PENOBSCOT
Job Corps Center Bangor, ME
Facility Planning Report Volume II
Supporting Data
Preliminary January 2018
Department of Labor/ Office of Job Corps
PENOBSCOT
Job Corps Center Bangor, ME
Facility Planning Report Volume II
Supporting Data
Preliminary January 2018
Flagpoles
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Existing Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The F status
The i
Secti detail status inform
Facility Surv . The inform s of the camp information
Existing s Overall st Space util Status of Details on and mech Presentati document Supportin meeting;
active wa on 1.0 of thi ls on the bui s as well as n mation as no
Appendix Appendix Appendix Appendix vey for the P mation presen pus.
includes the site layout tatus of exist lization by b environment n the site and hanical surve ion of the sta ted through t ng document survey brief rranties.
is volume ad ildings and s new ones ide oted below:
x A. Survey B x B. Life Saf x C. O&M D x D. Active W
Penobscot JC nted in Volu following:
ting building building and tal elements d buildings a ey and suppo atus of histor this survey tation, as pre f and student ddresses site structures. Se entified in th
Brief Questi fety Deficien
Deficiencies L Warranty Re
EXEC
CC was comp ume II, Suppo g and structu function com of the Cente and structure orting docum rical deficien esented in th t questionnai layout and p ection 3.0 pr his survey. T ionnaire ncies and Lis List eport
CUTIVE SU
pleted the w orting Data, ures mpared to re er’s operatio es based on a mentation ncies and co he appendice ire; life safet plans while S resents histo The appendi st
UMMARY
eek of Septe represents t ecommended ons architectural ompilation o es of the cent ty IA/IIA tra
Section 2.0 p oric deficienc ices provide ember 25, the current d standards l, electrical, f deficiencie ter review ansmittal;
presents cies and thei additional es ir
1.0 - Site Layout and Plans
PENOBSCOT
JOB CORPS CENTER
BANGOR, MAINE
PENOBSCOT JCC
10 MI5 0
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00103 PENOBSCOT 01/25/2018
1Page: of Date:
0005 - UNION STREET
0006 - DOW LANE STREET
0007 - FM GARAGE STORAGE
0008 - DINING HALL
0009 - VETERANS HALL
0010 - COOPER HALL DORMITORY
0011 - RECREATION CENTER
0015 - MAINTENANCE GARAGE
0016 - GROUP LIFE STORAGE
0026 - FM LANDSCAPE GARAGE
0028 - GATE HOUSE
0012 - GAZEBO (16Ft X 16Ft ) 0013 - GAZEBO (12Ft x 12Ft) 0014 - MAINTENANCE STORAGE 1 (16Ft x 16Ft) 0017 - HBI LUMBER STORAGE (16Ft x 40Ft)
0017A - CDC STORAGE (9FT X 9FT)
0017B - CDC STORAGE (9FT X 9FT)
0017C - MOCK-UP (6FT X 8FT)
0018 - MAINTENANCE STORAGE 2 (12Ft x 18Ft)
0019 - MAINT/MOTOR POOL GARAGE
(16Ft x 30Ft) 0020 - RECREATION STORAGE (20Ft x 24Ft) 0022 - SOLAR SHED (12Ft x 12Ft) 0023 - FM STORAGE SHED 2 (8Ft x 20Ft) 0024 - SAFETY SHED (10Ft x 12Ft) 0025 - FM STORAGE SHED 3 (6Ft x 8Ft) 0027 - PAVILION (14Ft x 24Ft)
0030 - BALLFIELD
00T1 - TRANSFORMER 1 (6Ft x 6Ft) 00T2 - TRANSFORMER 2 (6Ft x 6Ft) 00T3 - TRANSFORMER 3 (6Ft x 6Ft) 00T4 - TRANSFORMER 4 (6Ft x 6Ft) 00T5 - TRANSFORMER 5 (6Ft x 6Ft)
Name GSF
41,480 29,120 1,270
12,130 29,140 29,978 23,990
150,000
Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active Active Active Active
Active
Active
Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure
Structure
Structure Structure Structure Structure
Structure
Structure
Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business Business Storage Assembly Residential Residential Assembly Storage Storage Storage Utility/Misc.
Assembly Assembly Storage
Storage
Storage Storage Storage Storage
Storage
Storage
Storage Storage Storage Storage Assembly Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Good Good Good Good Good Good Good Good Fair
Good Good Good Fair
Good
Good
Good Good Good Fair
Good
Good
Good Good Fair Fair
Good Good Good Good Good Good Good
ConditionAsset Number
0010300006 0010300007 0010300008 0010300009 0010300010 0010300011 0010300012 0010300016 0010300017 0010308135 0010308137 0010300013 0010300014 0010300015
0010300018
0010308138 0010308139 0010308140 0010300019
0010300020
0010308127
0010308129 0010308130 0010308131 0010308133 0010308136 0010308146 0010308141 0010308142 0010308143 0010308144 0010308145
11 169,538
21 153,788
32 323,326
Buildings
Structures
Total
GSF
GSF
GSF
Summary
01/25/2018
Space Utilization By Function 00103 Penobscot Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 264 Non Residents 9
273Total Students
(264)
(346)
(273)
DIFFERENCE
28,512
23,280
7,098
38,559
30,948
7,244
Lounge Other Shower/Toilet Sleeping excl. SPD(72 rooms; 304 beds) Storage
Academic (346) Non-Academic
10 -- ACT (Off-Ctr) 10 -- Advanced Culinary Arts + 24 -- Carpentry + 60 -- Cert. Nursing Asst.
60 -- Culinary Arts + 48 -- Facilities Maint. and Const. + 30 -- Medical Assistant 24 -- Welding +
Vocational Theory (166)
Dining (1 Serving) Food Preparation Food Storage
1,121 6,989 5,637
24,443
5,842 7,826
2,247 2,949 4,684 1,596 3,717 1,373
2,554 3,760
2,640 2,112 3,168
19,008 1,584
3,460 3,460
1,800 2,400 3,600 3,600
1,800
1,660
4,368 1,638 1,092
-1,519 4,877 2,469 5,435 -1,215
2,382 4,366
1,084 -2,004 2,817
-427
-946
-1,814 2,122
-162
Vocations
10,047
7,668
Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 312.85 85,409 111,701
(273)
(273)
(273)
(273)
(273)
(0)
DIFFERENCE
13,335
1,445
5,460
5,460
17,524
2,954
6,428
5,986
1,616
Aerobics/Exercise Arts & Crafts Auditorium Gymnasium Miscellaneous Recreation Multipurpose Room Racquetball Recreation Hall Recreation Storage Snack Bar Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
SECURITY
Vacant
5.29
6,934 1,669
2,878 1,653
2,954
6,428
3,466 2,520
1,616
1,445
5,460
2,184 3,276
1,509
1,282 -756
-377
RESIDENT
NON-RESIDENT
(264)
(9) 15
50 13,200
4,189
1,509
-377
1,616
26,292
Page: 3 of Date:
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE DIFFERENCE
169,538
0.66
TOTAL GSF
NET TO GROSS RATIO
Net Square Footage By Building Date: 01/25/2018 Page: 1
Center: PENOBSCOT (00103) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
11,161 13,282
1,121
3,309 2,328
3,313 3,676
0010 - COOPER HALL DORMITORY
0009 - VETERANS HALL
0010 - COOPER HALL DORMITORY
0009 - VETERANS HALL
0010 - COOPER HALL DORMITORY
0010 - COOPER HALL DORMITORY
0009 - VETERANS HALL
0009 - VETERANS HALL
0010 - COOPER HALL DORMITORY
Bldg Name Actual NSF Difference
24,443
1,121
5,637
6,989
Sub Total: 38,559
19,008
2,640
1,584
3,168
2,112
28,512
5,435
-1,519
-1,215
2,469
4,877
( 264
10,047
36 rooms; 152 beds 36 rooms; 152 beds
Page: 2
Center: PENOBSCOT (00103) of 4
EDUCATION
FOOD SERVICE
Academic
Vocational Theory (166)
Carpentry
Culinary Arts
Welding
Facilities Maint. and Const.
Medical Assistant
Non-Academic
Cert. Nursing Asst.
Food Preparation
Food Storage
Dining (1 Serving)
Function Suggested
NSF
1,343
1,036 2,661
2,247
4,684
1,373
1,596
3,717
2,854 1,063
1,648
2,373
3,760
2,554
0006 - DOW LANE STREET
0006 - DOW LANE STREET
0006 - DOW LANE STREET
0006 - DOW LANE STREET
0005 - UNION STREET
0005 - UNION STREET
0005 - UNION STREET
0005 - UNION STREET
0005 - UNION STREET
0005 - UNION STREET
0006 - DOW LANE STREET
0005 - UNION STREET
0010 - COOPER HALL DORMITORY
0005 - UNION STREET
0005 - UNION STREET
0006 - DOW LANE STREET
0006 - DOW LANE STREET
0006 - DOW LANE STREET
0011 - RECREATION CENTER
0005 - UNION STREET
0006 - DOW LANE STREET
0008 - DINING HALL
0008 - DINING HALL
0008 - DINING HALL
Bldg Name Actual NSF Difference
5,842
2,247
4,684
1,373
1,596
3,717
7,826
2,949
3,760
2,554
Sub Total:
Sub Total:
30,948
7,244
3,460
1,660
1,800
3,600
1,800
3,600
3,460
2,400
1,638
1,092
4,368
22,680
7,098
2,382
-946
1,084
-427
-2,004
2,817
4,366
2,122
-162
-1,814
8,268
Page: 3
Center: PENOBSCOT (00103) of 4
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Multipurpose Room
Recreation Hall
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Auditorium
Racquetball
Miscellaneous Recreation
Aerobics/Exercise
Recreation Storage
Medical/Dental
Administration
Function Suggested
NSF
2,878
6,934
1,669
1,106
2,954
3,075 3,353
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0011 - RECREATION CENTER
0016 - GROUP LIFE STORAGE
0006 - DOW LANE STREET
0005 - UNION STREET
0006 - DOW LANE STREET
Bldg Name Actual NSF Difference
2,878
6,934
1,669
1,653
2,954
6,428
Sub Total:
Sub Total:
Sub Total:
17,524
2,954
6,428
1,445
5,460
13,335
1,445
5,460
1,509
4,189
1,509
Page: 4
Center: PENOBSCOT (00103) of 4
STORAGE/SUPPORT
SECURITY
VACANT
Warehouse
Operations & Maintenance
SECURITY
Vacant
Function Suggested
NSF
2,520
1,179 1,119
1,415
0005 - UNION STREET
0015 - MAINTENANCE GARAGE
0007 - FM GARAGE STORAGE
0006 - DOW LANE STREET
0026 - FM LANDSCAPE GARAGE
0028 - GATE HOUSE
0005 - UNION STREET
0006 - DOW LANE STREET
Bldg Name Actual NSF Difference
2,520
3,466
1,616
Sub Total:
Sub Total:
Sub Total:
5,986
1,616
3,276
2,184
5,460
-756
1,282
-377
1,616
-377
1,616
Environmental Management Report Center: PENOBSCOT (00103)
Page: 1 Date: 01/25/2018 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 5 (Union Street School)
Organic solvent (5 gals), oil-based paint (20 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Pine Tree Waste Yes
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service Clean Harbors, Inc.
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
03/28/1990 Friable/Non-Friable none
No No N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 01/25/2018Center : Penobscot (00103) Page: 1 of 1
Heating Heating Heating Heating Heating Floor Finishes Heating
Heating Heating Heating Heating Floor Finishes Floor Finishes Exterior Walls Floor Finishes
Bldg System
Bldg System
Pipe fitting insulation Pipe fitting insulation Pipe fitting insulation Pipe fitting insulation Pipe fitting insulation Mastic beneath 9x9 floor tile Pipe fitting insulation
Pipe fitting insulation Pipe fitting insulation Pipe fitting insulation Pipe fitting insulation Mastic beneath 9x9 floor tile Mastic beneath 9x9 floor tile Asbestos cement board Mastic beneath 9x9 floor tile
Category Description
Category Description
Ea.
Ea.
Ea.
Ea.
Ea.
Sq. Ft.
Ea.
Ea.
Ea.
Ea.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Unit
Unit
Quantity
Quantity
Clerical classroom Old locker room Culinary arts class Kitchen/cafeteria Boiler room Throughout Behind walls/ceiling
Stage area Maintenance storage Maintenance office Boiler room Health wing CSO classroom Above windows Corridors
20000
Building :
Building :
0005 - UNION STREET
0006 - DOW LANE STREET
Radon
Page: 1 of 1
0005 - UNION STREET
0006 - DOW LANE STREET
0007 - FM GARAGE STORAGE
0008 - DINING HALL
0009 - VETERANS HALL
0010 - COOPER HALL DORMITORY
0011 - RECREATION CENTER
0015 - MAINTENANCE GARAGE
0016 - GROUP LIFE STORAGE
0026 - FM LANDSCAPE GARAGE
0028 - GATE HOUSE
Bldg Name
05/16/1990
05/16/1990
05/16/1990
Test Date
Yes
Yes
Yes
No
No
No
No
N/A
N/A
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view of Penobscot JCC
Page: 1 Date: 01/25/2018 of 7
Comments:
Paving Type for Roads & Parking
Roadway deteriorating in areas. Granite curbing heaving upward.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. Rear portion of Center is not enclosed with a fence.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualBangor Water DistrictPublic Water Authority
None 0None
Number of Deficiencies = 4
Number of Deficiencies = 1
Number of Deficiencies = 2SITE FEATURES
UTILITIES
Buildings Structures11 21Flat
Surrounding
Outdoor Recreation
Light Commercial, Suburban
Field, Fitness Equip., Soft/Baseball Landscaped Garden, Woods
Border with Public Park
Service Vehicle Yard
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Fair
Number of Deficiencies = 4
Fencing
Other Features
Page: 2 Date: 01/25/2018 of 7
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 4None Municipal
2. Fire Protection System
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Page: 3 Date: 01/25/2018 of 7
Comments:
Sewage Treatment Flow
The sewer treatment system is connected to the publicly owned treatment system (City of Bangor Wastewater) and is in good condition.
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
3. Sanitary Sewer System/ Sewage Treatment Plant
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 1
Drain Type On-Site Storm Water Management
Underground N/A
Center Yes GoodCenter
Page: 4 Date: 01/25/2018 of 7
Comments: The Center previously used fuel oil, then propane. Now the Center has all natural gas.
Bangor Gas Company
5. Fuel Distribution System
Gas Company Metering
Individual
Center Center Yes Good
Page: 5 Date: 01/25/2018 of 7
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Bangor Hydro Power Company
The 12.4/7.15 kV primary service is brought to the Center at one location from overhead lines along Union Street.
The primary radial service feeds several Center pad-mounted and vault-mounted transformers. Vault-mounted transformers are provided in older Buildings 5 and 6.The Center has one pole-mounted primary meter near Building
5. There are five owner meters connected to the web-based metering system. The meters are located at the service entrances near the main distribution panelboards in all main buildings with the exception of Dining Hall Building 8.
The primary and secondary power lines are owned and maintained by the Center. Some smaller buildings and structures are sub-fed from adjacent buildings. The only 480/277V, 3-phase, 4 wire service is provided as a second service to Union Street Building 5. Surge protectors are provided in all buildings.
Pad and Vault Center
Center Center
No
12,4/7,2 kV, 3-Phase, 4 Wire
208/120 and 277/480V, 1 & 3-Phase, 4 WireUnderground
UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 17. Electrical (Service)
Transformer Maint Resp
Center
System Capacity Adequate System Condition
Yes Good
Generator
None
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Sport Light
Photocell Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: Building-mounted lighting consists of HID, CFL and LED light fixtures controlled by wall-mounted and fixture-mounted photocells and time clocks. Buildings 8 and 11 are provided with several wall-mounted 18W and 28W LED light fixtures. Roadway, parking and walkway lighting is provided by pole-mounted half-sphere shaped light fixtures mounted on extruded-aluminum arm, and are served from the nearest buildings and controlled by the time clocks.
Sports lighting is provided by pole-mounted flood lights (eight at each pole) served and controlled by the circuit breakers in two pole-mounted lighting panels located in the vicinity of the soft ball field.
ATS MTS
No No
Number of Deficiencies = 1
6. Central Plant: None
Metering Master
Page: 6 Date: 01/25/2018 of 7
Comments:
Telephone Company
On-site Line Owner
The Union Street Building (Building 5) is utilized as the main communication service entrance for the Center's five T1 telephone lines that serve the Center network. These five T1 lines are extended to Building 6 (Dow Lane) main computer closet. Building 6 is also where the main network closet and DEMARK are located. The data transmission is routed from the MC through a Cisco 6500 router. Each building on Center is connected to the network with both Category 5 and 6 Ethernet network cable connecting a Cisco 3500 XL switch. Building 5 has two steel wall mounted racks that house three 24 port Cisco 3500 XL switches. Three of theT1 lines are IPS circuits and used for Internet. 2 lines are connected to router 2 and are used for production services (Citrix and CDSS).
These switches provide the network to the entire Center. There are capabilities for 400 network drops. The Center also maintains 108 analog phone lines, 20 digital lines and 9 fax lines. Communication closets in Buildings 5 and 6 are kept locked using a dead-bolt key lock. The rooms are cooled to protect the sensitive equipment. The equipment in these rooms is protected by surge protectors. The Center Nortel Telecom telephone system has a UPS backup system for interruptions up to 20 minutes before an automated, graceful shut down is enacted. The T1 lines, long and local distance calls are managed by Fair Point. The network hardware is manufactured by Cisco, implemented and managed remotely by JCDC. The satellite/cable TV service is provided by the Time Warner Company to Dorm Buildings 9 and 10. A satellite dish is provided at Building 11. The Center security system consists of door contactors in the dorms. The Center fire alarm system is maintained by Eagle Security System (1-800-989-1730). Each of 6 buildings is wired at the control panel via dedicated line. In the event of alarm Eagle Security System notifies the local fire department and staff on the Center.
Fair Point
Maint. Responsibility
Center Center
Magnetic Door Alarms
9. Electrical (Communication/Alarm/Security)
No
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 12
STORAGE TANKS: None
Fire Alarm Security
Page: 7 Date: 01/25/2018 of 7
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low MediumLow LowIBC Medium
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
Deteriorated asphalt, concrete sidewalks, and heaving granite curbing.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
40 %
Building Descriptions and Structures
BUILDING 5 - UNION STREET
Building Descriptions
Page: 1 of 51
Building: 0005 - UNION STREET
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry CMU
Wall Roof Unknown Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 41,480 24,956 1 Owned 1965 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
Yes
Yes
Yes
No
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Material
This roof covers the Health Occupation Center in the old gym space.
This roof covers the majority of the building.
Drainage Year Life
Remaining Type Area Served
Single Ply
Single Ply
Surface Run-off
Interior Roof Drains
Arched
Flat
Day Care
Classrooms & Offices
Comments:
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 51
Building: 0005 - UNION STREET
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall Plaster Wood
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Comments: There are concrete steps at the loading dock in the receiving area of the warehouse.
Metal Unit - Metal Frame Storefront - Storefront Frame Wood Unit - Metal Frame
Awning Unit - Steel Frame; Single Glazing; Awning Unit - Wood Frame; Single Glazing;
Fixed - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exterior Doors5.
Windows6. Number of Deficiencies = 2
Floors1. Asbestos: Yes
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4. Number of Deficiencies = 1
Ceilings
Page: 3 of 51
Building: 0005 - UNION STREET
Mechanical Restroom, Shop Area
Ventilation Area ServedExhaust Ventilation
Number of Deficiencies = 2
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Healthcare vocation area is provided heat by a hydronic heating (hot water) system.
Some of the offices are provided with electric baseboard heaters.
The two gas-fired hot water boilers are Cleaver Brooks model CB200-40, each with a heat input rating of 1,675 MBTUH. The boilers were installed in 2002.
There are 5 rooftop packaged units. Two units are Trane model YCD061C4LCBF, each with a heat input capacity of 90,000 BTUH. One unit is a Trane model YCD121C4LCAA, with a heat input capacity of 150,000 BTUH. One unit is a Trane model YCD086C4LCBE, with a heat input capacity of 120,000 BTUH. One unit is a Trane model YCD049C4LCBF, with a heat input capacity of 90,000 BTUH. These units were installed in 1999.
Heating is also provided by hydronic (hot water) unit heaters and baseboard radiators.
There are three makeup air units. Shops and the main kitchen are served by two Captiveaire units. The bakery is served by a Greenheck unit.
Comments:
Comments:
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Electric Resistance
Gas-Fired Hot Water Boiler
Gas-Fired Packaged
Gas-Fired Hot Water Boiler
Gas-Fired Direct
Single Duct
Baseboard
Underfloor Radiant
Single Duct
Unit Heater
Makeup Air Unit
Two-Pipe
None
Two-Pipe
None
Two-Pipe
None
Pneumatic
Electric
Electric
Electric
Pneumatic
Electric
Mechanical
Natural
Mechanical
Mechanical
Mechanical
Mechanical
None
None
None
None
None
None
Day Care
Offices
Day Care
Classrooms and Offices
Classrooms and Offices
Kitchen
Ventilation2. Number of Deficiencies = 1
Page: 4 of 51
Building: 0005 - UNION STREET
Domestic water is heated by a gas-fired water heater (Rinnai #RC98i, 115 gallon, 199 MBH input). In addition, there an electric water heater (Bradford White #MII120R6DS1B, 60 gallon, 4.5 kW).
Comments:
Cast Iron Indoor Cast Iron
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Wet None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet
Chemical Comments: The entire building is protected by a wet sprinkler system. The three culinary arts hoods have a wet chemical fire suppression system. These units are Range Guard model RG-4GT.
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
Single Duct
Refrigerant
None
None
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
None
None
None
Day Care
Classrooms
Classrooms and Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Healthcare vocation is served by a split DX system, a Trane model TTA180B300CB. The condensing unit was installed in 1996. In addition, the Professional Development center is provided with a split DX system, a Goodman model PC048-1B.
There are 5 rooftop packaged units. Two units are Trane model YCD061C4LCBF. One unit is a Trane model YCD121C4LCAA. One unit is a Trane model YCD086C4LCBE. One unit is a Trane model YCD049C4LCBF. These units were installed in 1999.
Comments:
Comments:
Number of Deficiencies = 1
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Number of Deficiencies = 1Air Conditioning
Page: 5 of 51
Building: 0005 - UNION STREET
Comments: This building is provided with two services. First 120/208V, 3-phase, 4-wire service is provided from a pad-mounted, center-owned transformer located in the electrical vault. The service entrance has an 800A main distribution panelboard with an 800A main circuit breaker. The main distribution panel serves (8) 225A MLO wing panels, a 225A MLO kitchen panel and a 225A MLO daycare panel (from (10) 225A circuit breakers (CB)), a 225A MLO kitchen corridor panel and heater (from (2) 200A CB). The second 800A, 480/277V, 3-phase, 4-wire service is provided from a pad-mounted transformer located north of the building. Shop equipment in the welding shop, in the HBI shop and roof-mounted HVAC equipment are served from the 480/277V service. There is a 50 kVA step-down transformer located in the welding instructor's office. An owner meter connected to the web-based energy metering system is also provided.
There is no surge protection in the building.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. The day care center has fluorescent and compact fluorescent light fixtures. Each type of fixtures is controlled individually. Some rooms have occupancy sensors to control the lights.
High Intensity Discharge (HID) Comments: Building-mounted compact HID light fixtures and nearby pole-mounted light fixtures are controlled by a factory installed photocell in each light fixture and a timer, utilizing a lighting contactor located in the warehouse area.
T8 - Fluorescent
CFL and T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Equipment Rooms (Elec/Mech)
Toilets
Dishwashing
Food Preparation
Classrooms
Childcare
Vocational
Vocational
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Location UL300 Compliance Status Bakery
Culinary Arts Kitchen
Compliant
Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
LIGHTING
Page: 6 of 51
Building: 0005 - UNION STREET
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a 12-zone (3 spare) conventional Notifier 500 panel, installed in the reception area room. Building is wired at the control panel via dedicated line. In the event of alarm Eagle Security System notifies the local fire department and staff on the center.
Comments: The Union Street Building (Building 5) is utilized as the main communication service entrance for the center's two T1 telephone lines that serve the center network. These two lines are extended to Building 6 (Dow Lane) main computer closet. The center Nortel Telecom telephone system has a UPS backup system for interruptions up to 15 minutes. The T1 lines, long and local distance calls are managed by Fair Point. Intercom is provided at the entrance to CDC area. CDC computer system is a stand alone system, not connected with the center system. There is also a local magnetic door/alarm security system at the bakery exit door.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Magnetic Door Holder Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm None TV with VCR
Telephone Security Public Address Television
Comments: Remote head emergency light fixtures are also provided.
Battery Backup Battery Backup Emergency Exit
Number of Deficiencies = 2
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 6 - DOW LANE STREET
Page: 7 of 51
Building: 0006 - DOW LANE STREET
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry
Comments: Exterior walls also have spandrel panels and granite.
Wall Roof Unknown Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 29,120 19,720 1 Owned 1965 Not Evaluated
Comments: Audio/visual devices are installed in the corridor along egress pathways, and in some classrooms and multi-purpose rooms. There are no audio/visual devices in the toilet rooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Asbestos: Yes Number of Deficiencies = 1
Insulation4.
Material
This roof covers the majority of the building.
This roof has multiple gables (saw tooth) over the Library area.
Drainage Year Life
Remaining Type Area Served
Single Ply
Single Ply
Interior Roof Drains
Surface Run-off
Flat
Gable
Classrooms & Offices
Classrooms & Offices
Comments:
Comments:
3. Roof
Page: 8 of 51
Building: 0006 - DOW LANE STREET
INTERIOR FINISH
Carpet Ceramic Tile Vinyl Tile Wood
CMU Ceramic Tile Exposed Structure Plaster
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Wood Steps Comments: A short set of steps leads up to an office.
Metal Unit - Metal Frame Storefront - Storefront Frame Wood Unit - Metal Frame Wood Unit - Wood Frame
Awning Unit - Steel Frame; Double Glazing; Awning Unit - Wood Frame; Double Glazing;
Fixed - Aluminum Frame; Single Glazing; Fixed - Wood Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 2
Exterior Doors5.
Windows6. Number of Deficiencies = 1
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are six rooftop packaged units that were installed in 1999: One unit is a Trane model YCD074C3LCBE. Three units are Trane model YCD103C3LCAB. One unit is a Trane model YCD061C3LCBF. One unit is a Trane model YCD086C3LCBE. There are four units that were installed in 2013: Two units are Trane model YSC072F3RHA. One unit is a Trane model YSC102F3R, One unit is a Trane model YSC048.
The two gas-fired hot water boilers are Cleaver Brooks model CB200-40, each with a heat input rating of 1,675 MBTUH. The boilers were installed in 2002.
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes Number of Deficiencies = 2
Gas-Fired Packaged
Gas-Fired Hot Water Boiler
Single Duct
Unit Ventilator
None
Two-Pipe
Electric
Electric
Mechanical
Mechanical
None
None
Classrooms and Offices
Classrooms and Offices
Page: 9 of 51
Building: 0006 - DOW LANE STREET
Mechanical Toilet/Shower
The gas-fired water heater is a 140 gallon, A.O. Smith model COBT140-199 with a heat input rating of 199,000 BTUH. The water heater was installed in 2002. The oil-fired burner was replaced with a gas-fired burner in 2013. In addition, there is a 40 gallon electric water heater for the medical/dental area, a State Industries model CD64020RS973.
Comments:
Cast Iron None Cast Iron
Bathtub Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
Wet None ABC Type Fire Extinguisher
Comments: The building is protected by a wet sprinkler system.
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical None Classrooms and Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
There are six rooftop packaged units that were installed in 1999: One unit is a Trane model YCD074C3LCBE. Three units are Trane model YCD103C3LCAB. One unit is a Trane model YCD061C3LCBF. One unit is a Trane model YCD086C3LCBE. There are four units that were installed in 2013: Two units are Trane model YSC072F3RHA. One unit is a Trane model YSC102F3R, One unit is a Trane model YSC048.
Comments:
Number of Deficiencies = 1
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
3. Air Conditioning
Page: 10 of 51
Building: 0006 - DOW LANE STREET
Comments: Service for this building is provided from a pad-mounted, center-owned transformer located in the electrical vault. The service entrance has an 800A main distribution panelboard with an 800A main circuit breaker located in the main electrical room. The main distribution panel serves four 225A MLO panels (from (4) 225A circuit breakers (CB)) and five 225A MLO panels (from (5) 200A CB). A 600A MLO panel serving RTU units is located in the main electrical room. The service to this panel is tapped from the main line provided to the main distribution panel. An owner meter connected to the web-based energy metering system is also provided. There is a surge protection (GE Tranquell) type in the building. This building also serves Maintenance Storage Structure 14.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. In classrooms, offices corridors and toilet rooms lights are controlled by ceiling and wall-mounted occupancy sensors. Direct/indirect lighting is provided in some offices. Lighting level in the dental offices is about 90 fc.
High Intensity Discharge (HID) Comments: Surface building-mounted compact HID light fixtures and canopy-mounted square type HID light fixtures are controlled by a factory installed photocell in each light fixture. Pole-mounted exterior lighting is controlled by time clock located in the maintenance office.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T5 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Toilets
Storage Rooms
Classrooms
Classrooms
Housing Lounge
Study Room
Medical/Dental
Wards (Patient)
Maintenance Shop
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Page: 11 of 51
Building: 0006 - DOW LANE STREET
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an 8-zone conventional Notifier 5000 panel, installed in the administration room located adjacent to the main entrance. Knock box is installed at the building exterior.
Building is wired at the control panel via dedicated line. In the event of alarm Eagle Security System notifies the local fire department and staff on the center.
Comments: Two T1 lines from Building 5 extend to a main computer closet and DEMARK point housed in this building. The equipment in the computer closet is protected by surge protectors and has UPS (Tripp- Lite), which backup system up to 15 minutes. The network hardware is manufactured by Cisco, implemented and managed remotely by JCDC. The building has Cisco switches with both Cat 5 and Cat 6 Ethernet network cable to connect nodes with the computers and fiber optic cable to connect switches. The data closet houses three Cisco 3500 series switches, two Cisco 3800 series routers, one Catalyst 6500 switch, one Cisco Catalyst 2948G- Ethernet switch, Cisco 1841 series integrated service router, Blue Coat network filtering and Compaq server. A roof-mounted satellite dish is currently abandoned.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None Satellite Dish Telephone Security Public Address Television
Number of Deficiencies = 3
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location 120V w/Battery Backup Mechanical Room
Carbon monoxide detector is provided in the mechanical room by the AHU unit location.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 7 - FM GARAGE STORAGE
Page: 12 of 51
Building: 0007 - FM GARAGE STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Shingles
Wall Roof None None
Metal Overhead - Wood Frame Wood Units - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Storage 1,270 1,179 1 Owned 1988 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
Yes
No
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The remaining life of the roof was estimated by visual inspection at the time of the PY 2017 survey.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 1988 2 Gable Entire Building
Comments:
3. Roof
Page: 13 of 51
Building: 0007 - FM GARAGE STORAGE
INTERIOR FINISH
Concrete
Exposed Structure
None
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
Single Hung - Aluminum Frame; Double Glazing;
None None None None Natural None Entire Building
Exposed Structure
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 14 of 51
Building: 0007 - FM GARAGE STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The service is subfed from a 125A circuit breaker in a 225A, 120/208V, 3-Phase, 4 wire panelboard located in Building 5.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. Light fixtures are controlled by wall-mounted toggle switch located 3' from service entry door.
Compact Fluorescent Incandescent Comments: Exterior lights are controlled by a toggle switch located 3' from service entry door.
T12 - Fluorescent30Storage/Warehouse-Active 30
Area Recommended Level
Recorded Level Light Type
None None
Main Loadcenter 120/208V, 1-Phase, 3 Wire Service Equipment Only Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Page: 15 of 51
Building: 0007 - FM GARAGE STORAGE
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/ANo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: N/A Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 8 - DINING HALL
Page: 16 of 51
Building: 0008 - DINING HALL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
CMU Masonry
Wall Roof Rigid Rigid
Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Assembly 12,130 7,244 1 Owned 1994 Not Evaluated
Comments: Stairs are located at the loading dock only.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
No
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material
The remaining life of the roof was estimated by visual inspection at the time of the PY 2017 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Ballasted Single Ply Interior Roof Drains 1994 1 Flat Entire Building
Comments:
3. Roof
Page: 17 of 51
Building: 0008 - DINING HALL
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Vinyl Tile
CMU Ceramic Tile Drywall
Metal Units - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Comments: The exterior stairs are at the loading area only.
Awning Unit - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The kitchen and servery has an underfloor radiant heat system.
Heating for the storage area and the mechanical room is provided by hydronic (hot water) unit heaters.
The gas-fired hot water boiler is an HB Smith model 28A-9 with a heat input rating of 1,941 MBTUH.
The boiler was installed in 1994. There are air handlers that serve the dining hall and kitchen makeup air.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Underfloor Radiant
Radiator
Single Duct
One-Pipe
Two-Pipe
Two-Pipe
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
None
None
None
Kitchen
Common Area
Dining Hall
Page: 18 of 51
Building: 0008 - DINING HALL
Mechanical
Mechanical
Mechanical
Kitchen
Dishwashing
Restroom
The water heater is a Weil-McLain series 80 model 680 with a heat input rating of 551 MBTUH. The water heater was installed in 2005. The burner was changed from oil to gas in 2013. There are two 119 gallon hot water storage tanks, Amtrol model WH120ZCDW.
Comments:
Comments:
Cast Iron Outdoor Cast Iron
The grease trap has a capacity of 1,000 gallons.
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
None
None
Electric
Electric
Mechanical
Mechanical
None
None
Dining Hall
Offices
PLUMBING
Exhaust Ventilation
The dining room is cooled by four Arcoaire model PAX 360 rooftop units.Comments:
Number of Deficiencies = 1
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3.
Fuel Distribution4.
Page: 19 of 51
Building: 0008 - DINING HALL
Wet None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: Only the storage room is protected by a wet sprinkler system. The three kitchen hoods have wet chemical fire suppression system. Two of the units are ANSUL R-102 systems and one unit is a Range Guard model RG-4GM.
Comments: Underground service is provided from a pad-mounted center-owned transformer located at the west side of the building. The service entrance has an 800A main distribution panelboard with a 700A main circuit breaker located in the boiler/electrical room. The main distribution panelboard serves three 225A main-lug-only (MLO) kitchen panels (from a 125A, a 150A and a 175A circuit breakers (CB)), two 225A MLO general load panels (from (2) 150A CB), a dishwasher and a booster heater (from a 200A CB) and has two 100A spare CB. Service entrance is provided with surge protection (Tranquell, model 9L100AB314).
The owner metering system is not provided.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. Central area of the dining hall has been provided with HID light fixtures. Wall-mounted occupancy sensors are utilized in the toilet rooms, storage rooms and support rooms.
Compact Fluorescent High Intensity Discharge (HID)
LED
Comments: Surface building-mounted exterior lighting consists of compact fluorescent light fixtures, HID light fixtures and LED light fixtures, which are controlled by a photocell located on the roof, a time clock and a lighting contactor. Pole-mounted lighting is controlled by the time clock and another lighting contactor. The time clock and both lighting contactors are located in boiler/electrical room.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
CFL and T8 - Fluorescent
HID and T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Dining/Lunch Rooms
Dishwashing
Food Preparation
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Number of Deficiencies = 1FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Location UL300 Compliance Status Kitchen - 2 hoods / Serving Line - 1 hood Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 20 of 51
Building: 0008 - DINING HALL
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an 8-zone conventional Silent Knight SK-5207 panel, installed in the corridor near the back entrance. Fire alarm annunciator panel is provided at the same location as control/annunciator panel. Building is wired at the control panel via dedicated line.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.