
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
D A
T E
N O
D
E S
C R
I P
T I O
N
MR
JWVS
03-04-26
25107 electricalengineeringcompany engineering 4 tomorrow
800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:
world wide web: e2co.com
25105
L N N e U Q J L Q e e U L Q J Q c
W
O v e r l a n d
R d
S u i t e
B o i s e
P h o n e x t i k k e r t i k k e r e n g i n e e r i n g c o m
SHEET NO.
SHEET DATA
R E
V
IS
IO
N
K K
ER
EN
G
IN
EE
R
IN
G o P S O e o W D W e U e D W e U e S O D c e P e Q W
Q W D U L o
M I X
I N
G
V
A L V
E
M
O D
I F
I C
A T
I O
N S
E
E
B
U I L
D I N
G
B
E
L E
C T
R I C
M
O L
I T
I O
N
P
L A
N
E2.1D
SCALE: 1" = 10'-0"
BUILDING 'B' - ELECTRICAL DEMOLITION PLAN
B1
120/1
10 MCA
HWH
B2
120/1
10 MCA
TV-8
#10'S
TV-31
#10'S
6 6
T
A
'TV'
ENCLOSURE
BELOW THE
ROOF DECK
BY OTHERS
TV-33
TV-39
HOFFMAN
#10'S
TV-35
#10'S
TV-37
#10'S
#10'S
GENERAL NOTES:
1. COORDINATE ALL WORK ON HVAC SYSTEMS WITH DIVISION 15.
2. ALL BREAKERS SUPPLYING MECHANICAL EQUIPMENT SHALL BE HACR RATED.
3. CONTRACTOR SHALL ROUTE ALL CONDUIT AND CONDUCTORS IN CEILING
SPACE BELOW ROOF, IF CONTRACTOR ROUTES CONDUIT AND CONDUCTORS
ON ROOF, CONTRACTOR SHALL BE RESPONSIBLE FOR DE-RATING
CONDUCTORS PER SECTION 310.15(A)(2) OF THE 2017 NEC AND MODIFY
CONDUIT SIZES AS REQUIRED.
KEYED NOTES:
1. CONNECTION FOR 120V CONTROL POWER AND BLOWER POWER AT HOT
WATER HEATER. BRANCH CIRCUIT IS CONNECTED AT CONTROL PANEL AND
ROUTED FROM CONTROL PANEL TO BLOWER AT UNIT. THE WATER HEATER IS
MOUNTED ON THE ROOF - ALL FITTINGS AND CONNECTIONS SHALL BE
WEATHER TIGHT.
2. UTILIZE THE EXITING BRANCH CIRCUIT WHERE POSSIBLE ROUTED TO NEW
PANEL TV THAT WAS PREVIOUSLY UTILIZED TO POWER BOTH WATER
HEATERS AND THE HEAT TRACE. (PANEL TV IS BEING REPLACED WITH A NEW
PANEL IN THE SAME LOCATION.) UTILIZE THE BREAKER AT POSITION TV-8.
THIS BREAKER SHALL BE A GFEP TYPE BREAKER. FIELD VERIFY EXISTING
CONDITIONS.
3. FURNISH AND INSTALL NEW BRANCH CIRCUIT TO NEW BREAKER IN PANEL AT
POSITION TV-31. THIS BREAKER SHALL BE A GFEP TYPE BREAKER.
4. UTILIZE EXISTING RACEWAY SYSTEM AND THE EXISTING BRANCH CIRCUIT FOR
THIS WATER HEATER BRANCH CIRCUIT. EXISTING RECEPTACLES SHALL
REMAIN CONNECTED TO THIS BRANCH CIRCUIT- FIELD VERIFY EXISTING
CONDITIONS.
5. FURNISH AND INSTALL NEW CONDUIT AND CONDUCTORS ROUTED ON ROOF
TOP ADJACENT TO THE EXISTING BRANCH CIRCUIT CONDUITS ALREADY
ROUTED ON ROOF SUPPORTS - FIELD VERIFY EXISTING CONDITIONS.
6. LOCATION OF THE HOT WATER AND COLD WATER PIPING STUB DOWN INTO
THE FACILITY. COORDINATE WITH THE PLUMBING PLANS FOR THE EXACT
LOCATIONS FOR COLD AND HOT WATER STUB LOCATIONS.
7. FURNISH AND INSTALL HEAT TRACE ON THE COLD WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-B1. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
8. FURNISH AND INSTALL HEAT TRACE ON THE HOT WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-B1. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
9. FURNISH AND INSTALL HEAT TRACE ON THE COLD WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-B2. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
10. FURNISH AND INSTALL HEAT TRACE ON THE HOT WATER PIPING FROM THE
STUB DOWN LOCATION TO WATER HEATER HWH-B2. THE HEAT TRACE SHALL
BE POWERED FROM THE SAME BRANCH BREAKER UTILIZED TO POWER THE
CONTROLLER FOR THIS WATER HEATER. THE HEAT TRACE SHALL BE
RAYCHEM XL-TRACE EDGE (SELF REGULATING HEATING CABLE) - 8W/FT 120V
CATALOG # 2000002609, ITEM NUMBER 8XLE1-CR OR EQUAL IN ANOTHER
MANUFACTURER FOR USE WITH PIPING UNDER INSULATION. FURNISH AND
INSTALL WILL ALL REQUIRED EQUIPMENT FOR CONNECTION TO THE 120V
SOURCE AT THE CONTROLLER AND HEAT TRACE ON THE PIPING.
11. ROUTE CONDUIT AND CONDUCTORS TO THE NEW PANEL THAT IS REPLACING
THE EXISTING PANEL IN THE SAME LOCATION IN THE ELECTRICAL ROOM.
CONDUITS SHALL FOLLOW THE EXISTING CONDUIT ROUTING ALONG THE
ROOF UTILIZING THE EXISTING STAND OFF BLOCKS WHERE POSSIBLE. FIELD
VERIFY EXISTING ROUTE.
12. LOCATION OF THE EXISTING ELECTRICAL ROOM INSIDE THE BUILDING ON THE
FLOOR BELOW THE ROOF - FIELD VERIFY THE PANEL LAYOUT IN THE ROOM.
SEE THE PARTIAL ONELINE DIAGRAM FOR ADDITIONAL INFORMATION.
13. FURNISH AND INSTALL A HARD WIRED CONNECTION TO THE NEW DIGITAL
WATER MIXING VALVES INSTALLED WITHIN THE EXISTING MECHANICAL CHASE.
COORDINATE THE MOUNTING LOCATION AND CONNECTION AT THE
TERMINATIONS INSIDE OF THE VALVE CONTROL BOX (FURNISHED WITH THE
VALVE). COORDINATE WITH THE PLUMBING CONTRACTOR FOR LOCATIONS
AND WITH EXISTING CONDITIONS FOR CONDUIT ROUTING.
14. FURNISH AND INSTALL CONDUIT AND CONDUCTORS FOR MONITORING AND
CONTROL FOR THE MIXING VALVES AND SENSORS FROM A TV MPC
CONTROLLER LOCATED IN THE NEW ENCLOSURE TO THE UPC AT THE
MECHANICAL ROOF TOP UNIT. PROVIDE A BACNET CONNECTION FROM THE
VALVES TO THE UPC FOR EACH DIGITAL MIXING VALVE AND SENSOR.
COORDINATE THE BACNET SYSTEM CABLING REQUIREMENTS WITH THE
OWNER, FOR BACNET MS/TP THE CONDUCTORS SHALL BE RS-485 CABLES IN
3/4" CONDUIT.
15. CONNECTION FOR POWER SUPPLY FOR THE DIGITAL CONTROLLER THAT IS
BEING INSTALLED IN THE NEW ENCLOSURE. COORDINATE ALL CONNECTION
REQUIREMENTS WITH THE EQUIPMENT SUPPLIER.
DATE:
TE JOB #:
DRAWN BY:
CHECKED BY:
D A
T E
N O
D
E S
C R
I P
T I O
N
MR
JWVS
03-04-26
25107 electricalengineeringcompany engineering 4 tomorrow
800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:
world wide web: e2co.com
25105
L N N e U Q J L Q e e U L Q J Q c
W
O v e r l a n d
R d
S u i t e
B o i s e
P h o n e x t i k k e r t i k k e r e n g i n e e r i n g c o m
SHEET NO.
SHEET DATA
R E
V
IS
IO
N
K K
ER
EN
G
IN
EE
R
IN
G o P S O e o W D W e U e D W e U e S O D c e P e Q W
Q W D U L o
M I X
I N
G
V
A L V
E
M
O D
I F
I C
A T
I O
N S
E
E
B
U I L
D I N
G
B
E
L E
C T
R I C
A
N
E2.1E
SCALE: 1" = 10'-0"
BUILDING 'B' - ELECTRICAL PLAN
C2
120/1
HWH
C1
120/1
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAINTAINING AND
RESTORING; IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING
THROUGH RENOVATED AREAS THAT SERVE EQUIPMENT IN UNDISTURBED
AREAS.
2. EXISTING CONDUIT MAY BE UTILIZED FOR NEW INSTALLATION IF IT IS
CURRENTLY INSTALLED PER THE INSTALLATION REQUIREMENTS INDICATED
IN THESE CONTRACT DOCUMENTS (DRAWING AND SPECIFICATIONS).
3. PROVIDE BLANK COVERS FOR ALL JUNCTION BOXES THAT CANNOT BE
REMOVED DUE TO EXISTING INSTALLATION CONDITIONS.
4. CONTRACTOR TO COORDINATE ALL CONSTRUCTION ACTIVITY WITH OWNER
TO MINIMIZE ASSOCIATED DOWN TIME AND/OR POWER OUTAGES. ALL POWER
OUTAGES ARE TO BE COORDINATED WITH OWNER IN TERMS OF LENGTH OF
OUTAGE, AREA EFFECTED, AND ALTERNATIVE OPTIONS FOR TEMPORARY
POWER PRIOR TO BEGINNING WORK IN THE AREA EFFECTED BY OUTAGE.
5. ANY EXISTING ITEM TO BE REMOVED ON EXISTING WALLS THAT ARE TO
REMAIN, SHALL BE REMOVED OR ABANDONED WHERE REMOVAL IS NOT
POSSIBLE WITHOUT DAMAGE TO THOSE WALLS. ANY DAMAGE TO EXISTING
REMAINING WALLS AS A RESULT OF REMOVING THE ITEM SHALL BE REPAIRED
AT NO ADDITIONAL COST TO OWNER.
6. ELECTRICAL CONTRACTOR TO IDENTIFY NEW SPARE CIRCUITS AS A RESULT
OF REMOVAL OF ELECTRICAL EQUIPMENT AND REUSE NEW SPARE CIRCUIT
BREAKERS FOR NEW CIRCUITS.
7. ANY EXISTING ITEMS TO BE REMOVED AND REINSTALLED SHALL BE REMOVED
WITHOUT DAMAGING THE DEVICE. ANY DAMAGE TO THE ASSOCIATED
ELECTRICAL DEVICE AS A RESULT OF REMOVING AND REINSTALLATION SHALL
BE REPAIRED OR REPLACED AT NO COST TO OWNER.
KEYED NOTES:
1. DISCONNECT EXISTING 120V BRANCH CIRCUIT AT THE TURBO POWER WATER
HEATER BLOWER.
2. DISCONNECT EXISTING BRANCH CIRCUIT HOMERUN TO PANEL ASSOCIATED
WITH THE WATER HEATER. THE HOME RUN IS TO REMAIN AND BE REUSED
FOR (1) WATER HEATER AND A NEW HOMERUN IS TO BE INSTALLED FOR THE
OTHER WATER HEATER. THE EXISTING BRANCH CIRCUIT CAN ONLY
ACCOMODATE 1 OF THE NEW HEATERS. THE EXISTING BRANCH PANEL IS A
SQUARE D QOC342MQS LOAD CENTER, 208Y/120, 3Ø,125A MAIN BREAKER
THAT HAS 30 POSITIONS.