This solicitation seeks proposals to operate the San Diego Job Corps Center. The contractor will be responsible for providing academic, career technical, and career success skills training to 555 students, consisting of 300 residential male students, 218 residential female students, and 37 nonresidential students. Outreach and admissions services must enroll a minimum of 800 students annually. The contractor must ensure the center maintains an average monthly student enrollment of 100% of the planned 555 students. Career transition services must also be provided to all graduates and former students for their period of eligibility, including those who separated under the prior operator. The Department of Labor Employment and Training Administration is the issuing agency.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAN DIEGO
Job Corps Center Imperial Beach, CA
Facility Planning Report Volume II
Supporting Data
Final March 2018
Department of Labor/ Office of Job Corps
SAN DIEGO
Job Corps Center Imperial Beach, CA
Facility Planning Report Volume II
Supporting Data
Final March 2018
Dormitory area at the east side of campus
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Existing Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The f the w Data, The i
Secti detail as w inform facility surve week of Sept , represents t information
Existing s Overall st Space util Status of Details on and mech Presentati document Supportin meeting;
active wa on 1.0 of th ls on the bu well as new mation as no
Appendix Appendix Appendix Appendix ey for San D tember 11, 2 the current s includes the site layout tatus of exist lization by b environment n the site an hanical surve ion of the sta ted through t ng document survey brief rranties his volume uildings and ones ident oted below:
x A. Survey B x B. Life Saf x C. O&M D x D. Active W
Diego Job C 2017. The status of the following:
ting building building and tal elements nd buildings ey and suppo atus of histo this survey tation, as pr f and student addresses si structures. S tified in thi
Brief Questi fety Deficien
Deficiencies L Warranty Re
EXECUT
Corps Cent information campus.
g and structu function com of the Cente and structur orting docum rical deficien resented in t questionnai ite layout an Section 3.0 p is survey.
ionnaire ncies and Lis List eport
IVE SUMM
ter (San Die n presented i ures mpared to re er’s operatio ures based on mentation ncies and co the appendi ire; life safet nd plans wh presents def The append st
MARY
ego JCC) w in Volume I ecommended ons n architectur ompilation o ices of the c ty IA/IIA tra hile Section ficiencies an dices provid was complete II, Supportin d standards ral, electrica of deficiencie center review ansmittal; an n 2.0 present nd their statu de additiona ed ng al, es w nd ts us al
1.0 - Site Layout and Plans
SAN DIEGO
JOB CORPS CENTER
IMPERIAL BEACH, CALIFORNIA
SAN DIEGO JCC
10 MI50
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00909 SAN DIEGO 03/19/2018
1Page: of Date:
0013 - CONSTRUCTION TRADES BLDG
0015 - HEALTH SERVICES BUILDING
0016 - EDUCATION
0018 - VACANT
0019 - EDUCATION
0020/21 - CDSS/ADMIN
0022 - ADMISSIONS
0023 - ACADEMIC
0029/30 - MAINTENANCE
0031 - HEALTH OCCUPATION
0040 - GYMNASIUM
0048 - CHILD CARE & DEVELOPMENT
(VACANT)
0059 - RECREATION
0060 - ADMINISTRATION/SECURITY
0062 - ACADEMIC CLASSROOMS
0177 - DORMITORY
0178 - EDUCATION/DORMITORY
0179 - DORMITORY
0180 - POWER PLANT
0181 - DINING HALL
0190 - VACANT
0191 - DORMITORY
0192 - DORMITORY
0194 - HEATING PLANT
0195 - CULINARY ARTS
0225 - HARD VOCATIONS/RECEIVING
SD5 - TRADES STORAGE
0012 - VOCATION STORAGE (13Ft x 20Ft) 0013A - MOCK-UP CANOPY (8Ft x 8Ft) 0029A - STORAGE (8Ft x 50Ft) 0030A - STORAGE (12Ft x 12Ft) 0030B - STORAGE (12Ft x 12Ft) 0043 - CARPENTRY STORAGE (20Ft x 96Ft) 0045 - CARPENTRY STORAGE (20Ft x 146Ft) 0062A - STORAGE (8Ft x 10Ft) 0063 - COMFORT STATION (24Ft x 34Ft) 0108 - STORAGE (25Ft x 30Ft) 0109 - STORAGE (8Ft x 32Ft) 0110 - CONCRETE MOCK-UP (5Ft x 15Ft) 0183 - HBI STORAGE (20Ft x 30Ft) 0188 - STORAGE (20Ft x 35Ft) 0195A - CULINARY PERGOLA (13Ft x 14.5Ft) 0198 - SECURITY GATE HOUSE (12Ft x 16Ft) 0199 - BUS SHELTER (4Ft x 100Ft) 0200 - GRILL CANOPY (7Ft x 28Ft) 0201 - CARGO STORAGE #1 (8Ft x 20Ft)
Name GSF
17,027 10,400 11,342 3,062 2,820 6,897 2,507 6,670 6,554 3,964
16,595 2,625
16,769 11,560 6,920
21,635 21,635 21,635 1,512
15,016 36,213 12,411 12,411
10,420 17,510 2,983
1,800
2,820
Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active Active Active Active Active Active Active Active
Active
Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building
Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure
Structure
Structure Structure Structure Structure Structure Structure Structure Structure
Structure
Structure Structure Structure
Use Group Built Flrs Const
Business Business Business Business Business Business Business Business Business Business Assembly Day Care
Assembly Business Business Residential Residential Residential Utility/Misc.
Assembly Residential Residential Residential Utility/Misc.
Business Business Storage Storage Assembly Storage Storage Storage Storage
Storage
Storage Business Storage Storage Storage Storage Storage Assembly
Business
Assembly Assembly Storage
Good Good Good Poor Good Good Good Good Fair
Good Good Poor
Good Good Good Fair Fair
Good Good Good Fair
Good Good Fair
Good Good Good Good Good Good Good Good Good
Good
Good Good Good Good Good Good Poor Good
Good
Good Good Good
ConditionAsset Number
0090900002 0090900003 0090900004 0090900005 0090900006 0090900007 0090900009 0090900010 0090900016 0090900018 0090908007 0090900020
0090900021 0090900022 0090908013 0090900027 0090900028 0090900029 0090900041 0090900030 0090900031 0090900032 0090900033 0090900044 0090900034 0090908012 0090900049 0090900035 0090908024 0090908033 0090908037 0090908038 0090900037
0090900038
0090908034 0090900039 0090900026 0090908031 0090908032 0090900043 0090900042 0090908025
0090900045
0090908021 0090908022 0090908035
BUILDINGS AND STRUCTURES
00909 SAN DIEGO 03/19/2018
2Page: of Date:
0202 - CARGO STORAGE #2 - (8Ft x 20Ft) P-1 - PERGOLA #1 (12Ft x 40Ft) P-2 - PERGOLA #2 (7Ft x 28Ft) P3 - PERGOLA #3 (10Ft x 22Ft) P4 - PERGOLA #4 (10Ft x 22Ft) P5 - PERGOLA #5 (9Ft x 10Ft) SD1 - PAINT STORAGE (10Ft x 10Ft) SD10 - CDC PLAY STRUCTURE (8Ft x 10Ft) SD11 - STORAGE (12Ft x 16Ft) SD12 - CDC PLAY STRUCTURE (8Ft x 8Ft) SD13 - STORAGE (12Ft x 18Ft) SD14 - STORAGE (12Ft x 18Ft)
SD15 - CLOCK TOWER
SD2 - GROUP LIFE STORAGE (16Ft x 50Ft) SD4 - STORAGE (16Ft x 50Ft) SD6 - STORAGE (12Ft x 24Ft) SD8 - CDC STORAGE (8Ft x 10Ft) SD9 - CDC STORAGE (8Ft x 10Ft)
Name GSF
Active Active Active Active Active Active Active Active
Active Active
Active Active Active Active
Active Active Active Active
StatusType
Structure Structure Structure Structure Structure Structure Structure Structure
Structure Structure
Structure Structure Structure Structure
Structure Structure Structure Structure
Use Group Built Flrs Const
Storage Assembly Assembly Assembly Assembly Assembly Storage Storage
Storage Assembly
Storage Storage Assembly Residential
Residential Residential Storage Storage
Good Good Good Good Good Good Good Good
Good Good
Good Good Good Good
Good Good Good Good
ConditionAsset Number
0090908036 0090908019 0090908020 0090908026 0090908027 0090908028 0090908016 0090908017
0090908018 0090908029
0090908039 0090908040 0090908041 0090900047
0090900053 0090900054 0090908014 0090908015
27 299,561
37 14,350
64 313,911
Buildings
Structures
Total
GSF
GSF
GSF
Summary
03/19/2018
Space Utilization By Function 00909 San Diego Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 518 Non Residents 37
555Total Students
(518)
(555)
(555)
DIFFERENCE
55,944
45,090
9,990
62,185
66,749
14,558
Lounge Other Shower/Toilet Sleeping excl. SPD(146 rooms; 542 beds) Storage
Academic (555) Non-Academic
6 -- Advanced Career Training 24 -- Automotive Services + 20 -- Bricklayer + 40 -- Carpentry + 20 -- Cement Masonry + 30 -- Computer Service Tech.
60 -- Culinary Arts + 24 -- Electrical + 20 -- Floor Covering Layer + 30 -- Hotel/Motel Clerk 30 -- Medical Office Support 90 -- Nursing Assistant + 30 -- Office Administration 20 -- Painting + 30 -- Pharmacy Tech + 20 -- Plastering + 24 -- Plumbing + 30 -- Security Services 24 -- Welding +
Vocational Theory (416)
Dining (2 Servings) Food Preparation Food Storage
7,325 4,091 6,583
40,745 3,441
12,611 14,140
3,466 2,950 3,936 2,076 1,664 3,641 1,520 1,040
2,559 1,964 1,626
2,086 1,404 1,441 3,423
2,435
7,060 4,736 2,762
5,180 4,144 6,216
37,296 3,108
5,550 5,550
1,800 1,500 3,000 1,500
3,600 1,200 1,000
3,600 1,350 1,500 1,350 1,500 1,200 1,050 1,800
4,160
4,440 3,330 2,220
2,145 -53
3,449
7,061 8,590
1,666 1,450
-170
-1,041
-632
1,623
-1,725
2,620 1,406
Vocations
6,241
21,659
4,568
Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 296.38 164,489 233,631
(555)
(555)
(555)
(555)
(555)
(0)
DIFFERENCE
26,455
3,145
11,100
11,100
1,665
25,654
5,570
10,537
12,241
35,537
Aerobics/Exercise Arts & Crafts Cultural Center Gymnasium Learning Resource Center/Library Miscellaneous Recreation Pool Hall Recreation Office Recreation Storage Snack Bar T.V. Room Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
SECURITY
Vacant
5.67
2,924 2,640
9,700
1,906 3,514 1,560
1,378
5,570
10,537
6,416 5,825
35,537
3,145
11,100
4,440 6,660
1,665
2,425
-563
1,976 -835
-1,065
RESIDENT
NON-RESIDENT
(518)
(37) 15
50 25,900
-801
2,425
-563
1,141
-1,065
35,537
69,142
Page: 3 of Date:
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE DIFFERENCE
299,561
0.78
TOTAL GSF
NET TO GROSS RATIO
Net Square Footage By Building Date: 03/19/2018 Page: 1
Center: SAN DIEGO (00909) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
7,088 7,518 9,327 9,592 7,220
1,326 1,786
1,818 1,442
2,160
2,244 1,496 1,139
1,040
0192 - DORMITORY
0178 - EDUCATION/DORMITORY
0179 - DORMITORY
0177 - DORMITORY
0191 - DORMITORY
0191 - DORMITORY
0192 - DORMITORY
0177 - DORMITORY
0179 - DORMITORY
0178 - EDUCATION/DORMITORY
0191 - DORMITORY
0178 - EDUCATION/DORMITORY
0177 - DORMITORY
0179 - DORMITORY
0192 - DORMITORY
0192 - DORMITORY
0191 - DORMITORY
0179 - DORMITORY
0178 - EDUCATION/DORMITORY
0177 - DORMITORY
0191 - DORMITORY
0180 - POWER PLANT
0179 - DORMITORY
0178 - EDUCATION/DORMITORY
0192 - DORMITORY
0177 - DORMITORY
Bldg Name Actual NSF Difference
40,745
7,325
3,441
6,583
4,091
Sub Total: 62,185
37,296
5,180
3,108
6,216
4,144
55,944
3,449
2,145
-53
( 518
6,241
24 rooms; 96 beds 28 rooms; 100 beds 42 rooms; 150 beds 28 rooms; 100 beds 24 rooms; 96 beds
Page: 2
Center: SAN DIEGO (00909) of 5
EDUCATION
Academic
Vocational Theory (416)
Carpentry
Cement Masonry
Electrical
Plumbing
Culinary Arts
Welding
Painting
Plastering
Bricklayer
Floor Covering Layer
Computer Service Tech.
Security Services
Function Suggested
NSF
2,158
5,696
1,364
1,750
3,450
1,590
1,520
1,404
3,641
3,423
1,140
1,600
2,464
1,040
1,664
1,441
0062 - ACADEMIC CLASSROOMS
0062 - ACADEMIC CLASSROOMS
0062 - ACADEMIC CLASSROOMS
0062 - ACADEMIC CLASSROOMS
0019 - EDUCATION
0023 - ACADEMIC
0062 - ACADEMIC CLASSROOMS
0062 - ACADEMIC CLASSROOMS
0225 - HARD VOCATIONS/RECEIVING
0013 - CONSTRUCTION TRADES BLDG
SD5 - TRADES STORAGE
0013 - CONSTRUCTION TRADES BLDG
0013 - CONSTRUCTION TRADES BLDG
SD5 - TRADES STORAGE
0013 - CONSTRUCTION TRADES BLDG
0013 - CONSTRUCTION TRADES BLDG
0195 - CULINARY ARTS
0225 - HARD VOCATIONS/RECEIVING
0013 - CONSTRUCTION TRADES BLDG
SD5 - TRADES STORAGE
0013 - CONSTRUCTION TRADES BLDG
SD5 - TRADES STORAGE
0013 - CONSTRUCTION TRADES BLDG
SD5 - TRADES STORAGE
0013 - CONSTRUCTION TRADES BLDG
0016 - EDUCATION
0195 - CULINARY ARTS
Bldg Name Actual NSF Difference
12,611
2,435
3,936
2,076
1,520
1,404
3,641
3,423
1,626
2,086
2,950
1,040
1,664
1,441
5,550
4,160
3,000
1,500
1,200
1,200
3,600
1,800
1,500
1,500
1,500
1,000
1,050
7,061
-1,725
1,623
1,450
( 555 )
Page: 3
Center: SAN DIEGO (00909) of 5
EDUCATION
FOOD SERVICE
Non-Academic
Hotel/Motel Clerk
Automotive Services
Nursing Assistant
Advanced Career Training
Pharmacy Tech
Office Administration
Medical Office Support
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
4,428
1,773 2,433
1,874
3,466
2,559
1,964
7,060
4,736
2,762
0178 - EDUCATION/DORMITORY
0020/21 - CDSS/ADMIN
0015 - HEALTH SERVICES BUILDING
0016 - EDUCATION
0016 - EDUCATION
0020/21 - CDSS/ADMIN
0019 - EDUCATION
0023 - ACADEMIC
0019 - EDUCATION
0195 - CULINARY ARTS
0225 - HARD VOCATIONS/RECEIVING
0031 - HEALTH OCCUPATION
0016 - EDUCATION
0031 - HEALTH OCCUPATION
0016 - EDUCATION
0016 - EDUCATION
0181 - DINING HALL
0181 - DINING HALL
0181 - DINING HALL
Bldg Name Actual NSF Difference
14,140
3,466
2,559
1,964
7,060
4,736
2,762
Sub Total:
Sub Total:
66,749
14,558
5,550
1,800
3,600
1,350
1,350
4,440
3,330
2,220
45,090
9,990
8,590
-170
1,666
-1,041
-632
2,620
1,406
( 555
21,659
4,568
Page: 4
Center: SAN DIEGO (00909) of 5
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Miscellaneous Recreation
Pool Hall
Aerobics/Exercise
Cultural Center
T.V. Room
Learning Resource Center/Libr
Recreation Storage
Recreation Office
Medical/Dental
Administration
Function Suggested
NSF
2,640
9,700
1,906
3,514
1,864 1,060
1,378
1,280
5,570
1,601 2,082 6,854
0040 - GYMNASIUM
0059 - RECREATION
0040 - GYMNASIUM
0040 - GYMNASIUM
0059 - RECREATION
0059 - RECREATION
0059 - RECREATION
0040 - GYMNASIUM
0059 - RECREATION
0059 - RECREATION
0059 - RECREATION
0040 - GYMNASIUM
0040 - GYMNASIUM
0059 - RECREATION
0015 - HEALTH SERVICES BUILDING
0022 - ADMISSIONS
0020/21 - CDSS/ADMIN
0060 - ADMINISTRATION/SECURITY
Bldg Name Actual NSF Difference
2,640
9,700
1,906
3,514
2,924
1,378
1,560
5,570
10,537
Sub Total:
Sub Total:
Sub Total:
25,654
5,570
10,537
3,145
11,100
26,455
3,145
11,100
2,425
-563
-801
2,425
-563
Page: 5
Center: SAN DIEGO (00909) of 5
STORAGE/SUPPORT
SECURITY
VACANT
Warehouse
Operations & Maintenance
SECURITY
Vacant
Function Suggested
NSF
4,831
5,996
2,204 3,021
27,472 2,840
0177 - DORMITORY
0225 - HARD VOCATIONS/RECEIVING
0194 - HEATING PLANT
0029/30 - MAINTENANCE
0060 - ADMINISTRATION/SECURITY
0048 - CHILD CARE & DEVELOPMENT (VACANT)
0177 - DORMITORY
0190 - VACANT
0018 - VACANT
Bldg Name Actual NSF Difference
5,825
6,416
35,537
Sub Total:
Sub Total:
Sub Total:
12,241
35,537
6,660
4,440
1,665
11,100
1,665
-835
1,976
-1,065
35,537
1,141
-1,065
35,537
Environmental Management Report Center: SAN DIEGO (00909)
Page: 1 Date: 03/19/2018 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 12, Building SD-1
Acetlylene gas cylinders, argon gas cylinders, propane tanks Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
Natural gas boilers Minor Source - Exempt
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Pacific Waste Management Yes Pool chemicals
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service Safety Kleen, Inc.
Yes Yes
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
04/03/1989 Friable/Non-Friable Fred Latham 04/01/1998 Yes No N/A Yes No
Ozone
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 03/19/2018Center : San Diego (00909) Page: 1 of 3
Wall Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes
Floor Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes HVAC (Bldg) Floor Finishes
Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Asbestos cement board
9x9 floor tile, brn. (covered) 12x12 floor tile (covered) 9x9 floor tile, tan (covered)
12x12 floor tile, tan
12x12 floor tile (covered)
9x9 floor tile, brown/white 12x12 floor tile, off-white 9x9 floor tile, tan
9x9 fl. tile, black (covered) Flexible duct connector 9x9 fl. tile, maroon (covered)
9x9 floor tile, tan (covered)
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Mechanical room
Driver's education SW hallway storage Driver's education
East bathroom
Throughout
Throughout North storage North bathroom
TV room Pool room TV room
2nd floor
Building :
Building :
Building :
Building :
Building :
Building :
Building :
0015 - HEALTH SERVICES BUILDING
0016 - EDUCATION
0018 - VACANT
0022 - ADMISSIONS
0029/30 - MAINTENANCE
0059 - RECREATION
0060 - ADMINISTRATION/SECURITY
Page: 2 of 3
Floor Finishes Floor Finishes
Floor Finishes
Roof Repair/Replacement
Floor Finishes
Floor Finishes
Floor Finishes
Floor Finishes
Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
9x9 floor tile, white 9x9 floor tile, yellow
9x9 floor tile, white
Roof flashing
9x9 floor tile, white
12x12 floor tile (covered)
9x9 floor tile, white
9x9 floor tile, brown/white
9x9 floor tile, brown/white
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Throughout 1st floor hallway
Throughout
Roof perimeter
Storage room
Manager's office
Dormitory rooms
Throughout
Throughout
20000
20000
18000
10000
10000
Building :
Building :
Building :
Building :
Building :
Building :
Building :
Building :
0177 - DORMITORY
0178 - EDUCATION/DORMITORY
0179 - DORMITORY
0180 - POWER PLANT
0181 - DINING HALL
0190 - VACANT
0191 - DORMITORY
0192 - DORMITORY
Page: 3 of 3
Roof Repair/Replacement
HVAC (Bldg) Floor Finishes Floor Finishes Floor Finishes Roof Repair/Replacement
Bldg System
Bldg System
Roof flashing
Flexible duct connector 9x9 floor tile, white 9x9 floor tile, white 9x9 floor tile, beige Roof flashing
Category Description
Category Description
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Unit
Unit
Quantity
Quantity
Roof perimeter
Mechanical room Cafeteria Kitchen Kitchen storage room Roof perimeter
Building :
Building :
0194 - HEATING PLANT
0195 - CULINARY ARTS
Radon
Page: 1 of 2
0013 - CONSTRUCTION TRADES BLDG
0015 - HEALTH SERVICES BUILDING
0016 - EDUCATION
0018 - VACANT
0019 - EDUCATION
0020/21 - CDSS/ADMIN
0022 - ADMISSIONS
0023 - ACADEMIC
0029/30 - MAINTENANCE
0031 - HEALTH OCCUPATION
0040 - GYMNASIUM
0048 - CHILD CARE & DEVELOPMENT (VACANT)
0059 - RECREATION
0060 - ADMINISTRATION/SECURITY
0062 - ACADEMIC CLASSROOMS
0177 - DORMITORY
0178 - EDUCATION/DORMITORY
0179 - DORMITORY
0180 - POWER PLANT
0181 - DINING HALL
0190 - VACANT
0191 - DORMITORY
0192 - DORMITORY
0194 - HEATING PLANT
0195 - CULINARY ARTS
0225 - HARD VOCATIONS/RECEIVING
SD5 - TRADES STORAGE
Bldg Name
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
10/23/2008
10/20/2008
06/06/1990
06/06/1990
10/23/2008
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
N/A
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view of San Diego JCC
Page: 1 Date: 03/19/2018 of 4
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt/Concrete Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualSan Diego Public Water AuthorityPublic Water Authority
None 0None
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 7None Municipal
The adjacent naval air base provides fire protection services. An Inter-Service Support Agreement between the Navy and DOL in which DOL reimburses the Navy for fire protection and security services for the Center.
Sewage Treatment Flow
Navy
Publicly Owned Treatment Works
Navy
Gravity
Maintenance ResponsibilityOwnership
Number of Deficiencies = 2
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
3. Sanitary Sewer System/ Sewage Treatment Plant
2. Fire Protection System
Buildings Structures27 37Flat
Surrounding
Outdoor Recreation
Active Military Base, Residential
Ball Field, Basketball, Handball Court Amphitheater
Baseball Field
CDC area
Entire Site
Chain Link
Chain Link
CMU/ Stucco
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Navy Navy Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Navy Navy Yes Good
System Capacity Adequate System Condition
Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 03/19/2018 of 4
San Diego Gas and Electric Thru USN
Comments: The boiler in Building 180 serves Buildings 177, 178, and 179. The boiler in Building 194 serves Buildings 191 and
192. The boiler in Building 195 also serves Building 190.
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
San Diego Gas & Electric Thru USN
Services to the Center are both overhead and underground from pole-mounted and pad-mounted transformers throughout the Center. The overhead and underground services enter the center at multi points from power poles along Gatlin Street on the southern perimeter and along Lexington Street on the western perimeter of the campus.
Underground services are distributed to the dormitories and gymnasium on the east side of the campus via Substation 1 and Substation 2. Substation 1 serves Dormitory Buildings 177, 178, 179 and Power Plant Building
180. Substation 2 serves Dormitory Buildings 191, 192, Heating Plant Building 194 and Gymnasium Building 40.
The central group of buildings is served by either pole-mounted transformers or pad-mounted transformers located outside the respective building. Similarly Buildings on the west campus are served by either pole-mounted or pad-mounted transformers. The service equipment in the substations includes high voltage switchgear, pad-mounted transformers, low voltage switchgear and meters. Most buildings have their own meter while others are zoned. The Navy owns and maintains all pole and pad-mounted transformers, switchgear and meters. The Navy has recently replaced most of the existing analog meters with new digital meters which can be remotely monitored via GPS.
Pole and Pad Navy
Navy Navy
No
4.16/2.4 kV, 3-Ph, 4 W
480/277V, 120/208 V, 3-Ph, 4 WOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
5. Fuel Distribution System
6. Central Plant
Number of Deficiencies = 3
4. Storm Water System
Drain Type On-Site Storm Water Management
Surface Runoff/underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Navy Yes GoodNavy
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Navy Navy Yes Good
Type Energy Source
Heating Hot Water
Hot Water
Natural Gas
Natural Gas
Buildings 177, 178, 179, 180, 190, 191, 192, 194 and 195.
Bldgs Served
Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Navy
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
Metering Individual
Page: 3 Date: 03/19/2018 of 4
Comments:
Telephone Company
On-site Line Owner
AT&T provides seven T1 lines to the adjacent naval air base for the Center. These lines are then brought to the center and terminate in the main telephone/server room in Administration/Security Building 60. The network and data/communication systems equipment, including portable UPS modules, are all located in this room. Job Corps Data Center (JCDC) provides and maintains internal distribution Voice over IP (VoIP), LAN and WAN networks.
Four T1 lines are dedicated to staff network and the other three to student network. Fiber optic cabling is utilized for interconnections between the server and buildings. The building fire alarm systems are stand-alone. The Navy takes the ownership of the fire alarm and sprinkler systems on the Center. Satellite dish is provided in all dormitories and other recreational facilities. The Center's security system is limited to door alarms for unauthorized ingress/egress detection in all dormitories, and CCTV cameras in Gymnasium Building 40, Child Care & Development Building 48 and Administration/Security Building 60. The cameras are locally monitored from within the respective buildings via black and white and color monitors.
Pacific Bell/AT&T
Maint. Responsibility
Center, Navy Center, Navy
Door Alarms, CCTV, B&W Monitors
9. Electrical (Communication/Alarm/Security)
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole None Building None
Photocell, Time Clock Photocell, Time Clock N/A Photocell, Time Clock N/A
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center, Navy Center, Navy Yes Good
Comments: The Navy owns and maintains all pole-mounted lights and the center owns and maintains the building-mounted exterior lights.
Number of Deficiencies = 1
Number of Deficiencies = 16
STORAGE TANKS: None
Fire Alarm Security
Page: 4 Date: 03/19/2018 of 4
ACCESSIBILITY
Yes
Comments:
NoNoNo
Nine buildings were built in 1943 for the Naval Air Base located in Imperial Beach, CA.
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk High Low LowLow LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 14
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
3 %
Building Descriptions and Structures
BUILDING 13 - CONSTRUCTION TRADES BLDG
Building Descriptions
Page: 1 of 134
Building: 0013 - CONSTRUCTION TRADES BLDG
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Metal Siding Stucco
Wall Roof Rigid Rigid
Metal Rollup - Metal Frame Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 17,027 15,958 2 Owned 1980 Not Evaluated
Comments: Strobes are not provided in the restrooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
N/A
Yes
Yes
No
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Remaining Type Area Served
Metal Gutters and Downspouts 1999 22 Gable Entire Building
Number of Deficiencies = 33. Roof
Entire Building
Area Served
Page: 2 of 134
Building: 0013 - CONSTRUCTION TRADES BLDG
INTERIOR FINISH
Carpet Ceramic Tile Concrete Plywood
CMU Ceramic Tile Drywall Stone
Wood Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Metal Stairs Wood Stairs Comments: There are wood stairs and metal stairs leading to the storage mezzanine.
Fixed - Aluminum Frame; Single Glazing; Fixed - No Frame; Plexiglass Glazing;
Fixed - Wood Frame; Single Glazing; Sliding - Aluminum Frame; Single Glazing;
Ceramic Tile Exposed Structure Gypsum Board
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided by five gas-fired packaged rooftop units, manufactured by Bryant, typical model number is 582ANW024040NAAD and 582ANW048060NAAD, with an input heating capacity ranging from 40 to 60 MBH.
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Gas-Fired Hot Water Heater
Single Duct
Unit Heater
None
Two-Pipe
Electronic
Electric
Mechanical
Natural
None
None
Classrooms and Offices
Shop Area
Ceilings
Page: 3 of 134
Building: 0013 - CONSTRUCTION TRADES BLDG
Mechanical
Mechanical
Dust Collection
Shop Area
Restroom
Shop Area
Comments: Two ceiling hung air cleaners are provided in the carpentry shop, manufactured by Microair, model number is MX1800. The carpentry shop also has three portable dust collectors and one abandoned stationary dust collection system.
Domestic hot water is provided by an electric water heater, manufactured by American Standard, model E-30T-2-6-240V-4500W, with a capacity of 30 gallons and a power rating of 4500 watts.
Comments:
Cast-Iron None None
Drinking Fountain Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Portable Emergency Eyewash Service Sink Shower Urinal Water Closet (Flush Valve) Waterless Urinal
Gas (Natural)
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electronic Mechanical None Classrooms and Offices
PLUMBING
Exhaust Ventilation
Cooling is provided by five packaged rooftop units with DX-cooling coils, manufactured by Bryant, typical model number is 582ANW024040NAAD and 582ANW048060NAAD, with a cooling capacity ranging from 3 to 4-ton.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
3. Air Conditioning
Page: 4 of 134
Building: 0013 - CONSTRUCTION TRADES BLDG
None None ABC Type Fire Extinguisher
Comments: Underground service is brought from a 225 kVA pad-mounted transformer located outside at the back of the building. The transformer energizes an 800A MCB two section switchboard located outside nearby. A utility digital meter capable of being remotely monitored via GPS is installed on the switchboard main section. The switchboard is serving 100A MLO Panel A and 225A MCB in the carpentry shop (from a 225A and 150A CB), 225A MLO Panel C in the tile shop (from a 150A CB), 225A MLO Panel D in the plaster/cement shop (from a 225A CB), 150A MLO Panel E and 225A MCB Panel in the electrical/plumbing shop (from two 150A CB), and 150A MCB Panel H in the painting shop (from a 70A CB). Emergency shut off switches are provided in the carpentry shop. Solar array, consisting of nine solar panels (PS240P-201V, 240W, 29.8V, 8A) connected to the Sunny Boy inverter providing second source of power to the 225A MCB panel located in the electrical shop.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4004, located in the carpentry shop.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. The shops have pendant-mounted fixtures with two 8-foot long mix of T8 and T12 fluorescent lamps.
High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are photocell controlled.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 and T12 - Fluorescent
Offices
Offices
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Vocational
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
Number of Deficiencies = 1
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 5
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 3
Emergency /Exit Lighting3.
LIGHTING
Page: 5 of 134
Building: 0013 - CONSTRUCTION TRADES BLDG
Comments: The building is connected to the Center's LAN system. Classrooms are provided with TV/VCR.
Connected to Main System None None TV with VCR Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The exterior stucco walls are damaged.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
Type Location 120V w/Battery Backup Mechanical Room
Hard wired with battery backup combination carbon monoxide/smoke alarm is provided in the mechanical room.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 15 - HEALTH SERVICES BUILDING
Page: 6 of 134
Building: 0015 - HEALTH SERVICES BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Stucco
Wall Roof Batt Rigid
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 10,400 7,343 1 Owned 1943 Not Evaluated
Comments: Strobes are not provided in the restrooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Surface Run-off 2002 5 Flat Entire Building
3. Roof
Page: 7 of 134
Building: 0015 - HEALTH SERVICES BUILDING
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Concrete Drywall Vinyl Wall Covering
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Ramp Concrete Stairs Comments: There are concrete stairs and concrete ramp leading to the entry.
Fixed - Aluminum Frame; Single Glazing; Single Hung - Aluminum Frame; Single Glazing;
Sliding - Aluminum Frame; Single Glazing;
Acoustical Tile Gypsum Board
Exhaust Ventilation
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2. Asbestos: Yes
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided by ten gas-fired packaged rooftop units, manufactured by Bryant, typical model number is 582ANW030040NAAD and 582ANW060090NAAD, with an input heating capacity ranging in from 40 to 90 MBH.
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electronic Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 1
Page: 8 of 134
Building: 0015 - HEALTH SERVICES BUILDING
Domestic hot water is provided by a gas-fired water heater, manufactured by General Electric, model GG75T6A, with an input of 75.5 MBH, 75 gallons and located in the mechanical room.
Comments:
Cast-Iron None None
Bathtub Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Multi-Compartment Sink Portable Bottled Water Cooler Service Sink Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Packaged Direct
Expansion (Air Source)
Window Unit
Single Duct
None
None
Electric
Electronic
Mechanical
Mechanical
None
None
Offices
Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling is provided by ten packaged rooftop units with DX-cooling coils, manufactured by Bryant, typical model number is 582ANW030040NAAD and 582ANW060090NAAD, with a cooling capacity ranging from 2-1/2 to 5-ton.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Page: 9 of 134
Building: 0015 - HEALTH SERVICES BUILDING
Comments: Underground service is brought from three 25 kVA pole-mounted transformers located southeast of the building. Service terminates in a 400A MCB main distribution panel located in the main corridor near the medical office. A digital utility meter capable of being remotely monitored via GPS is installed on the exterior wall where the overhead service drop enters the building. The 400A MDP serves four 225A MCB panels and two 125A MLO panels providing for providing for general loads (from (4) 225A and (2) 100A
CB).
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an Edwards model 5700, located in the lab.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Corridor lighting is controlled by ceiling-mounted occupancy sensors.
Fluorescent High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are photocell controlled.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Toilets
Storage Rooms
Classrooms
Medical/Dental
Wards (Patient)
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
Type Location 120V w/Battery Backup Ward Room
Plug-in with battery backup carbon monoxide alarms are provided in two ward rooms. There is no carbon monoxide alarm in the isolation room.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required Yes
Number of Deficiencies = 1
Page: 10 of 134
Building: 0015 - HEALTH SERVICES BUILDING
Comments: The building is connected to the Center's LAN system. TV with VCR sets are also provided in the classrooms.
Connected to Main System None None Local Cable Company Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 16 - EDUCATION
Page: 11 of 134
Building: 0016 - EDUCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Stucco
Wall Roof Batt Rigid
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 11,342 7,938 1 Owned 1943 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 2002 5 Gable Entire Building
Number of Deficiencies = 23. Roof
Page: 12 of 134
Building: 0016 - EDUCATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
None
Fixed - Aluminum Frame; Double Glazing; Fixed - Wood Frame; Single Glazing;
Sliding - Aluminum Frame; Plexiglass Glazing;
Acoustical Tile Gypsum Board
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided by four grade-mounted gas-fired packaged units. The units are a mixture of International Comfort, model number GPCM060H100E, Rheem, model number RKMB-A090CM15E, Concord, model number RPG10B60D100LA and Payne, with an input heating capacity ranging from 100 to 150 MBH.
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electronic Mechanical None Entire Building
Page: 13 of 134
Building: 0016 - EDUCATION
Mechanical Restroom
A 30 gallon 4500 watt electric water heater provides domestic hot water to adjacent toilet sinksComments:
Cast Iron None None
Hose Bibb Lavatory Service Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Fan Coil
Single Duct
Refrigerant
None
Electric
Electronic
Natural
Mechanical
None
None
Electronic Equipment
Room
Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
The data room is served by a mini split ductless system A/C unit. The condensing unit is manufactured by Mitsubishi, model number MU12TN and uses refrigerant R-22, with a cooling capacity of 1-ton to an indoor ductless evaporating unit, model MS12TN.
Cooling is provided by four grade-mounted packaged units with DX-cooling coils. The units are a mixture of International Comfort, model number GPCM060H100E, Rheem, model number RKMB- A090CM15E, Concord, model number RPG10B60D100LA and Payne each having a 5-ton cooling capacity.
Comments:
Comments:
Number of Deficiencies = 1
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 14 of 134
Building: 0016 - EDUCATION
Comments: Overhead service is brought from three 25 kVA pole-mounted transformers located southwest of the building. Service terminates in a single section 450A switchboard (manufactured 05/2003, 65 kA), located in the electrical room. The switchboard consists of a digital utility meter capable of being remotely monitored via GPS, a 450A main circuit breaker, a 100A breaker for A/C units, a 225A and a 150A breaker for distribution panels. Same transformer bank also serves Health Occupation Building 31.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Silent Knight SK-6324, located in classroom 106A (Reading/Tabe).
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Pendant-mounted up-light fluorescent light fixtures are utilized in the classrooms. Occupancy sensors are provided for lighting control in the toilet and storage rooms.
Comments: Some combination exit signs emergency light fixtures with battery backup are also provided.
High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are photocell controlled.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 1
Type Location None None
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 15 of 134
Building: 0016 - EDUCATION
Comments: The building is connected to the Center's LAN system. Classrooms are provided with computer work stations. Wall-mounted motion sensors are provided in some classrooms for added protection.
Connected to Main System Motion Detector None TV with VCR Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 18 - VACANT
Page: 16 of 134
Building: 0018 - VACANT
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Stucco
Wall Roof Batt Rigid
Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 3,062 2,840 1 Owned 1943 Not Evaluated
Comments: The building's existing fire alarm system does not include visual alarm devices.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
N/A
N/A
Yes
Yes
N/A
N/A
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Rolled Asphalt Surface Run-off 1988 0 Gable Entire Building
3. Roof
Page: 17 of 134
Building: 0018 - VACANT
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile
Drywall
Wood Unit - Metal Frame Wood Unit - Wood Frame
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
Sliding - Aluminum Frame; Single Glazing;
None None None None Natural None None
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 18 of 134
Building: 0018 - VACANT
Cast-Iron None None
None
Gas (Natural)
Comments:
None None ABC Type Fire Extinguisher
Comments: Underground is service brought from a pole-mounted transformer, located north of the building. Service is terminated in a 200A main circuit breaker located in the same enclosure as the utility meter. The enclosure is located on the north exterior wall. The main circuit breaker serves a 200A MLO panelboard located in the former retail sales area. The transformer also serves Education Building 19 and north service to CDSS/Admin. Building 20/21. As of the September 2017 Facility Survey, Building 18 is scheduled to be demolished and the electrical service had been disconnected.
None Copper None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. This information remain unchanged, since during the September 2017 Facility Survey, the electrical service had been disconnected.
None Comments: As of the September 2017 Facility Survey, all exterior building-mounted light fixtures were removed.
The electrical…