Excelsior_Springs_Facility_Survey_2015_Final_Vol_2.pdf
PDF 19 MB Posted
- Attached to
- Excelsior Springs JCC Federal contract opportunity
- Solicitation number
- 1630J5-18-R-00007
About this file
Excelsior Springs Facility Survey 2015 Final Vol 2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Excelsior_Springs_Q_and_A_(2).docx | DOCX document | |
| 1630J5-18-R-00007_Amend_0002.pdf | ||
| Excelsior_Springs_Master_Property_Report.pdf | ||
| ES_Vehicle_Inventory_Estimate_Utility_Usage_March2017.docx | DOCX document | |
| Excelsior_Springs_Facility_Survey_2015_Final_Vol1_Part1.pdf | ||
| Sol_1630J5-18-R-00007.pdf | ||
| Sol_1630J5-18-R-00007_Amd_0001.pdf | ||
| Excel_Sp_Utilities_and_Fuel_Usage_2016.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXCELSIOR SPRINGS
Job Corps Center Excelsior Springs, MO
Facility Planning Report Volume II
Supporting Data
Final June 2016
Department of Labor/ Office of Job Corps
EXCELSIOR SPRINGS
Job Corps Center Excelsior Springs, MO
Facility Planning Report Volume II
Supporting Data
Final June 2016
Campus South West View
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The facility survey for the Excelsior Springs, Job Corps Center (Excelsior Springs JCC) was completed from July 27, 2015 through July 30, 2015. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the Center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans, while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new deficiencies identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. Operations and Maintenance (O&M) Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
EXCELSIOR SPRINGS
JOB CORPS CENTER
EXCELSIOR SPRINGS, MISSOURI
EXCELSIOR
SPRINGS JCC
10 MI5 0
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00701 EXCELSIOR SPRINGS 06/20/2016
1Page: of Date:
0002 - EDUCATION
0003 - WELCOME CENTER
0006 - VOCATIONAL BUILDING TRADES
0012 - ADMINISTRATION
0013 - SOCIAL HALL/CAREER
DEVELOPMENT
0014 - ELEANOR ROOSEVELT HALL
0016 - CULINARY ARTS
0028 - LINCOLN HALL (NAVY ROTC)
0032 - CAREER PREPARATION CENTER
0033 - HEALTH OCCUPATION/DRIVERS
EDUCATION
0036 - TRUTH HALL
0045 - EDUCATION &
VOCATIONAL/SWOPE SATELLITE
0046 - STORAGE/SWOPE SATELLITE
0048 - WELLNESS CENTER
0050 - MEDICAL OFFICE SUPPORT / TCU
0051 - GONZALEZ HALL
0052 - TRANSPORTATION/RECEIVING
0055 - GYMNASIUM
0056 - CAFETERIA
0057 - VOCATIONAL STORAGE
0058 - HBI VOCATIONS BUILDING
0010 - VOCATIONAL TRADES STORAGE
(17Ft x 101Ft) 0011 - STORAGE SHED (10Ft x 30Ft) 0015 - STORAGE (10Ft x 55Ft) 0016A - CULINARY STORAGE (10Ft x 16Ft) 0049 - STORAGE (10Ft x 71Ft)
0053 - VOCATIONAL TRAINING STORAGE
(14Ft x 29Ft) 0054 - PAINT BOOTH - STORAGE (13Ft x 40Ft) 0059 - GARDEN SHED (8Ft x 12Ft) PV-4 - PAVILION (10Ft x 27Ft) PV-6 - PAVILION (10Ft x 25Ft) PV-7 - PAVILION (10Ft x 45Ft) PV-8 - PAVILION (10Ft x 45Ft)
WT-1 - WATERTOWER
Name GSF
9,860 1,250
17,436 12,835 11,520
14,980 3,564 3,921 6,540 5,784
20,000 18,360
1,200 4,468 9,020
29,170 6,400
18,603 12,126 2,700 8,000 1,717
Active Active Active Active Active
Active Active Active Active Active
Active Active
Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active
Active
Active Active Active Active Active Active
StatusType
Building Building Building Building Building
Building Building Building Building Building
Building Building
Building Building Building Building Building Building Building Building Building Structure
Structure Structure Structure Structure Structure
Structure
Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
B B B B A-3,B
R-2 B B,S-2 B B
R-2 A-2,B
S-2 B B R-2 S-2 A-3 A-2 S-2 B Storage
Storage Storage Assembly Storage B
S-2
Storage A-3 A-3 A-3 A-3 U
Good Good Good Good Fair
Good Good Good Good Good
Good Good
Good Good Good Good Good Good Good Good Good Good
Good Good Good Good Good
Good
Good Good Good Good Good Good
ConditionAsset Number
0070100003 0070108065 0070100006 0070100011 0070100012
0070100013 0070100031 0070100017 0070100018 0070100019
0070100021 0070100029
0070100034 0070100037 0070100039 0070100040 0070100041 0070108051 0070108052 0070108053 0070108062 0070100030
0070100010 0070100026 0070108055 0070100038 0070100043
0070100042
0070108067 0070108057 0070108059 0070108060 0070108061 0070108066
21 217,737
13 6,354
34 224,091
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/20/2016
Space Utilization By Function 00701 Excelsior Springs Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 268 Non Residents 168
436Total Students
(268)
(436)
(436)
DIFFERENCE
28,944
36,190
7,848
41,287
56,092
10,111
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (436) Non-Academic
40 -- Carpentry + 20 -- Cement Masonry + 60 -- Culinary Arts + 48 -- Facilities Maint. and Const. + 30 -- Medical Assistant 30 -- Medical Office Support 90 -- Nursing Assistant +
6 -- OCT
20 -- Painting + 0 -- Pharmacy Tech + 30 -- Security Services 100 -- TCU Transportation 24 -- Welding +
Vocational Theory (302)
Dining (2 Servings) Food Preparation Food Storage
6,318 4,115 3,419
26,482
11,133 15,147
4,070 2,277 1,648 6,553
1,953 2,169
2,538
1,742 2,207
2,780
5,601 2,160 2,350
2,680 2,144 3,216
19,296 1,608
4,360 4,360
3,000 1,500 3,600 3,600
3,600
1,500
1,050 3,000 1,800
3,020
3,488 2,616 1,744
3,638 1,971
7,186
-655
6,773 10,787
1,070
-1,952 2,953
1,053 -1,431
1,038
-1,050 -1,258
-240
2,113 -456
Vocations
12,343
19,902
2,263
06/20/2016
Space Utilization By Function 00701 Excelsior Springs Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 250.05 109,022 148,976
(436)
(436)
(436)
(436)
(0)
DIFFERENCE
217,737
0.68
TOTAL GSF
NET TO GROSS RATIO
15,920
2,680
8,720
18,389
2,864
8,868
7,871
3,494
Arts & Crafts Auditorium Canteen Computer Lab Gymnasium Miscellaneous Recreation Multipurpose Room Recreation Hall Recreation Storage Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
6.15
1,014 3,488
7,533 1,378
1,407 1,103 1,021
2,864
8,868
3,254 4,617
3,494
2,680
5,232
1,014
7,533 1,378
1,407 1,103 1,021
-234 -615
3,494
RESIDENT
NON-RESIDENT
(268)
(168) 15
50 13,400 2,520
2,469
-849
3,494
39,954
Net Square Footage By Building Date: 06/20/2016 Page: 1
Center: EXCELSIOR SPRINGS (00701) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
8,981 11,240 6,261
2,619 3,220
1,039 2,380
1,444 1,041 1,630
0036 - TRUTH HALL
0051 - GONZALEZ HALL
0014 - ELEANOR ROOSEVELT HALL
0014 - ELEANOR ROOSEVELT HALL
0036 - TRUTH HALL
0051 - GONZALEZ HALL
0036 - TRUTH HALL
0051 - GONZALEZ HALL
0014 - ELEANOR ROOSEVELT HALL
0014 - ELEANOR ROOSEVELT HALL
0051 - GONZALEZ HALL
0014 - ELEANOR ROOSEVELT HALL
0036 - TRUTH HALL
0051 - GONZALEZ HALL
Bldg Name Actual NSF Difference
26,482
6,318
3,419
4,115
Sub Total: 41,287
19,296
2,680
1,608
3,216
2,144
28,944
7,186
3,638
-655
1,971
( 268
12,343 rooms; beds rooms; beds rooms; beds
Page: 2
Center: EXCELSIOR SPRINGS (00701) of 5
EDUCATION
Academic
Vocational Theory (302)
Carpentry
Cement Masonry
Culinary Arts
Welding
Painting
Facilities Maint. and Const.
Medical Assistant
Function Suggested
NSF
1,254
1,160
2,216 1,615 1,158
1,322
3,161
1,852
1,648
1,708
2,538
6,553
0002 - EDUCATION
0002 - EDUCATION
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0002 - EDUCATION
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0002 - EDUCATION
0002 - EDUCATION
0050 - MEDICAL OFFICE SUPPORT / TCU
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0006 - VOCATIONAL BUILDING TRADES
0058 - HBI VOCATIONS BUILDING
0016 - CULINARY ARTS
0006 - VOCATIONAL BUILDING TRADES
0057 - VOCATIONAL STORAGE
0033 - HEALTH OCCUPATION/DRIVERS EDUCATION
0006 - VOCATIONAL BUILDING TRADES
0057 - VOCATIONAL STORAGE
0016 - CULINARY ARTS
0006 - VOCATIONAL BUILDING TRADES
0057 - VOCATIONAL STORAGE
0006 - VOCATIONAL BUILDING TRADES
0058 - HBI VOCATIONS BUILDING
0033 - HEALTH OCCUPATION/DRIVERS EDUCATION
Bldg Name Actual NSF Difference
11,133
2,780
4,070
2,277
1,648
2,207
2,538
6,553
4,360
3,020
3,000
1,500
3,600
1,800
1,500
3,600
6,773
-240
1,070
-1,952
1,038
2,953
( 436 )
Page: 3
Center: EXCELSIOR SPRINGS (00701) of 5
EDUCATION
FOOD SERVICE
Non-Academic
Nursing Assistant
TCU Transportation
Pharmacy Tech
Medical Office Support
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
1,376
1,441 2,753
2,517 2,099
2,169
1,742
1,179
1,171 4,430
2,160
2,350
0014 - ELEANOR ROOSEVELT HALL
0032 - CAREER PREPARATION CENTER
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0032 - CAREER PREPARATION CENTER
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0032 - CAREER PREPARATION CENTER
0050 - MEDICAL OFFICE SUPPORT / TCU
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0002 - EDUCATION
0050 - MEDICAL OFFICE SUPPORT / TCU
0013 - SOCIAL HALL/CAREER DEVELOPMENT
0036 - TRUTH HALL
0028 - LINCOLN HALL (NAVY ROTC)
0032 - CAREER PREPARATION CENTER
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0050 - MEDICAL OFFICE SUPPORT / TCU
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0050 - MEDICAL OFFICE SUPPORT / TCU
0033 - HEALTH OCCUPATION/DRIVERS EDUCATION
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0056 - CAFETERIA
0056 - CAFETERIA
0056 - CAFETERIA
Bldg Name Actual NSF Difference
15,147
2,169
1,742
1,953
5,601
2,160
2,350
Sub Total:
Sub Total:
56,092
10,111
4,360
3,600
3,000
3,488
2,616
1,744
35,140
7,848
10,787
-1,431
-1,258
1,053
2,113
-456
( 436
20,952
2,263
Page: 4
Center: EXCELSIOR SPRINGS (00701) of 5
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Multipurpose Room
Recreation Hall
Arts & Crafts
Gymnasium
Weight Room
Auditorium
Miscellaneous Recreation
Canteen
Computer Lab
Recreation Storage
Medical/Dental
Administration
Function Suggested
NSF
1,407
1,014
7,533
1,021
3,488
1,378
2,864
7,510
0055 - GYMNASIUM
0055 - GYMNASIUM
0055 - GYMNASIUM
0055 - GYMNASIUM
0055 - GYMNASIUM
0013 - SOCIAL HALL/CAREER DEVELOPMENT
0055 - GYMNASIUM
0055 - GYMNASIUM
0055 - GYMNASIUM
0057 - VOCATIONAL STORAGE
0055 - GYMNASIUM
0048 - WELLNESS CENTER
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLITE
0012 - ADMINISTRATION
0003 - WELCOME CENTER
Bldg Name Actual NSF Difference
1,407
1,014
7,533
1,021
3,488
1,378
1,103
2,864
8,868
Sub Total:
Sub Total:
Sub Total:
18,389
2,864
8,868
2,680
8,720
15,920
2,680
8,720
2,469
Page: 5
Center: EXCELSIOR SPRINGS (00701) of 5
STORAGE/SUPPORT
VACANT
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
4,617
2,107
0052 - TRANSPORTATION/RECEIVING
0052 - TRANSPORTATION/RECEIVING
0046 - STORAGE/SWOPE SATELLITE
0028 - LINCOLN HALL (NAVY ROTC)
0048 - WELLNESS CENTER
0057 - VOCATIONAL STORAGE
0046 - STORAGE/SWOPE SATELLITE
0013 - SOCIAL HALL/CAREER DEVELOPMENT
0014 - ELEANOR ROOSEVELT HALL
0033 - HEALTH OCCUPATION/DRIVERS EDUCATION
Bldg Name Actual NSF Difference
4,617
3,254
3,494
Sub Total:
Sub Total:
7,871
3,494
5,232
3,488
8,720
-615
-234
3,494
-849
3,494
Environmental Management Report
Center: EXCELSIOR SPRINGS (00701) Page: 1 Date: 06/20/2016 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
No Building 6
Mineral spirits (<150 gals), oil-based paint (120 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Deffenbaugh Disposal Service Yes Organic Solvent (2 gallons average per month)
Small Quantity Generator D81506942022214 Commercial Hazardous Waste Disposal Service Phillips Service Co./BFI, Inc.
Yes No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
01/01/1998 Friable/Non-Friable Tom Green 03/01/2000 Yes No N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 06/20/2016Center : Excelsior Springs (00701) Page: 1 of 1
Floor Finishes
Heating Heating Floor Finishes Floor Finishes
Floor Finishes Heating Heating Floor Finishes Floor Finishes Floor Finishes Electrical (Bldg)
Heating Heating Floor Finishes Floor Finishes
Heating Heating
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Linoleum
Pipe insulation Pipe insulation (enclosed) 9x9 floor tile, white/black 9x9 floor tile, brown
9x9 floor tile, brown Pipe insulation Pipe insulation (enclosed) 9x9 floor tile, black Linoleum, brown 12x12 floor tile, off-white Asbestos paper
Pipe insulation Pipe insulation Linoleum, brown 9x9 floor tile, beige
Pipe insulation Tank insulation
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Stairwell
Basement, crawlspace Wall cavities Lower level Utility closets
Stairwells Mechanical room Wall cavities Mezzanine storage Social hall TV storage room Electrical panel
Crawlspace 1st floor 3rd floor, office Room 318
Mechanical room Mechanical room
Building :
Building :
Building :
Building :
Building :
0002 - EDUCATION
0012 - ADMINISTRATION
0013 - SOCIAL HALL/CAREER DEVELOPMENT
0014 - ELEANOR ROOSEVELT HALL
0028 - LINCOLN HALL (NAVY ROTC)
Radon
Page: 1 of 2
0002 - EDUCATION
0003 - WELCOME CENTER
0006 - VOCATIONAL BUILDING TRADES
0012 - ADMINISTRATION
0013 - SOCIAL HALL/CAREER DEVELOPMENT
0014 - ELEANOR ROOSEVELT HALL
0016 - CULINARY ARTS
0028 - LINCOLN HALL (NAVY ROTC)
0032 - CAREER PREPARATION CENTER
0033 - HEALTH OCCUPATION/DRIVERS EDUCATION
0036 - TRUTH HALL
0045 - EDUCATION & VOCATIONAL/SWOPE SATELLIT
0046 - STORAGE/SWOPE SATELLITE
0048 - WELLNESS CENTER
0050 - MEDICAL OFFICE SUPPORT / TCU
0051 - GONZALEZ HALL
0052 - TRANSPORTATION/RECEIVING
0055 - GYMNASIUM
0056 - CAFETERIA
0057 - VOCATIONAL STORAGE
0058 - HBI VOCATIONS BUILDING
Bldg Name
05/16/1990
05/31/2006
05/16/1990
05/16/1990
05/16/1990
05/31/2006
05/16/1990
05/16/1990
05/16/1990
05/31/2006
05/16/1990
05/31/2006
05/31/2006
05/31/2006
Test Date
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
No
No
No
N/A
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view from Google Earth
Page: 1 Date: 06/20/2016 of 5
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. Except for the NW corner of the site along St. Louis Avenue, the whole site is fenced.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterCity of Excelsior SpringsPublic Water Authority
None 150,000Underground
There is a single master meter located at the base of the elevated storage tank. The condition of the elevated water storage tank was studied by Pittsburg Tank and Tower Maintenance Company and found to be in need of repairs and rehabilitation. The tower lacks safety railings and stairs, has several leaks, and its structure is beginning to rust. During the July 2015 facility survey the Center stated the water tower bowl was cleaned to remove all sediment deposits. In case of an emergency, a shut off valve allows the center to by-pass the tower water supply and tap into the municipal water distribution system.
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 150,000 10Aboveground Tank Elevated Tank
Number of Deficiencies = 2
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures21 13Gently Sloping
Surrounding
Outdoor Recreation
Residential
Basketball, Field, Soft/Baseball Water Towers
East, South and West Sides
North End
Chain Link
Wrought Iron
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Fair
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 06/20/2016 of 5
Sewage Treatment Flow
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Natural gas consumption is metered at three locations; near Building 40, near Building 51, and one off-site, northeast of Building 10. No records are available indicating which buildings are served by each meter.
Missouri Gas Energy
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Ameren Missouri, KC P&L
The 12.47 kV and 2.4 kV primary services are delivered to the center from power poles and three platform-mounted transformers on St. Louis Avenue. A service meter is installed on a power pole at this location. The
12.47 kV feed serves Buildings 14, 32, 50 and 51 via 12.47 kV:120/208V pad-mounted transformers and Buildings 55, 56 via 12.47 kV:480/277V pad-mounted transformers located near the respective buildings.
Buildings 55 and 56 also have step down transformers providing 120/208V system. The 2.4 kV feed, derived from platform-mounted transformers serves Buildings 2, 5, 6, 12, 13, 15, 16, 28, 33, 36, 48 and 52 via 2.4 kV:120/208V pole-mounted or pad-mounted transformers located near the respective buildings. Except the platform-mounted transformers which are owned by the utility company, the center owns all pole and pad-mounted transformers.
Gymnasium Building 55 and Cafeteria Building 56 have a lightning protection system installed on the roof.
Kansas City Power & Lights (KC P&L) provides service to Swope Satellite site from three pole-mounted transformers on Cleaver Boulevard northeast of the site. The service meter for this site is installed on the exterior wall of Storage Building 46.
Pole, Pad and Platform Utility, Center
Center Center
No
12.47 kV, 2.4 kV, 3-Ph, 3 Wire
480/277V &120/208V 3-Ph, 4 WireOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
Number of Deficiencies = 1
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 4
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility,Center
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
6. Central Plant: None
Metering Master
Page: 3 Date: 06/20/2016 of 5
Comments:
Telephone Company
On-site Line Owner
AT&T provides three T1 lines to the center which terminate in the Main Telephone/Switchboard Equipment room on the first floor of Administration Building 12. Job Corps Data Center provides and maintains digital voice communication (VoIP) with one T1 line and data network LAN and WAN with two T1 lines. The fire alarm systems in buildings throughout the center are connected to the main fire alarm control panel in Security Building 40 and monitored in Gate House Building 3. CCTV cameras have recently been installed in Buildings 6, 55 and 56. The Swope Satellite site is provided with a security system that includes CCTV cameras, black and white monitors, motion detectors and a metal detector. The site fire alarm/security control panel is also located in the reception area. The fire alarm system is connected to the local fire station which has approximately 3-5 minutes response time. The door alarms in Building 45 are monitored at the local police department.
Southwestern Bell provides two T1 lines to the satellite site and Job Corps Data Center provides and maintains the VoiP and data networks.
AT & T, Southwestern Bell
Maint. Responsibility
Center Center
CCTVs, B & W Monitors, Motion Detectors, Metal Detector
01/01/1964CenterAbandoned AbovegroundNear Structure 11. NoNone
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
9. Electrical (Communication/Alarm/Security)
N/A
Purpose
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Pole, Building Pole
Photocell Photocell Photocell Photocell, Time Clock Photocell
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: The satellite site lighting consists of building-mounted and pole-mounted street lights. The building-mounted lights are controlled by photocells and time clock, owned and maintained by the center.
Number of Deficiencies = 1
Number of Deficiencies = 10
Fire Alarm Security
Page: 4 Date: 06/20/2016 of 5
ACCESSIBILITY
Yes
Comments:
UnknownNoNo
The 2012 Historic Survey found the site ineligible for listing on the NRHP. Buildings 13 and 14 were found eligible for listing on the NRHP.
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low LowMedium MediumIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 2
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Comments: Clearstory window in lobby of dormitory Gonzalez Hall Building 51 and timers on exterior lighting throughout the campus. Rains harvesting plastic cisterns are placed under the roof downspouts for irrigation of plaints at the Swope Satellite Center.
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
21 %
Page: 5 Date: 06/20/2016 of 5
SATELLITE SITE DESCRIPTION
Location:
Description:
Ownership Maintenance Responsibility
2402 Swope Parkway Kansas City, MO
There are two buildings on a small parcel of land fenced on three sides. The street side is not fenced.
Building 45: Is a three story building used for academic and vocational education.
Building 46: Is a one story building used as storage.
Lessor Center
Some of he major building repairs fall under the responsibility of the Lessor.Comments:
Rating The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Good Fair Poor
X
SATELLITE SITE CONDITION
Building Descriptions and Structures
BUILDING 2 - EDUCATION
Building Descriptions
Page: 1 of 106
Building: 0002 - EDUCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood and Steel
Brick Masonry
Wall Roof Batt Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 9,860 5,953 1 Owned 1980 Not Evaluated
Comments: The building fire alarm system has audio/visual devices throughout except in the toilets.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.
Drainage Year Life
Type Area Served
Concrete roof tiles
Single Ply
Gutters and Downspouts
Gutters and Downspouts
Gable
Flat
Entire Building
Classrooms
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 106
Building: 0002 - EDUCATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Concrete Drywall
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Metal Stairs Wood Stairs Comments: The stairs are for access to the mechanical room in the basement only.
Metal Unit - Metal Frame Storefront - Metal Frame
Casement - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 1
Exterior Doors5.
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The main part of the building is served by two systems. Each is comprised of a Trane model TWE240B300EL air handler with a direct expansion refrigerant coil and an electric heat section.
Upstream of each air handler are two duct furnaces in parallel. One air handler is served by Reznor model HX150-8-E units and the other is served by Sterling model CD-200 unit. The addition to the building is served by a Trane Furnace model # TOC1B060A9361AE
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Gas-Fired
Single Duct
Unit Heater
None
None
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Equipment Room
Ceilings
Page: 3 of 106
Building: 0002 - EDUCATION
Mechanical Restroom
None None None
Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: There is a single, wet pipe sprinkler head in the janitor's closet.
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
The main part of the building is served by two systems. Each is comprised of a Trane model TWE240B300EL air handler with a direct expansion refrigerant coil. One air handler is served by a York model HB2110C00A2AAA1A outdoor air cooled condensing unit and the other is served by a Carrier model 3 38AKS016-521-outdoor air cooled condensing unit.. The addition to the building is served by a Trane condensing unit Model # 4TTB30301000AA air cooled located on the ground outside the north end of the building.
Comments:
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 4 of 106
Building: 0002 - EDUCATION
Comments: Service is brought from a 112.5 kVA pad-mounted transformer outside to a 400A main circuit breaker main distribution panel located in the mechanical room.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Siemens Desigo located at the building main entrance.
Comments: CCTV cameras are installed in the corridors and monitored in the manager office. The reading classrooms are provided with computer work stations.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Manual Pull Station Visual Alarm
Connected to Main System Closed Circuit TV None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Motion sensor switches are installed in the classrooms and toilets.
High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
COMMUNICATION
Type Location None None
There are no CO detectors in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 5 of 106
Building: 0002 - EDUCATION
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Fair Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 3 - WELCOME CENTER
Page: 6 of 106
Building: 0003 - WELCOME CENTER
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Prefabricated Wood Truss
Composite Siding Glass
Wall Roof Composite Insulated Sheathing Blown In
Metal Unit - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 1,250 538 1 Owned 2011 Not Evaluated
Comments: An curb cut ramp leads to an accessible entrance at the east side of the building. The main entry at the northeast corner is accessed thru concrete steps with no railings.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
N/A
N/A
N/A
Yes
No
N/A
Yes
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 2011 19 Hip Entire Building
3. Roof
Page: 7 of 106
Building: 0003 - WELCOME CENTER
INTERIOR FINISH
Concrete Polished Concrete
CMU Drywall
Wood Unit - Metal Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Exterior Concrete Stairs Exterior Ramp
Fixed - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Double Glazing;
Storefront - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heat is provided by a Goodman model A8PF313716CA heat pump split system.Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Ventilation2.
Page: 8 of 106
Building: 0003 - WELCOME CENTER
PVC None
Hose Bibb Lavatory Mop Sink Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: 225A, 3PH, 4W, 208Y/120V secondary electrical service is being provided from 150A MCB MDP in Janitor's Closet, via concrete encased ductbank from a pole mounted utility transformer.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
High Intensity Discharge (HID) Comments: Exterior lighting is provided by site pole-mounted High Intensity Discharge (HID) light fixtures.
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling is provided by a Goodman model A8PF313716CA heat pump split system.Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
LIGHTING
Page: 9 of 106
Building: 0003 - WELCOME CENTER
FIRE ALARM
Comments: There are no fire alarm devices within this building.
Comments: The telephone and WAN server are located in the security area.
Connected to Main System Black & White Monitor None Local Cable Company
Telephone Security Public Address Television
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Area Recommended Recorded Light Type
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
There is no CO source in the building.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 6 - VOCATIONAL BUILDING TRADES
Page: 10 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick EIFS
Comments: Northwest offices and vocational shops have EIFS cladding. Southwest offices are clad with brick veneer.
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 17,436 10,581 1 Owned 1990 Not Evaluated
Comments: The building fire alarm system has adequate audio/visual alarm devices throughout except in toilets.
The building is split-level and the grade of the building site allows exterior access to both levels without ramps.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Material
The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.
Drainage Year Life
Type Area Served
Asphalt Shingles
Single Ply
Built-up Roofing
Gutters and Downspouts
Gutters and Downspouts
Gutters and Downspouts
Hip
Flat
Flat
Offices
Shop Area
Shop Area
Comments:
3. Roof
Page: 11 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
Wall Roof Polystyrene Batt
INTERIOR FINISH
Ceramic Tile Concrete Rubber Tile Vinyl Tile Wood
CMU Drywall Painted CMU
Metal Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder Wood Stairs
Metal Rollup - Metal Frame Metal Units - Metal Frame Storefront - Storefront Frame
Casement - Aluminum Frame; Double Glazing; Double Hung - Aluminum Frame; Double Glazing;
Double Hung - Steel Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Insulation4.
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Page: 12 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
Mechanical
Mechanical
Dust Collection
Restroom
Welding Booths
Shop Area
Comments: The carpentry shop is equipped with a dust collection system.
Ventilation Area Served
Split Direct Expansion (Air
Source)
Direct Expansion Refrigerant
Single Duct
Single Duct
Refrigerant
None
Electronic
Electric
Natural
Mechanical
None
None
Classrooms and Offices
Classrooms and Offices
Exhaust Ventilation
The Trane furnace is equipped with evaporator coils matched to a Trane outdoor air cooled condensing unit.
Three Carrier model 48TFE004---511-- packaged rooftop units serve classrooms and offices.
Comments:
Comments:
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Three Carrier model 48TFE004---511-- packaged rooftop units serve classrooms and offices.
An explosion-proof electric unit heater serves the flammable storage room.
A Trane model TUC1D100 furnace serves the addition.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Gas-Fired
Electric Resistance
Gas-Fired Furnace
Single Duct
Unit Heater
Unit Heater
Single Duct
None
None
None
None
Electric
Electric
Electric
Electronic
Mechanical
Natural
Natural
Natural
None
None
None
None
Classrooms and Offices
Shop Area
Storage
Classrooms and Offices
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Page: 13 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
Two A.O. Smith commercial water heaters serve the building. One is 50 gallons and one is 40 gallons.
Comments:
Cast-Iron None None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Portable Bottled Water Cooler Portable Emergency Eyewash Sink Urinal Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Service is brought from three 50 kVA pad-mounted transformers located in the back of the building and terminates in an 800A switchboard in the electrical room.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are controlled by time clock and photocell.
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Page: 14 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Siemens Desigo located in the Scheduling Office
Comments: CCTV cameras are installed in the corridor and on the building exterior.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Closed Circuit TV None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Motion sensor switches are installed in the toilets.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent & Incandescen
T8 - Fluorescent
T5 - Fluorescent
T8 - Fluorescent & Incandescen
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Vocational
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Good
Type Location None None
There are no CO detectors in this building.
CARBON MONOXIDE DETECTION
Detection Required No
IMPAIRMENT
Page: 15 of 106
Building: 0006 - VOCATIONAL BUILDING TRADES
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 12 - ADMINISTRATION
Page: 16 of 106
Building: 0012 - ADMINISTRATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Stucco on Structural Clay Tile
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 12,835 7,510 2 Owned 1930 Not Eligible
Comments: The first floor is accessible through a secondary entry at the north-east side of the building. The main entrance at the west side, is elevated above grade and is accessed through an exterior concrete stair.
The basement level is accessible through a newly built exterior concrete ramp and an interior ramp.
The building's fire alarm system does not have visual alarm devices.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
N/A
Yes
No
No
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Page: 17 of 106
Building: 0012 - ADMINISTRATION
Wall Roof None Gypsum Vermiculite
Metal Unit - Metal Frame Storefront - Storefront Frame
Double Hung - Vinyl Frame; Double Glazing; Double Hung - Wood Frame; Single Glazing;
Insulation4.
Exterior Doors5.
Windows6.
Material
Interior roof drains are supplemented with scuppers and downspouts. The roof membrane and parapet flashing show signs of premature deterioration and in some areas have come lose from the wall. The cornice above the first floor windows has a flat metal roof. The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.
The entry canopy roof was built by CTST and is covered with asphalt shingles.
Drainage Year Life
Type Area Served
Single Ply
Asphalt Shingles
EPDM
Asphalt Shingles
Interior Roof Drains
Gutters and Downspouts
Interior Roof Drains
Surface Run-off
Flat
Hip
Flat
Gable
Offices
Vestibule
Offices
Vestibule
Number of Deficiencies = 1
Comments:
Comments:
3. Roof
Page: 18 of 106
Building: 0012 - ADMINISTRATION
INTERIOR FINISH
Asbestos Tile Carpet Ceramic Tile Concrete Rubber Tile Vinyl Tile
Ceramic Tile Drywall Plaster Wallcovering Wood Paneling
Aluminum Storefront - Aluminum Frame Metal Unit - Metal Frame
Wood Unit - Metal Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Metal Stairs Ramp
Acoustical Tile Gypsum Board Plaster
Exhaust Ventilation
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Packaged Direct Expansion Heat PumpComments:
HVAC
Heat1. Asbestos: Yes
Gas-Fired Packaged
Electric Resistance
Single Duct
Baseboard Convector
None
None
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Offices
Page: 19 of 106
Building: 0012 - ADMINISTRATION
The water heater is a 40-gallon Reliance model 64020RT2 residential unit with a 4500W input.Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Lavatory Portable Bottled Water Cooler Sink Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Galvanized Steel Galvanized Steel Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Window Unit None Electric Mechanical None Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 20 of 106
Building: 0012 - ADMINISTRATION
Comments: Service is brought from platform-mounted transformers to a 1200A switchboard located in the Gear Room basement. The switchboard serves this building and Buildings 3 and 13. An electronic meter is installed next to the switchboard.
FIRE ALARM
Comments: The fire alarm devices in this building are not connected to a fire alarm control panel.
Comments: The main telephone switchboard, LAN and WAN server are located in this building on the first floor.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Motion sensor switches are installed in the toilets and copy room.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocell.
T8 - Fluorescent & incand
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 5
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
There is no CO source in the building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
Page: 21 of 106
Building: 0012 - ADMINISTRATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The exterior windows are not insulated and are deteriorating. Some basement walls suffered water damage from leaking windows. The roof is in poor condition.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AZone
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 13 - SOCIAL HALL/CAREER DEVELOPMENT
Page: 22 of 106
Building: 0013 - SOCIAL HALL/CAREER DEVELOPMENT
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood and Steel
Stucco on Structural Clay Tile
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3,B 11,520 6,958 2 Owned 1930 Eligible
Comments: The first floor is accessible via a concrete ramp. The basement level is at grade level. The stage on the first floor is not accessible. There are no restrooms on the first floor and the restrooms on the lower level are not ABA compliant. The building fire alarm system has adequate audio/visual alarm devices throughout except in toilets.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
Yes
Yes
Yes
No
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 2
Material
The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey. The gutters are undersized and leak. The wood eaves have rotted, broken and/or missing pieces.
Drainage Year Life
Type Area Served
Asphalt Shingles
Ballasted Built-up Roofing
Single Ply
Gutters and Downspouts
Leader Boxes and Downspouts
Surface Run-off
Gable
Flat
Flat
Entire Building
Auditorium
Porch
Comments:
3. Roof
Page: 23 of 106
Building: 0013 - SOCIAL HALL/CAREER DEVELOPMENT
Wall Roof None Rigid
Comments: The original single glazed basement windows have been replaced with insulated units.
INTERIOR FINISH
Asbestos Tile Carpet Ceramic Tile Concrete Epoxy Vinyl Tile Wood
Ceramic Tile Drywall Plaster Wood Panel
Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder Metal Stairs Ramp Wood Stairs
Metal Unit - Metal Frame Storefront - Storefront Frame
Double Hung - Vinyl Frame; Double Glazing; Double Hung - Wood Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Insulation4.
Exterior Doors5.
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Page: 24 of 106
Building: 0013 - SOCIAL HALL/CAREER DEVELOPMENT
Natural Restroom
Ventilation Area Served
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
Refrigerant
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Auditorium
Offices
Exhaust Ventilation
The first floor auditorium is cooled with packaged rooftop units.
The basement office furnaces are provided with evaporator coils matched to York model…
This is the start of the file's text. The full file is on GovTribe.