This Request for Proposal from the Smithsonian Institution seeks offers for the replacement of fire alarm panels and devices and fire stair doors and hardware at the National Museum of American History. The work includes demolishing existing Siemens System 3 and MXLV fire alarm control panels and installing new Siemens Desigo modular fire alarm control panels and a new digital addressable emergency voice communication fire alarm system. Additional requirements are the replacement of fire stair doors and hardware in accordance with the specifications and drawings. Offerors must meet all requirements in the solicitation documents. Upon selection of a successful offeror, the Smithsonian will execute a fixed price construction contract estimated between $8.9 million to $12.5 million, with work to be completed within 600 calendar days of the notice to proceed. Subcontracting goals are set at 40% of total cost, excluding Siemens panels and devices, with at least 6% to small disadvantaged businesses, 6% to women-owned small businesses, 3% to HUBZone small businesses, 3% to veteran-owned small businesses, and 3% to service-disabled veteran-owned small businesses.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R. McGhee & Associates 2031 Florida Avenue NW, Third Floor

Washington, DC 20009

SMITHSONIAN INSTITUTE

SF 1603107 | REPLACE FIRE STAIR DOORS

23 SEP 2019

100% CONSTRUCTION DOCUMENTS SUBMISSION

CUT SHEETS

FINAL CONSTRUCTION DOCUMENTS SUBMISSIONBID SET SUBMISION

(PACKAGE B)

Virginia Chan Typewriter Appendix 6

ECSI

NMAH – FIRE STAIR DOOR

REPLACEMENT

DOOR HARDWARE

PRODUCT DATA

Prepared: November, 2019

Erbschloe Consulting Services, Inc.

7820 Carters Run Drive Marshall, VA 20115 P. 540-351-0553 www.ecsi-ahc.com http://www.ecsi-ahc.com/

DOOR HARDWARE CUT SHEETS

HINGES

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 1

CYLINDERS

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 8

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 3

NOTE:

Medeco large format 6 pin IC Core Yale prep PT# 310100 Medeco large format 6 pin IC Housing Yale prep - length 1 3/8 PT# 31-0175

EXIT DEVICES AND ACCESSORIES

98-F/99-F Rim exit device

-F /9

-F

R im e xi t d ev ic e

98-F and 99-F Rim fire exit devices for all types of single doors up to 4' x 10' (1219mm x 3048mm) or 8' x 10' (2438mm x 3048mm) double doors with 9954 or 9854 mullion, UL listed for fire exit hardware. See page 76 for detailed information on UL listed fire exit hardware label and door opening size information. Devices are ANSI A156.3 – 2014 Grade 1. The 98-F device has a smooth mechanism case and the 99-F device has a grooved case. The rim device is non-handed except when the following device options are used: -2 (double cylinder) or SS (signal switch). See opposite page for available outside trim and device functions.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 3' 2'4' to 3' (711mm to 914 mm) Door size

4' 2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

39 13/16" (1011 mm)

39 11/16" (1008 mm) with mullion

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking, 3/4" (19mm) throw

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) and 2 1/4" (57mm) thick metal or wood doors. Optional 425 SNB available for metal doors. 425 & 825 SNB required on wood doors without SLM blocking. See page 11 for quantities.

Electric options LX Latchbolt monitor switch

RX Pushpad monitor switch

RX2 Double pushpad monitor switch

E Electric locking & unlocking trim

EL Electric latch retraction

QEL Quiet electric latch retraction

SS Signal switch

CX Chexit delayed exit

ALK Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

-2 Double cylinder

AX Accessible device GBK Glass bead kit

PN Pneumatic latch retraction

XP Extra protection

SNB Sex bolts

SEC Security screws

SLM Special Laminate Material Blocking

Dogging option No mechanical dogging. EL and QEL option available

Strikes 299F – Dull black, 499F with mullions

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

SG

Safety glow

• Shows exit door location in darkness or smoke

• Developed to meet MEA standards

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

XP

Extra protection

• 90˚ latch-to-strike contact

• Force resistance of 2,000+ lbs.

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

The 299F Strike ships standard, optional strikes available

499F Strike with

9854/9954 mullion

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

AX

Accessible device

• UL certified to meet new 5 lb.

maximum operating force requirement

• Exceeds ANSI/

BHMA

requirements

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 5

18 • Von Duprin • 98/99 Series

9875-F/9975-F Mortise lock fire exit device

-F

/9

-F

M o rt is e lo ck fi re e xi t d ev ic e

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw.

Device lengths 3' 2'4' to 3' (711mm to 914 mm) Door size

4' 2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

39 13/16" (1011 mm)

39 11/16" (1008 mm) with mullion

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) and 2 1/4" (57mm) thick metal or wood doors. Optional 425 SNB available for metal doors. 425 & 825 SNB required on wood doors without SLM blocking. See page 19 for quantities.

Electric options RX Pushpad monitor switch

RX2 Double pushpad monitor switch

E Electric locking & unlocking trim

EL Electric latch retraction

QEL Quiet electric latch retraction

SS Signal switch

CX Chexit delayed exit

ALK Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

-2 Double cylinder

GBK Glass bead kit

PN Pneumatic latch retraction

SNB Sex bolts

SEC Security screws

SLM Special Laminate Material Blocking

Dogging option No Mechanical Dogging. EL and QEL option available

Strikes 575 – Dull Black

SS 7500

Signal switch

• Signals unauthorized use of an opening

• Switch makes latch bolt tamper-resistant

E (E7500) Electric mortise lock device

• Remains latched while unlocked

• Remote electrical control

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

SG

Safety glow

• Shows exit door location in darkness or smoke

• Developed to meet MEA standards

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

7500 Mortise Lock

575 Strike

9875-F/9975-F Fire exit mortise lock devices for all types of single doors up to 4' x 10' (1219mm x

3048mm) or 8' x 10' (2438mm x 3048mm) double doors installations, UL listed for fire exit hardware; See page 76 for detailed information on UL listed fire exit hardware label and door opening size information. Devices are ANSI A156.3 – 2008 Grade 1. Fits door stiles as narrow as 4 3/4"

(121mm). The 9875-F device has a smooth mechanism case and the 9975-F device has a grooved case. The mortise lock device is non-handed except when the following device options are used: -2

(double cylinder) or SS (signal switch) devices. See opposite page for available outside trim and functions.

The 7500 Mortise lock is equipped with 3/4" (19mm) anti-friction latch bolt which is field reversible without removing the lock from the door. It has a non-handed auxiliary bolt for deadlocking and a faceplate with an adjustable bevel.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 6

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 20

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 7

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 21

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 8

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 22

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 9

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 17

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 10

SURFACE CLOSERS

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 4

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 13

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 5

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 14

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 6

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 15

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 7

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 16

DOOR TRIM

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 2

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 17

AUXILIARY HARDWARE

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 18

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 20

OVERHEAD HOLDS AND STOPS

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 11

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 22

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 07/2019 Page 12

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 23

THRESHOLDS

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 10

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 25

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 9

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 26

G en er al

In fo rm at io n

800-824-3018 | www.assaaabloydooraccessories.us Check the web site for the up-to-date catalog

Copyright © 2015-2018, Pemko Manufacturing Co., an ASSA ABLOY Group company. All rights reserved.

Reproduction in whole or in part without the express written permission of Pemko Manufacturing Co. is prohibited.

Pe m ko D oo r &

F ra m e

Ac ce ss or ie s

About the Pemko Product Line Since 1952, the Pemko name has been known as a key manufacturer in weatherstripping products. Over the years, as an ASSA ABLOY Group brand, we have expanded our product line into a full line of architectural door trim products to include thresholds, fire/smoke gaskets, door bottoms, perimeter gasketing, brush seals, astragals, continuous geared and stainless steel hinges, fire and life-safety products, lites and louvers, and sliding door hardware.

The Pemko product line offers offers sound-tested, smoke-labeled, fire-labeled, skid resistant, and ADA-compliant products, and aggressively pursues new product development to create solutions for new applications and requirements.

Applications

• Energy Efficiency: These products make a complete energy efficient door solution – door bottoms, astragals, meeting stiles, brush gasketing, perimeter gasketing, and thermal barrier thresholds.

• Smoke and Fire Gasketing: Hot Smoke Seal™ is an intumescent fire life-safety product that meets UBC7-2 (proposed UL10C) positive pressure testing. Pemko S88 and S773 silicone seals are also smoke and fire rated gaskets that meet UBC7-2 positive pressure testing and are Category G gaskets for edge sealing systems for use with Category B doors.

• Pemko Acoustic Solutions: As a result of extensive acoustic testing, our gasketing systems are used on openings with STC Ratings from the low-30’s and into the mid-50’s. Acoustic seal sets have been assembled to better assist with determining an operable rating when a door's sealed-in-place rating is known. See pages 222 to 224 for more info.

• Electrically Modified Pemko Hinges: Continuous geared hinges are designed for commercial doors of all traffic levels and offer many benefits for your opening. All of our commercial-grade continuous geared hinges have the added option for electrical modification.

Some of these options allow for electrical modifications to be made without removing the door from the opening.

• ADA-compliant aluminum and rubber ramps provide wheelchair access in public access doorways.

• Sustainability: Products are certified to GREENGUARD GOLD standards for low chemical emissions into indoor air during product usage.

All products in the Pemko line undergo rigorous testing to ensure that they meet or exceed the industry standards. Look for the logos next to the product drawings and see pages 12-13 for more information.

Sales & Support Customer Service Representatives are available from 7am to 7pm Central time at 1-800-824-3018 or visit the website for the current catalogs, sell sheets, and the most up-to-date templates.

There are over 50 items on the Pemko Quick Ship Program that ship within 24 hours. For the most up-to-date list see the Quick Ship flyer posted on www.assaaabloydooraccessories.us, in the literature section.

Need a Sales Rep?

Pemko is largely represented by the ASSA ABLOY Door Security Solutions team (except N CA, N NV) Contact your local ASSA ABLOY Door Security Solution Representative via e-mail by going to www.assaabloydss.com and clicking on “Sales Support” or call 1-800-DSS-EZ4U (800-377-3948).

For representation information in Northern California or Northern Nevada, please visit www.assaaabloydooraccessories.us to locate and view the sales contact for your area or call Pemko Customer Service at 1-800-824-3018.

Website: www.assaaabloydooraccessories.us Facebook: www.facebook.com/ASSAABLOYARCHIT/ Twitter: @ASSAABLOYARCHIT ASSA ABLOY has manufacturing and warehouse locations for the Pemko line in Memphis TN and Ventura CA as well as warehouse locations in Toronto ON and Vancouver BC.

U.S. Green Building Council logo is a trademark owned by the U.S. Green Building Council and is used with permission.

ASSA ABLOY is a member of the USGBC and CaGBC

LEED Certification Contribution ASSA ABLOY can help to achieve prerequisites and accumulate points in several categories and credit areas for LEED. For further information, please call 1-800-824-3018 or refer to our website to view our prepared LEED statement.

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 27

ELECTRIC STRIKES

Updated 6/7/19 Patent pending and/or patent www.assaabloydss.com/patents

Copyright © 2019, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Hanchett Entry Systems, Inc. is prohibited.

US assaabloyesh.com | 800.626.7590 | customerservice.esh@assaabloy.com

El ec tr ic S tr ik es

El ec tr ic

S tr ik es

Specifications Certifications

• ANSI/BHMA A156.31, Grade 1

• UL 1034 burglary-resistant listed and suitable for outdoor use

• UL 294 listed

• RoHS compliant

• UL 10C fire rated, 3-hour single door

(fail secure only)

• CAN/ULC-S104 fire door conformant

• NFPA-252 fire door compliant

• ASTM-E152 fire door compliant

• California Fire Marshal listed

• NFPA 80-07 compliant

• WHI fire door listed

Frame Application

• Metal

• Wood

Electrical (DC Continuous Duty)

• Dual voltage 12/24 VDC

• 450 mA at 12 VDC/250 mA at 24 VDC

Dimensions

How to Order Series Finish Option (s)

9500 – 630 – LBM

9500 Surface-Mounted Electric Strike for

3/4" Pullman Rim Exit Devices, fire rated; no faceplates required

605 Bright Brass LBM Latchbolt Monitor

606 Satin Brass LBSM Latchbolt Strike Monitor

612 Satin Bronze

613 Bronze Toned

613E Dark Oxidized Satin Bronze Powder

629 Bright Stainless Steel

630 Satin Stainless Steel

HES 9500 Surface Mounted Electric Strike

NOTE: Electric strike compatibility is determined at time of electric strike product release. ASSA ABLOY is not responsible for incompatibility of products that have changed in design or craftsmanship by their respective manufacturers. When compatibility is a concern, contact Customer Support for application assistance.

3/4" [19mm]

9" [228.6mm]

1-3/4" [44.5mm]

Page 1 Page 29

SYMPTOM: ELECTRIC RELEASE IS NOT ACTUATING:

1. Verify proper voltage is present AT STRIKE. If voltage is present: the strike may have been affected during the installation, or dirt or debris may be preventing proper operation. Inspect electric release and clean. NOTE: DO NOT LUBRICATE SOLENOID

2. If voltage IS NOT present:

A) Verify Circuit breaker is on, B) Verify voltage at the transformer/power supply output. C) Verify that there are no additional, external switches or devices which may be interrupting your circuit. D) Check for damaged wiring or bad wire splices.

SYMPTOM: STRIKE IS WORKING BUT WILL NOT OPEN:

1. Check for other locks on door

2. Check for proper lock-latch engagement

3. Check for excessive back pressure on door release latch by following these steps:

A) Push the door from the outside to try and relieve the bolt to latch pressure and actuate the 4800F. B) While the 4800F is unlatched swing the door open. If the door opens, then the bolt maybe applying pressure to the latch. Adjust the position of the 4800F to relieve the pressure.

POSSIBLE REMEDIES:

1. Re-adjust (or install) a door closer, Remove door silencers, Re-center electric release in jamb, Remove or trim weather stripping around the door.

2. Installing this strike on an uneven surface can cause problems with the internal mechanism of this device. Specifically, it will cause localized mechanical pinching of the moving parts. Locate where the pinching is occurring and level the frame surface at that location. (FIG W)

TRINE 4800F

THE FIRE RATED SOLUTION

FOR RIM PANIC EXIT DEVICES

4800F ELECTRICAL CHARACTERISTICS:

4800F

ELECTRIC

STRIKE

INSTALLATION INSTRUCTIONS

Congratulations on the purchase of this quality TRINE security product. This product has been designed to install easily, perform reliably, and provide years of trouble free security.

BEFORE PROCEEDING with your installation, please review the following list of features. If you have any questions after reading this document please call TRINE's TECHNICAL SUPPORT

(718) 829-2332, or visit us online @ trineonline.com

Built-in Electronics: The 4800F automaticallys allows 12-24AC & DC power, plus surge and kickback protection.

There are no external ‘pacs’ to use or install.

The 4800F is WH recognized for:

Class A, 3 Hour Single door / frame configuration

- UL10C, Fire Tests of Door Assemblies

- UBC 7-2, Uniform building Code

- CAN4 S104, Standard Method for Fire Tests of Door Assemblies NFPA 252 Issue: 1999/01/01 Standard Methods of Fire Tests of Door Assemblies

NOTE: WH fire listing is void when using fail safe action.

BHMA Grade 1 Electric Strike

9"

1 3/4"

8 1/4"

1 1/2"

1/8" 3/4"

7/8"

Pull-in/Hold Amps (A) DutyVoltage Sound

12DC .566 A/.217 A Intm/Cont. Silent 24DC .253 A/.099 A Intm/Cont. Silent 12AC @ 50-60Hz .509 A/.181 A Intm/Cont. Silent 16AC @ 50-60Hz .405 A/.149 A Intm/Cont. Silent 24AC @ 50-60Hz .215 A/.087 A Intm/Cont. Silent

OPERATING TEMP RANGE: -20°C TO +40°C

DO NOT APPLY AN OVER VOLTAGE OF MORE THAN 10%

OVER THE RATED OPERATING VOLTAGE OF THE

STRIKE OR THE SOLENOID WILL BE DAMAGED.

1440 Ferris Place l Bronx l New York l 10461

Page 1 Page 30

TO 120V

AC LINE

USE 12V THRU 24V

AC OR DC

TRANSFORMER

WIRING FOR

FAIL-SECURE MODE

SWITCH

NORMALLY

OPEN

FAIL-SECURE

CONFIGURED

STRIKE

OPTIONAL BUZZER

NOTE: MATCH THE VOLTAGE

OF THE TRANSFORMER

AND IF REQUIRED,

OBSERVE POLARITY

USE 12V THRU 24V

AC OR DC

TRANSFORMER

TO 120V

AC LINE

WIRING FOR

FAIL-SAFE MODE

SWITCH

NORMALLY

CLOSED

FAIL-SAFE

CONFIGURED

STRIKE

USE 12V THRU 24V

AC OR DC

TRANSFORMER

TO 120V

AC LINE

WIRING FOR

FAIL-SAFE MODE

WITH OPTIONAL BUZZER

SWITCH

SINGLE POLE

DOUBLE THROW

FAIL-SAFE

CONFIGURED

STRIKE

OPTIONAL BUZZER

NOTE: MATCH THE VOLTAGE

OF THE TRANSFORMER

AND IF REQUIRED,

OBSERVE POLARITY

RECOMMENDED PREINSTALLATION CHECK FOR THE 4800F SURFACE

MOUNT STRIKE:

1. Determine that door is properly adjusted; Door must operate properly in order for system to provide best results.

2. Door must swing properly, without interfering with jamb or sill

3. The door should be equipped with a door closer and the door closer "latch mode" must hold door in a completely closed position in order to avoid the lock latch from applying pressure against the releasing latch portion of the electric strike.

4. Electrical wire connections must be completed and ready to be terminated inside the frame.

5. Confirm that the power line in the frame is the correct voltage, amperage, and that the switch works properly.

6. Confirm proper clearance exists between the end of the lock latch and jamb.

7. The electric door strike must be aligned properly with lock latch when it is installed on the doorjamb.

8. For best installation results, the door frame must be reasonably flat and straight. 2.

WHAT IS INCLUDED IN THE 4800F BOX:

INCLUDED IN THE BOX ARE:

1 - (1) 4800 OR 4801 SURFACE MOUNTED STRIKE

2 - (2) 1/4-20 x 1" UH CAP SOCKET MOUNTING SCREWS

3 - (4) ANCHOR SYSTEM PINS

4 - (1) QUICK CONNECT SOCKET AND WIRE ASSEMBLY

5 - (2) SEALED CRIMP CONNECTORS

6 - (1) FAIL SAFE SPRING (RED COLORED) & SOLENOID PLUNGER

7 - (1) FAIL SAFE CAM (NOTE: NOT FIRE RATED WHEN CONFIGURED FAIL-SAFE)

8 - (1) 1/8" THICK SPACER PLATE/ FRAME MOUNTING TEMPLATE

RECOMMENDED

TOOLS:

- 3/32 inch Allen Wrench

- 3/16 inch Allen Wrench

- 3/4 inch diameter Drill Bit

- #7 (0.201 inch diameter) Drill Bit

- #30 (0.128 inch diameter) Drill Bit (for the optional Anchor Pins)

- 1/4-20 Tap

- Drill

- Marker

Page 1 Page 31

Figure 3

Figure 6

Figure 1 With the door closed, mark the position of the bolt on the frame.

Figure 2 Position the 4800F on the frame and mark the desire position.

Figure 4 Use the spacer as template to mark the holes you desire to use.

Push the anchor pins in the back of any 4800F series strike if you desire to use this

Figure 5 Crimp the quick connect socket assembly to the power wires.

Crimp Connectors

Quick Connect Socket Assembly

Power Wire

1. Mark the end position of the exit devices latchbolt on the doorframe.

(Take off the original strike if present). See Figure 1.

2. Using the marks you just made as your guide, position the 4800F over the mark on the frame. Make sure that the Auxiliary latch rides up properly over the 4800's edge, and is engaged, and that the door is in the fully closed position. See Figure 2

3. When you are confident with the position of the 4800F, mark two perpendicular edges of the 4800F on the frame See Figure 3

4. Put the 4800F aside for a moment and place the spacer supplied with the 4800F inside the marks you just made on the frame.

5. Using the spacer as a template; mark the two mounting holes and the wire exit hole. If you are using the optional anchor pins, mark the anchor pin positions using the spacer as a template. See Figure 4

6. Using a #7 bit, drill the two mounting holes and tap them ¼-20.

7. Using a ¾ inch diameter bit, drill the power wire exit hole

8. If you are utilizing the anchor pin system, use a #30 bit, drill the four anchor pin holes.

9. Deburr any sharp edges around the holes after drilling, so that the 4800F will rest on a smooth clean surface and the wires will not be accidentally cut or damaged while installing.

10. Pull the power wiring down the door frame and through the ¾ inch diameter power wire hole.

11. Using the provided sealed crimp connectors, terminate the quick connect socket assembly to the power wires. See Figure 5 (NOTE:

The 4800F is not polarized)

12. If you intend to use the anchor pins system, insert them into the four holes on the back side of the 4800F. See Figure 6. If you also intend to use the 1/8" thick spacer plate, you can now slip the plate over the pins.

13. Snap together the power supply side connector coming off the frame to the 4800 connector. Carefully push the wires and connectors back into the frame.

14. Using the 2 mounting screws, mount the 4800F strike to the frame.

15. Adjust the strike to the desired position and tighten the mounting screws using the 3/16 inch Allen wrench.

16. Using the 3/32 inch Allen wrench turn the two setscrews on the side of the 4800F until they support the strike. DO NOT over tighten the setscrews.

17. Turn the power ON and test your installation. Installation is now complete.

INSTALLATION PROCEDURE:

CAUTION: TO AVOID ELECTRICAL SHOCK AND INJURIES,

BEFORE DOING YOUR WIRING, TURN OFF THE POWER FROM

THE CIRCUIT BREAKER.

CHECK OUT THE VIDEO ON

SEARCH

“4850ITL”

USE THE 4850ITL TO QUICKLY

MARK, TEST, ADJUST, CENTER

PUNCH AND SKIP MOST OF

THESE STEPS! more info @ trineonline.com/4850itl.php

3.

Page 1 Page 32

Fail Safe (Fire Rating is void when 4800F is fail-safe)

You should NOT see the "X" on top of the actuator cam.

Use the plunger and RED colored solenoid spring assembly.

Fail Secure

You should have the "X" mark on top of the actuator cam.

Use the plunger and BLUE colored solenoid spring assembly.

DO NOT OPEN

THIS SIDE.

TROUBLESHOOTING THE COMPLETED INSTALLATION:

Seat wires properly in the housing channel so the cover will seat flat.

INSTRUCTIONS FOR CHANGING THE THE 4800F FROM FAIL SECURE

TO FAIL SAFE:

To change the Fail Secure 4800F into a Fail Safe , open the mechanism side of the strike (as shown on the right) by removing the mechanism cover screws (3 places) and the cover. Lift the solenoid and gently pull off the solenoid plunger and BLUE spring assembly and replace it with the solenoid plunger and RED colored spring assembly. Pull off the actuator cam, and replace it with the fail-safe cam.

Before closing the unit, make sure that the wires are properly seated on the wire channel (see figure on right). Save the plunger and BLUE colored spring assembly for future use.

For changing from Fail Safe to Fail Secure, just reverse the above procedure

SYMPTOM: ELECTRIC RELEASE IS NOT ACTUATING:

1. Verify proper voltage is present AT STRIKE. If voltage is present: the strike may have been affected during the installation, or dirt or debris may be preventing proper operation. Inspect electric release and clean. NOTE: DO NOT LUBRICATE SOLENOID

2. If voltage IS NOT present:

A) Verify Circuit breaker is on, B) Verify voltage at the transformer/power supply output. C) Verify that there are no additional, external switches or devices which may be interrupting your circuit. D) Check for damaged wiring or bad wire splices.

SYMPTOM: STRIKE IS WORKING BUT WILL NOT OPEN:

1. Check for other locks on door

2. Check for proper lock-latch engagement

3. Check for excessive back pressure on door release latch by following these steps:

A) Push the door from the outside to try and relieve the bolt to latch pressure and actuate the 4800F. B) While the 4800F is unlatched swing the door open. If the door opens, then the bolt maybe applying pressure to the latch. Adjust the position of the 4800F to relieve the pressure.

POSSIBLE REMEDIES:

1. Re-adjust (or install) a door closer, Remove door silencers, Re-center electric release in jamb, Remove or trim weather stripping around the door.

2. Installing this strike on an uneven surface can cause problems with the internal mechanism of this device. Specifically, it will cause localized mechanical pinching of the moving parts. Locate where the pinching is occurring and level the frame surface at that location. (FIG W)

4.

PHONE: (718) 829-2332

FAX: (718) 829-6405

1440 FERRIS PLACE

BRONX, NY 10461

email: customerservice@trineonline.com website: www.trineonline.comV. 15.0415

Uneven Frame Soffit

Ideal Frame Soffit Flatness

(FIG W)

Page 1 Page 33

MAGNETIC DOOR CONTACTS

E6 LCN Door Control Catalog phone: 877-671-7011 fax: 800-248-1460 www.allegion.com/us 009426 rev. 07/17

SEM7800

Series

Features and mounting details

Magnets

Mounting

Total Projection

Mounting

Total Projection

Note:

Outlet box not included.

Mounting

Total Projection

Note:

Outlet box not included.

1-7/8" 48 mm

1-5/8" 41 mm

1-11/16" 43 mm

2-3/8" 60 mm

2-1/2" 64 mm

2-13/16" 70 mm

4-5/8" 117 mm

1-7/8" 48 mm

1-5/8" 41 mm

1-11/16" 43 mm

2-3/8" 60 mm

1" 25 mm

2-13/16" 70 mm

4-5/8" 117 mm

1-7/8" 48 mm

2-3/8" 60 mm

1-11/16" 43 mm

2-5/8" 67 mm

1" 25 mm 2-13/16"

70 mm

4-5/8" 117 mm

4-9/16" 116 mm

1-7/8" 48 mm

1-5/8" 41 mm

1-11/16" 43 mm

2-3/8" 60 mm

3-7/16" 87 mm

2-1/8" 54 mm

5-1/8" 130 mm

Mounting

Total Projection

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 40

POWER TRANSFER DEVICES

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 19

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 42Page 42

Overview

Used when installing electric exit devices or electrified locks, armored door cords provide a simple and economical solution for transferring power from frame to door. Schlage flexible door cords are offered in two lengths each with options for less wires or including four, 20 gauge conductor wires (red, green, white and black).

Features and benefits

ANSI/UL 10C, CAN/ULC-S104-15

788/798 Series Armored door cords

E C S I Door Hardware Product Data NMAH – Fire Stair Door Replacement 11/2019 Page 1 Page 43Page 43

ELECTRONIC SECURITY CUT SHEETS

CARD READER

A Ty c o I n t e r n a t i o n a l C o m p a n y www.swhouse.com

Features That Make a Difference:

•Triple-receiverdesignallowssimultaneous
readingofHID®proximitycards,Indala®
proximitycards,andcontactlesssmart

cards

•Readsmorethan10differenttypesand
formatsofproximitycardsandcontactless
smartcards,includingmostcommon
Indalaformats
•Downloadnewfunctionalityor
enhancementsforafuture-proofsolution
•Encryptionandcustomkeysforsecure
transmissionofdata

• Mount on metal with optional isolation spacer

• Indoor/outdoor use

• Built-in tamper switch provides secure installation

• Plug-in screw terminals reduce installation time

• ISO compliant - 14443A, 14443B, 15693

• Lifetime warranty

Multi-Technology Reader with Indala Support (SWH-4130)

SoftwareHouseMulti-TechnologyReader
withIndalaSupportoffersaunique,
versatilesinglereadersolutionforreading
bothHIDandIndalaproximitycards
simultaneously,whilealsoreadingmultiple
13.56MHzsmartcardtechnologies–
includingMIFARE®encryptedsectors–all
withonereader.Thispowerfulreader
enablesyoutomixcardpopulationsof
HIDandIndalaproximitycardswithout
needingtwoseparatereaders,while
alsoallowingasmooth,cost-effective
transitiontosmartcardsovertime.
Thereadercontinuouslycyclesbetween
lowandhighfrequencysignalstoread
thepresentedcard.Readersmaybe
field-configuredtoenableordisable
selectedcardformatsandtechnologies.
TheMulti-TechnologyReaderwith
IndalaSupportcanbeupdatedatany
timewithflashfirmware.Thissaves
significanttimeandmoneybyallowing
youtosimplyflashnewcardprotocols
orformatsdirectlytothereader.The
readerisconfigurabletoreadaspecific
encryptedMIFAREsectorandblockusing
standardorcustomMIFAREreadkeys.
Importantfeaturessuchasabuilt-in
tamperswitch,two-piececonnectors,and
isolationspacershelpreduceinstallation
time.Coupledwithrobustenvironmental
ratingsandalifetimewarranty,theSoftware
HouseMulti-TechnologyReaderwithIndala
Supportistheclearchoiceforcompanies
lookingforapowerful,cost-effective
waytousemultiplecardtechnologies.

http://www.swhouse.com http://www.dsc.com http://www.swhouse.com

A Ty c o I n t e r n a t i o n a l C o m p a n y www.swhouse.com

Thetrademarks,logos,andservicemarksdisplayedonthisdocumentareregisteredintheUnitedStates[orothercountries].AnymisuseofthetrademarksisstrictlyprohibitedandTycoInternationalLtd.willaggressively
enforceitsintellectualpropertyrightstothefullestextentofthelaw,includingpursuitofcriminalprosecutionwherevernecessary.AlltrademarksnotownedbyTycoInternationalLtd.arethepropertyoftheirrespectiveowners,
andareusedwithpermissionorallowedunderapplicablelaws.
Productofferingsandspecificationsaresubjecttochangewithoutnotice.Actualproductsmayvaryfromphotos.Notallproductsincludeallfeatures.Availabilityvariesbyregion;contactyoursalesrepresentative.
©2011TycoInternationalLtd.anditsrespectivecompanies.Allrightsreserved.SH0152-DS-201108-R03-LT-EN

Related Products Approvals

Multi-Technology Reader with Indala Support

Physical

Dimensions(HxWxD). . . . . 111x84x28mm
(4.37x3.31x1.10in)
FormFactor. . . . . . . . . . . . . . Single-gangmounting
Environmental(Interior/Exterior)-35°to67°C(-31°to151°F)
0to100%relativehumidity
IndexofProtection. . . . . . . . IP65
Weight. . . . . . . . . . . . . . . . . . 0.34Kg(12oz.)

Color . . . . . . . . . . . . . . . . . . . Black Accessories. . . . . . . . . . . . . . Optional isolation spacer

Electrical

PowerRequirements . . . . . . . 9.6to16VDC,150mAmaximumcurrent
WiringTerminations . . . . . . . . Plug-inscrewterminals
WiringDetails
Pin1 . . . . . . . . . . . . . . . . . . Externalbeepercontrol
Pin2 . . . . . . . . . . . . . . . . . . Ground
Pin3 . . . . . . . . . . . . . . . . . . Power(8to16VDC)
Pin4 . . . . . . . . . . . . . . . . . . D1Wiegand
Pin5 . . . . . . . . . . . . . . . . . . D0Wiegand
Pin6 . . . . . . . . . . . . . . . . . . Reservedforfutureuse
Pin7 . . . . . . . . . . . . . . . . . . ExternalgreenLEDcontrol
Pin8 . . . . . . . . . . . . . . . . . . ExternalredLEDcontrol
Pin9 . . . . . . . . . . . . . . . . . . RS485/A–usedforflashupgrade
Pin10 . . . . . . . . . . . . . . . . . RS485/B–usedforflashupgrade
Pin11 . . . . . . . . . . . . . . . . . Tamper(normallyclosed)
Pin12 . . . . . . . . . . . . . . . . . Tamper(normallyclosed)
CableRecommendations. . . 22AWG[60m(200ft)max]or18
AWG[150m(500ft)max],stranded
Operational
ReadRange. . . . . . . . . . . . . Upto102mm(4in),dependingontechnology
ofcard
ReadTime. . . . . . . . . . . . . . . Technology-dependent
(typically<300msec)

Regulatory FCC Part 15 Class C

CE

RoHS

WEEE

ISO 14443A, 14443B, 15693

Card Technology and Format Information

Card Technologies Supported

HIDproximity
Indalaproximity
MIFAREserialnumber
DESFire®serialnumber
ISO14443A,14443B,and15693serialnumber
iCLASS®serialnumber
MIFAREsectorread

Communications

Wieganddatastreamtocontroller
FlashablevialocalRS-485

Proximity Configuration Using Program Card

Enable/disablespecificproximitytechnology
Indalaformatssupported:
Wiegand26-bit
ACC37-bit(default)
SWH37-bit
(Note:onlyoneIndalaformatissupportedatanyonetime)
HIDformatssupported:
Wiegand26-bit
Corporate100035-bit
SWH37-bit
Pass-throughHIDformats

Smart Card Configuration Using Program Card

Pass-throughoutput(128bits,entireMIFAREblock)
Fixedlengthoutput(26-bit,32-bit,35-bit,37-bit,64-bit)
MIFAREsector
Selectasector(0-15);selectablock(0-3)
Customizeencryptionkeys
Specifydataformat(numberofbitsoutput)

Ordering Information

Model Numbers Description

SWH-4130 Multi-Technology Reader with Indala Support, single-gang, black, ACC 37-bit format

SWH-4130-G Multi-Technology Reader with Indala Support, single-gang, gray, ACC 37-bit format

SWH-4130-26B Multi-Technology Reader with Indala Support, single-gang, black, 26-bit format

SWH-4130-G-26B Multi-Technology Reader with Indala Support, single-gang, gray, 26-bit format

SWH-4130-37B Multi-Technology Reader with Indala Support, single-gang, black, SWH 37-bit format

SWH-4130-G-37B Multi-Technology Reader with Indala Support, single-gang, gray, SWH 37-bit format

RM Readers iSTAR ProiSTAR Edge

DOOR CONTROLLER

D A T A s h e e T

RM-DCM-2

Door Control Module with Enclosure Features That Make a Difference:

Full-featured local door control module lowers wiring costs

Complete set of inputs and outputs to control one door

Flexible control options for reader LEDs and beep patterns

Easily expandable

Additional internal etch connections support magnetic lock features and accommodate local bypass switch

Optional LCD provides clear instructions that help simplify startup and diagnostics

Status LEDs on inputs and outputs for quick troubleshooting

Built-in tamper switch provides secure installation

Plug-in screw terminals reduce installation time

Put a full-featured RM-4E door control module in a UL listed, tamper-protected enclosure and you have the powerful Software House® RM-DCM-2. RM-DCM-2 is designed to support up to two RM-4Es and a choice of up to two I8 input boards or R8 output boards, providing a single enclosure for doors with IN and OUT readers.

RM-DCM-2 supports both Wiegand and magnetic stripe readers and provides additional wiring to magnetic locks if required.

The RM-4E modules create the connectivity between a reader and a control panel when third party card readers are used on a C•CURE® system. In addition, the RM-4E modules provide two supervised inputs and two SPDT relays (no ARM-1s are necessary). The LEDs and optional LCD display provide diagnostics to simplify the installation.

RM-DCM-2 provides standby power with its built-in uninterruptible power supply (UPS).

With its robust feature set, RM-DCM-2 is designed to handle the most demanding access control applications with ease while offering numerous installation and service features that lower its life cycle cost.

Shown with optional I8 input module, R8 output module, and battery http://www.tyco.com s p e C i F i C A T i o n s

Physical Enclosure Dimensions (H x W x D) . . 356 x 305 x 89 mm

(14 x 12 x 3.5 in) RM-4E Board-Only Dimensions (H x W) . . . . . . . . . . . . . 136 x 181 mm

(5.375 x 7.125 in) Weight (with 4Ah battery) . . . . . . . . .5.9 kg (11 lbs) Weight (without battery) . . . . . . . . . .4.5 kg (8 lbs) Construction . . . . . . . . . . . . . . . . . . . 20 AWG metal wall mounted locking cabinet with tamper switch on door Environmental Operating and Storage Temperature . . . . . . . . . . . . . . . . . . . 0 ° to 50°C (32° to 122°F)

5 to 95% RH, non-condensing

Electrical Power Requirements without Reader or Relays . . . . . . . . . +12 VDC +/- 5% or +24 VDC +/-10%, 280 mA max Power Requirements, Maximum, with Reader and Relays . . . . . . . . . . +12 VDC +/- 5% or +24 VDC +/-10%, 550 mA max Output Relay Power Ratings . . . . . . .Up to 30 VAC/DC, 5A maximum Reader LED Output Controls . . . . . .4.0 volts to 5.25 volts, 20mA max Power Available for Reader . . . . . . . . 5 VDC +/- 10% or 12 VDC +/- 10%, 125mA max (at 5V or 12V) Optional Battery . . . . . . . . . . . . . . . . 12V/4Ah battery provides nominal 4 hours backup time Regulatory

UL 294

CE, including EN50081-1, EN50130-4, EN50133 FCC Part 15 Class A RoHS

Communications Communications Bus . . . . . . . . . . . . RM bus from iSTAR controller or apC/8X panel Communications Type . . . . . . . . . . .RS-485 half duplex, two-wire Maximum Distance . . . . . . . . . . . . . .1,219 m (4,000 ft)

Reader, Inputs & Outputs Reader Ports . . . . . . . . . . . . . . . . . .One Reader Support . . . . . . . . . . . . . . . .Wiegand or magnetic stripe Reader Control Lines Available . . . . .Red LED, green LED, yellow LED, beeper Keypad Support . . . . . . . . . . . . . . . . Terminals provided for external 3x4 matrix keypad Supervised Inputs . . . . . . . . . . . . . . .Two, double-resistor Output Relays . . . . . . . . . . . . . . . . . .Two, Form C, dry contact Tamper Input . . . . . . . . . . . . . . . . . .One

Indicators and Switches

Three status LEDs for each supervised input LED on each relay output LEDs for RS-485 transmit and receive LED for power-on Optional LCD for diagnostics Eight position dipswitch for feature selection:

• Wiegand/magnetic stripe reader type

• Tamper bypass

• LED pattern

• RM bus termination

• Input LED disable

Mounting Specifications

Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Availability varies by region;

contact your sales representative. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.

©2008 Tyco International Ltd. and its respective companies. All rights reserved. SH0118-DS-200810-R02-A4-EN www.swhouse.com

30.48 cm (12.00 in)

26.67 cm (10.50 in)

3.81 cm (1.50 in)

3.175 cm (1.25 in)

33.02 cm (13.00 in)

35.56 cm (14.00 in)

SELF-CLOSING GATE HINGES

⅜⅜

SureClose® READYFIT 108 - D&D Technologies US https://us.ddtech.com/products/sureclose-readyfit-hinge-closer?variant=...

1 of 2 12/5/2020, 10:02 AM

[1 m m

8"

[4 m m

8"

[1 1mm] 8"

[28mm] 1 1 8"

[7 .5 m m

3"

[7 m m

4"

[9 .5 m m

3 8"

[60mm]

238"

[36mm]

1 38"

[38mm] 1 1 2"

[46mm]

1 34"

[60mm] 238"

[9 .5 m m

3 8"

[6.5mm] 4"

[7 .5 m m

3"

[8 m m

8"

[19mm] 4" [15mm]

8"

[4 m m

8"

Section I - Door Hardware Cut Sheets
a - Hinges
1
b - Cylinders
3
c - Exit devices
5
6
7
8
9
10
11
e - Surface closers
13
14
15
16
f - Door trim
18
g - Auxiliary Hardware
20
h - Overhead holds and stops
22
23
i - Thresholds
25
26
27
j - Electric Strikes
29
30
31
32
33
34
35
36
37
k - Magnetic Door Contacts
40
l - Power Transfer Devices
42
43
Section II - Electronic Security Cutsheets
a - Card Readers
b - Door Controllers

File details come from the government source that posted it. Updated .