Amendment_1_16-102-SOL-00001.pdf

PDF 537 KB Posted

Attached to
Chemawa Indian Health Center Modernization Construction
Solicitation number
16-102-SOL-00001
Issued by

About this file

Amendment 1 16-102-SOL-00001

View the file

Other files

File Type Posted
Amendment_3_16-102-SOL-00001.pdf PDF
Amendment_2_16-102-SOL-00001.pdf PDF
Amd_1_Exhibit_5_Asbestos_Abatement_-_Taholah _Queets_ _Chemawa_Close_Out_Report.pdf PDF
Amd_1_Exhibit_2_7309_271500_-_Communications_Cabling_REV_1.pdf PDF
Amd_1_Exhibit_1_Attendees_for_the_Pre-Bid_Meeting.pdf PDF
Amd_1_Exhibit_3_7309_230548_SF_-_VIBRATION_AND_SEISMIC_CONTROLS_FOR_HVAC.pdf PDF
Amd_1_Exhibit_4_7309_233713_FL_-_DIFFUSERS _REGISTERS _AND_GRILLES.pdf PDF
Attachment_12_Infection_Control_Risk_Assessment_Policy_IC.2014.17.0.pdf PDF
Attachment_13_Bond_Forms.pdf PDF
Attachment_6_Structural_Drawings.zip ZIP file
Attachment_10_Required_Background_Investigation_Information_Form_(e-QIP).pdf PDF
Attachment_4_Architectural_Drawings_Part_2_of_3.zip ZIP file
Attachment_8_Electrical_Drawings.zip ZIP file
Attachment_7_Mechanical_Drawings.zip ZIP file
Attachment_9_Supplemental_Design_Clarifications.pdf PDF
Attachment_1_Chemawa_Health_Modernization_Specifications.pdf PDF
Attachment_3_Architectual_Drawings_Part_1_of_3.zip ZIP file
Attachment_11_Department_of_Health_and_Human_Services_(HHS)_identification_(ID)_Badge_Request_(HHS-775).pdf PDF
16-102-SOL-00001.pdf PDF
Attachment_14_Department_of_Labor _General_Decision_No_OR150028_dated_10_09_15.pdf PDF
Attachment_2_Civil_Drawings.zip ZIP file
Attachment_5_Architectural_Drawings_Part_3_of_3.zip ZIP file
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Chemawa Indian Health Center Modernization Solicitation Amendment 1, Solicitation 16-102-SOL-00001 Questions and Answers 11/17/15

1. 56. Notice: The Bid Opening Date is hereby changed to be Tuesday, December 8, 2015 at 2:00 PM, Pacific Standard Time at the Indian Health Service, Division of Engineering Services, Suite 1600, 701 5th Avenue, Seattle, WA 98104. Be AWARE that the 16th Floor is NOT a public access floor. Bidders are required to be at the elevator bank for the 16th floor no later than 1:30 PM Pacific Standard Time so we can provide access to the bid opening room. Bidders late for the floor access may not be able to submit their bids in a timely manner.

2. The attendance list for the Pre-bid Meeting is provided as Amd 1 Exhibit 1 Attendees for the Pre-Bid Meeting.

3. Question: Page 271500-3, 1.9 You are asking for a Systimax 20 year warranty Print E501 Detail 1, shows Leviton jacks and faceplates, which is it for warranty?

Answer: DELETE Specification Section 271500 in its entirety. Insert Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

4. Question: Page 271500-2, 4a, coil 15 feet for owners to terminate. For a warranty from manufacturer you must terminate and test everything, do you want a factory warranty?

Answer: Yes. See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1. Delete coil requirement. The Contractor shall terminate and test per factory warranty requirements and provide warranty.

5. Question: Page 271500-4, 2.3, A, customer to provide patch panels, for warranty you must show all materials used, is this going to be warranty?

Answer: All work shall be covered by warranty per industry standards. See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1. The Contractor shall be responsible for providing and installing Patch Panels and Patch Cords. Items NOT REQUIRED to be installed by the Contractor will not require warranty.

6. Question: Are we to supply jacks and faceplates? Are we to terminate them?

Answer: Yes. All jacks and faceplates shall be provided by contractor and terminated by contractor.

7. Question: Page 271500-10, 3, label each exposed cable labeled every 15’, this is not a standard, is this needed?

Answer: See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

8. Question: Print E501, flag note 2, ½ way down, provide and terminate fiber patch panel and terminate with LC connectors, patch panels and copper patch cords.

Answer: The Contractor shall provide and terminate all fiber and cable. See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

9. Question: Page 271500-2, 1.5, A, 2, terminations by owner, which is it?

Answer: Contractor shall make all terminations. See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

10. Question: Page 271500-4, 2.3, A, patch cords and patch panels provided by owner, which is it?

Answer: Contractor shall provide patch cords and patch panels. See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

11. Question: Does the structured cable (cat 6, Cat 6A) need to be plenum?

Answer: See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1.

12. Question: Page 271500-5, 2. states 6, A and B, 6 and 12 fiber which is it, 6 fiber?

Answer: Plan Sheet E501, Detail 6 and 7 shows one 6-stand fiber from IDF Rack (Rm 162) to MDF Rack (Rm 160A); provide second “spare” 6-stand fiber from IDF Rack (Rm 162) to MDF Rack (Rm 160A); with fiber strand terminal ends on, ready for insertion.

13. Question: triangles, some are bold, what is the difference between light triangle and dark triangle?

Answer: The lighter (dithered) triangle’s indicates an existing data J-box (note some of these existing do not have an existing raceway) and the “BOLDER” triangle’s indicate a new data J-box & raceway is required.

14. Question: Do I need to separate quote for phases or one lump sum?

Answer: A separate bid on each of the items in the Schedule of (Bid) Items is required in order to be considered responsive to this Invitation for Bids/Solicitation.

15. Question: “Please provide the contents of the Finish Schedule. A122 is showing the header of the finish schedule only.

To be more clear – I am looking for a room by room finish schedule. Or you can tell me which walls of each room receive the accent paint.”

Answer: See Drawing Sheet A122, FINISH SCHEDULE table.

1. Delete Walk-off Carpet, “Connex, Super Nop 52, Steel Blue” and insert “Mannington, Liaison Collection, Byway Brown 8615.”

2. Delete “SW 7004 Snowbound” as the GENERAL PAINT and insert “SW 7036 Accessible Beige” as the GENERAL PAINT.

3. Delete “SW 7036 Accessible Beige” as an Accent Tan. Insert “All Accent Walls shall be SW 6191 Contented.”

4. All Accent Walls shall be opposite the entrance into the room unless otherwise indicated on the following Accent Wall Table.

ASSUME NORTH IS UP (top of sheet) on Sheets A121 – A123.

Accent Wall Table

Drawing Sheet A121

Room No. Accent Wall Room No. Accent Wall

303 North Wall 340 South Wall

305 NO ACCENT 131 South Wall

306 South Wall 141 South Wall

310 NO ACCENT 142 North Wall

311 North wall

Drawing Sheet A122

Room No. Accent Wall Room No. Accent Wall

219 East Wall 223 East Wall

220 NO ACCENT 224 East Wall

221 North Wall 225 South Wall

222 West Wall 226 South Wall

Drawing Sheet A123

Room No. Accent Wall Room No. Accent Wall

1551 Northeast Wall 213 North Wall

1562 North AND South Walls 229 North AND SW Walls

201 East Wall 1RM 155 Northeast wall along rooms 163 to 168 Verify intent.

2Rm 156 South wall along rooms 196-199, and North wall along room 157. Verify intent.

16. Question: “The spec table of contents calls for sections 230578 & 233713 to have been included, but it looks like they were not.”

Answer: There was a typographical error in the Table of Contents, Section 230578 should have been numbered 230548. These specification sections were unintentionally omitted and are attached as Amd 1 Exhibit 3: 7309 230548 SF - VIBRATION AND SEISMIC CONTROLS FOR HVAC and Amd 1 Exhibit 4: 7309

233713 FL - DIFFUSERS, REGISTERS, AND GRILLES.

17. Question: “Sheet A101 and Sheet A102 indicate work outside the defined phases or options.

Please indicate to which line item you want that work assigned.”

Answer: If work is located outside of the dashed lines indicating Phases of Construction, Offerors shall place work within the most logical Phase, unless otherwise required (see Question 56 this Amendment 1.) It is the Offeror’s responsibility to ensure all work require by the Solicitation is included within their Bid. Which Phase work items are contained (as bidded by the Contractor) under shall be provided to the Government after award in a detailed breakout by the successful Contractor.

18. Question: “What is the purpose of breaking the Base bid into 11 line items? The multiple line items will often generate miss-bidding on the part of the sub. Take a doors and hardware vendor. They seldom look at the plans and almost never look at the bid form the GC is required to submit. If the door schedule does not reflect the bid form break-out, we are very likely to receive a quote with a single number.

This break-out is something you can require during a schedule of values submittal.”

Answer: All work shall be provided for within the Schedule of (Bid) Items and if there is not clear understanding which Phase to place work, place under the most logical location. See above answer, Question 17.

19. Question: “Will post walk questions be allowed? The walk might generate questions.”

Answer: The intent of requesting questions prior to the Pre-Bid Meeting is to prompt interested offerors to review construction documents thoroughly prior to the meeting. It is often times not productive if people attend the meeting without having reviewed these and folks ask questions resulting in the mere referral to a spec section and/or drawing set.

Questions are always welcomed. We will make a determination whether we will respond to questions that are received too close to the bid opening date based on the content of the questions.

20. Question: “Do we have to submit bids on each or all of the alternates? If don’t submit pricing on the alternates and we are lowest bidder would we be awarded the project?”

Answer: The intent of the Solicitation is to require all items to be priced. Section M-3, Price Evaluation from the specification, describes how the low bid will be determined. If you do not price an option, you will not be able to be considered because we will not be able to evaluate your company with respect to that clause.

Submit a bid on each item or your bid will be considered non-responsive and will not be considered for award.

21. Question: “If said swing space will be needed will it be the Agencies responsibility to handle or that of the Primary selected for the award?

The solicitation but did not speak of the need or no need to move existing personnel during construction. Rarely do solicitations spell that out and we as CORT work backwards to follow the path and see if needed an if so who the responsibility of setting it up would fall under” Answer: The Solicitation/Invitation for Bids does not intend for the requirement of “swing space” other than that which has been indicated by the Phased design, within the confines of the existing building.

22. Correction: Solicitation Correction Only: J-3 Supplemental Design Clarifications, Page 26 of 39, change “Attachment 8 Supplemental Design Clarifications” to “Attachment 9 Supplemental Design Clarifications.”

23. Question: Print E001, general notes, 27, Provide 3 cables per outlet 271500-1,1.4, A4, Provide 2 cables per outlet, which is it, 2 or 3 cables per?

Answer: Drawing Sheet E001, Delete General Note 27 and replace with the following:

“27. CAT-6A DATA CABLE BUILDING STANDARD: UL LISTED CAT6A F/UTP 0.29” O.D. AT 40% FILL MAX: (3 IN 3/4” EMT) (20 IN 2” PVC) (80 IN 4” PVC)' MEETING TIA-568-C.2 CATEGORY 6A

REQUIREMENTS CREATING A TESTED CHANNEL CAPABLE OF SUPPORTING 10GBASE-T

OPERATION AT 100 METERS. COLOR: 06=BLUE; FOR EACH TV LOCATION PROVIDE (2) CAT 6A

CABLES; COLOR: 02=WHITE (HDMI IN AT SIGNAL SOURCE); 02=WHITE (HDMI OUT AT TV); FOR

TV RUNS LONGER THAN 25 FEET, PROVIDE POWER EXTENDER AT TV END. PROVIDE CAT-6A

CABLES STANDARD AT EACH OUTLET PER PLANS. CONTRACTOR RESPONSIBLE FOR

QUANTITIES.”

Refer to Sheets E310, 311, and 312; the number adjacent to each communication outlet reflects the number of cables to be provided for that respective outlet.

24. Question: The documents conflict in areas. Mainly these two things:

1. CAT6A (10 GB) or CAT6 (1 GB)

2. Shielded cable & Connectivity vs non-shielded cable and connectivity

Answer: Owner has ran CAT 6 cabling in “Modular” building from outlets to rack shown on E312; awaiting for contractor to provide final terminations at rack on punch-down as noted. CAT 6 cabling is compatible with CAT 6A jacks & punch-down specified. Extended warranty N/A for “Modular” building. There are no planned outlets at this time for “Shop” building; just fiber, rack & other shown on E312. Extended warranty N/A for “Shop” building.

25. Question: Is this project on an Indian Reservation?

Answer: This project is not located on an Indian Reservation. See Solicitation Section H-9 Site Ownership.

26. Question: Will we be required to hire and utilize Indian/Native American labor? Are we required to solicit from Native American vendors?

Answer: There are clauses included within the Solicitation which require consideration for Indian hiring.

They are:

52.222-26 Equal Opportunity (APR 2015) - Alternate I (FEB 1999) Notice. The following terms of this clause are waived for this contract: Indian Preference for hiring is allowed under this contract.

352.270-2 INDIAN PREFERENCE (APR 1984)

352.270-3 INDIAN PREFERENCE PROGRAM (JAN 2006)

27. Correction: Sheet E107: Referring to the Shop, delete “VAULT BY OTHER” and add, “VAULT TO BE INSTALLED BY CONTRACTOR”, similar to Flag Note 6.

28. Question: Is there any interest in upgrading/replacing the existing fire alarm system, or is this going to be a re-locate and expand scenario? There’s nothing in the specs I could find regarding the fire alarm system, and all the sheet notes point to relocating the existing system.

Answer: The intent for altering the fire alarm system includes only specific alterations which are shown throughout the plans, specifically E-300 series sheets.

29. Question/Comment: Attached are specs for the storefront 084113 as there are some mistakes and I have highlighted them so they will match the existing storefronts. The existing newer frames are an Offset glazing system, Dark Bronze and the vent window is a zero sightline window.

Answer: (Corrected Specifications not provided.) Section 084113 – 2.3.A.3. Replace “Center” with “Offset”. Section 084113 – 2.8.A. Replace “Clear” with “Dark Bronze”. Add General Note, “Field verify existing storefront style and finish, match adjacent.”

30. Question: I am also requesting a substitution request for Arcadia Inc. for the storefront and the doors. The odd thing is that in specs 085113 Aluminum Windows the Arcadia window is listed. The Arcadia product is an equal to the Kawneer or any of the other manufactures that are listed.

Answer: No pre approvals for submittals are being considered. Please see Supplemental Design Clarifications.

31. Question: What quality and quantity of cabling is required at a standard communications outlet?

The specifications state CAT6 the plans call for CAT6A? Section 271500-Sub-section 1.4 A-4 calls for (2) CAT6 cables. The Electrical Cover Sheet E001 Note #27 calls for (3) CAT6A cables? Sheet E202 note #13 calls for (2) cables typical?

Answer: Refer to answer to Question 11.

32. Question: Is an extended Warranty Required?

Answer: In regards to what component? Provide warranties required by the specifications.

33. Question: What Manufacturer is Approved. The specs call for a Systimax Warranty section 271500 sub-section 1.9. Then in sub-section 2.4 and 2.5 it calls out several other manufacturers?

Answer: Refer to answer to Question 3.

34. Question: Who is responsible for Patch Panels? Section 271500 subsection 2.3 A-1 states the owners forces will be providing and installing then? Sheet E501 Flag Note #2 says that the patch panels should be provided?

Answer: See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1 and answer to Question 9, this Amendment.

35. Who is terminating the copper and fiber cabling? The Specifications repeatedly call for the Owners forces to terminate all copper and fiber at the closet. Section 271500 Sub-Section 1.4-a and sub-section 1.5 a, b calls for leaving a 15’ coil at the cabinet or rack for termination by owners forces?

Sheet E205 note #11 calls for leaving the fiber coiled for termination by owner’s forces?

Answer: See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1 and the answer to Question 5.

36. Question: Sheet E310 Flag Note #1 calls for cabling to the speakers are the speakers New or Existing?

Answer: Plans per Flag Note 1, E310 show PA speaker punch-down and wiring to speakers provided by contractor. Speakers and PA system are by owner, not included in this contract.

37. Question: Sheet E310 Flag Note #5 calls out up to (90) occurrences of cabling that needs to be replaced but are not shown? How many cables per occurrence and what length should be assumed?

Answer: Some cabling does not have existing raceways due to construction modification that occurred in the 1990s. These locations are not identified. The contractor shall anticipate one raceway per occurrence and the length should be assumed to be the floor to ceiling height.

38. Question: Sheet E312 Flag Note #4 calls for Fibertronics enclosure, Commscope Fiber, Leviton Patch Panels? This cannot be warrantied with an extended warranty.

Answer: The intent is to have continuity throughout a manufacturer’s family of parts. Install equipment that will ensure warranties are achievable.

39. Question: Sheet E501 Flag Note #2 the components called for cannot be used together for an extended product warranty. Components must be from a matching manufacturer or manufacturing partner.

Answer: The intent is to have continuity throughout a manufacturer’s family of parts. Install equipment that will ensure warranties are achievable.

40. Question: Spec Section 271500 Sub-Section 2.6-B calls for 50 micron fiber. Sub-Section C calls for it to have an orange jacket? 50 Micron cable is an industry standard aqua Color but can be purchased in other colors. Which color is requested?

Answer: See Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1. Color required is Orange.

41. Question: Spec Section 271500 Sub-Section 2.8-B, 1 calls for Plastic Faceplates except (Stainless Steel Where Present)? How should this be quoted? Stainless steel faceplates are much more expensive than plastic. Is there an approximate Number of faceplates to quote as Stainless Steel?

Answer: The faceplates (and other materials) should be included within the Construction Phase, as shown on the Schedule of (Bid) Items. There is no “approximate Number of faceplates” provided in the Solicitation. Field verify.

42. Question: Spec Section 271500 Sub-Section 3.8 B-C cannot be fulfilled if other people are performing terminations.

Answer: All terminations shall be performed by the Contractor.

43. Question: Could we please get the asbestos & lead paint reports for this facility and any approximate locations and quantity of asbestos & lead paint.

Answer: See the construction documents and the Asbestos Report attached as “Amd 1 Exhibit 5:

Asbestos Abatement – Taholah, Queets & Chemawa Close Out Report. There is no known lead based paint present.

44. Question: Is there any medical gas that may need to be rerouted and/or decommissioned? I noticed a dental clinic and most of the ones I have been in have at least a vacuum system and a couple bottles of oxygen and nitrous hooked up to a header. I also was curious about any chemical waste piping, mainly around the film processor area, that we may encounter.

Answer: See Sheet M101, Flag Note 2. No other central medical gas systems are present. Film processor drainage piping to be abandoned is anticipated to be normal waste piping.

45. Question: Will there be future opportunities for pre-bid site visit?

Answer: There is an opportunity to visit the site on Wednesday, November 25, 2015. The interior of the building will be open for viewing at 8:30 – 9:30 interior tour, afterward; there will be additional opportunity to walk the outside area. Please check in at the front reception area beginning 8:00 AM PST and RSVP to Gene Kompkoff no later than Tuesday, November 24 at noon. His email address is Gene.Kompkoff@ihs.gov.

46. Question: Note 7 on M001 states that drawings that are not stamped and signed should not be used for bidding unless expressly approved in writing by Meier. The drawings do not appear to be signed. Has Meier approved these drawings for bidding?

Answer: The drawings have been electronically stamped and are approved for bidding purposes.

47. Question: Asbestos abatement is typically done by specialists. Hazardous materials are typically removed from the space prior to other trades starting work. Is the intent to have subcontractors abate asbestos as it is found, as seems to be indicated by the Bldg Hazardous Materials Notes on M002? The scope of abatement work will not be known until after the contract has been awarded. The government may not receive comparable bids when the scope is unknown.

Answer: The successful Contractor is responsible for abating all Asbestos.

48. Question: Please define the comfort criteria for temporary heating and cooling where FC-4-8 and FC-4-9 will not be available to serve phase 3 until phase 4 is done? For example, can the temperatures rooms be controlled by a central temporary thermostat and therefore some rooms may be a few degrees warmer or cooler than others? Or will a more elaborate temporary system be required that will keep all rooms in the affected area within a degree or two of the setpoint.

Answer: Temporary heating and cooling shall meet the following conditions: Relative Humidity: 30 – 60%; CO2 Concentrations < 1,000 PPM; Summer Temperature Range: 72.5°F – 80°F; Winter Temperature Range: 68°F – 76°F.

49. Question: Structural details for supporting rooftop units Sections A through E on S503 are not referenced elsewhere in the plan set except generally by the Mechanical roof plan M210. Even though the structural drawings are referenced by the mechanical roof plan it appears that the work is to be installed below the roof. On what basis will approval be granted for the delegated design of the structural steel design and unit support?

mailto:Gene.Kompkoff@ihs.gov

Answer: The work is installed below the roof. Install supports per the structural drawings. There is no delegated design intended for the support structure.

50. Question: Detail 1/A111 shows a curb for a standard exhaust fan. The detail does not pertain to anchoring of the VRV heat pumps to the roof. Can additional details be provided, so bids are based on the same information?

Answer: Provide rail similar to curb shown in detail 1/A101 with (3) 2x built up and fully attached to roof deck. Run roof membrane up all sides and under continuous metal cap. Lap and heat weld roofing membrane as shown in detail.

51. Question: What are the criteria by which the government will determine whether the structural supports and attachment details are adequate? Will the government provide special inspections outside of the contract?

Answer: Supports per the design documents shall be deemed adequate.

52. Question: Are as-built drawings of the mechanical systems available?

Answer: No.

53. Question: What is the make and model of the existing Chiller?

Answer: The make and model of the existing Chiller is: YORK YCAZ33B3.

54. Question: Is your MOD 1 the changes, I do not see anything for voice/data, all I see is moving camera.

Looking at MOD 1 it looks like there are two sets of prints with different info.

E310, E311 and E312 are those the prints to bid off?

E202, E203 and E205 are those the prints I bid off?

Answer: Assuming this question relates to communication, see Sheets E310, E311, and E312.

55. Question: Several contractors and subcontractors are asking for approvals prior to bid/award.

Answer: Please see the Supplemental Design Clarifications where it states that pre-approval for products will not be provided.

56. Question: 1- Are the new ADA ramps to the Southeast to be included in Base Bid Phase 1 or in option #1?

Answer: There are no ADA ramps to the SE of the building. If the question is in reference to the site work at the entrance on the SW, that work shall be included in the Base Bid.

57. Amendment 1 Exhibits are included and are entitled as follows:

Amd 1 Exhibit 1 Attendees for the Pre-Bid Meeting, 3 pages Amd 1 Exhibit 2 7309 271500 - Communications Cabling REV 1, 12 pages Amd 1 Exhibit 3 7309 230548 SF - VIBRATION AND SEISMIC CONTROLS FOR HVAC, 7 pages Amd 1 Exhibit 4 7309 233713 FL - DIFFUSERS, REGISTERS, AND GRILLES, 6 pages Amd 1 Exhibit 5 Asbestos Abatement - Taholah, Queets & Chemawa Close Out Report, 81 pages

kamd 1
Amd 1 Text