Attachment_J-9_Facility_Survey-Volume_II.pdf

PDF 7 MB Posted

Attached to
Solicitation for Milwaukee JCC Federal contract opportunity
Solicitation number
1630J4-18-R-00002
Issued by
Department of Labor Employment and Training Administration

About this file

Attachment J-9 Facility Survey-Volume II

View the file

Other files for this federal contract opportunity

Other files attached to Solicitation for Milwaukee JCC, newest first.
File Type Posted
1630J4-18-R-00002_Amendment_0004_Milwaukee_Q&A.docx DOCX document
1630J4-18-R00002_Amendment_0004_GSA_Fleet_Milwaukee.pdf PDF
1630J4-18-R-00002_Amendment_0004_Revised_pg_40-41.docx DOCX document
1630J4-18-R00002_Amendment_0004_F.5_Deliverable_Schedule_Milwaukee.docx DOCX document
Sol_1630J4-18-R-00002_Amd_0004.pdf PDF
1630J4-18-R-00002_-__Amendment_0003_-_Milwaukee_Q&A.pdf PDF
1630J4-18-R-00002_Amendment_0003.pdf PDF
Sol_1630J4-18-R-00002_Amd_0002.pdf PDF
Final_Milwaukee.pdf PDF
Price_Detail_(Attachment_J-1_Revised_1-25-2018).xlsx XLSX spreadsheet
1630J4-18-R-00002_Amendment_0002.pdf PDF
1630J4-18-R-00002_Amendment_0002_Milwaukee_Q&A.pdf PDF
Amendment_0002(Attachment_J-1_Revised_1-25-2018).xlsx XLSX spreadsheet
Attachment_J-12_Utilities_and_Fuel_Usage.pdf PDF
Sol_1630J4-18-R-00002_Amd_0001.pdf PDF
Attachment_J-10_-_Master_Property_List.pdf PDF
Attachment_J-6_Subcontracting_Plan_Summary_Sheet.docx DOCX document
Attachment_J-11_Inventory_Estimate.xlsx XLSX spreadsheet
Attachment_J-9_Facility_Survey_-_Volume_I.pdf PDF
Attachment_J-1_Price_Detail.xlsx XLSX spreadsheet
Attachment_J-2_Statement_of_Financial_Capability.docx DOCX document
Attachment_J-4_Staffing_Chart.docx DOCX document
Attachment_J-7_Past_Performance_Questionnaire.docx DOCX document
Attachment_J-8_Statement_and_Acknowledgement.docx DOCX document
Attachment_J-5_List_of_CTST_Slots.docx DOCX document
Sol_1630J4-18-R-00002.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MILWAUKEE

Job Corps Center Milwaukee, WI

Facility Planning Report Volume II

Supporting Data

Final March 2016

Department of Labor/ Office of Job Corps

MILWAUKEE

Job Corps Center Milwaukee, WI

Facility Planning Report Volume II

Supporting Data

Final March 2016

Campus Yard between Dormitories and Gymnasium/Recreation Buildings

VOLUME II - SUPPORTING DATA

EXECUTIVE SUMMARY

1.0 SITE LAYOUT AND PLANS

• Location Map

• Exisiting Site Plan

2.0 DESCRIPTIONS

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Environmental Management Report

• Asbestos Report

• Radon Report

• Site Descriptions

• Building Descriptions

3.0 DEFICIENCIES

APPENDICES - CORRESPONDENCE AND REPORTS

Appendix A.

• Center Review Meeting Minutes

• Survey Brief

• Student Questionnaire

Appendix B.

• Life Safety Defi ciencies and List

Appendix C.

• O&M Defi ciencies List

Appendix D.

• Active Warranty List

Executive Summary

The facility survey for the Grafton JCC was completed July 13, 2015 – July 17, 2015.

The information presented in Volume II, Supporting Data, represents the current status of the campus.

The information includes the following:

Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;

active warranties; and Federal Real Property Council (FRPC) Measures Matrix

Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:

Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix

EXECUTIVE SUMMARY

1.0 - Site Layout and Plans

MILWAUKEE

JOB CORPS CENTER

MILWAUKEE, WISCONSIN

MILWAUKEE

JCC

10 MI50

2.0 - Descriptions

BUILDINGS AND STRUCTURES

00513 MILWAUKEE 03/30/2016

1Page: of Date:

0100 - WELCOME CENTER

0101 - ADMINISTRATION/WELLNESS

CENTER

0102 - STUDENT SERVICES

0103 - EDUCATION/MAINTENANCE

0104 - CAFETERIA/WAREHOUSE

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0107 - GYMNASIUM/RECREATION

B - MASONRY MATERIALS BIN (12Ft x 24Ft) C - MASONRY MATERIALS BIN (12Ft x 12Ft)

Name GSF

1,427 11,735

9,658 42,494 13,973 26,679 27,401 21,035

Active Active

Active Active Active Active Active Active Active

Active

StatusType

Building Building

Building Building Building Building Building Building Structure

Structure

Use Group Built Flrs Const

B B

B B A-2 R-2 R-2 A-3 Storage

Storage

Good Good

Good Good Good Good Good Good Good

Good

ConditionAsset Number

0051300004 0051300005

0051300006 0051300007 0051300008 0051300009 0051300010 0051300011 0051300013

0051300014

8 154,402

2 432

10 154,834

Buildings

Structures

Total

GSF

GSF

GSF

Summary

03/30/2016

Space Utilization By Function 00513 Milwaukee Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 212 Non Residents 25

237Total Students

(212)

(237)

(237)

DIFFERENCE

22,896

17,880

1,896

34,983

28,168

2,590

Lounge Other Shower/Toilet Sleeping excl. SPD(72 rooms; 272 beds) Storage

Academic (237) Non-Academic

13 -- ACT (Off-Ctr) 20 -- Cement Masonry + 30 -- Manufacturing Technology + 30 -- Material Handler 30 -- Medical Office Support 80 -- Nursing Assistant + 24 -- Welding +

Vocational Theory (154)

Dining (2 Servings)

6,050 2,412 5,600

19,578 1,343

4,687 6,429

3,055 3,053 2,610

2,609 3,035

1,741

2,590

2,120 1,696 2,544

15,264 1,272

2,370 2,370

1,500 2,250 1,950

3,200 1,800

1,540

1,896

3,930

3,056 4,314

2,317 4,059

1,555

-591 1,235

Vocations

12,087

10,288

03/30/2016

Space Utilization By Function 00513 Milwaukee Page: 2 of Date:

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 272.46 64,572 99,654

(237)

(237)

(237)

(237)

(0)

DIFFERENCE

154,402

0.65

TOTAL GSF

NET TO GROSS RATIO

10,975

1,445

4,740

15,270

2,428

7,213

5,509

3,493

Aerobics/Exercise Arts & Crafts Gymnasium Learning Resource Center/Library Meeting Room Miscellaneous Recreation Recreation Hall Recreation Office Recreation Storage Snack Bar Theater Weight Room

Medical/Dental

Administration

Operations & Maintenance Warehouse

Vacant

6.10

7,248

1,315 1,509

2,428

7,213

2,635 2,874

3,493

1,445

1,896 2,844

7,248

1,315 1,509

2,473

3,493

RESIDENT

NON-RESIDENT

(212)

(25) 15

50 10,600

4,295

2,473

3,493

35,082

Net Square Footage By Building Date: 03/30/2016 Page: 1

Center: MILWAUKEE (00513) of 3

HOUSING

EDUCATION

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Academic

Vocational Theory (154)

Cement Masonry

Welding

Non-Academic

Nursing Assistant

Material Handler

Medical Office Support

Manufacturing Technology

Function Suggested

NSF

9,772 9,806

3,066 2,984

2,800 2,800

1,329 1,083

4,687

1,741

3,055

3,035

6,429

2,609

2,610

3,053

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0106 - MEN'S DORMITORY

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0105 - WOMEN'S DORMITORY

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

0102 - STUDENT SERVICES

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

Bldg Name Actual NSF Difference

19,578

6,050

1,343

5,600

2,412

4,687

1,741

3,055

3,035

6,429

2,609

2,610

3,053

Sub Total:

Sub Total:

34,983

28,168

15,264

2,120

1,272

2,544

1,696

2,370

1,540

1,500

1,800

2,370

3,200

1,950

2,250

22,896

17,880

4,314

3,930

3,056

2,317

1,555

1,235

4,059

-591

12,087

10,288

36 rooms; 136 beds 36 rooms; 136 beds

Page: 2

Center: MILWAUKEE (00513) of 3

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

Dining (2 Servings)

Recreation Hall

Snack Bar

Arts & Crafts

Gymnasium

Weight Room

Theater

Miscellaneous Recreation

Aerobics/Exercise

Meeting Room

Learning Resource Center/Lib

Recreation Storage

Recreation Office

Medical/Dental

Function Suggested

NSF

2,590

1,509

7,248

1,315

2,428

0104 - CAFETERIA/WAREHOUSE

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0107 - GYMNASIUM/RECREATION

0101 - ADMINISTRATION/WELLNESS CENTER

Bldg Name Actual NSF Difference

2,590

1,509

7,248

1,315

2,428

Sub Total:

Sub Total:

Sub Total:

2,590

15,270

2,428

1,896

1,445

1,896

10,975

1,445

4,295

Page: 3

Center: MILWAUKEE (00513) of 3

ADMINISTRATION

STORAGE/SUPPORT

VACANT

Administration

Warehouse

Operations & Maintenance

Vacant

Function Suggested

NSF

5,665

2,874

2,635

3,493

0100 - WELCOME CENTER

0101 - ADMINISTRATION/WELLNESS CENTER

0103 - EDUCATION/MAINTENANCE

0104 - CAFETERIA/WAREHOUSE

0103 - EDUCATION/MAINTENANCE

0103 - EDUCATION/MAINTENANCE

Bldg Name Actual NSF Difference

7,213

2,874

2,635

3,493

Sub Total:

Sub Total:

Sub Total:

7,213

5,509

3,493

4,740

2,844

1,896

4,740

4,740

2,473

3,493

2,473

3,493

Environmental Management Report

Center: MILWAUKEE (00513) Page: 1 Date: 03/30/2016 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

HAZARDOUS MATERIALS STORAGE (EPCRA)

N/A

No

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance :

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Yes

No N/A

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

No Survey Required due to Age of Buildings None

N/A No N/A No No

ID Fuel Type Capacity Location Overfill

Prevention Secondary ContainmentTank Status

Tank Status Prevention/Detection

Radon

Date: 03/30/2016Center : Milwaukee (00513) Page: 1 of 1

0100 - WELCOME CENTER

0101 - ADMINISTRATION/WELLNESS CENTER

0102 - STUDENT SERVICES

0103 - EDUCATION/MAINTENANCE

0104 - CAFETERIA/WAREHOUSE

0105 - WOMEN'S DORMITORY

0106 - MEN'S DORMITORY

0107 - GYMNASIUM/RECREATION

Bldg Name Test Date

No

No

No

No

No

No

No

No

Radon Testing

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description

Aerial photogrph of the Center and surroundings

Page: 1 Date: 03/30/2016 of 4

Comments:

Paving Type for Roads & Parking

Parking spaces are adequate throughout the Center. However, the asphalt roads throughout the Center have single line and alligator cracks. At the time of the July 2015 facility survey the Center was in the process of repairing some of the single line cracks in the asphalt roads. The areas with alligator cracks, if not repaired, will further deteriorate to become depressions in the road. A deficiency was written to address this issue.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing. The Center also has a frisbee golf course around the entire Center.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterCity of MilwaukeePublic Water Authority

None 0None

Each building has its own sub meter. Cafeteria is supplied with water softener system.Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time

(Minutes)

Yes 0 3None Municipal

Number of Deficiencies = 3

Number of Deficiencies = 1

SITE FEATURES

UTILITIES

2. Fire Protection System

Buildings Structures8 2Gently Sloping

Surrounding

Outdoor Recreation

Light Industrial, Residential

Basketball, Field, Soft/Baseball, Volleyball Rail Road Tracks

Along east side of the site

Along three sides of the site

Entrance

Wrought Iron

Chain Link

Automatic Gate and Manual

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good

Fencing

Other Features

Page: 2 Date: 03/30/2016 of 4

Sewage Treatment Flow

Utility

Publicly Owned Treatment Works

Center

Gravity

Maintenance ResponsibilityOwnership

WE Energies

Comments: Heating and Cooling is provided by a geothermal heat pump system and four heating boilers. It consists of 60 bores under the north parking lot. Water flow is maintained in the system using primary/secondary pumping system using n+1 redundancy, two pumps in parallel flow and one in standby each with variable speed drives.

Heat pumps add or remove heat from the loop to maintain space temperature of areas they serve. Primary pumps are manufactured by Bell & Gossett, model 1510BFW10.25, with a capacity of 190 GPM and 100 feet of head each. The four gas-fired boilers are manufactured by Lockinvar; model KBN399, with a capacity of 383.9 MBH each. The three secondary circulating pumps are manufactured by Bell and Gosset, model 1510BFW12.125, with a capacity of 235 GPM and 145 feet of head each. The system circulates water in the range of 55 to 90 degrees fahrenheit to all water source heat pumps on the site.

3. Sanitary Sewer System/ Sewage Treatment Plant

5. Fuel Distribution System

6. Central Plant

System Capacity Adequate System Condition

Yes Good

4. Storm Water System

Drain Type On-Site Storm Water Management

Underground Retention Pond

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

Comments: All the storm water inlets around the Center drain into the large storm water retention pond which is located at the south end of the Center near Welcome Center Building100.

Gas Company Metering

Individual

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Utility Yes Good

Type Energy Source

Geothermal with Gas Boilers Natural Gas Building 101 thru 107 Bldgs Served

Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition

Center Center Yes Good

Page: 3 Date: 03/30/2016 of 4

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Wisconsin Electric (WE) Energies

The primary overhead service is brought to the Center from transmission lines along the west perimeter of the campus. The overhead lines transit to underground service which loops around the campus, starting from the northwest of the campus and connecting back to the overhead lines at the southwest of the Campus. The underground service feeds pad-mounted transformers with corresponding current transformer cabinets and secondary meters located behind each building served. Welcome Center Building 100 is subfed from Administration/ Wellness Center Building 101.

Pad Utility

Utility, Center Utility, Center

No

Comments:

Telephone Company

On-site Line Owner

Each building on Center is protected by an addressable central fire alarm control panel. The fire alarm system in each building on Center is connected to the central fire alarm control/annunciator panel located in the security office in Welcome Center Building 100. Direct Television (TV) satellite dishes are installed on the roof of all buildings except Welcome Center Building 100 and Administartion/Wellness Building 101.

AT&T

Maint. Responsibility

Center Utility, Center

IP Cameras, Welcome Center Building 100

UnknownCenterActive Underground, RegulatedSouth side of Cafeteria/Warehouse

Building 104

NoN/A

STORAGE TANKS

TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date

24.94/14.4 kV, 3-Phase, 4 Wire

120/208 Volt, 3-Phase, 4 WireUnderground

UndergroundPrimary Service

Secondary Service

Distribution Characteristics

ID

Reg.

Number of Deficiencies = 2

9. Electrical (Communication/Alarm/Security)

Cooking

Purpose

7. Electrical (Service)

Yes

Central

VOIP

System Capacity Adequate System Condition

GoodYes

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Good

Generator

None

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Pole, Building Sport Light

Lighting Control Panel Lighting Control Panel Lighting Control Panel Lighting Control Panel Lighting Control Panel

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Comments: The site lighting on Center is both pole and building mounted controlled by lighting control panels. All site lighting on Center is owned and maintained by the Center.

ATS MTS

No Yes

Number of Deficiencies = 2

Fire Alarm Security

Metering Individual

Page: 4 Date: 03/30/2016 of 4

ACCESSIBILITY

Yes

Comments:

NoNoNo

There are no historical preservation issues at the Milwaukee JCC. All eight (8) buildings were constructed in 2010.

No

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk Low Low LowLow LowIBC Low

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

Yes

Yes

NO

Yes

Yes

Yes

Yes

Yes

26 %

Building Descriptions and Structures

BUILDING 100 - WELCOME CENTER

Building Descriptions

Page: 1 of 57

Building: 0100 - WELCOME CENTER

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Steel

Brick Masonry Concrete Corrugated Metal Panels Phenolic Panels System

Wall Roof Rigid Rigid

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 1,427 554 1 Owned 2010 Not Evaluated

Comments: Toilet rooms are designed and designated for severe weather shelter areas. A severe weather shelter sign is posted at the entrance of the designated toilet rooms.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

N/A

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.

Drainage Year Life

Type Area Served

EPDM

Metal

Interior Roof Drains

Gutters and Downspouts

Flat

Shed

Western half of building

Eastern half of building

Comments:

3. Roof

Entire Building

Area Served

Page: 2 of 57

Building: 0100 - WELCOME CENTER

INTERIOR FINISH

Carpet Ceramic Tile Vinyl Tile

CMU

Wood Unit - Metal Frame

Mechanical

Mechanical

Restroom

Janitor's Closet

Comments:

Comments:

EF-W-1 75 CFM, 115V/1p direct drive serve room 101. Manufactured by Cook

EF-W-2 75 CFM, 115V/1p direct drive serve room 106. Manufactured by Cook

Ventilation Area Served

VERTICAL CIRCULATION

None

Aluminum Unit - Aluminum Frame

Fixed - Aluminum Frame; Double Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

EDH-W-1 Electric duct heater Carrier model 0FCIII114, 4.0 kW 208V/1p 365 CFM is controlled by wall mounted thermostat iin the control room. There is a wall mounted unit heater at the south-east entrance door..

Comments:

HVAC

Heat1. Number of Deficiencies = 1

Electric Resistance

Single Duct None Direct Digital Control (DDC)

Mechanical None Lounge

Ventilation2.

Ceilings

Page: 3 of 57

Building: 0100 - WELCOME CENTER

Water heating is by two instantaneous electric water heaters one is located in the rest room and the other is located in the janitor's closet.

Comments:

PVC None PVC

Drinking Fountain Lavatory Mop Sink Wall Hydrant Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Copper Copper Tankless Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Single Duct None Electronic Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

FC-W-1 DX fan coil ( Carrier model FE4ANFOO2, SN 0909A8F973), 17.3 mbh gross cooling with 8.1 kW electric heat 208V/1p. Condensing unit ACCU-W-1 (Carrier model 25HPA51BA300, SN 2106E13736)) 17.0 mbh gross 208V/1p and 13.00 minimum EER, R410A. The unit, when running, provide 150 cfm of oustide air thru wall vent that provide makeup air for exhaust and ventilation requirements.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Air Conditioning

Page: 4 of 57

Building: 0100 - WELCOME CENTER

Comments: Underground service for the 150A main branch panel in this building is provided from a 150A breaker in the 400A main distribution panel (MDP), located in the electrical room of the Administration/Wellness Center Building 100. A meter is located on the outside of this Building.

FIRE ALARM

Comments: The fire alarm control/annunciator panel is a Simplex 4100U unit located in the Security Staff area. This panel is the central fire alarm panel that monitors all other panels on Center.

Comments: This building houses the monitor for all cameras on the Center. All cameras on Center are connected to the network. This building also houses the wireless public address system.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Central Annunciator Panel Smoke Detector

Connected to Main System Color Monitor Connected to Main System None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

Compact Fluorescent Comments: Exterior lighting is controlled by a lighting control panel.

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

Offices

Reception

Toilets

Storage Rooms

Area Recommended Recorded Light Type

None None

Main Branch Panel 120/208V, 3-Phase, 4 Wire Branch Panel Only GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas Yes N/AZone

BUILDING UTILITY METERING

Type Location

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required No

Number of Deficiencies = 0

Page: 5 of 57

Building: 0100 - WELCOME CENTER

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

Potential Impaired Comments DOL Determination Discussion/Comments

BUILDING 101 - ADMINISTRATION/WELLNESS CENTER

Page: 6 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Steel

Brick Masonry Concrete Corrugated Metal Phenolic Panel System

Wall Roof Rigid Rigid

Aluminum Units - Aluminum Frame Metal Unit - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 11,735 8,093 1 Owned 2010 Not Evaluated

Comments: Toilet rooms are designed and designated for severe weather shelter areas. A severe weather shelter sign is posted at the entrance of the designated toilet rooms.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

There are overflow scuppers on the roof to assist with drainage.

Drainage Year Life

Type Area Served

EPDM Interior Roof Drains 2010 15 Flat Entire Building

Comments:

3. Roof

Page: 7 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

CMU Ceramic Tile Drywall

Wood Unit - Metal Frame

VERTICAL CIRCULATION

None

Fixed - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure Gypsum Board

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop through units HPU-A-1 thru 4, manufactured by AQUARIUS model AP025-1HZC, AP025-1HZC, AP049-1HZC and AP049-1HZC respectively. Air temperature supplied by these units is controlled by temperature sensors installed in return air ducts.

Comments:

HVAC

Heat1. Number of Deficiencies = 1

Packaged Heat Pump (Water

Source)

Single Duct Two-Pipe Direct Digital Control (DDC)

Mechanical Heat Recovery Entire Building

Page: 8 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

Mechanical

Mechanical

Mechanical

Entire Building

Mechanical Room

Electrical Room

Comments:

Comments:

Comments:

An energy recovery unit ERV-A-1 serves this entire building by exhausting air from the building and bringing in fresh air from the outside, while transferring heating or cooling energy from the exhaust air to the fresh air. The fresh air from the ERV-A-1 is ducted into the return of HVAC air distribution system, units HPU-A-1 thru 4. ERV-A-1 is manufactured by GREENHECK, model ERV-3615-15-B-ES, with a supply fan having a capacity of 1055 CFM and an exhaust fan having a capacity of 1055 CFM (980 CFM actual exhaust)

Exhaust fan EF-A-1 serves Mechanical Room 108. EF-A-1 is manufactured by Faco, with a supply fan capacity of 125 CFM and characteristics: 129W, 115V, single phase, direct drive.

Exhaust fan EF-A-2 serves Electrical Room 109. EF-A-2 is manufactured by Cook with a supply fan capacity of 40 CFM and characteristics: 38W, 115V, single phase, direct drive.

Ventilation Area Served

Packaged Heat Pump (Water

Source)

Split Direct Expansion (Air

Source)

Single Duct

Single Duct

Two-Pipe

None

Direct Digital Control (DDC)

Electronic

Mechanical

Natural

Heat Recovery

None

Entire Building

Electronic Equipment

Room

Exhaust Ventilation

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop through units HPU-A-1 thru 4, manufactured by AQUARIUS model AP025-1HZC, AP025-1HZC, AP049-1HZC and AP049-1HZC respectively. Air temperature supplied by these units is controlled by temperature sensors installed in return air ducts.

A 4 ton split-system which consists of a condensing unit, ACCU-A-1 with a capacity of 42 MBH, and an indoor fan-coil unit, ACU-A-1, with a supply fan capacity of 950 CFM, serves Computer Room 155.

The fan-coil unit is manufactured by Mitsubishi, model PLAA42BA.

Comments:

Comments:

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Page: 9 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

This building also has electric instantaneous water heaters.Comments:

PVC None PVC

Drinking Fountain Lavatory Mop Sink Shower Sink Wall Hydrant Water Closet (Flush Valve) Waterless Urinal

Gas (Natural)

Comments:

None None ABC Type Fire Extinguisher

Comments: Electrical service to this building is provided from a utility-owned pad-mounted 150 kVA transformer, located north of the building and terminates in a 400A main distribution panel (MDP), located in the electrical room. The MDP is protected by a factory-installed 250 kA transient surge suppression (TVSS) module. The MDP feeds panelboards in the building and also provides 150A service to the Welcome Center. A meter is located on the building near the transformer.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Compact Fluorescent Comments: Exterior lighting is controlled by a lighting control panel.

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Branch Panel & Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2. Number of Deficiencies = 1

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Natural gas water heaters WH-A-1 AO Smith MODEL BTH120100 with circulting pump PWH-A-A B&G 1032571000

LIGHTING

Page: 10 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

FIRE ALARM

Comments: The fire alarm control/annunciator panel is a Simplex 4100U unit located in the vestibule. The building fire alarm system is monitored by the central fire alarm control/annunciator panel in Welcome Center Building 100.

Comments: The CCTV cameras in this building are monitored from the Welcome Center Building 100. The public address system is a wireless connection to Welcome Center Building 100.

Audible Alarm Control/Annunciator Panel Magnetic Door Holder Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV Connected to Main System None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. A lighting control relay panel is located in Storage Room 102.

T5 - Fluorescent

T5 - Fluorescent & CFL

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

Offices

Conference Rooms

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Lounges

Toilets

Storage Rooms

Medical/Dental

Wards (Patient)

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Emergency Exit

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas Yes YesZone

BUILDING UTILITY METERING

Type Location There is no plausible means by which harmful levels of CO could enter sleeping rooms.

CARBON MONOXIDE DETECTION

Detection Required

Page: 11 of 57

Building: 0101 - ADMINISTRATION/WELLNESS CENTER

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 102 - STUDENT SERVICES

Page: 12 of 57

Building: 0102 - STUDENT SERVICES

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Metal Steel

Brick Masonry CMU Masonry Corrugated Metal Phenolic Panel System

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 9,658 6,429 1 Owned 2010 Not Evaluated

Comments: There are enclosed straight run egress stairs located on the east side of the building which access the emergency exit door. The stair landing is designed as an area of refuge for persons with physical limitations. If the person requires assistance with exiting the building there is a rescue assistance button on the wall at the landing that will signal at the Welcome Center Building 100.

Toilet rooms are designed and designated for severe weather shelter areas. A severe weather shelter sign is posted at the entrance of the designated toilet rooms.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Material

There are overflow scuppers on the roof to assist with drainage. The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.

Drainage Year Life

Type Area Served

EPDM

Metal

Interior Roof Drains

Gutters and Downspouts

Flat

Shed

Southern half of builing

Northern half of building

Comments:

3. Roof

Page: 13 of 57

Building: 0102 - STUDENT SERVICES

Wall Roof Rigid Rigid

Comments: There are clerestory windows that provide natural light to the corridor.

INTERIOR FINISH

Carpet Ceramic Tile Vinyl Tile

CMU Drywall

Wood Unit - Metal Frame

VERTICAL CIRCULATION

None

Aluminum - Aluminum Frame Metal Unit - Metal Frame

Fixed - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure Metal Acoustical Panels

Insulation4.

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Page: 14 of 57

Building: 0102 - STUDENT SERVICES

Mechanical

Mechanical

Mechanical

Entire Building

Electrical Room

Mechanical Room

Comments:

Comments:

Comments:

An energy recovery unit ERV-S-1 serves this entire building by exhausting air from the building and bringing in fresh air from the outside, while transferring heating or cooling energy from the exhaust air to the fresh air. The fresh air from the ERV-A-1 is ducted into the return air of the HVAC air distribution system, units HPU-S-1 thru 4. ERV-S-1 is manufactured by GreenHeck, model ERV-361S-15-B-ES, with a supply fan with a capacity of 650 CFM and an exhaust fan with a capacity of 650 CFM.

Exhaust fan EF-S-1 serves Electrical Room 113. EF-S-1 is manufactured by Cook, with a supply fan capacity of 40 CFM and characteristics: 54W, 115V, single phase, direct drive.

Exhaust fan EF-S-2 serves Mechanical Room 112. EF-S-2 is manufactured by Cook, with a supply fan capacity of 40 CFM and characteristics: 54W, 115V, single phase, direct drive.

Ventilation Area Served

Packaged Heat Pump (Water

Source)

Single Duct Two-Pipe Direct Digital Control (DDC)

Mechanical Heat Recovery Entire Building

Exhaust Ventilation

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop through units HPU-S-1 thru 4 are manufactured by Florida Heat Pump (FHP), model AP049-1HZC, AP049-1HZC, AP075-1HZC & SG119120 respectively.

Comments:

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating is provided by a geothermal heat pump system. The geothermal system consists of 60 borefields with three end suction pumps that have variable frequency drives. These three pumps are manufactured by Bell & Gossett, model 1510BFW10.25, with a capacity of 190 gpm and 100 feet of head each. Four gas-fired boilers, manufactured by Lockinvar, model KBN399, with a capacity of

383.9 MBH each. The four boilers have a total of three circulating pumps, manufactured by Bell & Gosset, model 1510BFW12.125, with a capacity of 235 gpm and 145 feet of head each. These pumps distribute water to the Center that allows the heat pumps in this building to deliver warm air.

The heat pumps that serve this building are HPU-S-1 through 4, manufactured by Florida Heat Pump (FHP), model AP049-1HZC, AP049-1HZC, AP075-1HZC & SG119120 respectively.

Comments:

HVAC

Heat1. Number of Deficiencies = 1

Packaged Heat Pump (Water

Source)

Single Duct Two-Pipe Direct Digital Control (DDC)

Mechanical Heat Recovery Entire Building

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Page: 15 of 57

Building: 0102 - STUDENT SERVICES

PVC None PVC

Drinking Fountain Lavatory Mop Sink Multi-Compartment Sink Wall Hydrant Water Closet (Flush Valve) Waterless Urinal

None

None None ABC Type Fire Extinguisher

Comments: Electrical service to this building is provided from a 75 kVA utility owned pad-mounted transformer, located south of the building and terminates in a 400A main distribution panel (MDP), located in the electrical room. The MDP is protected by a factory-installed 250 kA transient surge suppression (TVSS) module. A meter is located on the building near the transformer.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Compact Fluorescent Comments: Exterior lighting is controlled by a lighting control panel.

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

Page: 16 of 57

Building: 0102 - STUDENT SERVICES

FIRE ALARM

Comments: The fire alarm control/annunciator panel is a Simplex 4100U unit located in the vestibule. The building fire alarm system is monitored by the central fire alarm control/annunciator panel in Welcome Center Building 100.

Comments: The cameras in this building are monitored from Welcome Center Building 100. The public address system is a wireless connection to Welcome Center Building 100.

Audible Alarm Control/Annunciator Panel Magnetic Door Holder Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV Connected to Main System Satellite Dish

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. A lighting control relay panel is located in electrical room 113.

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

Offices

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Lounges

Toilets

Storage Rooms

Classrooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Emergency Exit

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas Yes N/AYes

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

Type Location

CARBON MONOXIDE DETECTION

Detection Required

Page: 17 of 57

Building: 0102 - STUDENT SERVICES

IMPAIRMENT

Potentially Impaired

DOL Responded

BUILDING 103 - EDUCATION/MAINTENANCE

Page: 18 of 57

Building: 0103 - EDUCATION/MAINTENANCE

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Steel

Brick Masonry CMU Masonry Corrugated Metal Panels Phenolic Panel System

Wall Roof Rigid Rigid

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

B 42,494 28,861 1 Owned 2010 Not Evaluated

Comments: Toilet rooms are designed and designated for severe weather shelter areas. A severe weather shelter sign is posted at the entrance of the designated toilet rooms.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

There are overflow scuppers on the roof to assist with drainage. The condition and life expectancy of the roof is based on visual observation during the July 2015 Facility Survey.

Drainage Year Life

Type Area Served

EPDM

Metal

Interior Roof Drains

Surface Run-off

Flat

Shed

The southern half of building

Northern half of roof

Comments:

3. Roof

Page: 19 of 57

Building: 0103 - EDUCATION/MAINTENANCE

Comments: There are fixed rated wire safety glass and clerestory windows in the corridor.

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

CMU Ceramic Tile Drywall

Aluminum - Aluminum Frame Metal Unit - Metal Frame

VERTICAL CIRCULATION

None

Aluminum - Aluminum Frame Metal Unit - Metal Frame

Fixed - Aluminum Frame; Double Glazing; Fixed - Metal Frame; Double Glazing;

Acoustical Tile Exposed Structure Gypsum Board Wood Planks

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Page: 20 of 57

Building: 0103 - EDUCATION/MAINTENANCE

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

AT-E-2 60 mbh output gas fired unit heater; 7000 CFM propeller fan with 500 CFM induced outside air, 208V/3p, 2"TA 30%.Johnson/Arizon model AR05.5SAA-1-FG-1, SN 1-30-09-21064-AT-E-2

AT-E-3 60 mbh output gas fired unit heater; 7000 CFM propeller fan with 500 CFM induced outside air, 208V/3p, 2"TA 30%.Johnson/Arizon model AR05.5SAA-1-FG-1, SN 1-30-09-21064-AT-E-3

AT-E-4 228.7 mbh output gas fired unit heater; 7000 CFM propeller fan with 2500 CFM induced outside air, 208V/3p, 2"TA 30%. Johnson/Arizon model AR05.5SAA-1-FG-1, SN 1-30-09-21064-AT-E-

AT-E-5 228.4 mbh output gas fired unit heater; 7000 CFM propeller fan with 2500 CFM induced outside air, 208V/3p, 2"TA 30%. Johnson/Arizon model AR05.5SAA-1-FG-F, SN 1-30-09-21064-AT-E-

AT-E-6 148.3 mbh output gas fired unit heater; 7000 CFM propeller fan with 1500 CFM induced outside air, 208V/3p, 2"TA 30%. Johnson/Arizon model AR05.5SAA-1-FG-F, SN 1-30-09-21064-AT-E-

B-E-1,2,3 & 4 in Mechanical room 100D; Building supplementary water heating system consists of 4 water boilers. Each natural gas boiler is capable of providing 384 mbh net output, 120V-1p. The system includes 3 primary pumps and 3 secondary pumps with variable frequency drives. The system has an additional pump for corridor in-floor heating zone1 which is tapped directly off the supplementary boilers.

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Hot Water Boiler

None

None

None

None

None

None

Geothermal Secondary

Loop

None

None

None

None

None

None

Electronic

Electronic

Electronic

Electronic

Electronic

Electronic

Direct Digital Control (DDC)

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

None

None

None

None

None

None

None

Shop Area

Shop Area

Shop Area

Shop Area

Shop Area

Shop Area

Page: 21 of 57

Building: 0103 - EDUCATION/MAINTENANCE

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Entire Building

Mechanical Room

Electric Room

Equipment Room

Shop Area

Welding Booths

Battery Room

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

Two energy recovery units ERV-E-1 and ERV-E-2 serve this entire building by exhausting air from the building and bringing in fresh air from the outside, while transferring heating or cooling energy from the exhaust air to the fresh air. The fresh air from the ERV-E-1 and ERV-E-2 is ducted into the HVAC air distribution system. ERV-E-1 serves units HPU-E-1, 6 and7 and ERV-E-2 serves units HPU-E-2 thru 5. ERV-E-1 is manufactured by GreenHeck, model ERV-361S-15-B-ES, with a supply fan capacity of 900 CFM and an exhaust fan capacity of 900 CFM. ERV-E-2 is manufactured by GreenHeck, model ERV-361H-30-B-ES, with a supply fan capacity of 1245 CFM and an exhaust fan capacity of 1245

CFM.

Exhaust fan EF-E-1 serves Mech Room 106. EF-E-1 is manufactured by Cook, model 135ACE135CI0D, with a supply fan capacity of 1081 CFM and characteristics: 1/4HP, 115V, single phase, direct drive.

Exhaust fan EF-E-2 serves Electrical Room 106A. EF-E-2 is manufactured by Cook with a supply fan capacity of 230 CFM and characteristics: 135W, 115V, single phase, direct drive.

Exhaust fan EF-E-3 serves Lawn Equipment Storage Room 105A. EF-E-3 is manufactured by Cook with a supply fan capacity of 680 CFM and characteristics: 350W, 115V, single phase, direct drive.

Exhaust fan EF-E-4 serves Block Saw Room 103E. EF-E-4 is manufactured by Cook with a supply fan capacity of 680 CFM and characteristics: 350W, 115V, single phase, direct drive.

Exhaust fans EF-E-5 and EF-E-6 serve Welding Room 102. EF-E-5 and EF-E-6 are manufactured by Cook, with a supply fan capacity of 2500 CFM each and characteristics: 1HP, 208V, three phase, direct drive.

Exhaust fan EF-E-7 serves the battery charging area in Manufacturing Room 100. EF-E-7 is manufactured by Cook with a supply fan capacity of 1500 CFM and characteristics: 1/2HP, 115V, single phase, direct drive.

Ventilation Area ServedExhaust Ventilation

Page: 22 of 57

Building: 0103 - EDUCATION/MAINTENANCE

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Packaged Heat Pump (Water

Source)

Single Duct

Single Duct

Single Duct

Single Duct

Single Duct

Single Duct

Single Duct

Two-Pipe

Two-Pipe

Two-Pipe

Two-Pipe

Two-Pipe

Two-Pipe

Two-Pipe

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Direct Digital Control (DDC)

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Heat Recovery

Heat Recovery

Heat Recovery

Heat Recovery

Heat Recovery

Heat Recovery

Heat Recovery

Classrooms and Offices

Classrooms and Offices

Classrooms and Offices

Classrooms and Offices

Classrooms and Offices

Classrooms and Offices

Classrooms and Offices

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-1. Manufactured by FHP, model AP025- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-1, 2.0 Ton water source HP 21.3/29.9 mbh clg/24.6 mbh htg, 13 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E- 2. Manufactured by FHP, model AP035- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-2, 3.0 Ton water source HP 28.0/39.0 mbh clg/33.1 mbh htg, 13 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-3. Manufactured by FHP, model AP035- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-3, 3.0 Ton water source HP 31.2/40.6 mbh clg/31.9 mbh htg, 13 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-4. Manufactured by FHP, model AP049- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-4, 4.0 Ton water source HP 34.1/51.0 mbh clg/46.1 mbh htg, 15 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-5. Manufactured by FHP, model AP049- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-5, 4.0 Ton water source HP 34.2/51.0 mbh clg/45.1 mbh htg, 15 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-6. Manufactured by FHP, model AP025- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-6, 2.0 Ton water source HP 20.8/27.9 mbh clg/23.2 mbh htg, 8 gpm

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-7. Manufactured by FHP, model AP061- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-7, 5.0Ton water source HP 50.1/67.5 mbh clg/56.6 mbh htg, 16 gpm

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Page: 23 of 57

Building: 0103 - EDUCATION/MAINTENANCE some Lavs with instantaneous electric heatersComments:

PVC None PVC

Drinking Fountain Fixed Emergency Eyewash Hose Bibb Lavatory Mop Sink Wall Hydrant Water Closet (Flush Valve) Water Closet (Tank) Waterless Urinal

Gas (Natural)

None None ABC Type Fire Extinguisher

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Heat Pump (Water

Source)

Single Duct Two-Pipe Direct Digital Control (DDC)

Mechanical Heat Recovery Classrooms and Offices

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Heat pumps with extended range deliver cooled/heated forced air to the building using the geothermal system secondary water loop thru units HPU-E-8. Manufactured by FHP, model AP061- 1HZC. Unit supply air temperature is controlled using temperature sensor installed in return air duct.

HPU-E-8, 5.0 Ton water source HP 51.9/66.4 mbh clg/57.3 mbh htg, 16 gpm

Comments:

Water Distribution1.

Sanitary Distribution2. Number of Deficiencies = 1

Fixtures3.

Fuel Distribution4.

Page: 24 of 57

Building: 0103 - EDUCATION/MAINTENANCE

Comments: Electrical service to this building is provided from a utility owned 500 kVA pad-mounted transformer, located west of the building and terminates in a 1600A main switchboard, located in the electrical room.

The MDP is protected by a factory-installed 250 kA transient surge suppression (TVSS) module. A meter is located on the building near the transformer.

FIRE ALARM

Comments: The fire alarm control/annunciator panel is a Simplex 4100U unit located in the vestibule. The building fire alarm system is monitored by the central fire alarm control/annunciator panel in Welcome Center Building 100.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Magnetic Door Holder Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution. There are two lighting control relay panels in this building, located in Electrical Room 106A and Student Commons Room 128C.

Compact Fluorescent Comments: Exterior lighting is controlled by a lighting control panel.

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

T5 - Fluorescent

O…