FINCH-HENRY
Job Corps Center Batesville, MS
Facility Planning Report Volume II
Supporting Data
Final June 2016
Department of Labor/ Office of Job Corps
FINCH-HENRY
Job Corps Center Batesville, MS
Facility Planning Report Volume II
Supporting Data
Final June 2016
Cafeteria north elevation
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The facility survey for Finch-Henry, Batesville, Mississippi Job Corps Center (Finch-Henry JCC) was completed from February 17, 2016 through February 19, 2016. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing buildings and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site, buildings, and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through the Program Year 2015 Survey Supporting documentation, as presented in the appendices of the Center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans, while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new deficiencies identified in this Program Year 2015 Survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. Operations and Maintenance (O&M) Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
FINCH-HENRY
JOB CORPS CENTER
BATESVILLE, MISSISSIPPI
FINCH-HENRY JCC
10 MI50
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00412 FINCH-HENRY 06/22/2016
1Page: of Date:
0001 - ADMIN/HEALTH SERVICES
0002 - CAFETERIA/CULINARY ARTS
0003 - EDUCATION/HARD VOC
0004 - RECREATION
0005 - FEMALE DORMITORY
0006 - MALE DORMITORY
0007 - WAREHOUSE
0008 - GYMNASIUM
0009 - MALE DORMITORY
0010 - GUARD HOUSE
0010A - SECURITY/EDUCATION
0011 - STORAGE
0014 - MULTIPURPOSE
0019 - STUDENT GOVERNMENT
0021 - VACANT
0022 - VACANT
0024 - CTS CAREER CENTER
0029 - VOC STORAGE
0030 - MALE DORMITORY
0001A - ADMIN GAZEBO (12Ft x 28Ft) 0004A - RECREATION GAZEBO (12Ft x 12Ft) 0010B - EDUCATION GAZEBO (12Ft x 12Ft) 0015 - PRESS BOX (10Ft x 12Ft) 0016 - PICNIC SHELTER (17Ft x 13Ft) 0018 - PICNIC SHELTER (13Ft x 14Ft) 0020 - GAZEBO (12Ft x 12Ft) 0025 - RECYCLING (12Ft x 12Ft) 0026 - STORAGE (12Ft x 12Ft) 0027 - COVERED WALKWAY (8Ft x 154Ft) 0028 - GREENHOUSE (24Ft x 10Ft) 0031 - PICNIC SHELTER (25Ft x 38Ft)
0032 - STUDENT BLEACHERS
0033 - STUDENT BLEACHERS
0034 - PEDESTRIAN BRIDGE
0035 - PEDESTRIAN BRIDGE
0036 - MASONRY BENCH
0037 - DUGOUT
0038 - DUGOUT
0039 - BALL FIELD BLEACHER
0040 - BALL FIELD BLEACHER
Name GSF
14,375 9,175
26,130 8,075
13,350 7,282
10,785 9,965
13,350
3,120
5,145
2,870 1,800
13,500
1,500
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure
Structure
Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
B A-2,B B,F-1 A-3 R-2 R-2 S-1,B A-3 R-2 B B S-1 B,A-3 A-3 R-2 R-2 B S-1 Residential U U
U
B A-3 A-3 U U S-1 U B Assembly Assembly Assembly Assembly Assembly Assembly Assembly Assembly Assembly Assembly
Good Good Good Good Fair Poor Good Good Fair
Good Good Good Good Fair Poor Poor Good Good Good Good Good
Good
Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0041200002 0041200003 0041200004 0041200005 0041200006 0041200007 0041200008 0041200009 0041200010 0041200011 0041200021 0041200012 0041200015 0041200020 0041200024 0041200025 0041208099 0041208105 0041208106 0041208098 0041208096
0041208097
0041200016 0041200017 0041200019 0041200022 0041208100 0041208101 0041208102 0041208104 0041208120 0041208121 0041208122 0041208142 0041208143 0041208144 0041208145 0041208146 0041208147 0041208148
BUILDINGS AND STRUCTURES
00412 FINCH-HENRY 06/22/2016
2Page: of Date:
19 141,362
21 5,631
40 146,993
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/22/2016
Space Utilization By Function 00412 Finch-Henry Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 200 Non Residents 26
226Total Students
(200)
(300)
(226)
DIFFERENCE
21,600
20,670
4,068
32,988
29,572
5,295
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (300) Non-Academic
10 -- ACT (Off-Ctr) 24 -- Bricklayer + 24 -- Carpentry + 30 -- Culinary Arts + 24 -- Material Handler 30 -- Nurse's Aide + 30 -- Office Administration 24 -- Painting + 24 -- Welding +
Vocational Theory (156)
Dining (2 Servings) Food Preparation Food Storage
3,716 2,268 2,467
24,321
3,592 8,034
2,689 2,460 1,450 2,360 2,069 1,210 2,102 2,388
1,218
2,465 1,901
2,000 1,600 2,400
14,400 1,200
3,000 3,000
1,800 1,800 1,800 1,560 1,200 1,350 1,800 1,800
1,560
1,808 1,356
1,716
9,921 -984
5,034
-350 -140
-342
Vocations
11,388
8,902
1,227
06/22/2016
Space Utilization By Function 00412 Finch-Henry Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 297.40 67,213 100,865
(226)
(226)
(226)
(226)
(0)
DIFFERENCE
141,362
0.71
TOTAL GSF
NET TO GROSS RATIO
10,390
1,445
4,520
14,786
1,910
6,134
9,180
1,000
Gymnasium Hair Salon Meeting Room Miscellaneous Recreation Recreation Office Recreation Room Recreation Storage Snack Bar T.V. Room Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
6.39
6,336
4,287
1,910
6,134
1,875 7,305
1,000
1,445
1,808 2,712
6,336
4,287
1,614
4,593
1,000
RESIDENT
NON-RESIDENT
(200)
(26) 15
50 10,000
4,396
1,614
4,660
1,000
33,652
Net Square Footage By Building Date: 06/22/2016 Page: 1
Center: FINCH-HENRY (00412) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
6,500 6,500 8,000 3,321
1,710
1,634
1,113
0005 - FEMALE DORMITORY
0009 - MALE DORMITORY
0030 - MALE DORMITORY
0006 - MALE DORMITORY
0005 - FEMALE DORMITORY
0006 - MALE DORMITORY
0009 - MALE DORMITORY
0011 - STORAGE
0014 - MULTIPURPOSE
0009 - MALE DORMITORY
0006 - MALE DORMITORY
0005 - FEMALE DORMITORY
0006 - MALE DORMITORY
0009 - MALE DORMITORY
0005 - FEMALE DORMITORY
Bldg Name Actual NSF Difference
24,321
3,716
2,467
2,268
Sub Total: 32,988
14,400
2,000
1,200
2,400
1,600
21,600
9,921
1,716
-984
( 200
11,388 rooms; beds rooms; beds rooms; beds rooms; beds
Page: 2
Center: FINCH-HENRY (00412) of 4
EDUCATION
Academic
Vocational Theory (156)
Carpentry
Culinary Arts
Welding
Painting
Bricklayer
Non-Academic
Nurse's Aide
Material Handler
Office Administration
Function Suggested
NSF
1,348
1,256
1,218
1,916
1,450
2,388
1,550
2,145
1,260
1,085 1,120
1,059
2,069
2,360
1,210
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0029 - VOC STORAGE
0002 - CAFETERIA/CULINARY ARTS
0003 - EDUCATION/HARD VOC
0029 - VOC STORAGE
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
0029 - VOC STORAGE
0002 - CAFETERIA/CULINARY ARTS
0010A - SECURITY/EDUCATION
0001 - ADMIN/HEALTH SERVICES
0005 - FEMALE DORMITORY
0014 - MULTIPURPOSE
0010A - SECURITY/EDUCATION
0014 - MULTIPURPOSE
0003 - EDUCATION/HARD VOC
0024 - CTS CAREER CENTER
0003 - EDUCATION/HARD VOC
0024 - CTS CAREER CENTER
0001 - ADMIN/HEALTH SERVICES
0014 - MULTIPURPOSE
0003 - EDUCATION/HARD VOC
0003 - EDUCATION/HARD VOC
Bldg Name Actual NSF Difference
3,592
1,218
2,460
1,450
2,388
2,102
2,689
8,034
2,069
2,360
1,210
Sub Total: 29,572
3,000
1,560
1,800
1,800
1,800
1,800
1,800
3,000
1,200
1,560
1,350
20,670
-342
-350
5,034
-140
( 300
8,902
Page: 3
Center: FINCH-HENRY (00412) of 4
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Dining (2 Servings)
Food Preparation
Food Storage
Snack Bar
Gymnasium
Weight Room
Miscellaneous Recreation
Hair Salon
Recreation Room
T.V. Room
Meeting Room
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
2,465
1,901
6,336
4,287
1,910
0002 - CAFETERIA/CULINARY ARTS
0002 - CAFETERIA/CULINARY ARTS
0002 - CAFETERIA/CULINARY ARTS
0004 - RECREATION
0008 - GYMNASIUM
0004 - RECREATION
0004 - RECREATION
0008 - GYMNASIUM
0004 - RECREATION
0004 - RECREATION
0004 - RECREATION
0019 - STUDENT GOVERNMENT
0008 - GYMNASIUM
0008 - GYMNASIUM
0001 - ADMIN/HEALTH SERVICES
Bldg Name Actual NSF Difference
2,465
1,901
6,336
4,287
1,910
Sub Total:
Sub Total:
Sub Total:
5,295
14,786
1,910
1,808
1,356
1,445
4,068
10,390
1,445
1,227
4,396
Page: 4
Center: FINCH-HENRY (00412) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
5,259
7,305
1,655
0003 - EDUCATION/HARD VOC
0010 - GUARD HOUSE
0001 - ADMIN/HEALTH SERVICES
0010A - SECURITY/EDUCATION
0007 - WAREHOUSE
0011 - STORAGE
0007 - WAREHOUSE
0022 - VACANT
0021 - VACANT
Bldg Name Actual NSF Difference
6,134
7,305
1,875
1,000
Sub Total:
Sub Total:
Sub Total:
6,134
9,180
1,000
4,520
2,712
1,808
4,520
4,520
1,614
4,593
1,000
1,614
4,660
1,000
Environmental Management Report
Center: FINCH-HENRY (00412) Page: 1 Date: 06/22/2016 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
N/A N/A
N/A No
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
BFI, Inc.
No N/A
N/A N/A N/A N/A
N/A N/A
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
05/22/1990 None N/A
N/A N/A N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Radon
Date: 06/22/2016Center : Finch-Henry (00412) Page: 1 of 1
0001 - ADMIN/HEALTH SERVICES
0002 - CAFETERIA/CULINARY ARTS
0003 - EDUCATION/HARD VOC
0004 - RECREATION
0005 - FEMALE DORMITORY
0006 - MALE DORMITORY
0007 - WAREHOUSE
0008 - GYMNASIUM
0009 - MALE DORMITORY
0010 - GUARD HOUSE
0010A - SECURITY/EDUCATION
0011 - STORAGE
0014 - MULTIPURPOSE
0019 - STUDENT GOVERNMENT
0021 - VACANT
0022 - VACANT
0024 - CTS CAREER CENTER
0029 - VOC STORAGE
0030 - MALE DORMITORY
Bldg Name
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
N/A
No
N/A
N/A
N/A
No
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Site Area
Page: 1 Date: 06/22/2016 of 4
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualCity of BatesvillePublic Water Authority
None 0None
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 0 7None Municipal
The nearest Batesville fire station is about two miles away from the center and the emergency response time is about 7 minutes.
Number of Deficiencies = 3
Number of Deficiencies = 2
Number of Deficiencies = 1
Number of Deficiencies = 1SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures19 21Gently Sloping
Surrounding
Outdoor Recreation
Light Industrial, Rural
Ball Field, Field, Volleyball Creek, Pedestrian Bridges
Ball Field
Lift Station
Portion of Property Line -East
Portion of Property Line-South
Property Line -North & West
Chain Link
Chain Link
Wrought Iron with Brick Piers
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Poor Yes Fair
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 06/22/2016 of 4
Comments:
Sewage Treatment Flow
Sewer from the center flows into the city sewer system by means of a lift station located on the northern side of the center within the security fence. The City of Batesville owns, operates and maintains the lift station.
Center
Publicly Owned Treatment Works
Center
Gravity and Lift Stations
Maintenance ResponsibilityOwnership
Comments: The City of Batesville supplies natural gas for cooking and domestic water heating.
City of Batesville
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Tallahatchie Valley Electric Power Association
Service is brought to the center from primary overhead lines along Highway 51 east of the campus. The system is radial with single point of entry at the center main entrance where primary metering occurs. From the entry point at the east, the primary overhead lines branch out to the southwest and northwest serving buildings throughout the center. The secondary services are mostly underground with pole-mounted transformers. There are two small capacity movable gas-engine-driven generators located in Warehouse Building 7.
Pole Utility
Utility Utility
No
13.200/7.620 kV, 3-Phase
120/208V, 3-Phase, 4 WireOverhead
OverheadPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
Number of Deficiencies = 2
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 6
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes FairCenter
Comments: There are surface water runoff catch basins strategically located within the center. These catch basins are connected to underground drain pipes which drain the surface water runoff into the creek. Some leaking underground drain pipes have undermined the soil, resulting in sinkholes.
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Gasoline
ATS MTS
No No
6. Central Plant: None
Metering Master
Page: 3 Date: 06/22/2016 of 4
Comments:
Telephone Company
On-site Line Owner
Telephone service is provided by AT&T with three T1 lines which terminate in the main electrical room of Admin/Health Services Building 1. Local telephone service is provided by Universal Solutions. Long distance telephone service and LAN and WAN networks are provided by Job Corps Data Center (JCDC). The telephone system equipment, including cables, is maintained under the services contract with Universal Solutions. Data transmission between buildings and the server is by fiber optic cables. The server is supported by a 2 kVA portable UPS module. The phone system has limited public address (PA) capability, using the phone internal speakers. The fire alarm system in buildings on center is stand-alone. Carbon monoxide detectors are provided in all dormitories. Cable TV is provided in the dormitory, dining and recreational facilities.
AT&T/Universal Solutions
Maint. Responsibility
Utility Utility
None
N/AN/AN/A NoneN/A NoN/A
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
9. Electrical (Communication/Alarm/Security)
N/A
Purpose
No
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Sport Light
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Time Clock, Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Fair
Comments: The utility owns and maintains all lights on power poles along the roadways. The center owns and maintains all building-mounted exterior lights, sport lights and pole-mounted walkway lights.
Number of Deficiencies = 2
Number of Deficiencies = 8
Fire Alarm Security
Page: 4 Date: 06/22/2016 of 4
ACCESSIBILITY
Yes
Multipurpose Building 14 and the softball field are separated from the main campus by a creek. Two pedestrian bridges, one of which is ADA accessible, provide access to this area.
Comments:
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Medium MediumMedium MediumIBC Medium
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 2
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
The site has poor drainage. Broken/separated underground storm drain lines are deteriorated and leaking causing depressions and sinkholes. During periods of heavy rain large quantities of run-off flow in to the sinkholes increasing the rate of erosion. Roadways and paved concrete surfaces are deteriorated exhibiting potholes throughout the Center.
Due to high water levels during flooding seasons the drainage ditch embankments are eroded. Soil was also washed out from underneath concrete approach aprons making both bridges unsafe to use.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Yes
NO
NO
NO
NO
Yes
Yes
Yes
Building Descriptions and Structures
BUILDING 1 - ADMIN/HEALTH SERVICES
Building Descriptions
Page: 1 of 92
Building: 0001 - ADMIN/HEALTH SERVICES
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
CMU Masonry Wood Siding
Wall Roof Styrofoam Cell Inserts Batt
Metal Unit - Metal Frame Storefront - Aluminum Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 14,375 8,277 1 Owned 1980 Not Evaluated
Comments: The restroom grab bars are of an older design and do not meet the current guidelines for accessibility in stalls. The building fire alarm system has adequate audio/visual alarm devices throughout except in toilets. Finshes are old and worn - especially the carpet floor throughout the building Administartion wing.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2009 33 Gable Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 92
Building: 0001 - ADMIN/HEALTH SERVICES
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Comments: Garpet is old, stained and worn throughout the Admin wing
CMU Ceramic Tile Drywall Wall Covering Wood Paneling
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
Mechanical Toilet/Shower
Comments: Ceiling-mounted exhaust fans ventilate the toilet/shower rooms.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There are concrete ramps leading to the entries.
Fixed - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile
Exhaust Ventilation
Number of Deficiencies = 2
Number of Deficiencies = 1
Windows6. Number of Deficiencies = 1
Floors1. Number of Deficiencies = 2
Interior Walls2. Number of Deficiencies = 2
3.
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Nine vertical gas-fired furnaces (eight units are in a twinned arrangement) provide heating to the health services, orientation wing and administration part of the building. These are located in three mechanical rooms. The typical furnace is a Goodman model GMS81155CNAA, 115 MBH gas input, built in 05/2006.
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Furnace
Single Duct None Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 3
Ceilings
Page: 3 of 92
Building: 0001 - ADMIN/HEALTH SERVICES
Three gas-fired water heaters provide domestic hot water to the building. Two 40-gallon capacity Rheem Fury water heaters (model 22V40F1, S/N RHLN0907A21835 and RHLN0900782183, 38 MBH gas input, built in 09/2007 and 03/2011) are located in a janitor closet in the administration area and in a mechanical room in the orientation wing. Another 85-gallon capacity PVI water heater is located in the mechanical room adjacent to the male ward.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Hose Bibb Lavatory Service Sink Shower/Bathtub Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
Refrigerant
None
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Nine vertical gas-fired furnaces (eight units are in a twinned arrangement) with DX-cooling coils (Goodman model CAPF4860C6AA, built in 03/2006) mounted on the discharge provide cooling to the health services, orientation wing and administration part of the building. These are located in three mechanical rooms. The outdoor condensing units (on-grade, R-22 refrigerant) are Goodman model CLK120-3L, 10-ton cooling capacity, built in 06/2006, Goodman model GSC101203BB-10-10 ton capacity built in 2015.
Three Haier window air conditioning units provide supplemental cooling to the northeast corner offices.
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 4 of 92
Building: 0001 - ADMIN/HEALTH SERVICES
Comments: The underground service is brought from three 37.5 kVA pole-mounted transformers east of the building. Service terminates in a 600A MDP, main lug only (MLO) located in the electrical room. The health service in this building is supported by a 5 kW movable gas-engine-driven generator located in Warehouse Building 7.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4100U, located in the electrical room. A Simplex remote annunciator panel is located in the building main entrance.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Comments: In addition to fluorescent lights there are some self-contained emergency lights in the corridor.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Reception
Toilets
Toilets
Storage Rooms
Classrooms
Medical/Dental
Wards (Patient)
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 5
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 3
LIGHTING
Page: 5 of 92
Building: 0001 - ADMIN/HEALTH SERVICES
Comments: The server and telephone equipment are located in the main electrical room of this building.
Connected to Main System None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Carpets are old, stained and deteriorated throughout the building.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good
Type Location
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 1
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 2 - CAFETERIA/CULINARY ARTS
Page: 6 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Pre-engineered building system
CMU Masonry Metal Siding
Wall Roof Styrofoam Cell Inserts Batt
Metal Unit - Metal Frame Storefront - Aluminum Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-2,B 9,175 7,125 1 Owned 1980 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 2
Material
The roof was repaired and re-coated in September 2011.
Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2011 16 Shed Entire Building
Comments:
3. Roof
Entire Building
Comments:
Page: 7 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Vinyl Tile
CMU Ceramic Tile Exposed Structure Metal Siding
Aluminum Storefront - Aluminum Frame Automatic Sliding Unit - Aluminum Frame
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
None
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A package (on-grade) gas-fired unit provides heating and fresh air to the dining and food services areas. The unit is a Trane Voyager model YCH480AELK0B3LE1A0C0000HJ0, S/N C02L10266, built in 12/2002 with rated input of 400 MBH and output of 324 MBH.
A split-system heat pump provides heating to the culinary arts classroom. The indoor unit is located in the attic. The outdoor condensing unit (on-grade, R-22 refrigerant) is a York model E1FD042S06D with 42 MBH heating capacity.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Split Heat Pump (Air
Source)
Single Duct
Single Duct
None
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Dining Hall
Classrooms
Page: 8 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
Mechanical
Mechanical
Mechanical
Kitchen
Dishwashing Hood
Restroom
Comments:
Comments:
Comments:
The kitchen hood is a Greenheck II model CD 16-SP, S/N 1152-H-1 with a supply capacity of 7650 CFM at 0.4" SP, and exhaust capacity of 8400 CFM at 1" SP.
A roof-mounted exhaust fan ventilates the dishwashing hood.
Ceiling-mounted exhaust fans ventilate the restrooms.
Ventilation Area Served
Split Heat Pump (Air
Source)
Packaged Direct
Expansion (Air Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
Single Duct
Refrigerant
None
None
Electric
Electric
Electric
Mechanical
Natural
Mechanical
None
None
None
Classrooms
Kitchen
Dining Hall
Exhaust Ventilation
A split-system heat pump provides cooling to the culinary arts classroom. The indoor unit is located in the attic. The outdoor condensing unit (on-grade, R-22 refrigerant) is a York model E1FD042S06D with a 3.5-ton cooling capacity.
Two window air conditioning units provide supplemental cooling to the kitchen.
A package (on-grade, R-22 refrigerant, three compressors) unit provides cooling and fresh air to the dining and food services areas. The unit is a Trane Voyager model YCH480AELK0B3LE1A0C0000HJ0, S/N C02L10266, built in 12/2002 with a 40-ton cooling capacity.
Comments:
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
3. Number of Deficiencies = 1Air Conditioning
Page: 9 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
A 250-gallon capacity PVI Ventura gas-fired water heater (model 54V250, S/N 0504113357, 540 MBH gas input, and 648 GPH recovery) located in the mechanical room provides domestic hot water to the building. The hot water loop has an in-line circulating pump (Armstrong model Astro-50B). Another 19-gallon capacity Bradford electric water heater (model M120U6SS-1NAL, S/N GH13885480, 1.5 kW) is located in the mechanical closet behind the women's toilet room in the dining area.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Multi-Compartment Sink Portable Emergency Eyewash Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING Number of Deficiencies = 1
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
Location UL300 Compliance Status Kitchen and Culinary Arts Compliant
Comments: The Ansul fire suppression systems in the kitchen and culinary arts are UL-300 Standard listed, have automatic shutoff gas valves, and a shunt-trip for electric cooking equipment under the hoods.
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 10 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
Comments: The underground service is brought from three 50 kVA pole-mounted transformers southeast of the building. Service terminates in an 800A MDP, main lug only (MLO), located in the electrical room.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4100U, located in the mechanical/electrical room. A Simplex remote annunciator panel is located in the manager's office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Equipment Rooms (Elec/Mech)
Toilets
Dining/Lunch Rooms
Dishwashing
Food Preparation
Classrooms
Storage/Warehouse-Active
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 9
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 3
Type Location
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 11 of 92
Building: 0002 - CAFETERIA/CULINARY ARTS
Connected to Main System None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 3 - EDUCATION/HARD VOC
Page: 12 of 92
Building: 0003 - EDUCATION/HARD VOC
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Portion of the building structure is a pre-engineered system
CMU Masonry Metal Siding Wood Siding
Wall Roof Styrofoam Cell Inserts Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B,F-1 26,130 18,675 1 Owned 1980 Not Evaluated
Comments: The building fire alarm system has adequate audio/visual alarm devices throughout except in toilets.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
The new shingle roof on the Building Addition/AA Meeting Classroom was installed in 2013.
Drainage Year Life
Type Area Served
Metal
Asphalt Shingles
Gutters and Downspouts
Gutters and Downspouts
Shed
Gable
Original Building
Building Addition/AA
Meeting Classroom
Comments:
3. Roof
Entire Building
Page: 13 of 92
Building: 0003 - EDUCATION/HARD VOC
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall Plywood Wall Covering Wood Paneling
Aluminum Storefront - Aluminum Frame Metal Unit - Metal Frame
Wood Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Metal Stairs Comments: There are stairs leading to the mezzanine floor in the material handler shop.
Metal Rollup - Metal Frame Metal Unit - Metal Frame Storefront - Aluminum Frame
Clerestory - Aluminum Frame; Fiberglass Glazing; Fixed - Aluminum Frame; Double Glazing;
Single Hung - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure
Number of Deficiencies = 1
Exterior Doors5.
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Page: 14 of 92
Building: 0003 - EDUCATION/HARD VOC
Dust Collection
Welding Fume Exhaust
Mechanical
Mechanical
Mechanical
Shop Area
Welding Booths
Shop Area
Paint Booth
Restroom
Comments:
Comments:
Comments:
Comments:
Comments:
The carpentry shop also has a cyclone type dust collector and the masonry shop is provided with a central exhaust fan with ducted intakes from selected workstations.
A ThermoTek heating and ventilation system (model TTH-18, 455 MBH gas input, built in 07/2011) provides tempered make-up air and ventilates the welding booths.
Wall-mounted exhaust fans provide general exhaust ventilation to each of the vocational shops.
A roof-mounted exhaust fan ventilates the paint booth.
Ceiling-mounted exhaust fans ventilate the restrooms.
Ventilation Area ServedExhaust Ventilation
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Four packaged through-the-wall heat pumps with supplemental electric resistance heating coils provide heating to the GED and reading classrooms. The typical heat pump is an Amana model PTH153A50AD, 13.3 MBH heating capacity.
Six vertical gas-fired furnaces in a twinned arrangement provide heating to the offices and classrooms. These are located in two mechanical rooms. The typical furnaces are Lennox model G40UH-60C-110-15, 110 MBH gas input, built in 09/2007 and Carrier model 58PAV111-20, 110 MBH gas input, built in 09/1996.
An air-handling unit with electric resistance heating coils provides heating to the retail sales classroom in the building annex. It is located above the ceiling.
A vertical gas-fired furnace provides heating to the office and classroom of the material handling shop. The unit is a Trane model TUD080C948H4 with 80 MBH gas input. It is located in the mezzanine mechanical room.
The gas-fired infrared tube heaters provide heating to the material handling and paint shops.
The gas-fired unit heaters provide heating to the welding, bricklayer and carpentry shops. The typical units are Sterling and Trane model GAND010AEF1000D with 100 MBH gas input.
Comments:
Comments:
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Gas-Fired Furnace
Electric Resistance
Gas-Fired Furnace
Gas-Fired
Gas-Fired
Through-The- Wall Unit
Single Duct
Single Duct
Single Duct
Radiant Heater
Unit Heater
None
None
None
None
None
None
Electric
Electric
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
Natural
Natural
None
None
None
None
None
None
Classrooms
Classrooms and Offices
Classrooms
Classrooms and Offices
Shop Area
Shop Area
Ventilation2. Number of Deficiencies = 3
Page: 15 of 92
Building: 0003 - EDUCATION/HARD VOC
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
Through-The- Wall Unit
Single Duct
Refrigerant
Refrigerant
None
Refrigerant
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
None
None
None
None
Classrooms
Classrooms and Offices
Classrooms
Classrooms and Offices
A split-system with DX-cooling coils mounted on the discharge provides cooling to the retail sales classroom in the building annex. It is located above the ceiling. The outdoor condensing unit (on-grade, R-22 refrigerant) is a Carrier model 38CKC060300, built in 03/1999, with a 5-ton cooling capacity.
A split-system with DX-cooling coils mounted on the discharge provides cooling to the office and classroom of the material handling shop. It is located in the mezzanine mechanical room. The outdoor condensing unit (on-grade, R-22 refrigerant) is a Trane model TTR060C100A1, built in 05/1999, with a 5-ton cooling capacity.
Four packaged through-the-wall heat pumps provide DX-cooling to the GED and reading classrooms.
The typical heat pump is an Amana model PTH153A50AD, 14 MBH cooling capacity.
Six vertical gas-fired furnaces in a twinned arrangement with DX-cooling coils (Lennox model C33- 62C-2F-3) mounted on the discharge provide cooling to the offices and classrooms. These are located in two mechanical rooms. The typical condensing unit (on-grade, R-22 refrigerant) is a Lennox model HS29-120-3Y, built in 05/2007 and 02/2008, with a 10-ton cooling capacity.
Comments:
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
3. Number of Deficiencies = 2Air Conditioning
Page: 16 of 92
Building: 0003 - EDUCATION/HARD VOC
Two 40-gallon capacity Rheem gas-fired water heaters (model 22V40F1, 38 MBH gas input and 38.4 GPH recovery) provide domestic hot water to the building.
Comments:
Comments:
Cast Iron None Cast Iron
The bricklayer, painting and material handling shops are provided with drain interceptors.
Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Multi-Compartment Sink Service Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher, Dry Chemical
Comments: The paint booth in the painting shop is provided with an Amerex dry chemical fire suppression system (model IS35ABC).
Comments: Underground service is brought from three 75 kVA pole-mounted transformers northeast of the building.
Service terminates in a 2000A switchboard located in the electrical room. The Center has a 5 kW movable gas-engine-driven generator located in Warehouse Building 7.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 7
Exterior Lighting1. Number of Deficiencies = 1
Page: 17 of 92
Building: 0003 - EDUCATION/HARD VOC
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4100U, located in the electrical room.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. The computer lab classrooms are provided with decorative track lights with compact fluorescent lamps.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Classrooms
Vocational
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 4
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location
CARBON MONOXIDE DETECTION
Detection Required No
IMPAIRMENT
Page: 18 of 92
Building: 0003 - EDUCATION/HARD VOC
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 4 - RECREATION
Page: 19 of 92
Building: 0004 - RECREATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Pre-engineered system
CMU Masonry Metal Siding
Wall Roof Styrofoam Cell Inserts Batt
Metal Unit - Metal Frame Storefront - Aluminum Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3 8,075 6,523 1 Owned 1980 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Roof over the rear service portion of the building is leaking.
Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 1980 5 Shed Entire Building
Number of Deficiencies = 2
Comments:
3. Roof
Entire Building
Page: 20 of 92
Building: 0004 - RECREATION
INTERIOR FINISH
Carpet Ceramic Tile Quarry Tile Rubber Vinyl Tile
CMU Ceramic Tile Drywall Metal Siding Wall Covering Wood Paneling
Wood Unit - Metal Frame
Mechanical
Mechanical
Snack Bar Hood
Restroom
Comments:
Comments:
A roof-mounted exhaust fan ventilates the snack bar cooking hood.
A roof-mounted exhaust fan ventilates the restroom.
Ventilation Area Served
VERTICAL CIRCULATION
None
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Fiberglass Glazing;
Single Hung - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plywood
Exhaust Ventilation
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A packaged gas-fired unit provides heating and fresh air to the building. The unit is a Trane model YCD300B4L0HB and S/N 353100379D, 250 MBH gas input, built in 01/2004, located on the ground at the southwest corner of the building.
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 2
Page: 21 of 92
Building: 0004 - RECREATION
A 40-gallon capacity Bradford White gas-fired water heater (200 MBH gas input) provides domestic hot water to the building. It is located in the storage room adjacent to the restrooms. In addition, a 30-gallon capacity Reliance electric water heater, 4.5 kW, provides domestic water to the beauty/barber shop.
Comments:
Cast Iron None None
Electric Water Cooler Lavatory Multi-Compartment Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
A packaged unit provides DX-cooling and fresh air to the building. The unit is a Trane model YCD300B4L0HB and S/N 353100379D, 25-ton cooling capacity, built in 01/2004, located on the ground at the southwest corner of the building.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Page: 22 of 92
Building: 0004 - RECREATION
Comments: Underground service is brought from three 37.5 kVA pole-mounted transformers southwest of the building. Service terminates in an 800A MDP located in the mechanical room.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4100U, located in the electrical room..
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Visual Alarm
Connected to Main System None None Local Cable Company
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. The TV room is provided with recessed compact fluorescent downlights.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
Equipment Rooms (Elec/Mech)
Toilets
Shaving, Make-Up, Grooming
Recreation
Recreation
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 3
COMMUNICATION
Electric Water Gas Yes YesNo
BUILDING UTILITY METERING
Type Location
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
Page: 23 of 92
Building: 0004 - RECREATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The "back of the house" service area (approximately 1000 square feet) has a leaky roof.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY…