16-26-S NVARNG Add Shore Power Infra for ALSMWO at LVRC-100 CD - ds.pdf
PDF 2 MB Posted
- Solicitation number
- 43ADG-S3970
- Issued by
- Clark County, Fish Springs CDP, Nevada
About this file
This is a 100% Construction Documents (CD) electrical design package for the Nevada Army National Guard (NVARNG) to add shore power infrastructure for Armored Labor Support/Maintenance and Welfare Operations (ALS/MWO) at the Las Vegas Readiness Center (LVRC) in Las Vegas, Nevada. The project involves installation of a dedicated shore power assembly system on the north exterior side of the facility, including one 100-amp, 208-volt single-phase disconnect mounted on a uni-strut assembly, one W3P1 cable assembly (owner-furnished, contractor-installed), one weatherproof duplex receptacle for maintenance, new electrical feeders, surface-mounted conduit routing along the existing wall with underground routing through landscaping areas, and a new NEMA 4 enclosure for cable storage and protection. The design package was prepared by ATL (Atlas Electrical) with a review date of May 27, 2026, and includes a 100% design development (DD) phase dated April 7, 2026. The project must comply with the 2024 International Building Code (IBC) and 2023 National Electric Code (NEC), along with Nevada State Public Works Division electrical standards covering equipment ratings, conduit and raceway specifications, conductor materials, lighting controls, grounding requirements, and seismic bracing for all electrical equipment.
The scope of work requires the contractor to meticulously review all construction documents to identify trade-specific scope items, coordinate with the structural engineer for any conduit routing through slabs, provide all required phase, neutral, and ground conductors, furnish bollard vehicular protection, install grounding rods per NEC 250.53, and ensure the entire installation meets all applicable national and local electrical codes with all equipment bearing UL labels. New feeders consist of 1.5-inch rigid galvanized conduit (RGC) with 40 PVC underground protection, containing two 2-AWG conductors and one 8-AWG ground conductor, with a pigtail connector assembly supplied by the owner. The project includes requirements for arc flash warning labels on all electrical equipment, equipment grounding conductor sizing in accordance with NEC standards, fire-rated penetration sealing using 3M fire barrier products, and a concrete housekeeping pad extending 3 feet in front of the equipment assembly. Failure to conduct a thorough review of scope-related discrepancies will leave the contractor responsible for any resulting cost overruns, delays, or project complications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Proposal Evaluation and Scoring - LVRC Shore Power.pdf | ||
| Quote Instructions.pdf | ||
| Invitation to Bid - LVRC Shore Power.pdf | ||
| SOW LVRC Shore Power.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet Number
P R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L C
O V
E R
P A
G E
G0.0
NVARNG - ADD SHORE POWER INFRA FOR ALSMWO AT
LVRC
LAS VEGAS READINESS CENTER FOR THE NEVADA
NATIONAL GUARD
LAS VEGAS, NEVADA
PROJECT NUMBER: 16-26-S
STATE OF NEVADA
PUBLIC WORKS DIVISION
CONSULTANT:
REVIEW PACKAGE:
100% CD SET
DATE:
MAY 27, 2026
ELECTRICAL:
· 2024 INTERNATIONAL BUILDING CODE (IBC)
· 2023 NATIONAL ELECTRIC CODE (NEC)
APPLICABLE CODES
07/08/2026
06.30.2027
R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L C
O V
E R
S H
E E
T
E0.0
DRAWING INDEX
DATE DELTA REVISION DESCRIPTION
05/27/2026 100% CD
04/07/2026 100% DD
SHEET NUMBER SHEET DESCRIPTION
● ● G0.0 ELECTRICAL COVER PAGE
● ● E0.0 ELECTRICAL COVER SHEET
● ● E0.5 ELECTRICAL SITE PLAN
● ● E1.1 ELECTRICAL ENLARGED POWER PLAN
● ● E5.0 ELECTRICAL SINGLE LINE DIAGRAM
● ● E8.0 ELECTRICAL DIAGRAMS
NOTICE TO CONTRACTOR(S)
AS OUTLINED IN THE SUBJECT CONSTRUCTION DOCUMENTS, IT IS THE ABSOLUTE RESPONSIBILITY OF
EACH GENERAL CONTRACTOR / SUB-CONTRACTOR TO METICULOUSLY EXAMINE THE DOCUMENTS
TO IDENTIFY AND COMPREHEND ALL SCOPE-RELATED ITEMS PERTAINING TO YOUR SPECIFIC TRADE.
WILLFULLY OR SELECTIVELY NEGLECTING THIS ESSENTIAL REVIEW PROCESS MAY LEAD TO SIGNIFICANT CONSEQUENCES. IN THE EVENT THAT SCOPE ITEMS RELEVANT TO YOUR TRADE ARE OVERLOOKED, MISUNDERSTOOD, OR MISINTERPRETED DUE TO AN INSUFFICIENT REVIEW, IT IS CRUCIAL TO
UNDERSTAND THAT PROCEEDING WITHOUT ADDRESSING THESE ISSUES WILL INHERENTLY POSE RISKS TO THE PROJECT'S TIMELINE, BUDGET, AND OVERALL SUCCESS. FAILURE TO CONDUCT A THOROUGH
REVIEW OF THE CONSTRUCTION DOCUMENTS, AS IT PERTAINS TO YOUR DESIGNATED SCOPE OF
WORK, WILL LEAVE YOUR ORGANIZATION AND THE PROJECT AS A WHOLE IN A VULNERABLE
POSITION, TERMED "AT RISK." THIS DESIGNATION SIGNIFIES THAT ANY POTENTIAL COST OVERRUNS, DELAYS, OR COMPLICATIONS RESULTING FROM UNADDRESSED SCOPE-RELATED DISCREPANCIES
WILL BE THE SOLE RESPONSIBILITY OF THE PARTY FAILING TO PERFORM THE NECESSARY REVIEW.
LEGEND
X
X.X
X X.X
X
X
ST
GFI
DM
K
V
A
M
G
S
TV
TC
OS
PC
SHUNT TRIP
GROUND FAULT INTERRUPTER
DIGITAL METER
PULLBOX
PTZ
PAN-TILT-ZOOM CAMERA WITH 3/4"C, UNO
WALL MOUNTED PAY TELEPHONE OUTLET @+48" AFF, UNOP
LOWER CASE LETTER DENOTES CONTROL DESIGNATION
SWITCH WITH PILOT LIGHT
KEY OPERATED SWITCH
(SWITCHES FLUSH MOUNTED @+48" AFF, UNO)
'NL' DENOTES UNSWITCHED NIGHT LIGHT
MECHANICAL EQUIPMENT CALLOUT
DIAGRAM CALLOUT
REVISION SYMBOL
KEY NOTE
ANNOTATIONS
DRAWOUT TYPE CIRCUIT BREAKER
SINGLE LINE DIAGRAM SYMBOLS
TIMECLOCK
JUNCTION BOX
RELAY
ENCLOSED CIRCUIT BREAKER
FUSED DISCONNECT SWITCH (3-POLE, UNO)
NON-FUSED DISCONNECT SWITCH (3-POLE, UNO)
(FLUSH MOUNTED @+18" AFF, UNO)
POWER DISTRIBUTION SYSTEM SYMBOLS
GROUND CONNECTION
CONDUIT WITH SEAL-OFF
CONDUIT STUBBED AND CAPPED
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CONDUIT HOMERUN
RACEWAY SYMBOLS
POWER POLE
SPEAKER - CEILING MOUNTED, UNO
W WALL MOUNTED TELEPHONE OUTLET @+48" AFF, UNO
FLOOR MOUNTED TELEPHONE/DATA OUTLET
COMMUNICATION SYMBOLSMULTI-OUTLET ASSEMBLY
DUPLEX RECEPTACLE - SWITCHED
GFCI DUPLEX RECEPTACLE
SINGLE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - FLOOR MOUNTED
LIGHTING CONTROL STATION
MANUAL MOTOR STARTER WITH THERMAL OVERLOADS
DIMMER SWITCH
4-WAY SWITCH
3-WAY SWITCH
CONTROL DEVICE SYMBOLS
NUMBER OF HEADS AS SHOWN
WALL MOUNTED LUMINAIRE
EMERGENCY LUMINAIRE FIXTURE (SIZE AS INDICATED)
NUMBER DENOTES CIRCUIT NUMBER
LOWER CASE LETTER DENOTES CONTROL DESIGNATION
UPPER CASE LETTER DENOTES FIXTURE TYPE
RECEPTACLE SYMBOLS
LUMINAIRE SYMBOLS
LED SURFACE STRIP LUMINAIRE (LENGTH AS INDICATED)
TRACK LIGHTING LUMINAIRE WITH LENGTH AND
FLOOD TYPE LUMINAIRE
1/2" CONCEALED CONDUIT WITH (3) #12 WIRES, UNO
MOTOR
TRANSFORMER
ENCLOSED MOTOR CONTROLLER/STARTER
PANELBOARD - FLUSH/RECESSED MOUNTED
PANELBOARD - SURFACE MOUNTED
SINGLE POLE SWITCH
DUPLEX RECEPTACLE
AND FUSED DISCONNECT SWITCH
COMBINATION ENCLOSED MOTOR CONTROLLER/STARTER
COMBINATION TELEPHONE/DATA OUTLET WITH 3/4"C, UNO
FLUSH WALL MOUNTED @+18" AFF
DATA OUTLET WITH 3/4"C, UNO - FLUSH WALL
TELEPHONE OUTLET WITH 3/4"C, UNO
(VERIFY MOUNTING)
EXIT SIGN - SHADED AREAS INDICATE ILLUMINATED
FACES - PROVIDE DIRECTIONAL ARROWS AS INDICATED
CEILING OR GRADE MOUNTED LUMINAIRE (AS SCHEDULED)
LED LUMINAIRE (SIZE AS INDICATED)
MOUNTED @+18" AFF
FLUSH WALL MOUNTED @+18" AFF
TELEPHONE TERMINAL CABINET
TELEPHONE TERMINAL BOARD - 4' X 8' X 3/4"
ISOLATED GROUND DUPLEX RECEPTACLE (ORANGE, UNO)
SPECIAL PURPOSE RECEPTACLE (NEMA TYPE AS NOTED)
CONDUIT UNDERGROUND OR BELOW GRADE
CONTACTOR
SWITCHBOARD OR DISTRIBUTION BOARD
PHOTOCELL
OCCUPANCY SENSOR
TELEVISION OUTLET - MOUNTED @+18" AFF, UNO
FIXED CAMERA WITH 3/4"C, UNO
AUTOMATIC TRANSFER SWITCH
AMMETER
VOLTMETER
ENGINE GENERATOR
METERING - PER LOCAL UTILITY REQUIREMENTS
CIRCUIT BREAKER
FEEDER SCHEDULE CALLOUT
KIRK KEY
FIRE RATED PLYWOOD, UNO
FUSIBLE SWITCH
COMMON RECEPTACLE SUBSCRIPT DESIGNATIONS:
SWITCH WITH OCCUPANCY SENSOR
ALL DATA/TELEPHONE DROPS TO BE ROUTED BACK TO NEAREST
IT ROOM OR AS REQUIRED BY OWNER, UNO.
HANGING POWER CORD
KEYPAD - MOUNTED @+48" AFF, UNOKP
LED TAPELIGHT LUMINAIRE (LENGTH AS INDICATED)
DS DAYLIGHT SENSOR
DIMMER SWITCH W/OCCUPANCY SENSOR
FIRE SMOKE DAMPER
VENDOR FURNISHED VFD
J PP
DUPLEX RECEPTACLE - MILLWORK MOUNTED POP-UP
GFCI DOUBLE DUPLEX RECEPTACLEGFCI
COMMON FLOOR BOX FOR POWER/DATA
SWITCH WITH VACANCY SENSOR
SDS SWITCH WITH DAYLIGHT SENSOR
SOS
SVS
SP
S M
SK
SDOS
SD
S 4
S 3
S
KEY FOB/CARD READER - MOUNTED @+48" AFF, UNOCR
C - MOUNTED ABOVE COUNTER
CLG - CEILING MOUNT
USB - DUPLEX WITH DUAL CHARGING USB PORTS
TV - DUPLEX TO BE MOUNTED AS PART OF TV BACKING
WP - WEATHERPROOF IN-USE
+60" - MOUNTED AT 60" AFF
POWER PEDESTAL
CAR CHARGER STATION
T
VFD
F
C
CB
R
J
PB
FSD
PP
CCS
ABBREVIATIONS
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
A, AMP AMPERE J-BOX JUNCTION BOX
ACT ACOUSTICAL TILE KCMIL THOUSAND CIRCULAR MILS
AFF ABOVE FINISHED FLOOR KV KILOVOLT
AFG ABOVE FINISHED GRADE KVA KILOVOLT AMPERE
AHJ AUTHORITY HAVING JURISDICTION KVAR KILOVOLT AMPERE REACTIVE
AHU AIR HANDLING UNIT KW KILOWATT
AIC AMPERE INTERRUPTING CAPACITY KWH KILOWATT HOUR
AL ALUMINUM MCB MAIN CIRCUIT BREAKER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MEZZ MEZZANINE
APPROX APPROXIMATE MFG MANUFACTURER
ARCH ACHITECTURAL MLO MAIN LUGS ONLY
ATS AUTOMATIC TRANSFER SWITCH NEC NATIONAL ELECTRIC CODE
AWG AMERICAN WIRE GAUGE NECA NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
BD BOARD NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
BLDG BUILDING NFC NATIONAL FIRE CODE
C CONDUIT NC NORMALLY CLOSED
CB CIRCUIT BREAKER NFPA NATIONAL FIRE PROTECTION ASSOCIATION
CCTV CLOSED CIRCUIT TELEVISION NIC NOT IN CONTRACT
CKT CIRCUIT NO NORMALLY OPEN
CLG CEILING NRTL NATIONAL RECOGNIZED TESTING LABORATORY
CO CONDUIT ONLY NVE NV ENERGY POWER COMPANY
CRI COLOR RENDERING INDEX NTS NOT TO SCALE
CT CURRENT TRASFORMER OFCI OWNER FURNISHED CONTRACTOR INSTALLED
CU COPPER OFOI OWNER FURNISHED OWNER INSTALLED
CW COLD WATER OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
(D) DEMO PF POWER FACTOR
DEG DEGREE Ø, PH PHASE
DEMO DEMOLITION/DEMOLISH PNL PANEL
DISC DISCONNECT PVC POLY VINYL CHLORIDE
DWG DRAWING QTY QUANTITY
(E) EXISTING (R) RELOCATE
EC ELECTRICAL CONTRACTOR RGS RIGID GALVANIZED STEEL CONDUIT
EGC EQUIPMENT GROUNDING CONDUCTOR SPEC(S) SPECIFICATION(S)
EIFS EXTERIOR INSTALLATION AND FINISH SYSTEM SPD SURGE PROTECTION DEVICE
ELEV ELEVATOR SW SWITCH
EM, EMER EMERGENCY TEL TELEPHONE
EMT ELECTRICAL METALLIC TUBING T-STAT THERMOSTAT
EQUIP EQUIPMENT TTB TELEPHONE TERMINAL BOARD
EWC ELECTRIC WATER COOLER TYP TYPICAL
FBO FURNISHED BY OTHERS UL UNDERWRITER'S LABORATORY
GC GENERAL CONTRACTOR UNO UNLESS NOTED OTHERWISE
GFCI GROUND FAULT CIRCUIT INTERRUPTER V VOLT OR VOLTAGE
GND GROUND VA VOLT AMPERE
GYP BOARD GYPSUM BOARD VCT VINYL COMPOSITION TILE
HP HORSEPOWER VFD VARIABLE FREQUENCY DRIVE
IECC INTERNATIONAL EMERGENCY CONSERVATION CODE W WATT
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS WP WEATHERPROOF
IES ILLUMINATING ENGINEERING SOCIETY XFMR TRANSFORMER
IMC INTERMEDIATE METALLIC CONDUIT Z IMPEDANCE
ISC SHORT CIRCUIT AMPERES, KA %Z PERCENT IMPEDANCE
IG ISOLATED GROUND
IP INGRESS PROTECTION
SPDSPD
STATE PUBLIC WORKS SECTION 8 ELECTRICAL STANDARDS
8.1 GENERAL
8.1.1 ELECTRICAL AND LIGHTING SYSTEMS SHALL BE DESIGNED TO COMPLY WITH THE REQUIREMENTS OF THE ADOPTED CODES AND REGULATIONS LISTED IN SECTION 2, AND WITH THE MOST CURRENT EDITION OF THE FOLLOWING REFERENCE STANDARDS, AS
APPLICABLE TO EACH SPECIFIC PROJECT:
A. NFPA 70E (STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE)
B. NFPA 70B (RECOMMENDED PRACTICE FOR ELECTRICAL EQUIPMENT MAINTENANCE)
C. LIGHTING HANDBOOK PUBLISHED BY THE ILLUMINATING ENGINEERING SOCIETY (IES)
D. IEEE RECOMMENDED PRACTICE COLOR BOOK SERIES PUBLISHED BY THE INSTITUTE OF ELECTRICAL AND ELECTRONICS
ENGINEERS (IEEE)
E. EIA/TIA-568, COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD, PUBLISHED BY THE
ELECTRONICS INDUSTRY ASSOCIATION (EIA) AND THE TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) F. EIA/TIA-569, COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS PATHWAYS AND SPACES G. EIA/TIA-606, ADMINISTRATION FOR TELECOMMUNICATIONS INFRASTRUCTURE FOR COMMERCIAL BUILDINGS H. EIA/TIA-607, COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS
8.1.2 ELECTRICAL EQUIPMENT AND EQUIPMENT ROOMS SHALL BE DESIGNED TO ENSURE ADEQUATE PROVISIONS FOR SERVICE, MAINTENANCE, AND REMOVAL/REPLACEMENT OF ELECTRICAL EQUIPMENT, PANELS, SWITCHBOARDS, TRANSFORMERS, AND
GENERATORS.
8.1.3 ELECTRICAL EQUIPMENT, DISTRIBUTION SYSTEMS, AND LIGHT FIXTURES SHALL BE SECURELY ANCHORED TO RESIST EARTHQUAKE LOADS. SEISMIC BRACING SPECIFICATIONS SHALL REQUIRE COMPLIANCE WITH ALL APPLICABLE PORTIONS OF THE INTERNATIONAL
BUILDING CODE.
8.2 ENERGY CONSERVATION
8.2.1 ELECTRICAL AND LIGHTING SYSTEMS SHALL BE DESIGNED AND DOCUMENTED TO COMPLY WITH THE REQUIREMENTS OF THE
INTERNATIONAL ENERGY CONSERVATION CODE AND/OR ASHRAE/IESNA STANDARD 90.1.
8.2.2 BUILDINGS WITH A GROSS FLOOR AREA GREATER THAN 20,000 SQUARE FEET SHALL COMPLY WITH THE MINIMUM GREEN
BUILDING DESIGN STANDARDS AS DEFINED BY THE STATE FOR EACH PROJECT.
8.3 ELECTRICAL SYSTEMS AND EQUIPMENT
8.3.1 VOLTAGE AND DISTRIBUTION SYSTEMS SHALL BE SELECTED BASED ON A STUDY OF THE REQUIREMENTS OF THE BUILDING TO
DETERMINE WHICH IS THE MOST ECONOMICAL FROM A LIFE CYCLE COST PERSPECTIVE.
8.3.2 GENERALLY, BUILDING ELECTRICAL POWER SERVICE SHALL BE 208Y/120 VOLT, 3 PHASE, 4 WIRE, OR 480Y/277 VOLT, 3 PHASE, 4 WIRE, EXCEPT IN CASES WHERE THE LOCAL POWER COMPANY WILL NOT PROVIDE THIS TYPE OF SERVICE.
8.3.3 ELECTRICAL SWITCHBOARDS SHALL BE LOCATED INDOORS UNLESS AN EXTERIOR LOCATION IS SPECIFICALLY APPROVED BY THE
STATE IN WRITING.
8.3.4 SPECIFICATIONS FOR ALL ELECTRICAL SWITCHBOARDS AND PANELBOARDS SHALL REQUIRE COPPER BUSES.
8.3.5 EACH INTERIOR BUILDING SWITCHBOARD MAIN CIRCUIT BREAKER SHALL BE PROVIDED WITH A TRIP COIL AND AN EXTERIOR SHUNT-TRIP SWITCH. SHUNT-TRIP SWITCH LOCATION SHALL BE COORDINATED WITH THE FIRE AUTHORITY.
8.3.6 MAIN SERVICE TRANSFORMERS SHALL BE LOCATED OUTDOORS, BE LOCATED AT LEAST 10 FEET FROM COMBUSTIBLE WALLS, SHALL BE PAD MOUNTED, AND SHALL HAVE FULL RANGE OVERLOAD PROTECTION COORDINATED WITH THE PRIMARY CIRCUIT PROTECTION. TRANSFORMERS SHALL BE PROTECTED WITH BOLLARDS WHERE NECESSARY TO PREVENT POTENTIAL DAMAGE BY
VEHICLES.
8.3.7 INDOOR DRY-TYPE TRANSFORMERS SHALL BE SPECIFIED TO CONFORM TO DEPARTMENT OF ENERGY EFFICIENCY STANDARD 10 CFR 431.196 FOR LOW VOLTAGE DISTRIBUTION TRANSFORMERS MANUFACTURED AFTER 2016. INDOOR TRANSFORMERS
SHALL BE SPECIFIED FOR A MAXIMUM 80°C TEMPERATURE RISE.
8.3.8 OUTDOOR OIL-FILLED AND DRY-TYPE TRANSFORMERS SHALL BE SPECIFIED TO CONFORM TO DEPARTMENT OF ENERGY EFFICIENCY STANDARD 10 CFR 431.196 FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS MANUFACTURED AFTER 2016. OUTDOOR DRY-TYPE TRANSFORMERS SHALL BE SPECIFIED FOR A MAXIMUM 115°C TEMPERATURE RISE.
8.3.9 ALL DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, AND BRANCH CIRCUIT PANELS SHALL HAVE A MINIMUM OF 10% SPARE POSITIONS, BUT IN NO CASE LESS THAN 6 POLES. REFURBISHED UNITS ARE ACCEPTABLE.
8.3.10 WHEN FEASIBLE, SEPARATE PANELS SHALL BE UTILIZED TO SEPARATE LIGHTING, RECEPTACLE, AND EQUIPMENT LOADS, TO
ALLOW FOR INSTALLATION OF MEASUREMENT AND VERIFICATION METERING.
8.3.11 WHERE A PANEL IS INSTALLED FLUSH WITH A WALL, EMPTY CONDUITS SHALL BE EXTENDED FROM THE PANEL TO AN ACCESSIBLE SPACE ABOVE OR BELOW. A MINIMUM OF ONE 3/4 INCH CONDUIT SHALL BE INSTALLED FOR EVERY THREE SINGLE POLE SPARE CIRCUIT BREAKERS OR SPACES, OR FRACTION THEREOF, BUT NOT LESS THAN TWO EMPTY CONDUITS.
8.3.12 WHERE UNDER FLOOR SPACE IS ACCESSIBLE, SPARE CONDUITS SHALL BE EXTENDED THERE IN ADDITION TO THE CEILING
LOADS.
8.3.13 PANELS SHALL HAVE A TYPEWRITTEN DIRECTORY, FORMATTED WITH MULTIPLE COLUMNS THAT MATCH THE CIRCUIT BREAKER CONFIGURATION, WITH LEFT/RIGHT ALTERNATING CIRCUIT NUMBERS, AND A COMPLETE DESCRIPTION OF ALL LOADS CONTROLLED BY EACH BREAKER. DIRECTORIES SHALL INCLUDE THE PANEL DESIGNATION, THE UPSTREAM PANEL OR SWITCHBOARD THAT IT IS FED
FROM, VOLTAGE RATING, AND CURRENT RATING.
8.3.14 PROVIDE MEANS FOR HARMONIC SUPPRESSION IN ALL AREAS THAT ARE LIKELY TO HAVE SIGNIFICANT HARMONIC CONTENT.
COORDINATE SPECIFIC MEANS OF HARMONIC SUPPRESSION WITH THE STATE PUBLIC WORKS DIVISION AND THE USING
AGENCY PRIOR TO COMMENCING WITH THE DESIGN.
8.3.15 EMERGENCY GENERATORS SHALL BE SPECIFIED FOR A COMBINED MECHANICAL AND ELECTRICAL EFFICIENCY OF 80% OR
GREATER.
8.3.16 EMERGENCY GENERATORS SHALL BE SPECIFIED WITH THE CAPABILITY FOR RECOVERY TO 90% OF THE RATED VOLTAGE AND 90
% OF THE RATED FREQUENCY WITHIN TWO SECONDS (120 CYCLES) AT SITE CONDITIONS.
8.3.17 ELECTRICAL EQUIPMENT ROOMS AND DATA EQUIPMENT ROOMS IN MULTI-STORY BUILDINGS SHALL BE VERTICALLY STACKED.
8.3.18 WHENEVER ELECTRICAL PANELS OR SWITCHBOARDS ARE PLACED ON A WALL THAT ADJOINS AN OFFICE OR OTHER OCCUPIED SPACE, THE WALL SHALL BE SHIELDED TO PREVENT TRANSFERENCE OF ELECTROMAGNETIC FIELDS INTO THE OCCUPIED
SPACE.
8.3.19 PHOTOVOLTAIC SYSTEM INVERTERS SHALL BE DESIGNED AND INSTALLED WITH THE CAPABILITY TO CONTROL OR CORRECT THE SYSTEM POWER FACTOR. PROJECT SPECIFICATIONS SHALL REQUIRE ASSESSMENT AND ADJUSTMENT OF THE POWER FACTOR
WHILE THE PHOTOVOLTAIC SYSTEM IS OPERATING AT OR NEAR CAPACITY.
8.4 CONDUITS AND RACEWAYS
8.4.1 FLEXIBLE CONDUIT SHALL BE LIMITED TO CONNECTIONS BETWEEN EQUIPMENT AND OTHER RACEWAY SYSTEMS, AND SHALL NOT
EXCEED SIX FEET IN LENGTH.
8.4.2 METAL-CLAD CABLE (MC CABLE) SHALL NOT BE SPECIFIED.
8.4.3 FITTINGS FOR ELECTRICAL METALLIC TUBING SHALL BE STEEL, WATERTIGHT, GLAND-RING TYPE OR STEEL SET-SCREW TYPE.
8.4.4 ALL METAL CONDUIT, COUPLINGS, ELBOWS, AND FITTINGS BURIED BELOW GRADE SHALL BE COATED WITH PVC OR 2-LAP WRAPPED WITH AN APPROVED TAPE (COATING OR WRAPPING SHALL BE A MINIMUM 20 MIL THICKNESS).
8.4.5 IN LIEU OF RIGID GALVANIZED CONDUIT FOR HORIZONTAL SECONDARY SERVICE RACEWAYS AND BRANCH CIRCUIT WIRING IN OR UNDER A FLOOR SLAB, SCHEDULE 40 PVC MAY BE USED WITH PVC-COATED RIGID STEEL CONDUIT TERMINATION STUB-UPS
OUT OF THE GROUND OR SLAB AND INTO THE BUILDING.
8.4.6 TO THE GREATEST EXTENT POSSIBLE, CONDUITS SHALL NOT BE PLACED WITHIN CONCRETE SLABS AND SHALL BE DESIGNED AND SPECIFIED TO BE PLACED BENEATH CONCRETE SLABS-ON-GRADE, OR SUSPENDED BENEATH THE STRUCTURAL FLOOR OR ROOF DECK ABOVE. CONDUITS SHALL BE PLACED A MINIMUM OF 3 INCHES BELOW METAL DECKS (RATHER THAN A MINIMUM OF 1.5 INCHES AS REQUIRED BY THE NATIONAL ELECTRICAL CODE). FOR SLABS-ON-GRADE, THE CONDUITS SHALL BE PLACED AT THE BOTTOM OF THE BASE OR GRAVEL COURSE. WHERE KNOWN STORAGE SHELVING OR FF&E ELEMENTS ARE TO BE INSTALLED INTO OR ONTO THE CONCRETE SLABS, THESE AREAS SHALL BE GRAPHICALLY DEPICTED AND NOTED TO NOT ALLOW ANY
ELECTRICAL CONDUITS IN THESE CONCRETE SLABS.
8.4.7 WHERE NECESSARY, CONDUITS LOCATED IN CONCRETE SLABS SHALL NOT EXCEED ¾ INCH AND SHALL BE SPACED NO CLOSER THAN EIGHT INCHES ON CENTER EXCEPT AT PANEL AND JUNCTION BOXES WHERE THEY SHALL BE SPREAD AS WIDELY AS POSSIBLE.
PROVIDE FOR SPECIAL FRAMING WHEN REQUIRED WHERE CONDUITS ENTER A PANEL BOARD. WHERE CONDUITS LARGER THAN ¾ INCH ARE TO BE PLACED IN A CONCRETE SLAB, THE STRUCTURAL ENGINEER SHALL BE NOTIFIED FOR REVIEW
AND APPROVAL.
8.4.8 CONDUITS LOCATED VERTICALLY IN A CONCRETE SLAB SHALL BE RIGID GALVANIZED STEEL COATED WITH PVC OR 2-LAP WRAPPED WITH AN APPROVED TAPE (COATING OR WRAPPING SHALL BE A MINIMUM 20 MIL THICKNESS).
8.4.9 LOW VOLTAGE WIRING DISTRIBUTION SYSTEMS (INCLUDING J-SUPPORTS) SHALL BE INSTALLED IN STRICT CONFORMANCE WITH THE MOST CURRENT EDITION OF NECA/BICSI STANDARD 568 AND WITH THE CABLE MANUFACTURER’S WRITTEN INSTALLATION
RECOMMENDATIONS/REQUIREMENTS.
8.4.10 ALL LOW VOLTAGE WIRING (WHETHER PLENUM RATED OR NOT) SHALL BE INSTALLED IN RACEWAYS WITH THE FOLLOWING
CONDITIONS, CLARIFICATIONS, AND EXCEPTIONS:
A. FIRE ALARM AND SECURITY SYSTEM WIRING SHALL BE INSTALLED IN RACEWAYS WITH NO EXCEPTIONS.
B. RACEWAYS SHALL BE AS DEFINED IN THE NATIONAL ELECTRICAL CODE. OPEN CABLE TRAYS SHALL NOT BE CONSTRUED
AS MEETING THE DEFINITION OF A RACEWAY.
C. LOW VOLTAGE WIRING FOR TELEPHONE, DATA, COMMUNICATIONS, INTERCOM, TEMPERATURE CONTROLS, AND ENERGY
MANAGEMENT SYSTEMS MAY BE ROUTED UTILIZING OPEN CABLE TRAYS ABOVE ACCESSIBLE CEILINGS.
D. WHERE OPEN CABLE TRAYS ARE UTILIZED ABOVE ACCESSIBLE CEILINGS THE FOLLOWING CONDITIONS APPLY:
LOW VOLTAGE WIRING ROUTED IN OPEN CABLE TRAYS SHALL BE PLENUM-RATED (WHETHER OR NOT THE CEILING
SPACE IS UTILIZED AS A RETURN AIR PLENUM).
1. LOW VOLTAGE WIRING CONCEALED IN WALLS, FLOORS, AND ABOVE INACCESSIBLE CEILINGS SHALL BE ROUTED IN
RACEWAYS.
2. LOW VOLTAGE WIRING ROUTED BETWEEN CONDUIT STUBS AND CABLE TRAYS SHALL BE SECURED WITH
APPROPRIATELY SPACED J-SUPPORTS.
8.5 CONDUCTORS
8.5.1 CONDUCTOR MATERIAL SHALL BE COPPER FOR ALL WIRE SIZES.
8.5.2 METAL-CLAD CABLE (MC CABLE) SHALL NOT BE SPECIFIED.
8.5.3 NEUTRAL CONDUCTORS FOR 208Y/120 VOLT SYSTEMS SHALL BE WHITE AND NEUTRAL CONDUCTORS FOR 480Y/277 VOLT
SYSTEMS SHALL BE GRAY.
8.5.4 NO WIRE SMALLER THAN #12 AWG SHALL BE SPECIFIED FOR LIGHT AND POWER CIRCUITS.
8.5.5 PROVIDE SEPARATE RACEWAYS AND CONDUCTORS FOR LINE SIDE AND LOAD SIDE WIRING FOR ALL VARIABLE FREQUENCY
DRIVES.
8.6 LIGHTING
8.6.1 LIGHTING IN ALL OFFICE AND CLASSROOM AREAS SHALL BE DESIGNED FOR A MINIMUM MAINTAINED AVERAGE LIGHTING
LEVEL OF 40 FOOT-CANDLES AT THE DESK SURFACE.
8.6.2 ALL LIGHT FIXTURES SHALL BE LED TYPE WITH A MINIMUM EFFICIENCY OF 100 LUMENS PER WATT, UNLESS ANOTHER FIXTURE TYPE IS APPROVED BY THE STATE IN WRITING. LED LIGHT FIXTURES SHALL BE SPECIFIED WITH HIGH FREQUENCY ELECTRONIC DRIVERS HAVING A TOTAL HARMONIC DISTORTION OF 20% OR LESS AND A POWER FACTOR OF 90% OR GREATER.
8.6.3 LIGHTING CONTROLS SHALL BE PROVIDED FOR ALL BUILDING SPACES EXCEPT FOR SMALL SPACES SERVED BY A SINGLE FIXTURE. LIGHTING SHALL BE CONTROLLED
BY MOTION SENSORS, MULTI-LEVEL SWITCHING, OR DAYLIGHT DIMMING, AS APPROPRIATE.
8.6.4 THE PROPOSED METHOD OF LIGHTING CONTROL FOR EACH TYPE OF SPACE IN THE BUILDING SHALL BE REVIEWED AND APPROVED BY THE STATE DURING THE EARLY
STAGES OF DESIGN.
8.6.5 SPECIAL USE AREAS OR AREAS USED FOR MULTIPLE PURPOSES WHICH MAY REQUIRE UNUSUAL LEVELS OF ILLUMINATION SHALL BE REVIEWED AND APPROVED BY THE
STATE DURING THE EARLY STAGES OF DESIGN.
8.6.6 LIGHTING CONTROLS SHALL INCLUDE PHOTOCELL CONTROL OF EXTERIOR LIGHTING. PHOTOCELL LOCATION SHALL BE REVIEWED AND APPROVED BY THE STATE.
8.6.7 EXTERIOR DOORS AND ENTRIES SHALL HAVE ILLUMINATION ON THE OUTSIDE.
8.6.8 IN-GROUND EXTERIOR LIGHT FIXTURES SHALL NOT BE SPECIFIED.
8.7 SWITCHES AND RECEPTACLES
8.7.1 PROVIDE A FOURPLEX RECEPTACLE AT THE DESK LOCATION IN EACH OFFICE AND AT EACH COMPUTER WORKSTATION.
8.7.2 ALL CORRIDORS AND HALLWAYS SHALL HAVE DUPLEX RECEPTACLES SPACED AT NOT MORE THAN 30 FEET ON CENTER.
8.7.3 PROVIDE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION FOR ALL ELECTRICAL RECEPTACLES LOCATED WITHIN 6 FEET OF A WET BAR SINK (SUCH AS IN BREAK
ROOMS, KITCHENETTES, ETC.).
8.7.4 OUTLET BOXES, COVERS, RINGS, AND OTHER SIMILAR FITTINGS SHALL BE GALVANIZED STEEL.
8.7.5 WALL SWITCHES NEAR DOORS SHALL BE MOUNTED WITHIN 12 INCHES OF THE TRIM ON THE LATCH SIDE OF THE DOOR.
8.7.6 GANG TYPE PLATES SHALL BE USED FOR MULTIPLE GANG BOXES.
8.8 GROUNDING
8.8.1 PROPER GROUNDING SHALL BE PROVIDED FOR ALL ELECTRICAL SYSTEMS. REQUIREMENTS FOR BONDING CONNECTIONS AT SERVICE ENTRANCES, METAL PIPING, STRUCTURES, PANEL BOARDS, AND TRANSFORMERS SHALL BE CLEARLY NOTED ON THE APPROPRIATE DRAWINGS.
8.8.2 ALL CIRCUIT GROUNDS SHALL BE MADE UP SUCH THAT A CONTINUOUS PATH IS RELIABLY MAINTAINED TO A GROUNDING ELECTRODE OR SYSTEM. THE GROUND
FIELD (RODS, GRIDS, PLATES, ETC.) SHALL HAVE A MAXIMUM RESISTANCE OF 5 OHMS.
8.8.3 SPECIAL CONSIDERATION SHALL BE GIVEN TO GROUNDING OF SENSITIVE OFFICE EQUIPMENT (COMPUTERS, SERVERS, DATA CIRCUITS, ETC.).
8.8.4 SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED WITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY. INSULATION COLOR FOR GROUND CONDUCTORS SHALL BE GREEN. TERMINATE THE ENDS OF EACH GROUND CONDUCTOR WITH A SUITABLE LUG, BUS, OR BUSHING. INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR BUSWAY SUPPLY CIRCUITS SHALL BE INSTALLED FROM THE GROUNDING BUS IN THE SWITCHGEAR, SWITCHBOARD, OR DISTRIBUTION
PANEL TO THE EQUIPMENT GROUNDING TERMINAL BAR ON THE BUSWAY.
8.9 TESTING OF ELECTRICAL SYSTEMS
8.9.1 SPECIFICATIONS SHALL INCLUDE REQUIREMENTS FOR ELECTRICAL SYSTEMS TESTING, INCLUDING DOCUMENTATION OF TEST RESULTS, AS APPROPRIATE FOR THE ELECTRICAL SYSTEMS UTILIZED IN THE PROJECT. ELECTRICAL SYSTEMS TESTING AND DOCUMENTATION REQUIREMENTS SHALL BE IN ACCORDANCE WITH A RECOGNIZED TESTING STANDARD (SUCH AS THOSE PUBLISHED BY THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA).
8.10 TELEPHONE AND DATA SYSTEMS
8.10.1 IN ALL NEW BUILDINGS, AND WHERE REQUIRED AS PART OF THE PROJECT SCOPE OF WORK, THE DESIGN SHALL PROVIDE FOR COMMUNICATIONS PATHWAYS AND SPACES FOR THE ELEMENTS OF THE COMMUNICATIONS SYSTEMS INCLUDING, BUT NOT LIMITED TO, MULTI-SERVICE COMMUNICATION SYSTEMS, TWISTED-PAIR SYSTEMS, COAXIAL CABLE SYSTEMS, AND OPTICAL
FIBER SYSTEMS.
8.10.2 DATA EQUIPMENT ROOMS SHALL BE LOCATED ON EACH FLOOR AND ALL DATA DROPS SHALL BE LESS THAN 300 FEET FROM FACE PLATE TO THE POINT OF TERMINATION. DISTANCES SHALL BE MEASURED ALONG THE ACTUAL CABLE PATH INCLUDING SERVICE LOOPS.
8.10.3 COORDINATE THE EXTENT AND LAYOUT OF CONDUITS, RACEWAYS, CONDUCTORS, AND CABLES WITH THE USING AGENCY AND ALLOW FOR SIGNIFICANT BUT
REASONABLE CHANGES IN USE OF THE SPACES SERVED.
8.10.4 WHEREVER MULTIPLE DATA/VOICE CONNECTIONS ARE SPECIFIED AT A SINGLE LOCATION, EACH DATA/VOICE CONNECTION TYPE SHALL BE A DIFFERENT COLOR
(GENERALLY BLUE FOR DATA AND WHITE FOR VOICE).
8.11 FIRE ALARM SYSTEMS
8.11.1 NEW BUILDINGS SHALL BE EQUIPPED WITH A FIRE ALARM SYSTEM WHEN REQUIRED BY THE INTERNATIONAL BUILDING CODE. WHEN A FIRE ALARM SYSTEM IS REQUIRED, THE SYSTEM SHALL BE DESIGNED IN CONFORMANCE WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE AND THE INTERNATIONAL FIRE CODE.
8.11.2 ALL INITIATING AND INDICATING DEVICES SHALL BE SPECIFIED TO BE TESTED FOR BOTH "ALARM" AND "TROUBLE" CONDITIONS IN A TEST CONDUCTED BY THE INSTALLING CONTRACTOR AND WITNESSED BY THE APPROPRIATE FIRE AUTHORITY AND BY THE STATE’S DESIGNATED REPRESENTATIVE.
8.12 SEISMIC BRACING FOR ELECTRICAL SYSTEMS
8.12.1 ALL ELECTRICAL EQUIPMENT, CABLE TRAYS, AND CONDUIT SHALL BE APPROPRIATELY BRACED FOR THE SEISMIC CONDITIONS AT THE PROJECT LOCATION. SEISMIC BRACING SPECIFICATIONS SHALL REQUIRE COMPLIANCE WITH ALL APPLICABLE PORTIONS OF THE INTERNATIONAL BUILDING CODE AND SHALL REQUIRE COMPLIANCE WITH THE MEANS AND METHODS OUTLINED IN THE INTERNATIONAL SEISMIC APPLICATION TECHNOLOGY (ISAT) MANUAL, OR AN APPROVED EQUIVALENT MANUAL.
SPECIFICATIONS SHALL REQUIRE THAT A COPY OF THE SPECIFIC BRACING INSTRUCTIONS FOR ALL EQUIPMENT, DUCTWORK, AND PIPING BE MAINTAINED BY THE CONTRACTOR AT THE PROJECT SITE AND THAT THE BRACING INSTRUCTIONS SHALL BE AVAILABLE
AT ALL TIMES FOR USE BY THE STATE.
(NOT ALL SYMBOLS WILL BE USED)
THE PROJECT IS TO PLACE A SHORE POWER ASSEMBLY WITHIN THE IDENTIFIED EXTERIOR AREA AT THE NORTH SIDE OF THE FACILITY. THE SHORE POWER ASSEMBLY SYSTEM INCLUDES SUPPORT FOR THE
FOLLOWING:
· (1) 100 AMP, 208V SINGLE-PHASE DISCONNECT ON A NEW UNI-STRUT ASSEMBLY.
· (1) W3P1, CABLE ASSEMBLY W3, 7056681-501 SHORE POWER CABLE ASSEMBLY OFCI ON A NEW
UNI-STRUT ASSEMBLY.
· (1) WEATERPROOF DUPLEX RECEPTACLE FOR CONVENIENCE ON A NEW UNI-STRUT ASSEMBLY.
· NEW FEEDERS TO BE INSTALLED WITH NEW DISCONNECT.
· ROUTING OF CONDUIT TO BE SURFACE MOUNTED ALONG EXISTING WALL AS MUCH AS POSSIBLE, UNDERGROUND ROUTING FROM WALL TO NEW UNI-STRUT ASSEMBLY IN EXISTING DIRT
LANDSCAPING ONLY.
· NEW NEMA 4 ENCLOSURE FOR STORAGE AND PROTECTION OF THE CABLE ASSEMBLY.
SCOPE
(E)(E)(E)
(E) (E)(E)(E)
(E)
(E)
(E) (E)(E)
(E)
(E) (E)
(E) (E)
(E)
(E)
(E)
(E)
(E) (E)
(E)
(E)
(E)
(E)(E)
(E)
(E)
(E) (E) (E) (E)
(E)
(E)
(E)
(E)
(E) (E)
(E)
(E)
(E)
(E)
(E) (E)
(E)
(E) (E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
Sheet Number
P R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L S
IT
E
P L A
N
E0.5
SCALE: 1
ELECTRICAL SITE PLAN
1/64"=1'-0"
(THIS SHEET ONLY)GENERAL NOTES
1. OVERALL PLAN SHOWN FOR PROJECT SCOPE AND REFERENCE ONLY.
AREA OF WORK
LDP-9 4
WP
(E)
(E)
(E)L1B-28
1'
2'-6" 2'-6"
9(TYP. OF 3)
REFER TO DIAGRAM 2
ON THIS SHEET
12"x12"x6" PULL BOX
TO
DISCONNECT
TO
RECEPT 77
OPENING
Sheet Number
P R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L E
N L A
R G
E D
P O
W E
R P
L A
N
E1.1
(THIS SHEET ONLY)GENERAL NOTES
1. COORDINATE AND OBTAIN APPROVAL FROM STRUCTURAL ENGINEER FOR
ROUTING OF ANY CONDUIT OR RACEWAY IN SLAB PRIOR TO ROUGH-IN.
2. ALL CIRCUITS SHOWN ARE HOMERUNS UNLESS NOTED OTHERWISE. DO NOT
COMBINE HOMERUNS.
3. FOR ANY PENETRATION THROUGH FIRE RATED WALLS. PROVIDE FIRE RATED
SLEEVES, ETC. AS REQUIRED BY APPLICATION. REFER TO FIRE RATED
APPLICATION DIAGRAM 4 ON SHEET E8.0 FOR ADDITIONAL INFORMATION.
4. TICK MARKS NOT SHOWN FOR CLARITY. CONTRACTOR SHALL PROVIDE ALL
REQUIRED PHASE, NEUTRAL, SWITCHED AND GROUND CONDUCTORS
REQUIRED FOR CONTROLS INDICATED.
5. ENTIRE INSTALLATION SHALL MEET ALL REQUIREMENTS OF NATIONAL OR
LOCAL ELECTRICAL CODES. ALL EQUIPMENT SHALL BEAR UL LABELS.
WORK NOTES (THIS SHEET ONLY)
1 PROVIDE NEMA 4X DISCONNECT ON AN UNI-STRUT ASSEMBLY. REFER TO
DIAGRAM 1 ON SHEET E8.0 FOR UNI-STRUT ASSEMBLY REQUIREMENTS.
PROVIDE 'W3P1, CABLE ASSEMBLY W3, 7056681-501' SHORE POWER CABLE
ASSEMBLY (OFCI) TO STORE IN ENCLOSURE. REFER TO SINGLE LINE
DIAGRAM ON SHEET E5.0 FOR CONNECTION REQUIREMENTS.
CONCRETE PAD, REFER TO DIAGRAM 1 ON SHEET E8.0 FOR REQUIREMENTS.
REFER TO SINGLE LINE DIAGRAM ON SHEET E5.0 FOR FEEDER REQUIREMENTS.
PROPOSED ROUTING ALONG WALL TO AVOID EXISTING BANK OF
CONDUITS EXISTING MAIN ELECTRICAL ROOM, CONTRACTOR TO ASSESS
EXISTING CONDITION TO SEE IF AN ALTERNATE ROUTE IS MORE COST
EFFECTIVE.
PROPOSED NEMA 4, 12" X 12" X 6" PULLBOX.
CONTRACTOR TO PROVIDE TRANSITION FROM RGC TO PVC BETWEEN
PULLBOX AND UNDERGROUND.
PROVIDE WEATHERPROOF EXTRA DUTY NONMETALLIC IN-USE CLEAR
COVER, HUBBELL TAYMAC TUFF #MM420C OR APPROVED EQUAL FOR
MAINTENANCE RECEPTACLE.
PROVIDE VEHICULAR PROTECTION BOLLARDS, REFER TO DIAGRAM 5 ON
SHEET E8.0 FOR ADDITIONAL INFORMATION.
EXTEND 3/4"C, (2) 10 AWG & (1) 10 AWG GND FROM EXISTING
MAINTENANCE RECEPTACLE TO NEW MAINTENANCE RECEPTACLE
MOUNTED ON EXTERIOR UNI-STRUT ASSEMBLY.
PROVIDE NEMA 4 LOCKABLE 30"x30"x10" HOFFMAN BOX OR APPROVED
EQUAL ASSEMBLY WITH A CABLE HOOK (LEVITON 'EHOOK') MOUNTED
INSIDE TO STORE THE CABLE ASSEMBLY INDICATED BY WORK NOTE 2.
MOUNT HOFFMAN BOX TO UNI-STRUT ASSEMBLY.
SCALE: 1
ELECTRICAL ENLARGED POWER PLAN
3/16"=1'-0"
SCALE: 2
ENLARGED EXTERIOR WALL
1/2"=1'-0"
(E)NV ENERGY
XFMR
TO (E)UTILITY
POINT OF
SERVICE
'H1A'
PANEL
1 2 3 4 5 6
(E)600A 3P
(E)350A 3P
(E)225A 3P
(E)
'H1B'
PANEL
(E)225A 3P
(E)
'AC1'
PANEL
(E)200A 3P
(E)
'AC2'
PANEL
(E)200A 3P
(E) (E) SPARE
(939.0KVA | 1129.0A)
955.8KVA| 1150.2A
1600A BUS, 480Y/277V, 3PH, 4W
AIC= 65,000
(E)MAIN SWITCHBOARD 'MS'
1 2 3
(E)60A 3P
(E)1600A 3P
(989.0KVA | 1190.0A)
1005.8KVA| 1210.3A
M
(E)NVE MTR#
AA018679192
(E)SPACE
(E)ATS 'EH'
60A
4P,4W
C
N G
(E)UFER
(E)TMGB
(E) (E)
T
(E)
'EHA'
PANEL
(E)
(E)XFMR
'T-ELA'
15KVA
'ELA'
PANEL
(E)
(E)ATS 'XHA'
1600A 4P,4W
(MAIN ELECTRICAL ROOM)
1600A BUS, 480Y/277V, 3PH, 4W
AIC= 65,000
(E)MAIN SWITCHBOARD 'MSA'
(MAIN ELECTRICAL ROOM)
(E)GFP
C
TO
(E)SHUTDOWN
CTRLS
'LMS'
PANEL
(E)45A 3P
(E)
(E)110A 3P
(E)400A 3P
(E) SPARE
(E)400A 3P
(E) SPARE
(E)400A 3P
(E) SPARE
(E)400A 3P
(E)45A 3P
1 2 3 4 5 6
(E)200A 3P
(E)200A 3P
(145.0KVA | 397.0A)
161.8KVA| 448.2 A
800A BUS, 208Y/120V, 3PH, 4W
AIC= 65,000
(E)DISTRIBUTION BOARD 'LDP'
(MAIN ELECTRICAL ROOM)
(E)200A 3P
10 11 12
(E)600AS
3P
(354.0KVA | 425.0A)
600A BUS, 480Y/277V, 3PH, 4W
AIC= 65,000
(E)DISTRIBUTION BOARD 'HCPDP'
(CHILLER ROOM)
(E)100AF
FRS-R
(E)CH
MCA=263
(E)30AS
3P
(E)20AF
FRS-R
(E)CT
7.5 HP
(E)VFD-C1
(E)30AS
3P
(E)20AF
FRS-R
(E)TP
15 HP
(E)30AS
3P
(E)20AF
FRS-R
(E)TP
15 HP
(E)30AS
3P
(E)20AF
FRS-R
(E)P
10 HP
(E)VFD-P1
(E)30AS
3P
(E)20AF
FRS-R
(E)P
10 HP
(E)VFD-P2
(E)30AS
3P
(E)15AF
FRS-R
(E)PP
5 HP
(E)30AS
3P
(E)15AF
FRS-R
(E)PP
5 HP
(E)600AS
3P
(E)100AF
FRS-R
(E)CH
MCA=263
(E)SPACE
FOR
100A/3P
(E)SPACE
FOR
100A/3P
10 11
T
(E)
(E)XFMR
'T-LDP'
225KVA
T
(E)
(E)XFMR
'T-L1E'
75KVA
'L1E'
PANEL
(E)
'L1ES'
PANEL
(E)
'L1F'
PANEL
(E)
'AC1S'
PANEL
(E)
(E) (E)(E)
T
(E)
(E)XFMR
'T-XLA'
75KVA
'XLA'
PANEL
(E)
(E) F
'XLB'
PANEL
(E)
(E)F
T
(E)
(E)XFMR
'T-GS'
30KVA
'GS'
PANEL
(E)
(E) F
(E)800A 3P
(E)200A 3P
(E)200A 3P
100A 2P
(E)200A 3P
(E)SPACE
FOR
200A/3P
(E)SPACE
FOR
200A/3P
(E)SPACE
FOR
200A/3P
'L1A'
PANEL
(E)
'L1AS'
PANEL
(E)
'L1B'
PANEL
(E)
'L1BS'
PANEL
(E)
'L1C'
PANEL
(E)
'L1CS'
PANEL
(E)
'L1D'
PANEL
(E)
'L1DS'
PANEL
(E)
'L1K'
PANEL
(E)
'L1KS'
PANEL
(E)
(E) SPARE
(E)60A 3P
'LDP-B'
PANEL
(E)
ROOF-TOP
UNIT CU-1
(E)60A 3P
(E)GENERATOR 'G-1'
800KW/1000KVA
277/480V
NEMA 3R
EXTERIOR UTILITY YARD
(E)1500A 3P
(E)
(E)
X - F1
EXTERIOR
SHORE POWER
DISCONNECT
(YARD)
(E)200A 3P
(E) SPARE
102PT
X-(E)ISC=39,994
X-(E)ISC=36,557
X-(E)ISC=27,185
(E)ISC=36,111-X
X-(E)ISC=14,574
X-(E)ISC=30,814
X-(E)ISC=5,261
X-(E)ISC=
33,494
X-(E)ISC=
10,519
X-(E)ISC=
33,021
X-(E)ISC=
11,911
X-(E)ISC=
6,153
(E)ISC=5,617-X X-(E)ISC=5,617
(23.0KVA)
23.2KVA
Sheet Number
P R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L S
IN
G
L E
L
IN
E D
IA
G
R A
M
E5.0
SCALE: 1
ELECTRICAL SINGLE LINE DIAGRAM
N.T.S
(THIS SHEET ONLY)GENERAL NOTES
1. EXISTING OVERALL SINGLE LINE DIAGRAM SHOWN FOR REFERENCE ONLY
AND UPDATED BASED ON VISIBLE SITE CONDITIONS DURING SITE VISIT(S).
2. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE FULLY RATED TO
WITHSTAND THE AVAILABLE FAULT, UNLESS NOTED OTHERWISE.
3. PROVIDE 4" HIGH HOUSEKEEPING PAD UNDER ALL FLOOR MOUNTED
ELECTRICAL EQUIPMENT.
4. MATERIALS AND INSTALLATION SHALL COMPLY WITH THE LATEST CODES,
LAWS AND ORDINANCES OF THE AUTHORITY HAVING JURISDICTION
INCLUDING THE LOCALLY ADOPTED AMENDMENTS.
5. FAULT CURRENT AMP INTERRUPTING CAPACITIES ARE MINIMUM. IF
STANDARD EQUIPMENT RATING IS GREATER, PROVIDE STANDARD RATING.
WORK NOTES (THIS SHEET ONLY)
1 EXISTING LOADS TAKEN FROM LAS VEGAS (HENDERSON) READINESS CENTER
FOR THE NEVADA NATIONAL GUARD RECORD DRAWINGS DATED
08/12/2005 BY JBA CONSULTING ENGINEERS. EXISTING LOADS SHOWN IN
PARANTHESIS, NEW LOADS SHOWN WITHOUT.
EXISTING 200A/3P BLANK SPACE TO BE PREPPED FOR NEW 100A/2P CIRCUIT
BREAKER. MATCH EXISTING DISTRIBUTION BOARD AIC RATINGS.
PROVIDE NEMA 4 DISCONNECT MOUNTED TO AN UNI-STRUT SYSTEM. REFER
TO DIAGRAM 1 ON SHEET E8.0 FOR ADDITIONAL INFORMATION. PROVIDE
LABELING ON DISCONNECT 'SHORE POWER DISCONNECT' PER DIAGRAM 3
ON SHEET E8.0.
CONTRACTOR TO CONNECT (1) 2 AWG TO PIGTAIL PHASE A (RED), (1) 2
AWG TO PIGTAIL PHASE B (ORANGE), (1) 8 AWG GROUND TO BE TIED
TOGETHER WITH PIGTAIL GROUNDS G1, G2, G3, AND G4. REFER TO
DIAGRAM 2 ON SHEET E8.0 FOR ADDITIONAL INFORMATION.
PROVIDE A 'W3P1, CABLE ASSEMBLY W3, 7056681-501' SHORE POWER
PIGTAIL ADAPTER (OFCI). REFER TO DIAGRAM 2 ON SHEET E8.0 FOR
ADDITIONAL INFORMATION. COIL CABLE ASSEMBLY ON CABLE HOOK.
FEEDER SCHEDULE
FEEDER CONDUIT AND 75°C WIRE (COPPER) THHN/THWN
1-1/2"C RGC (#40 PVC UNDERGROUND), (2) 2 AWG, (1) 8 AWG GND
PIGTAIL CONNECTOR (BY OWNER) WITH (2) 2 AWG, (4) 8 AWG GND
102PT
FEEDER SCHEDULE NOTES
1. ALL FEEDERS SHOWN MAY NOT BE USED.
2. PROVIDE INCREASED SIZED EQUIPMENT GROUNDING CONDUCTORS LARGER THAN THOSE SHOWN WHERE
UNGROUNDED CONDUCTORS HAVE BEEN INCREASED FOR VOLTAGE DROP PER NEC 250.122(B).
3. PROVIDE INCREASED SIZED EQUIPMENT GROUNDING CONDUCTORS LARGER THAN THOSE SHOWN FOR MOTOR CIRCUITS PER NEC 250.122 & 430, BASED UPON MOTOR CIRCUIT OVERCURRENT PROTECTIVE DEVICE
RATING.
4. WHERE FEEDER HAS A SUFFIX 'U' ON SINGLE LINE DIAGRAM DO NOT PROVIDE EQUIPMENT GROUNDING
CONDUCTOR FOR UTILITY SERVICE ENTRANCE.
(E) PANELBOARD 'L1B' SCHEDULE
VOLTAGE: 208Y/120V, 3Ø, 4W MOUNTING: SURFACE CIRCUIT BREAKER DEMAND CODES
BUS (AMPS): 225A ENCLOSURE: NEMA 1 1=CONTINUOUS LOAD
MAINS: MLO BUS TYPE: COPPER 2=NON-CONTINUOUS LOAD
AIC RATING: 25,000 LOCATION: ELECT RM B241 3=RECEPTACLE LOAD
(AMPS): 225 UPSTREAM OVERCURRENT PROTECTION 4=KITCHEN LOAD
DEVICE 5=GUESTROOM LOAD
CKT BREAKER
NOTE(S)
BREAKER LOAD LOAD PHASE LOAD LOAD BREAKER BREAKER
NOTE(S)
CKT
NO. CODE TRIP POLE DESCRIPTION VA A B C VA DESCRIPTION TRIP POLE CODE NO.
1 20 1 (E) REC - VENDING 0 --- --- (E) REC - ROOF, EF-6 20 1 2
3 20 1 (E) REC - VENDING --- 0 --- (E) LTG - AH UNITS 20 1 4
5 20 1 (E) REC - VENDING --- --- 0 (E) REF-1 20 1 6
7 20 1 (E) REC - VENDING 0 --- --- (E) REC - CONF RM CLG 20 1 8
9 20 1 (E) REC - VENDING --- 0 --- (E) REC - CONF RM CLG 20 1 10
11 20 1 (E) REC - VENDING --- --- 0 (E) REC - CONF RM CLG 20 1 12
13 20 1 (E) REC - BREAK ROOM 0 --- --- (E) REC - CLASSROOM 20 1 14
15 20 1 (E) REC - BREAK ROOM --- 0 --- (E) REC - CLASSROOM 20 1 16
17 20 1 (E) REC - CONFERENCE RM --- --- 0 (E) REC - CLASSROOM 20 1 18
19 20 1 (E) REC - CONFERENCE RM 0 --- --- (E) WATER TREATMENT 20 1 20
21 20 1 (E) REC - CONFERENCE RM --- 0 --- (E) B-1 20 1 22
23 20 1 (E) REC - CORRIDOR --- --- 0 (E) B-2 20 1 24
25 20 1 (E) REC - CORRIDOR 0 --- --- (E) WH-1/WH-2 20 1 26
27 20 1 (E) REC - CORRIDOR --- 180 --- 180 (E) RECS (ADD 180VA TO 720VA) 20 1 3 28
29 20 1 (E) REC - EWC --- --- 0 (E) RECEPTS 20 1 30
31 20 1 (E) REC - RR/LOCKERS 0 --- --- (E) REC - PARKING LOT 20 1 32
33 20 1 (E) REC - RR/LOCKERS --- 0 --- (E) REC - PARKING LOT 20 1 34
35 20 1 (E) FC-1/FC-3 --- 0 (E) REC - PARKING LOT 20 1 36
37 20 1 (E) FC-2/FC-4/FC-8 0 --- --- (E) CLASSROOM 20 1 38
39 20 1 (E) EF-6 --- 0 --- (E) EQ. RACK 20 1 40
41 20 1 (E) CLASSROOM --- --- 0 (E) REC - CLASSROOM 20 1 42
0 180 0 CONNECTED KVA 0.2
NOTES: EXISTING LOAD 23.0 kva CODE 1 KVA 0.0
REMOVED LOAD 0.0 kva CODE 2 KVA 0.0 ADDED LOAD 0.2 kva CODE 3 KVA 0.2
TOTAL LOAD 23.2 kva CODE 4 KVA 0.0
64.3 A @208Y/120V CODE 5 KVA 0.0
DATE: 5/5/26 11:36 AM DEMAND LOAD (KVA) 0.2
DEMAND LOAD (A) 0.5
R
O
JE
C T N
A M
E
S H
E E
T T
IT
L E
S e a l
Revisions
05/27/2026
ATL
920.25.002.00
100% CD
N V
A R
N G
A
D D
S H
O R
E P
O W
E R
I N
F R
A F
O R
A L S
M W
O A
T L
V R
C L A
S V
E G
A S
N
V
AS
ATL
AS
E L E
C T R
IC
A
L D
IA
G
R A
M S
E8.0
3"
1"
1. NORMAL POWER - BLACK BACKGROUND, WHITE LETTERS
2. EMERGENCY POWER - RED BACKGROUND, WHITE LETTERING
NAMEPLATES ARE REQUIRED ON ALL PANELBOARD, STARTERS AND
DISCONNECT SWITCHES.
ALL PANELS SHALL BE LABELED ON INSIDE OF DOOR WITH LIST OF CIRCUITS
AND THEIR APPROPRIATE NAMES.
1-1/2 INCH FROM TOP OF
ANCHOR BOLTS TO GRADE
ENGRAVED LAMACOID,
5/32 INCH LETTERS
SELF TAPPING
SCREWS
PANELBOARD
WARNING!
Shock, Arc Flash, and Arc Blast Hazard Comply with OSHA requirements, including the following prior to working on this equipment:
· Work permit
· Pre-job safety briefing
· Qualified electrical workers trained to operate and work on this equipment
· Appropriate PPE required Failure to Comply Can Result in Injury or Death
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL
EQUIPMENT TO WARN OF ARC FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH
THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY
VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION,
ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
NOTES
PANEL "X
WA
RN
ING
Shock, Arc Flash, and Arc Blast Hazard
Comply with OSHA requirements, including the following prior to working on this equipment:
Work permit
Pre-job safety briefing
Qualifie d electrical workers tra ined to operate and work on this equipment
Appropriate PPE required
Failure to Comply Can Result in Injury or Death
STANDARD COLORS
WIDTH
HEIGHT PANEL X-XXX
225A 480/277V 3 PHASE
FED FROM X-XX-XXX
SCALE: 3
TYPICAL EQUIPMENT LABELING
N.T.S
SCALE: 1
UNI-STRUT ASSEMBLY WITH CABLE HOOK
N.T.S
SCALE: 2
'W3P1, CABLE ASSEMBLY W3, 7056681-501' SHORE POWER PIGTAIL ADAPTER REQUIREMENTS
N.T.S
CONTRACTOR TO WELD 3"
SQUARE STEEL CAP ON
POST TO PREVENT RUST.
PRIME AND PAINT GRAY
(TYPICAL OF 2)
3" SQUARE STEEL POST. PRIME AND PAINT.
SPACED TO CREATE A 36" WIDE ASSEMBLY
(TYPICAL OF 2)
1-5/8" U CHANNEL
(TYPICAL OF 4)
6" THICK CONCRETE
HOUSEKEEPING PAD. EXTEND
HORIZONTALLY 1" ON ALL
SIDES AND 3 FEET IN FRONT.
3' MIN
PVC ADAPTER
GRS CONDUITS BELOW GRADE
SHALL BE HALF LAPPED WITH
SCOTCHRAP 50 10-MIL TAPE
TO 18" ABOVE GRADE.
(2) 5/8" x 10'-0"
CU GND RODS,
INSTALL PER
NEC 250.53
" M
IN
FINISH GRADE
" O
.C
" M
IN
4" U CHANNEL
(TYPICAL OF 1)
NEMA 4 LOCKABLE HOFFMAN BOX MOUNTED ON THE REAR
NEMA 4
DISCONNECT
WEATHERPROOF DUPLEX RECEPTACLE
3M FIRE BARRIER 1003 SL SEALANT
3MU/FRD 120-18
3M FIRE BARRIER WATERTIGHT
SEALANT 1003 SL C-AJ-8075
3M INTERAM ENDOTHERMIC MAT
E-5A-4 SYSTEM NO.8
3M FIRE BARRIER
WRAP STRIP FS-195+ C-AJ-5002
3M FIRE BARRIER WRAP STRIP CS-195+,
FS-195+, MP+ PUTTY STICK C-AJ-8001
FIRE BARRIER BLOCKS/PLANKS C-AJ-8253
3M FIRE BARRIER SEALANT
IC 15WB+ W-L-3195
3M FIRE BARRIER PLUG W-L-3426
3M FIRE DAM SEALANT CP 25 WB+
C-AJ-1427
3M FIRE DAM SPRAY 200 HW-D-0020
3M FIRE BARRIER WATERTIGHT
SEALANT 100 NS HW-D-0168
3M FIRE BARRIER WATERTIGHT
SEALANT 1003 SL FLOOR TO FLOOR
JOINT ASSEMBLY FF-D-1021
3M FIRE BARRIER
SEALANT CP 25WB+ C-AJ-1551
3M FIRE BARRIER PLENUM
WRAP FA+3MU/BI 120-01
3M FIRE BARRIER BLOCKS
AND 3M FIRE BARRIER RATED
FOAM FIP 1-STEP C-AJ-1668
3M FIRE BARRIER ULTRA PLASTIC
PIPE DEVICE C-AJ-2227
3M FIRE BARRIER PUTTY SLEEVE KIT
C-AJ-3310
3M FIRE BARRIER TUCK-IN WRAP
STRIP C-AJ-2643
3M FIRE BARRIER WRAP
STRIPULTRA GS RC-1
RESTRICTING COLLAR,
ULTRA RC PACK W-L-2147
3M FIRE BARRIER PILLOW OR
3M FIRE BARRIER SELF-
LOCKING PILLOW W-L-4037
3M FIRE BARRIER
BLOCKS/PLANKS W-L-4090
3M FIRE BARRIER 3000 WT
SEALANT C-AJ-2510
3M FIRE BARRIER WATER TIGHT
SEALANT 3000 WT C-AJ-2299
3M FIRE BARRIER
CAST-IN DEVICE
F-A-5028
3M FIRE BARRIER
MOLDABLE PUTTY
PAD MPP+ CLIV
3M FIRE BARRIER SEALANT CP WB+&
PACKING MATERIAL PM 4C-AJ-5210
3M FIRE BARRIER
PASS THROUGH
DEVICE C-AJ-3250
SCALE: 4
APPLICATIONS - COMMERCIAL
N.T.S
4" SCH. 40 STEEL PIPE, 6'-0"
LONG, CONCRETE FILLED
W/CONC. CAP. SHOP
PRIME & FIELD PAINT WITH
"CAUTION YELLOW" OSHA
SAFETY PAINT.
REFLECTOR TAPE
CONCRETE - 3000 PSI @ 28
DAYS
VEHICLE PROTECTION BARRIER
SHALL NOT BE FURTHER THEN 18"
FROM THE BASE OF THE EVSE
CONCRETE SLAB
2"
3' 3"
3"
1'
TYPICAL FIRE PENETRATION
SCALE: 5
SLAB ON GRADE DIAGRAM
N.T.S
VEHICULAR PROTECTION BOLLARD -
(BY NVARG,
INSTALLED ON
THE VEHICLE,
NO WORK BY
CONTRACTOR)
OFCI
(BY NVARG,
INSTALLED BY
CONTRACTOR)
OFCI
(BY NVARG,
INSTALLED BY
CONTRACTOR)
OFCI
(BY NVARG,
INSTALLED BY
CONTRACTOR)
(BY NVARG,
INSTALLED ON
THE VEHICLE,
NO WORK BY
CONTRACTOR)
3" SQUARE STEEL POST.
PRIME AND PAINT.
SPACED TO CREATE A
36" WIDE ASSEMBLY
(TYPICAL OF 2)
1-5/8" U CHANNEL
(TYPICAL OF 4)
6" THICK CONCRETE
HOUSEKEEPING PAD. EXTEND
HORIZONTALLY 1" ON ALL
SIDES AND 3 FEET IN FRONT.
3' MIN
PVC ADAPTER
GRS CONDUITS BELOW GRADE
SHALL BE HALF LAPPED WITH
SCOTCHRAP 50 10-MIL TAPE
TO 18" ABOVE GRADE.
(2) 5/8" x 10'-0"
CU GND RODS,
INSTALL PER
NEC 250.53
" M
IN
FINISH GRADE
" O
.C
CABLE HOOK, LEVITON 'EHOOK' OR APPROVED
EQUAL MOUNTED TO U-CHANNEL FOR SUPPORT
4" U CHANNEL
(TYPICAL OF 1)
NEMA 4 LOCKABLE 30"x30"x10" HOFFMAN BOX (BY CONTRACTOR)
TO HOUSE 'W3P1, CABLE ASSEMBLY W3, 7056681-501 OFCI'
REAR ELEVATION FRONT ELEVATION
CONTRACTOR TO WELD 3"
SQUARE STEEL CAP ON
POST TO PREVENT RUST.
PRIME AND PAINT GRAY
(TYPICAL OF 2)
NOTE: CONTRACTOR TO CONFIRM FINAL UNI-STRUT ASSEMBLY WIDTH WITH FINAL PRODUCT SELECTIONS PRIOR TO INSTALLATION OF UNI-STRUT ASSEMBLY.
6" OPENING ON THE BOTTOM
WITH A TWISTLOCK CAP CHAINED
TO THE BOTTOM OF THE
ENCLOSURE
2" CONDUIT BETWEEN
THE TWO WITH
WEATHERPROOF OF
LOCKNUTS AND SEALS
| Sheets and Views |
| G0.0 ELECTRICAL COVER PAGE |
| E0.0 ELECTRICAL COVER SHEET |
| E0.5 ELECTRICAL SITE PLAN |
| E1.1 ELECTRICAL ENLARGED POWER PLAN |
| E5.0 ELECTRICAL SINGLE LINE DIAGRAM |
| E8.0 ELECTRICAL DIAGRAMS |
| 702.296.1087 | |
| 2026-07-08T13:33:27-0700 | |
| Las Vegas, NV | |
| Stephen M Hall | |
| I have reviewed this document |
File details come from the government source that posted it. Updated .