154B-WPC_512_305_1_-_-.pdf

PDF 349 KB Posted

Attached to
USCGC Joseph Gerczak Dockside HVAC Clean & Inspect
Solicitation number
70Z03426QHONO1002
Issued by

About this file

This is an HVAC Equipment List for the 154-foot Fast Response Cutter (FRC) Sentinel Class vessel built by Bollinger Shipyards Lockport, LLC under U.S. Coast Guard Contract No. HSCG23-16-C-AFR625. The document, designated CDRL 085-511 and U.S.C.G. Document No. 154B-WPC-512-305, provides comprehensive technical specifications for heating, ventilation, and air conditioning systems applicable to Hull 33 and subsequent vessels in the class.

The equipment lists include 23 fans with specified airflow ratings (ranging from 120 to 10,000 CFM), seven cooling coils with total connected cooling capacity of 21.81 tons, and 37 heater units with electrical and convection heating elements distributed throughout accommodation, operational, engine, and auxiliary spaces. The document details two air conditioning plants (C-1 at 18.97 tons and C-2 at 5.86 tons) utilizing piston compressors located in the engine room. Additional specifications cover 80 closures, dampers, and valves including fire dampers, watertight closures, and smoke dampers; seven installed filters in standard HVAC configurations; and zero service filter quantities. The heater list identifies specific thermostat settings, temperature control arrangements, and spaces heated, with the majority of accommodation spaces maintained at 64.4°F. The document references Drawing 154B-WPC-512-302 for HVAC control system details and complies with NAVSEA T9500-AA-PRO-130 design practices. All data are marked with limited rights and restricted export classification under the Arms Export Control Act.

View the file

Other files

File Type Posted
154-WPC_512_201_1_-_-.pdf PDF
154-WPC_512_301_1_-_B.pdf PDF
154B-WPC_512_301_1_-_A.pdf PDF
SFLC-Std-Spec-0000-(2022).pdf PDF
SFLC-Std-Spec-5100-(2022).pdf PDF
Wage Determination Honolulu.txt TXT text file
SF1449.pdf PDF
154B-WPC_512_201_1_-_C.pdf PDF
154-WPC_512_305_1_-_-.pdf PDF
WI 6 Spec.pdf PDF
dockside SOW.docx DOCX document
Fixed_Price_Service_FAR_HSAR_Clauses.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

154 FT FAST RESPONSE CUTTER (FRC)

SENTINEL CLASS

CDRL 085-511

HVAC Equipment List

U.S.C.G. Document No. 154B-WPC-512-305

Contact No. HSCG23-16-C-AFR625

Bollinger Shipyards Lockport, LLC

8365 Highway 308 South

Lockport, LA 70374

This document requires Government approval

Distribution Statement F Further dissemination only as directed by Commandant (CG-9324) or higher Coast Guard authority.

Limited Rights Notice

(a) These data are submitted with limited rights under Government Contract number: HSCG23-16-C-AFR625 for the Fast Response Cutter (FRC). These data may be reproduced and used by the Government with the express limitation that they will not, without written permission of the Contractor, be used for purposes of manufacture nor disclosed outside the Government; except that the Government may disclose these data outside the Government for the following purposes, provided that the Government makes such disclosure subject to prohibition against further use and disclosure:

• The operation, maintenance, diagnosis, and repair of the Fast Response Cutter by the Coast Guard or support contractors.

• The development of operations, maintenance, diagnosis, and repair documentation (traditional and electronic) in support of the FRC system by the Coast Guard or support contractors.

• The training of operators, maintainers, diagnosticians, and repairers of the FRC system by the Coast Guard or support contractors.

• The development of training materials (traditional and electronic) in support of the FRC system by the Coast Guard or support contractors.

(b) This Notice shall be marked on any reproduction of these data, in whole or in part.

End of Notice

Warning - This document contains technical data whose export is restricted by the Arms Export-Control Act (Title 22, U.S.C., Sec 2751, et. seq.)

or the Export Administration Act of 1979, as amended, Title 50, U.S.C. App 2401 et. seq. Violations of these export laws are subject to severe criminal penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.

PREPARED BY: D. L. Stewart /S/ APPROVED BY: Kyle Tyson /S/ 3/3/20 USCG APPROVED BY: LT Sam Bacon /S/

Fast Response Cutter 154B-WPC-512-305 Rev -

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

ii

REVISION HISTORY

Revision Description Date Initials & Org

- Initial Release 3/3/20

4/1/20

DLS /S/

KT /S/

SGB /S/

HULL APPLICABILITY

Applicable Hulls Hull 33 and on.

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any iii

TABLE OF CONTENTS

REVISION HISTORY .......................................................................................... II

HULL APPLICABILITY ..................................................................................... II

1.0 PURPOSE

2.0 REFERENCES

3.0 HVAC EQUIPMENT LISTS

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any

1.0 PURPOSE

The purpose of this CDRL is to provide the HVAC Equipment Lists as required by Reference (1). The “Cooling Coil List” and “Heater List” both indicate temperature control arrangement sketches are to be provided. The drawing has been developed and added as a reference to this submittal, Reference (2); as the drawing provides details, it is noted in both lists for the arrangement “sketches”.

2.0 REFERENCES

1. NAVSEA T9500-AA-PRO-130, NAVSEA Design Practices and Criteria Manual for Air Conditioning, Ventilation, and Heating of Surface Ships (DPM)

2. Drawing 154B-WPC-512-302, HVAC Control System

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

3.0 HVAC EQUIPMENT LISTS

Fan List

FAN ITEM NO. SYS NO. FAN NO. FAN LCTN DESIGN CFM PT SIZE HP D C

CLASS

SH'P AND

NAVSEA

DWG NO.

MOTOR

CONTR

LCTN

MASTER

SWITCH

LCTN

SPECIAL

FEATURES

SPACES SERVED

[In wg] 1 AC-1 1-25-1 1-24-1-Q 3014 10.58 N/A 8.45 W N/A N/A N/A None *1) Accomodation 2 FCU-1 01-23-1 01-19-0-C 607 N/A N/A 0.315 W N/A N/A N/A None Pilot house (01-19-0-C) 3 FCU-1 01-21-2 01-19-0-C 190 N/A N/A 0.087 W N/A N/A N/A None Pilot house (01-19-0-C) 4 FCU-1 01-21-1 01-19-0-C 190 N/A N/A 0.087 W N/A N/A N/A None Pilot house (01-19-0-C) 5 FCU-2 2-22-1 2-23-3-Q 905 N/A N/A 0.331 W N/A N/A N/A None C4ISR (2-23-3-Q) 6 FCU-3 1-22-2 1-18-2-Q 265 N/A N/A 0.107 Z N/A N/A N/A None Galley (1-18-2-Q) 7 RS - 1 1-23-11 1-24-1-Q 2200 2.84 N/A 1.88 W N/A N/A N/A None *2) Return air accomodation 8 ES - 1 1-27-1 1-17-0-L 401 2.49 N/A 1.48 W N/A N/A N/A None *3) Exhaust from toilets 9 ES - 2 1-21-2 1-18-2-Q 450 2.33 N/A 0.50 Z N/A N/A N/A None Exhaust from Galley (1-18-2-Q)

10 ES - 3 3-9-2 3-3-0-E 329 0.64 N/A 0.50 W N/A N/A N/A None Exhaust from Fwd Aux (3-3-0-E) 11 ES - 4 1-11-2 1-10-0-E 161 1.12 N/A 0.07 W N/A N/A N/A None Exhaust from EDG (1-10-0-E) 12 ES - 5 1-28-2 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Exhaust from ER (3-27-0-E) 13 ES - 6 1-28-1 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Exhaust from ER (3-27-0-E) 14 SS - 7 1-32-2 1-28-0-Q 1457 1.71 N/A 0.77 W N/A N/A N/A None Recirc to Exhaust Comp (1-28-0-Q) 15 SS - 8 1-32-1 1-28-0-Q 1457 1.71 N/A 0.77 W N/A N/A N/A None Recirc to Exhaust Comp (1-28-0-Q) 16 SS - 9 1-34-2 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Supply to ER (3-27-0-E) 17 SS - 10 1-34-1 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Supply to ER (3-27-0-E) 18 ES - 11 1-37-2 3-36-0-E 6259 0.97 N/A 2.41 W N/A N/A N/A None Exhaust from Gen Room (3-36-0-E) 19 SS - 12 1-37-1 3-36-0-E 7379 0.97 N/A 2.41 W N/A N/A N/A None Supply to Gen Room (3-36-0-E) 20 ES - 13 3-40-2 3-40-2-E 120 0.32 N/A 0.03 W N/A N/A N/A None Exhaust from Steering Room (3-40-2-E) 21 ES - 14 3-40-1 3-40-1-E 120 0.32 N/A 0.03 W N/A N/A N/A None Exhaust from Steering Room (3-40-1-E) 22 ES - 15 1-27-1 1-28-0-Q 996 1.00 N/A 1.50 W N/A N/A N/A None Exhaust from Exhaust Comp (1-28-0-Q) 23 ES - 16 1-21-2 1-28-0-Q 996 1.00 N/A 1.50 W N/A N/A N/A None Exhaust from Exhaust Comp (1-28-0-Q)

FAN LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

*1) Accomodation *3) Exhaust from toilets Pilot House 01-19-0-C Toilet Main deck front 1-12-0-L XO Stateroom 1-12-2-L Toilet Main deck 1-15-1-L CO Cabin 1-12-1-L Toilet Main deck between AC and Mess 1-23-1-L OPS CPO STRM 1-15-2-L Toilet Second deck next to C4ISR 2-23-1-L Office 1-16-1-A HEAD Second deck front PS 2-12-2-L Galley 1-18-2-Q HEAD Second deck front PS 2-13-2-L Mess 1-17-0-Q HEAD Second deck front PS 2-14-2-L Cabin 2-10-2-L SHOWER Second deck front SB 2-12-1-L Cabin 2-15-2-L SHOWER Second deck front SB 2-13-1-L Cabin 2-15-1-L SHOWER Second deck front SB 2-14-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L *2) Return air accomodation EPO Stateroom 2-23-2-L Passageway Main deck aft. 1-23-0-L C4ISR 2-23-3-Q Passageway Main deck front 1-15-0-L Cabin 2-10-1-L Passageway Second deck front 2-10-0-L Climate Controlled Store Room 2-23-4-A Passageway Second deck Middle 2-17-0-L

C4ISR Equipment Room 2-23-3-Q

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Cooling Coil List

COIL

ITEM NO

COIL NO RECIRC

SYS NO.

TYPE tW tC Hsr/Htr Hsc/Htc TNS t1 t2 CFM CFM BY-

PASS

CFM

REPL AIR

PL

SIZE

FLOW

GPM DC

CLASS

TEMP. CONTROL

ARRGT

AC

PLANT

NO.

SPACES SERVED REMARKS

[In wg] 1 1-25-1 AC-1 DX N/A 70 0.799 0.622 16.45 80.8 66.6 3014 N/A 814 2.13 N/A N/A W 154B-WPC-512-302 C-1 *1) Accomodation 2 1-22-2 FCU-3 DX N/A 80 0.88 0.883 0.92 80 62 265 N/A 0 N/A N/A N/A Z 154B-WPC-512-302 C-1 Galley (1-18-2-Q) 3 1-8-2 GC-1 DX N/A 85 1 N/A 0.13 N/A N/A N/A N/A 0 N/A N/A N/A W 154B-WPC-512-302 C-1 Magazine (1-0-8-M) 4 01-23-1 FCU-1 DX N/A 70 0.95 0.958 1.8 69.8 55 607 N/A 0 N/A N/A N/A W 154B-WPC-512-302 C-2 Pilot house (01-19-0-C) 5 01-21-2 FCU-1 DX N/A 70 0.95 0.958 0.38 69.8 55 190 N/A 0 N/A N/A N/A W 154B-WPC-512-302 C-2 Pilot house (01-19-0-C) 6 01-21-1 FCU-1 DX N/A 70 0.95 0.958 0.38 69.8 55 190 N/A 0 N/A N/A N/A W 154B-WPC-512-302 C-2 Pilot house (01-19-0-C) 7 2-22-1 FCU-2 DX N/A 80 1 1 2.67 80 60 905 N/A 0 N/A N/A N/A W 154B-WPC-512-302 C-2 C4ISR (2-23-3-Q)

*1) Accomodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-0-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

COOLING COIL LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Heater List

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

COOL HEAT REQ'D ACT

[C] [F] [C] [F] [kW] [kW] [In wg] 1 1-25-1 AC-1 Electrical P 3014 8.1 46.6 12 53.6 6.9 7.2 64.4 0.209 W 154B-WPC-512-302 N/A N/A N/A *1)Accomodation 2 01-23-1 FCU-1 Electrical R 607 21 69.8 N/A N/A 0.741 1 64.4 N/A W N/A N/A 64.4 Pilot house (01-19-0-C) 3 01-21-2 FCU-1 Electrical R 190 21 69.8 N/A N/A 0.325 0.425 64.4 N/A W N/A N/A 64.4 Pilot house (01-19-0-C) 4 01-21-1 FCU-1 Electrical R 190 21 69.8 N/A N/A 0.325 0.425 64.4 N/A W N/A N/A 64.4 Pilot house (01-19-0-C) 5 1-25-3 AC-1 Electrical N/A 3014 12 53.6 26.2 79.16 7.5 7.5 N/A 0.020 W 154B-WPC-512-302 N/A N/A N/A *1) Humidifying (Acc.)

6 1-13-2 AC-1 Electrical R 135 12 53.6 22.2 71.96 0.748 0.8 64.4 0.595 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 XO Stateroom 201 (1-12-2-L)

7 1-13-1 AC-1 Electrical R 165 12 53.6 20.2 68.36 0.774 0.8 64.4 0.885 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 CO Cabin 202 (1-12-1-L)

8 1-15-2 AC-1 Electrical R 125 12 53.6 22.2 71.96 0.725 0.8 64.4 0.511 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 OPS CPO STRM 203 (1-15-2-L)

9 1-16-1 AC-1 Electrical R 104 12 53.6 19.6 67.28 0.452 0.4 64.4 0.353 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Office 204 (1-16-1-A)

10 1-18-1 AC-1 Electrical R 210 12 53.6 18.2 64.76 0.745 1.2 64.4 1.261 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Mess 206 (1-17-1-Q)

11 1-20-1 AC-1 Electrical R 211 12 53.6 18.2 64.76 0.745 1.2 64.4 1.261 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Mess 206 (1-17-1-Q)

12 1-21-1 AC-1 Electrical R 210 12 53.6 18.2 64.76 0.745 0.8 64.4 1.261 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Mess 206 (1-17-1-Q)

13 1-25-1 AC-1 Electrical R 211 12 53.6 18.2 64.76 0.745 0.8 64.4 1.261 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Mess 206 (1-17-1-Q)

14 2-10-2 AC-1 Electrical R 102 12 53.6 21.5 70.7 0.551 0.8 64.4 0.341 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 301 (2-10-2-L)

15 2-15-2 AC-1 Electrical R 99 12 53.6 21.7 71.06 0.55 0.8 64.4 0.321 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 302 (2-15-2-L)

16 2-15-1 AC-1 Electrical R 99 12 53.6 21.4 70.52 0.533 0.8 64.4 0.321 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 303 (2-15-1-L)

17 2-17-2 AC-1 Electrical R 165 12 53.6 22.3 72.14 0.971 1.2 64.4 0.772 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 304 (2-17-2-L)

18 2-21-1 AC-1 Electrical R 172 12 53.6 21.7 71.06 0.949 1.2 64.4 0.845 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 305 (2-20-1-L)

19 2-21-2 AC-1 Electrical R 94 12 53.6 22.7 72.86 0.574 0.8 64.4 0.288 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 306 (2-21-2-L)

20 2-17-1 AC-1 Electrical R 89 12 53.6 22.8 73.04 0.549 0.8 64.4 0.261 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 307 (2-17-1-L)

21 2-24-2 AC-1 Electrical R 164 12 53.6 21.6 70.88 0.901 1.2 64.4 0.766 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 EPO Stateroom 308 (2-23-2-L)

22 2-10-1 AC-1 Electrical R 107 12 53.6 21.3 70.34 0.565 0.8 64.4 0.369 W 154B-WPC-512-302 N/A Eberle RTR-E

3521/16 A 64.4 Cabin 310 (2-10-1-L) 23 1-12-2 CE-1 Convection N/A N/A N/A N/A N/A N/A 0.307 0.4 75 N/A Z N/A N/A N/A N/A Head (1-12-0-L) 24 1-15-1 CE-2 Convection N/A N/A N/A N/A N/A N/A 0.423 0.8 75 N/A Z N/A N/A N/A N/A Head (1-15-1-L) 25 1-23-1 CE-3 Convection N/A N/A N/A N/A N/A N/A 0.371 0.8 75 N/A Z N/A N/A N/A N/A Head (1-23-1-L) 26 2-12-2 CE-4 Convection N/A N/A N/A N/A N/A N/A 0.286 0.4 75 N/A Z N/A N/A N/A N/A Head (2-12-2-L) 27 2-13-2 CE-6 Convection N/A N/A N/A N/A N/A N/A 0.288 0.4 75 N/A Z N/A N/A N/A N/A Head (2-13-2-L) 28 2-14-2 CE-8 Convection N/A N/A N/A N/A N/A N/A 0.285 0.4 75 N/A Z N/A N/A N/A N/A Head (2-14-2-L) 29 2-23-1 CE-10 Convection N/A N/A N/A N/A N/A N/A 0.551 0.8 75 N/A Z N/A N/A N/A N/A Head (2-23-1-L) 30 1-10-2 CE-11 Convection N/A N/A N/A N/A N/A N/A 2.35 2.50 40 N/A Z N/A N/A N/A N/A EDG Room (1-10-0-E) 31 3-5-2 CE-12 Convection N/A N/A N/A N/A N/A N/A 3.00 4.00 39.1 N/A Z N/A N/A N/A N/A Fwd Aux (3-3-0-E) 32 3-27-1 CE-13 Convection N/A N/A N/A N/A N/A N/A 8.00 50 N/A Z N/A N/A N/A N/A Enigne Room (3-27-0-E) 33 3-32-2 CE-14 Convection N/A N/A N/A N/A N/A N/A 8.00 50 N/A Z N/A N/A N/A N/A Enigne Room (3-27-0-E) 34 3-36-2 CE-15 Convection N/A N/A N/A N/A N/A N/A 2.25 40 N/A Z N/A N/A N/A N/A Generator Room (3-36-0-E) 35 3-39-1 CE-16 Convection N/A N/A N/A N/A N/A N/A 2.25 40 N/A Z N/A N/A N/A N/A Generator Room (3-36-0-E) 36 3-45-1 CE-17 Convection N/A N/A N/A N/A N/A N/A 1.18 1.50 35 N/A Z N/A N/A N/A N/A Steering Gear Room (3-40-1-E) 37 3-45-2 CE-18 Convection N/A N/A N/A N/A N/A N/A 1.18 1.50 35 N/A Z N/A N/A N/A N/A Steering Gear Room (3-40-2-E)

13.00

3.64

HEATER LIST

THERMO

STAT

SETTING

POWER

SPACES HEATEDTEMP CTRL ARRGMT

D C

CLASSTYPE

ENTRANCE

TEMP t

EXIT

TEMP

THERMOSTAT

TYPE

TYPE OF

CONTROL

VALVE

SYS NO.

ENTRANCE

TEMP

Siemens RDG

EXIT

TEMP PL

HTR ITEM

NO. USE SIZE

CFM

HTR NO.

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

*1) Accomodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-1-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Installed Filter List

SIZE N POWER CLEAN DIRTY

[kW]

1 AC-1 Standard HVAC room 20x35 1 N/A N/A N/A 0.19 0.40 2 FCU-1 Standard Pilot house 30x10 2 N/A N/A N/A N/A N/A 3 FCU-1 Standard Pilot house 23x8 1 N/A N/A N/A N/A N/A 4 FCU-1 Standard Pilot house 23x8 1 N/A N/A N/A N/A N/A 5 FCU-2 Standard C4ISR 30x10 2 N/A N/A N/A N/A N/A 6 FCU-3 Standard Galley 35x8 1 N/A N/A N/A N/A N/A 7 SS-12 Standard Gen Room 29x29 1 N/A N/A N/A N/A N/A

*1) Accomodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-1-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

ESP PL SPACES SERVED

INSTALLED FILTER LIST

SIZE NFLTR

ITEM NO.

SYSTEM

NO. TYPE FILTER

LCTN

*1) Accomodation Pilot house (01-19-0-C) Pilot house (01-19-0-C) Pilot house (01-19-0-C)

Galley (1-18-2-Q) Generator Room (3-36-0-E)

C4ISR (2-23-3-Q)

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Service Filter List

0 10 10

QUANTITY 0 0 0 0 0 0 0 0 0 0 0 0

SERVICE FILTER LIST

13AF HEPA CBR REMARKSSIZE 10AF 11AF 12AF 14AF 15AF 16AF

ESP

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Total Connected Load

N TYPE SIZE

TOTAL

TONS

C-1 1 Cooling coil AC N/A 16.45 N/A N/A N/A W C-1 1 Fan Coil Unit N/A 0.92 N/A N/A N/A Z C-1 1 Gravity Coil N/A 0.13 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 1.80 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 0.38 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 0.38 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 2.67 N/A N/A N/A W

N/A N/A N/A N/A 21.81 N/A N/A N/A W N/A N/A N/A N/A 0.92 N/A N/A N/A Z

FCU-2

Total load Total load

FCU-1B

FCU-3

t1 t2

FCU-1A

FCU-1B

AC-1

GC-1

TOTAL CONNECTED LOAD - SUMMARY LIST

TOTAL

GPM

HEAT TRANSFER EQUIP.

APPLICATION NOTESD C

CLASS

CONNECTED

TO PLANT

NO.

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Air Conditioning Plant Summary

LOCATION N TN HP tc te t1 t2 t SIZE HP P N SIZE HP P C-1 Piston compressor Engine room 1 18.97 27.8 114 35.6 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A C-2 Piston compressor Engine room 1 5.86 8.2 110 35.6 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

AIR CONDITIONING PLANTS SUMMARY LIST

PLANT

NO. TYPE

REFRIGERATING MACHINES C W PUMPS S W PUMPS

NOTES

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Closures, Dampers and Valve List

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

ITEM NO. VLV NO. SYS NO. TYP TYP OF

CNTL

ACTUATOR SIZE

(mm)

CFM LOCATION DC

CLASS

PWR

REQ'S

[W]

SPECIAL

FEATURES

SPACES SERVED

1 1-24-1 AC-1 Fire Damper Automatic Motorized 100 164 HVAC Equipment room (1-24-1-Q) W 8 None Supply Galley (1-18-2-Q) 2 1-25-5 AC-1 Shut-off damper Automatic Motorized 300x400 792 HVAC Equipment room (1-24-1-Q) W 1W None Fresh air AC-1 3 01-28-1 ES-1 Closure Manual Manual 200 401 Aft of Pilot House (01-19-0-C) W N/A None Sanitary exhaust outlet 4 1-21-2 ES-2 Shut-off damper Automatic Motorized 200x200 450 Galley (1-18-2-Q) W 1W None Exhaust Galley (1-18-2-Q) 5 1-17-2 ES-2 Shut-off damper Automatic Motorized 200x200 286 Galley (1-18-2-Q) W 1W None Supply Galley (1-18-2-Q) 6 01-26-1 AC-1 Smoke damper Manual Manual 100 774 Pilot House (01-19-0-C) Y N/A None Pilot House (01-19-0-C) 7 1-23-9 AC-1 Smoke damper Manual Manual 160 554 Head (1-23-1-L) W N/A None *2) Accomodation 8 2-25-3 AC-1 Smoke damper Manual Manual 100 246 C4ISR (2-23-3-Q) Y N/A None C4ISR (2-23-3-Q) 9 2-25-1 AC-1 Smoke damper Manual Manual 125 246 Passageway (2-25-0-L) W N/A None *1) Accomodation 10 1-24-7 RS-1 Regulation Damper Manual Manual 125 208 HVAC Equipment room (1-24-1-Q) W N/A None Passage (1-23-0-L) 11 1-24-3 RS-1 Regulation Damper Manual Manual 250 1022 HVAC Equipment room (1-24-1-Q) W N/A None Passage (1-23-0-L) 12 1-17-3 RS-1 Regulation Damper Manual Manual 160 521 Office (1-16-1-A) W N/A None Passage (2-17-0-L) 13 1-16-3 RS-1 Regulation Damper Manual Manual 125 197 Office (1-16-1-A) W N/A None Passage (2-10-0-L) 14 1-22-7 AC-1 Regulation Damper Manual Manual 160 780 Mess (1-17-0-Q) W N/A None *3) Accomodation 15 1-22-3 AC-1 Regulation Damper Manual Manual 160 525 Mess (1-17-0-Q) W N/A None *4) Accomodation 16 1-22-1 AC-1 Regulation Damper Manual Manual 100 211 HVAC Equipment room (1-24-1-Q) W N/A None Mess (1-17-0-Q) 17 1-24-5 RS-1 Smoke damper Manual Manual 125 255 HVAC Equipment room (1-24-1-Q) W N/A None *6) Accomodation 18 1-17-1 RS-1 Smoke damper Manual Manual 160 521 Office (1-16-1-A) W N/A None Passage (2-17-0-L) 19 1-25-1 AC-1 Smoke damper Manual Manual 125 321 HVAC Equipment room (1-24-1-Q) W N/A None *5) Accomodation 20 1-27-1 ES-1 Shut-off damper Automatic Motorized 200x200 401 Passage (1-23-0-L) W 1W None *7) Toilets 21 1-3-1 NS-1 Watertight Closure Manual Manual 194 329 Main Deck (1-A-0-X) W N/A None Fwd Aux (3-3-0-E) 22 1-9-2 NS-1 Watertight Closure Manual Manual 194 329 Main Deck (1-A-0-X) W N/A None Fwd Aux (3-3-0-E)

23 1-10-2 NS-2 Watertight Closure Manual Manual 1005x1665 9406 S 3475 W Main Deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

24 1-10-2 NS-2 Demister Manual Manual 686x1676 9406 S 3475 W Main Deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

25 1-10-2 NS-2 Fire Damper Automatic Motorized 686x1280 9406 S 3475 W EDG Room (1-10-0-E) W 7.2 None EDG Room (1-10-0-E)

26 1-10-1 NS-2 Fire Damper Automatic Motorized 829x1508 9000 S 3069 W EDG Room (1-10-0-E) W 7.2 None EDG Room (1-10-0-E)

27 1-10-1 NS-2 Watertight Closure Manual Manual 715x1600 9000 S 3069 W Main Deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

28 01-10-2 ES-4 Watertight Closure Manual Manual 100 161 01 Deck (01-08-X) W N/A None EDG Room (1-10-0-E) 29 1-28-2 ES-5 Watertight Closure Manual Manual 905x1018 10000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 30 1-28-2 ES-5 Demister Manual Manual 801x912 10000 1-28-2-E W N/A None ER (3-27-0-E) 31 1-28-2 ES-5 Fire Damper Automatic Motorized 648x648 10000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E) 32 1-28-1 ES-6 Watertight Closure Manual Manual 905x1018 10000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 33 1-28-1 ES-6 Demister Manual Manual 801x912 10000 1-28-1-E W N/A None ER (3-27-0-E) 34 1-28-1 ES-6 Fire Damper Automatic Motorized 648x648 10000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E) 35 1-34-2 SS-9 Watertight Closure Manual Manual 1017x1254 10000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 36 1-34-2 SS-9 Demister Manual Manual 838x1062 10000 1-34-2-E W N/A None ER (3-27-0-E) 37 3-34-2 SS-9 Fire Damper Automatic Motorized 648x648 10000 ER (3-27-0-E) W 7.2 None ER (3-27-0-E) 38 1-34-1 SS-10 Watertight Closure Manual Manual 1017x1254 10000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 39 1-34-1 SS-10 Demister Manual Manual 838x1062 10000 1-34-1-E W N/A None ER (3-27-0-E) 40 3-34-1 SS-10 Fire Damper Automatic Motorized 648x648 10000 ER (3-27-0-E) W 7.2 None ER (3-27-0-E)

CLOSURES, DAMPERS, AND VALVE LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

41 1-38-2 ES-11 Watertight Closure Manual Manual 1011x1011 6259 Main Deck (1-A-0-X) W N/A None Generator Room (3-36-0-E) 42 1-38-2 ES-11 Demister Manual Manual 814x876 6259 1-37-2-E W N/A None Generator Room (3-36-0-E) 43 3-38-2 ES-11 Fire Damper Automatic Motorized 648x648 6259 Generator Room (3-36-0-E) W 7.2 None Generator Room (3-36-0-E) 44 1-38-1 SS-12 Watertight Closure Manual Manual 1011x1011 7379 Main Deck (1-A-0-X) W N/A None Generator Room (3-36-0-E) 45 1-38-1 SS-12 Demister Manual Manual 814x876 7379 1-37-1-E W N/A None Generator Room (3-36-0-E) 46 3-38-1 SS-12 Fire Damper Automatic Motorized 648x648 7379 Generator Room (3-36-0-E) W 7.2 None Generator Room (3-36-0-E) 47 1-40-2 NS-3 Watertight Closure Manual Manual 146 120 Main Deck (1-A-0-X) W N/A None Steering Gear Room (3-40-2-E) 48 1-43-2 NS-3 Watertight Closure Manual Manual 146 120 Main Deck (1-A-0-X) W N/A None Steering Gear Room (3-40-2-E) 49 1-40-1 NS-4 Watertight Closure Manual Manual 146 120 Main Deck (1-A-0-X) W N/A None Steering Gear Room (3-40-1-E) 50 1-43-1 NS-4 Watertight Closure Manual Manual 146 120 Main Deck (1-A-0-X) W N/A None Steering Gear Room (3-40-1-E) 51 1-26-1 AC-1 Smoke damper Manual Manual 100 227 Passage (1-23-0-L) W N/A None Pilot House (01-19-0-C) 52 1-25-5 RS-1 Demister Manual Manual 406x483 810 Main Deck (1-A-0-X) W N/A None HVAC Equipment room (1-24-1-Q) 53 1-21-4 RS-1 Demister Manual Manual 305x330 450 Main Deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 54 1-17-4 RS-1 Demister Manual Manual 254x330 286 Main Deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 55 1-25-7 RS-1 Watertight Closure Manual Manual 590x390 792 Main Deck (1-A-0-X) W N/A None HVAC Equipment room (1-24-1-Q) 56 1-17-6 RS-1 Watertight Closure Manual Manual 390x290 450 Main Deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 57 1-21-6 RS-1 Watertight Closure Manual Manual 390x290 286 Main Deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 58 1-26-3 AC-1 Regulation Damper Manual Manual 100 227 Passage (1-23-0-L) W N/A None Pilot House (01-19-0-C) 59 1-23-3 ES-1 Smoke damper Manual Manual 100 66 Head (1-23-1-L) W N/A None Head (1-23-1-L) 60 1-17-5 AC-1 Smoke damper Manual Manual 160 521 Office (1-16-1-A) W N/A None *8) Accomodation 61 1-14-1 AC-1 Smoke damper Manual Manual 160 407 CO Cabin (1-12-1-L) W N/A None *9) Accomodation 62 1-14-5 ES-1 Smoke damper Manual Manual 160 212 CO Cabin (1-12-1-L) W N/A None *10) Toilets 63 2-14-1 ES-1 Regulation Damper Manual Manual 100 31 Shower (2-14-1-L) W N/A None Shower (2-14-1-L) 64 2-14-3 ES-1 Regulation Damper Manual Manual 125 75 Shower (2-14-1-L) W N/A None *11) Toilets 65 2-24-1 RS-1 Regulation Damper Manual Manual 100 75 C4ISR (2-23-3-Q) W N/A None C4ISR (2-23-3-Q) 66 1-14-7 ES-1 Regulation Damper Manual Manual 160 212 CO Cabin (1-12-1-L) W N/A None *10) Toilets 67 1-14-3 AC-1 Regulation Damper Manual Manual 160 407 CO Cabin (1-12-1-L) W N/A None *9) Accomodation 68 1-16-1 RS-1 Smoke damper Manual Manual 125 197 Office (1-16-1-A) W N/A None Passage (2-10-0-L) 69 1-17-7 AC-1 Smoke damper Manual Manual 160 521 Office (1-16-1-A) W N/A None *8) Accomodation 70 1-22-9 AC-1 Regulation Damper Manual Manual 160 573 Mess (1-17-0-Q) W N/A None *2) Accomodation 71 1-22-11 ES-1 Regulation Damper Manual Manual 160 292 Mess (1-17-0-Q) W N/A None *7) Toilets 72 1-22-5 RS-1 Regulation Damper Manual Manual 200 718 Head (1-23-1-L) W N/A None Passage (2-10-0-L) & (2-17-0-L) 73 1-23-5 ES-1 Regulation Damper Manual Manual 100 66 Head (1-23-1-L) W N/A None Head (1-23-1-L) 74 1-26-3 AC-1 Regulation Damper Manual Manual 100 227 Passage (1-23-0-L) W N/A None Pilot House (01-19-0-C) 75 1-28-1 ES-15 Watertight Closure Manual Manual 841x526 2000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 76 1-28-1 ES-15 Demister Manual Manual 670x359 2000 1-28-1-E W N/A None ER (3-27-0-E) 77 1-28-1 ES-15 Fire Damper Automatic Motorized 203x203 2000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E) 78 1-28-2 ES-15 Watertight Closure Manual Manual 841x526 2000 Main Deck (1-A-0-X) W N/A None ER (3-27-0-E) 79 1-28-2 ES-15 Demister Manual Manual 670x359 2000 1-28-2-E W N/A None ER (3-27-0-E) 80 1-28-2 ES-15 Fire Damper Automatic Motorized 203x203 2000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E)

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

*1) Accomodation *3) Accomodation *5) Accomodation *7) Toilets Climate Controlled Store Room 2-23-4-A XO Stateroom 1-12-2-L Eng CPO Stateroom 2-23-3-L Toilet Main deck front 1-12-0-L EPO Stateroom 2-23-2-A OPS CPO Stateroom 1-15-2-L Climate controlled storeroom 2-23-4-A Toilet Main deck 1-15-1-L

Cabin 2-17-1-L C4ISR 2-23-3-Q Toilet Main deck between AC and Mess 1-23-1-L Cabin 2-20-1-L Toilet Second deck next to C4ISR 2-23-1-L

*2) Accomodation Cabin 2-21-2-L *6) Accomodation HEAD Second deck front PS 2-12-2-L CO Cabin 1-12-1-L Cabin 2-17-2-L Climate controlled storeroom 2-23-4-A HEAD Second deck front PS 2-13-2-L Cabin 2-15-2-L C4ISR 2-23-3-Q HEAD Second deck front PS 2-14-2-L Cabin 2-10-2-L *4) Accomodation SHOWER Second deck front SB 2-12-1-L Cabin 2-10-1-L Mess 1-17-0-Q SHOWER Second deck front SB 2-13-1-L Cabin 2-15-1-L Workstation 1-16-1-A SHOWER Second deck front SB 2-14-1-L

*10) Toilets HEAD Second deck front PS 2-12-2-L

*8) Accomodation *9) Accomodation HEAD Second deck front PS 2-13-2-L *11) Toilets Cabin 2-17-1-L Cabin 2-15-2-L HEAD Second deck front PS 2-14-2-L SHOWER Second deck front SB 2-12-1-L Cabin 2-20-1-L Cabin 2-10-2-L SHOWER Second deck front SB 2-12-1-L SHOWER Second deck front SB 2-13-1-L Cabin 2-21-2-L Cabin 2-10-1-L SHOWER Second deck front SB 2-13-1-L Cabin 2-17-2-L Cabin 2-15-1-L SHOWER Second deck front SB 2-14-1-L

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

Portable Test Covers List

ITEM NO.

PORTABLE TEST

COVER NO. SYSTEM NO. SIZE LOCATION SPACES SERVED

None None None None None None

PORTABLE TEST COVERS LIST

The vessel has no portable test covers.

Revision History
Hull Applicability
1.0 Purpose
2.0 References
3.0 HVAC Equipment Lists

File details come from the government source that posted it. Updated .