Amd_1_Exhibit_3_7309_230548_SF_-_VIBRATION_AND_SEISMIC_CONTROLS_FOR_HVAC.pdf

PDF 58 KB Posted

Attached to
Chemawa Indian Health Center Modernization Construction
Solicitation number
16-102-SOL-00001
Issued by

About this file

Amd 1 Exhibit 3 7309 230548 SF - VIBRATION AND SEISMIC CONTROLS FOR HVAC

View the file

Other files

File Type Posted
Amendment_3_16-102-SOL-00001.pdf PDF
Amendment_2_16-102-SOL-00001.pdf PDF
Amd_1_Exhibit_5_Asbestos_Abatement_-_Taholah _Queets_ _Chemawa_Close_Out_Report.pdf PDF
Amd_1_Exhibit_2_7309_271500_-_Communications_Cabling_REV_1.pdf PDF
Amd_1_Exhibit_1_Attendees_for_the_Pre-Bid_Meeting.pdf PDF
Amd_1_Exhibit_4_7309_233713_FL_-_DIFFUSERS _REGISTERS _AND_GRILLES.pdf PDF
Amendment_1_16-102-SOL-00001.pdf PDF
Attachment_12_Infection_Control_Risk_Assessment_Policy_IC.2014.17.0.pdf PDF
Attachment_13_Bond_Forms.pdf PDF
Attachment_6_Structural_Drawings.zip ZIP file
Attachment_10_Required_Background_Investigation_Information_Form_(e-QIP).pdf PDF
Attachment_4_Architectural_Drawings_Part_2_of_3.zip ZIP file
Attachment_8_Electrical_Drawings.zip ZIP file
Attachment_7_Mechanical_Drawings.zip ZIP file
Attachment_9_Supplemental_Design_Clarifications.pdf PDF
Attachment_1_Chemawa_Health_Modernization_Specifications.pdf PDF
Attachment_3_Architectual_Drawings_Part_1_of_3.zip ZIP file
Attachment_11_Department_of_Health_and_Human_Services_(HHS)_identification_(ID)_Badge_Request_(HHS-775).pdf PDF
16-102-SOL-00001.pdf PDF
Attachment_14_Department_of_Labor _General_Decision_No_OR150028_dated_10_09_15.pdf PDF
Attachment_2_Civil_Drawings.zip ZIP file
Attachment_5_Architectural_Drawings_Part_3_of_3.zip ZIP file
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Chemawa Health Modification August 2015

Meier Project No. 13-7309 IHS Contract No. HHSI102201100001I

230548 - 1

SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Elastomeric isolation pads.

2. Elastomeric isolation mounts.

3. Housed-restrained-spring isolators.

4. Pipe-riser resilient supports.

5. Resilient pipe guides.

6. Elastomeric hangers.

7. Restraint channel bracings.

8. Restraint cables.

9. Seismic-restraint accessories.

10. Mechanical anchor bolts.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Delegated-Design Submittal: For each vibration isolation and seismic-restraint device.

1. Include design calculations and details for selecting vibration isolators and seismic restraints complying with performance requirements, design criteria, and analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

1.3 INFORMATIONAL SUBMITTALS

A. Welding certificates.

B. Field quality-control reports.

1.4 QUALITY ASSURANCE

A. Comply with seismic-restraint requirements in the IBC unless requirements in this Section are more stringent.

B. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

C. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and shall bear anchorage preapproval OPA number from OSHPD, preapproval by ICC-ES, or preapproval by another agency acceptable to authorities having jurisdiction, showing maximum seismic-restraint ratings. Alternately, calculations (including combining shear and tensile loads) to support seismic-restraint designs must be signed and sealed by a qualified professional engineer.

230548 - 2

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Wind-Restraint Loading:

1. Basic Wind Speed: 115.

2. Building Classification Category: II.

3. Minimum 10 lb/sq. ft. multiplied by maximum area of HVAC component projected on vertical plane normal to wind direction, and 45 degrees either side of normal.

B. Seismic-Restraint Loading:

1. Site Class as Defined in the IBC: D.

2. Assigned Seismic Use Group or Building Category as Defined in the IBC: II.

a. Component Importance Factor: 1.0.

b. Component Response Modification Factor: Per ASCE 7-10

c. Component Amplification Factor: Per ASCE 7-10.

3. Design Spectral Response Acceleration at Short Periods (0.2 Second): 0.697.

4. Design Spectral Response Acceleration at 1.0-Second Period: 0.452.

2.2 ELASTOMERIC ISOLATION PADS

A. Elastomeric Isolation Pads:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Kinetics Noise Control, Inc.

b. Mason Industries, Inc.

c. Vibration Eliminator Co., Inc.

d. Vibration Isolation.

e. Vibration Mountings & Controls, Inc.

2. Fabrication: Single or multiple layers of sufficient durometer stiffness for uniform loading over pad area.

3. Size: Factory or field cut to match requirements of supported equipment.

4. Pad Material: Oil and water resistant with elastomeric properties.

5. Surface Pattern: [Waffle] pattern.

6. Load-bearing metal plates adhered to pads.

2.3 ELASTOMERIC ISOLATION MOUNTS

A. Double-Deflection, Elastomeric Isolation Mounts:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Kinetics Noise Control, Inc.

b. Mason Industries, Inc.

c. Vibration Eliminator Co., Inc.

d. Vibration Isolation.

e. Vibration Mountings & Controls, Inc.

2. Mounting Plates:

a. Top Plate: Encapsulated steel load transfer top plates, factory drilled and threaded with threaded studs or bolts.

b. Baseplate: Encapsulated steel bottom plates with holes provided for anchoring to support structure.

http://www.specagent.com/Lookup?ulid=7632 http://www.specagent.com/Lookup?uid=123456867202 http://www.specagent.com/Lookup?uid=123456867203 http://www.specagent.com/Lookup?uid=123456867204 http://www.specagent.com/Lookup?uid=123456867205 http://www.specagent.com/Lookup?uid=123456867206 http://www.specagent.com/Lookup?ulid=7633 http://www.specagent.com/Lookup?uid=123456867210 http://www.specagent.com/Lookup?uid=123456867211 http://www.specagent.com/Lookup?uid=123456867212 http://www.specagent.com/Lookup?uid=123456867213 http://www.specagent.com/Lookup?uid=123456867214

230548 - 3

3. Elastomeric Material: Molded, oil-resistant rubber, neoprene, or other elastomeric material.

2.4 HOUSED-RESTRAINED-SPRING ISOLATORS

A. Freestanding, Steel, Open-Spring Isolators with Vertical-Limit Stop Restraint in Two-Part Telescoping Housing:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Kinetics Noise Control, Inc.

b. Mason Industries, Inc.

c. Vibration Eliminator Co., Inc.

d. Vibration Isolation.

e. Vibration Mountings & Controls, Inc.

2. Two-Part Telescoping Housing: A steel top and bottom frame separated by an elastomeric material and enclosing the spring isolators. Housings are equipped with adjustable snubbers to limit vertical movement.

a. Drilled base housing for bolting to structure with an elastomeric isolator pad attached to the underside. Bases shall limit floor load to 500 psig.

b. Threaded top housing with adjustment bolt and cap screw to fasten and level equipment.

3. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.

4. Minimum Additional Travel: 50 percent of the required deflection at rated load.

5. Lateral Stiffness: More than 80 percent of rated vertical stiffness.

6. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure.

2.5 PIPE-RISER RESILIENT SUPPORT

A. Description: All-directional, acoustical pipe anchor consisting of two steel tubes separated by a minimum 1/2-inch-thick neoprene.

1. Vertical-Limit Stops: Steel and neoprene vertical-limit stops arranged to prevent vertical travel in both directions.

2. Maximum Load Per Support: 500 psigon isolation material providing equal isolation in all directions.

2.6 RESILIENT PIPE GUIDES

A. Description: Telescopic arrangement of two steel tubes or post and sleeve arrangement separated by a minimum 1/2-inch-thick neoprene.

1. Factory-Set Height Guide with Shear Pin: Shear pin shall be removable and reinsertable to allow for selection of pipe movement. Guides shall be capable of motion to meet location requirements.

2.7 ELASTOMERIC HANGERS

A. Elastomeric Mount in a Steel Frame with Upper and Lower Steel Hanger Rods:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Kinetics Noise Control, Inc.

http://www.specagent.com/Lookup?ulid=7645 http://www.specagent.com/Lookup?uid=123456867267 http://www.specagent.com/Lookup?uid=123456867268 http://www.specagent.com/Lookup?uid=123456867269 http://www.specagent.com/Lookup?uid=123456867270 http://www.specagent.com/Lookup?uid=123456867271 http://www.specagent.com/Lookup?ulid=7635 http://www.specagent.com/Lookup?uid=123456867226

230548 - 4

b. Mason Industries, Inc.

c. Vibration Eliminator Co., Inc.

d. Vibration Mountings & Controls, Inc.

2. Frame: Steel, fabricated with a connection for an upper threaded hanger rod and an opening on the underside to allow for a maximum of 30 degrees of angular lower hanger-rod misalignment without binding or reducing isolation efficiency.

3. Dampening Element: Molded, oil-resistant rubber, neoprene, or other elastomeric material with a projecting bushing for the underside opening preventing steel to steel contact.

2.8 RESTRAINT CHANNEL BRACINGS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. B-line, an Eaton business.

2. Hilti, Inc.

3. Mason Industries, Inc.

4. Unistrut; Part of Atkore International.

B. Description: MFMA-4, shop- or field-fabricated bracing assembly made of slotted steel channels with accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosion-resistant coating;

rated in tension, compression, and torsion forces.

2.9 RESTRAINT CABLES

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Kinetics Noise Control, Inc.

2. Mason Industries, Inc.

3. Vibration Mountings & Controls, Inc.

B. Restraint Cables: ASTM A 603 galvanized -steel cables. End connections made of steel assemblies with thimbles, brackets, swivel, and bolts designed for restraining cable service;

with a minimum of two clamping bolts for cable engagement.

2.10 SEISMIC-RESTRAINT ACCESSORIES

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. B-line, an Eaton business.

2. Kinetics Noise Control, Inc.

3. Mason Industries, Inc.

4. TOLCO.

B. Hanger-Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally bolted connections to hanger rod.

C. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for rigid equipment mountings, and matched to type and size of anchor bolts and studs.

http://www.specagent.com/Lookup?uid=123456867227 http://www.specagent.com/Lookup?uid=123456867228 http://www.specagent.com/Lookup?uid=123456867229 http://www.specagent.com/Lookup?ulid=7637 http://www.specagent.com/Lookup?uid=123456867233 http://www.specagent.com/Lookup?uid=123456867234 http://www.specagent.com/Lookup?uid=123456867235 http://www.specagent.com/Lookup?uid=123456867236 http://www.specagent.com/Lookup?ulid=7647 http://www.specagent.com/Lookup?uid=123456867279 http://www.specagent.com/Lookup?uid=123456891656 http://www.specagent.com/Lookup?uid=123456867281 http://www.specagent.com/Lookup?ulid=7638 http://www.specagent.com/Lookup?uid=123456867237 http://www.specagent.com/Lookup?uid=123456867238 http://www.specagent.com/Lookup?uid=123456867239 http://www.specagent.com/Lookup?uid=123456867240

230548 - 5

D. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene elements and steel sleeves designed for rigid equipment mountings, and matched to type and size of attachment devices used.

E. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant neoprene, with a flat washer face.

F. Mechanical Anchor Bolts: Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488.

PART 3 - EXECUTION

3.1 APPLICATIONS

A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application by an agency acceptable to authorities having jurisdiction.

B. Hanger-Rod Stiffeners: Install hanger-rod stiffeners where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces.

C. Strength of Support and Seismic-Restraint Assemblies: Where not indicated, select sizes of components so strength is adequate to carry present and future static and seismic loads within specified loading limits.

3.2 VIBRATION CONTROL AND SEISMIC-RESTRAINT DEVICE INSTALLATION

A. Coordinate the location of embedded connection hardware with supported equipment attachment and mounting points.

B. Installation of vibration isolators must not cause any change of position of equipment, piping, or ductwork resulting in stresses or misalignment.

C. Equipment Restraints:

1. Install seismic snubbers on HVAC equipment mounted on vibration isolators. Locate snubbers as close as possible to vibration isolators and bolt to equipment base and supporting structure.

2. Install resilient bolt isolation washers on equipment anchor bolts where clearance between anchor and adjacent surface exceeds 0.125 inch.

3. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.

D. Piping Restraints:

1. Comply with requirements in MSS SP-127.

2. Space lateral supports a maximum of 40 feet o.c., and longitudinal supports a maximum of 80 feet o.c.

3. Brace a change of direction longer than 12 feet.

E. Install cables so they do not bend across edges of adjacent equipment or building structure.

230548 - 6

F. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.

G. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide resilient media between anchor bolt and mounting hole in concrete base.

H. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall.

I. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members.

J. Drilled-in Anchors:

1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling.

Notify the structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines.

2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength.

3. Wedge Anchors: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened.

4. Set anchors to manufacturer's recommended torque, using a torque wrench.

5. Install zinc-coated steel anchors for interior and stainless-steel anchors for exterior applications.

3.3 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION

A. Install flexible connections in piping where they cross seismic joints, where adjacent sections or branches are supported by different structural elements, and where the connections terminate with connection to equipment that is anchored to a different structural element from the one supporting the connections as they approach equipment. Comply with requirements in Section 232113 "Hydronic Piping" for piping flexible connections.

3.4 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction.

2. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice.

3. Obtain Architect's approval before transmitting test loads to structure. Provide temporary load-spreading members.

4. Test at least four of each type and size of installed anchors and fasteners .

5. Test to 90 percent of rated proof load of device.

6. Measure isolator restraint clearance.

7. Measure isolator deflection.

230548 - 7

8. Verify snubber minimum clearances.

C. Remove and replace malfunctioning units and retest as specified above.

D. Prepare test and inspection reports.

3.5 ADJUSTING

A. Adjust isolators after piping system is at operating weight.

B. Adjust limit stops on restrained-spring isolators to mount equipment at normal operating height.

After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.

END OF SECTION 230548

PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Elastomeric isolation pads.
2. Elastomeric isolation mounts.
3. Housed-restrained-spring isolators.
4. Pipe-riser resilient supports.
5. Resilient pipe guides.
6. Elastomeric hangers.
7. Restraint channel bracings.
8. Restraint cables.
9. Seismic-restraint accessories.
10. Mechanical anchor bolts.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Delegated-Design Submittal: For each vibration isolation and seismic-restraint device.
1. Include design calculations and details for selecting vibration isolators and seismic restraints complying with performance requirements, design criteria, and analysis data signed and sealed by the qualified professional engineer responsible for th...
1.3 INFORMATIONAL SUBMITTALS
A. Welding certificates.
B. Field quality-control reports.
1.4 QUALITY ASSURANCE
A. Comply with seismic-restraint requirements in the IBC unless requirements in this Section are more stringent.
B. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."
C. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and shall bear anchorage preapproval OPA number from OSHPD, preapproval by ICC-ES, or preapproval by another agency acceptable to authorities having jurisdiction...
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Wind-Restraint Loading:
1. Basic Wind Speed: 115.
2. Building Classification Category: II.
3. Minimum 2T10 lb/sq. ft.2T multiplied by maximum area of HVAC component projected on vertical plane normal to wind direction, and 45 degrees either side of normal.
B. Seismic-Restraint Loading:
1. Site Class as Defined in the IBC: D.
2. Assigned Seismic Use Group or Building Category as Defined in the IBC: II.
a. Component Importance Factor: 1.0.
b. Component Response Modification Factor: Per ASCE 7-10
c. Component Amplification Factor: Per ASCE 7-10.
3. Design Spectral Response Acceleration at Short Periods (0.2 Second): 0.697.
4. Design Spectral Response Acceleration at 1.0-Second Period: 0.452.
2.2 ELASTOMERIC ISOLATION PADS
A. Elastomeric Isolation Pads:
1. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
a. 5TKinetics Noise Control, Inc.
b. 5TMason Industries, Inc.
c. 5TVibration Eliminator Co., Inc.
d. 5TVibration Isolation.
e. 5TVibration Mountings & Controls, Inc.
2. Fabrication: Single or multiple layers of sufficient durometer stiffness for uniform loading over pad area.
3. Size: Factory or field cut to match requirements of supported equipment.
4. Pad Material: Oil and water resistant with elastomeric properties.
5. Surface Pattern: [Waffle] pattern.
6. Load-bearing metal plates adhered to pads.
2.3 ELASTOMERIC ISOLATION MOUNTS
A. Double-Deflection, Elastomeric Isolation Mounts:
1. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
a. 5TKinetics Noise Control, Inc.
b. 5TMason Industries, Inc.
c. 5TVibration Eliminator Co., Inc.
d. 5TVibration Isolation.
e. 5TVibration Mountings & Controls, Inc.
2. Mounting Plates:
a. Top Plate: Encapsulated steel load transfer top plates, factory drilled and threaded with threaded studs or bolts.
b. Baseplate: Encapsulated steel bottom plates with holes provided for anchoring to support structure.

3. Elastomeric Material: Molded, oil-resistant rubber, neoprene, or other elastomeric material.

2.4 HOUSED-RESTRAINED-SPRING ISOLATORS
A. Freestanding, Steel, Open-Spring Isolators with Vertical-Limit Stop Restraint in Two-Part Telescoping Housing:
1. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
a. 5TKinetics Noise Control, Inc.
b. 5TMason Industries, Inc.
c. 5TVibration Eliminator Co., Inc.
d. 5TVibration Isolation.
e. 5TVibration Mountings & Controls, Inc.
2. Two-Part Telescoping Housing: A steel top and bottom frame separated by an elastomeric material and enclosing the spring isolators. Housings are equipped with adjustable snubbers to limit vertical movement.
a. Drilled base housing for bolting to structure with an elastomeric isolator pad attached to the underside. Bases shall limit floor load to 2T500 psig2T.
b. Threaded top housing with adjustment bolt and cap screw to fasten and level equipment.
3. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.
4. Minimum Additional Travel: 50 percent of the required deflection at rated load.
5. Lateral Stiffness: More than 80 percent of rated vertical stiffness.
6. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure.
2.5 PIPE-RISER RESILIENT SUPPORT
A. Description: All-directional, acoustical pipe anchor consisting of two steel tubes separated by a minimum 2T1/2-inch-2Tthick neoprene.
1. Vertical-Limit Stops: Steel and neoprene vertical-limit stops arranged to prevent vertical travel in both directions.
2. Maximum Load Per Support: 2T500 psig2Ton isolation material providing equal isolation in all directions.
2.6 RESILIENT PIPE GUIDES
A. Description: Telescopic arrangement of two steel tubes or post and sleeve arrangement separated by a minimum 2T1/2-inch-2Tthick neoprene.
1. Factory-Set Height Guide with Shear Pin: Shear pin shall be removable and reinsertable to allow for selection of pipe movement. Guides shall be capable of motion to meet location requirements.
2.7 ELASTOMERIC HANGERS
A. Elastomeric Mount in a Steel Frame with Upper and Lower Steel Hanger Rods:
1. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
a. 5TKinetics Noise Control, Inc.
b. 5TMason Industries, Inc.
c. 5TVibration Eliminator Co., Inc.
d. 5TVibration Mountings & Controls, Inc.
2. Frame: Steel, fabricated with a connection for an upper threaded hanger rod and an opening on the underside to allow for a maximum of 30 degrees of angular lower hanger-rod misalignment without binding or reducing isolation efficiency.
3. Dampening Element: Molded, oil-resistant rubber, neoprene, or other elastomeric material with a projecting bushing for the underside opening preventing steel to steel contact.
2.8 RESTRAINT CHANNEL BRACINGS
A. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
1. 5TB-line, an Eaton business.
2. 5THilti, Inc.
3. 5TMason Industries, Inc.
4. 5TUnistrut; Part of Atkore International.

B. Description: MFMA-4, shop- or field-fabricated bracing assembly made of slotted steel channels with accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosio...

2.9 RESTRAINT CABLES
A. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
1. 5TKinetics Noise Control, Inc.
2. 5TMason Industries, Inc.
3. 5TVibration Mountings & Controls, Inc.

B. Restraint Cables: ASTM A 603 galvanized -steel cables. End connections made of steel assemblies with thimbles, brackets, swivel, and bolts designed for restraining cable service; with a minimum of two clamping bolts for cable engagement.

2.10 SEISMIC-RESTRAINT ACCESSORIES
A. 5TManufacturers: Subject to compliance with requirements, provide products by one of the following:
1. 5TB-line, an Eaton business.
2. 5TKinetics Noise Control, Inc.
3. 5TMason Industries, Inc.
4. 5TTOLCO.
B. Hanger-Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally bolted connections to hanger rod.
C. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for rigid equipment mountings, and matched to type and size of anchor bolts and studs.
D. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene elements and steel sleeves designed for rigid equipment mountings, and matched to type and size of attachment devices used.
E. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant neoprene, with a flat washer face.
F. Mechanical Anchor Bolts: Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to A...
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application by an agency acceptable to authorities having jurisdiction.
B. Hanger-Rod Stiffeners: Install hanger-rod stiffeners where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces.
C. Strength of Support and Seismic-Restraint Assemblies: Where not indicated, select sizes of components so strength is adequate to carry present and future static and seismic loads within specified loading limits.
3.2 VIBRATION CONTROL AND SEISMIC-RESTRAINT DEVICE INSTALLATION
A. Coordinate the location of embedded connection hardware with supported equipment attachment and mounting points.
B. Installation of vibration isolators must not cause any change of position of equipment, piping, or ductwork resulting in stresses or misalignment.
C. Equipment Restraints:
1. Install seismic snubbers on HVAC equipment mounted on vibration isolators. Locate snubbers as close as possible to vibration isolators and bolt to equipment base and supporting structure.
2. Install resilient bolt isolation washers on equipment anchor bolts where clearance between anchor and adjacent surface exceeds 2T0.125 inch2T.
3. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.
D. Piping Restraints:
1. Comply with requirements in MSS SP-127.
2. Space lateral supports a maximum of 2T40 feet2T o.c., and longitudinal supports a maximum of 2T80 feet2T o.c.
3. Brace a change of direction longer than 2T12 feet2T.
E. Install cables so they do not bend across edges of adjacent equipment or building structure.
F. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.
G. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide resilient media between anchor bolt and mounting hole in concrete base.
H. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall.
I. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members.
J. Drilled-in Anchors:
1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling. Notify the structural engineer if reinforcing steel or other embedd...
2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength.
3. Wedge Anchors: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened.
4. Set anchors to manufacturer's recommended torque, using a torque wrench.
5. Install zinc-coated steel anchors for interior and stainless-steel anchors for exterior applications.
3.3 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION
A. Install flexible connections in piping where they cross seismic joints, where adjacent sections or branches are supported by different structural elements, and where the connections terminate with connection to equipment that is anchored to a diffe...
3.4 FIELD QUALITY CONTROL
A. Perform tests and inspections.
B. Tests and Inspections:
1. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction.
2. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice.
3. Obtain Architect's approval before transmitting test loads to structure. Provide temporary load-spreading members.
4. Test at least four of each type and size of installed anchors and fasteners .
5. Test to 90 percent of rated proof load of device.
6. Measure isolator restraint clearance.
7. Measure isolator deflection.
8. Verify snubber minimum clearances.
C. Remove and replace malfunctioning units and retest as specified above.
D. Prepare test and inspection reports.
3.5 ADJUSTING
A. Adjust isolators after piping system is at operating weight.
B. Adjust limit stops on restrained-spring isolators to mount equipment at normal operating height. After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.

File details come from the government source that posted it. Updated .