This is an HVAC Equipment List for the 154-foot Fast Response Cutter (FRC) Sentinel Class vessel, prepared under U.S. Coast Guard Contract HSCG23-08-C-2FR125, CLIN 0007. The document is a Contractor Deliverable Requirements List (CDRL 085-511) submitted by Bollinger Shipyards and requires government approval.

The document provides comprehensive technical specifications for all HVAC systems installed aboard the vessel, organized into multiple equipment lists. The Fan List details 24 fans across various systems, including accommodation cooling units (2,992 CFM), exhaust fans for engine rooms (10,000 CFM capacity), and supply fans for generator rooms (7,379 CFM). The Cooling Coil List specifies seven cooling coils supporting accommodation spaces, pilot house, C4ISR equipment room, and galley facilities, with capacities ranging from 190 to 2,992 CFM and direct expansion (DX) cooling type. The Heater List identifies 23 heating elements—including electrical heaters for accommodation and reheat applications and convection heaters for machinery spaces—with power requirements from 0.25 to 8.0 kW. Supporting lists detail installed filters, closures, dampers, and valves (79 items total including fire dampers, watertight closures, and regulation dampers), the air conditioning plant summary showing three piston compressor configurations with varying capacities, and total connected cooling loads of 22.32 tons for the main system and 0.92 tons for backup systems. The vessel has no portable test covers. All systems are classified as Design Class W or Z, with equipment located throughout accommodation, engine room, generator room, and auxiliary spaces.

View the file

Other files

File Type Posted
SFLC-Std-Spec-0000-(2022).pdf PDF
SFLC-Std-Spec-5100-(2022).pdf PDF
Wage Determination Honolulu.txt TXT text file
154-WPC_512_201_1_-_-.pdf PDF
154-WPC_512_301_1_-_B.pdf PDF
154B-WPC_512_301_1_-_A.pdf PDF
SF1449.pdf PDF
154B-WPC_512_201_1_-_C.pdf PDF
WI 6 Spec.pdf PDF
dockside SOW.docx DOCX document
154B-WPC_512_305_1_-_-.pdf PDF
Fixed_Price_Service_FAR_HSAR_Clauses.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

154FT FAST RESPONSE CUTTER (FRC)

SENTINEL CLASS

CDRL 085-511

HVAC Equipment List

U.S.C.G. Document No. 154-WPC-512-305

Revision -

HSCG23-08-C-2FR125 / CLIN 0007

This document requires Government approval

Distribution Statement F

Further dissemination only as directed by Commandant (CG-936) or higher Coast Guard authority.

Limited Rights Notice

(a) These data are submitted with limited rights under Government Contract number: HSCG23-08-C-2FR125 for the Fast Response Cutter (FRC). These data may be reproduced and used by the Government with the express limitation that they will not, without written permission of the Contractor, be used for purposes of manufacture nor disclosed outside the Government; except that the Government may disclose these data outside the Government for the following purposes, provided that the Government makes such disclosure subject to prohibition against further use and disclosure:

• The operation, maintenance, diagnosis, and repair of the Fast Response Cutter by the Coast Guard or support contractors.

• The development of operations, maintenance, diagnosis, and repair documentation (traditional and electronic) in support of the FRC system by the

Coast Guard or support contractors.

• The training of operators, maintainers, diagnosticians, and repairers of the FRC system by the Coast Guard or support contractors.

• The development of training materials (traditional and electronic) in support of the FRC system by the Coast Guard or support contractors.

(b) This Notice shall be marked on any reproduction of these data, in whole or in part.

End of Notice

APPLICABLE TO: All USCG APPROVAL:

PREPARED BY: APPROVED BY: Chris Laughlin /S/ 10/25/17

Fast Response Cutter

154-WPC-512-305 Rev -

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

- ii -

Revision History

Revision Description Date

Initial Release JCL /S/ 10/25/17

TDK/S/ LT DAO

1/4/18

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

- iii -

Table of Contents

Revision History ............................................................................................................................................ ii Table of Contents .......................................................................................................................................... iii

1.0 Purpose ............................................................................................................................................ iv

2.0 References ....................................................................................................................................... iv

3.0 HVAC Equipment Lists

Fan List Cooling Coil List Heater List Installed Filter List Service Filter List Total Connected Load Air Conditioning Plant Summary Closures, Dampers and Valve List Portable Test Covers List

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

- iv -

1.0 Purpose

The purpose of this CDRL is to provide the HVAC Equipment Lists as required by Reference (1). The “Cooling Coil List” and “Heater List” both indicate temperature control arrangement sketches are to be provided. The drawing has been developed and added as a reference to this submittal, Reference (2); as the drawing provides details, it is noted in both lists for the arrangement “sketches”.

2.0 References

1. NAVSEA T9500-AA-PRO-130, NAVSEA Design Practices and Criteria Manual for Air Conditioning, Ventilation, and Heating of Surface Ships (DPM)

2. Drawing 154-WPC-512-302, HVAC Control System

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this information is subject to the restriction of the title page.

- 1 -

3.0 HVAC Equipment Lists

Fan List

FAN ITEM NO. SYS NO. FAN NO. FAN LCTN DESIGN CFM PT SIZE HP D C

CLASS

SH'P AND

NAVSEA

DWG NO.

MOTOR

CONTR

LCTN

MASTER

SWITCH

LCTN

SPECIAL

FEATURES SPACES SERVED

[In wg] 1 AC-1 1-25-1 1-24-1-Q 2992 10.58 N/A 8.85 W N/A N/A N/A None *1) Accommodation 2 FCU-1 01-23-1 01-19-0-C 527 N/A N/A 0.315 W N/A N/A N/A None Pilot house (01-19-0-C) 3 FCU-1 01-21-2 01-19-0-C 190 N/A N/A 0.087 W N/A N/A N/A None Pilot house (01-19-0-C) 4 FCU-1 01-21-1 01-19-0-C 190 N/A N/A 0.087 W N/A N/A N/A None Pilot house (01-19-0-C) 5 FCU-2 2-22-1 2-23-3-Q 891 N/A N/A 0.331 W N/A N/A N/A None C4ISR (2-23-3-Q) 6 FCU-3 1-22-2 1-18-2-Q 265 N/A N/A 0.107 Z N/A N/A N/A None Galley (1-18-2-Q) 7 RS - 1 1-24-1 1-24-1-Q 2200 2.84 N/A 1.88 W N/A N/A N/A None *2) Return air accommodation 8 ES - 1 1-27-1 1-23-0-L 401 2.49 N/A 0.50 W N/A N/A N/A None *3) Exhaust from toilets 9 ES - 2 1-21-2 1-18-2-Q 450 2.33 N/A 0.50 Z N/A N/A N/A None Exhaust from Galley (1-18-2-Q) 10 ES - 3 3-9-2 3-3-0-E 329 0.64 N/A 0.50 W N/A N/A N/A None Exhaust from Fwd Aux (3-3-0-E) 11 ES - 4 1-11-2 1-10-0-E 161 1.12 N/A 0.07 W N/A N/A N/A None Exhaust from EDG (1-10-0-E) 12 ES - 5 1-28-4 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Exhaust from ER (3-27-0-E) 13 ES - 6 1-28-3 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Exhaust from ER (3-27-0-E) 14 SS - 7 1-32-2 1-28-0-Q 1457 1.71 N/A 0.77 W N/A N/A N/A None Recirc to Exhaust Comp (1-28-0-Q) 15 SS - 8 1-32-1 1-28-0-Q 1457 1.71 N/A 0.77 W N/A N/A N/A None Recirc to Exhaust Comp (1-28-0-Q) 16 SS - 9 1-34-2 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Supply to ER (3-27-0-E) 17 SS - 10 1-34-1 3-27-0-E 10000 1.25 N/A 4.50 W N/A N/A N/A None Supply to ER (3-27-0-E) 18 ES - 11 1-37-2 1-37-2-E 6259 0.97 N/A 2.41 W N/A N/A N/A None Exhaust from Gen Room (3-36-0-E) 19 SS - 12 1-37-1 1-37-1-E 7379 0.97 N/A 2.41 W N/A N/A N/A None Supply to Gen Room (3-36-0-E) 20 ES - 13 3-40-2 3-40-2-E 120 0.32 N/A 0.03 W N/A N/A N/A None Exhaust from Steering Rm (3-40-2-E) 21 ES - 14 3-40-1 3-40-1-E 120 0.32 N/A 0.03 W N/A N/A N/A None Exhaust from Steering Rm (3-40-1-E) 22 ES - 15 1-28-1 1-28-0-Q 1300 3.28 N/A 2.00 W N/A N/A N/A None Exhaust from Exhaust Comp (1-28-0-Q) 23 ES - 16 1-28-2 1-28-0-Q 1300 3.28 N/A 2.00 W N/A N/A N/A None Exhaust from Exhaust Comp (1-28-0-Q) 24 CF - 1 2-23-1 2-23-3-Q 2200 N/A N/A 0.07 W N/A N/A N/A None C4ISR (2-23-3-Q)

FAN LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 2 -

*1) Accommodation *3) Exhaust from toilets Pilot House 01-19-0-C HEAD Main deck front 1-12-0-L XO Stateroom 1-12-2-L HEAD Main deck 1-15-1-L CO Cabin 1-12-1-L HEAD Main deck between AC and Mess 1-23-1-L OPS CPO STRM 1-15-2-L HEAD Second deck next to C4ISR 2-23-1-L Office 1-16-1-A HEAD Second deck front PS 2-12-2-L Galley 1-18-2-Q HEAD Second deck front PS 2-13-2-L Mess 1-17-0-Q HEAD Second deck front PS 2-14-2-L Cabin 2-10-2-L SHOWER Second deck front SB 2-12-1-L Cabin 2-15-2-L SHOWER Second deck front SB 2-13-1-L Cabin 2-15-1-L SHOWER Second deck front SB 2-14-1-L Cabin 2-17-2-L Cabin 2-20-1-L *2) Return air accommodation Cabin 2-21-2-L Passageway Main deck aft. 1-23-0-L Cabin 2-17-1-L Passageway Main deck front 1-15-0-L EPO Stateroom 2-23-2-L Passageway Second deck front 2-10-0-L C4ISR 2-23-3-Q Passageway Second deck Middle 2-17-0-L Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A Climate Controlled Store Room 2-23-4-A C4ISR Equipment Room 2-23-3-Q

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 3 -

Cooling Coil List

COIL

ITEM NO COIL NO RECIRC

SYS NO. TYPE tW tC Hsr/Htr Hsc/Htc THS t1 t2 CFM CFM BY

MASS

CFM

REPL AIR PL

SIZE

FLOW GPM DC

CLASS

TEMP. CONTROL

ARRGT

AC

PLANT

NO.

SPACES SERVED REMARKS

[In wg] 1 1-25-1 AC-1 DX N/A 70 0.799 0.622 16.58 80.8 66.6 2992 3590.4 793 2.78 N/A N/A W 154-WPC-512-302 C-1 *1) Accommodation 2 1-22-2 FCU-3 DX N/A 80 0.88 0.883 0.92 80 62 265 318.0 0 N/A N/A N/A Z 154-WPC-512-302 C-1 Galley (1-18-2-Q) 3 1-8-2 GC-1 DX N/A 85 1 N/A 0.13 N/A N/A N/A N/A 0 N/A N/A N/A W 154-WPC-512-302 C-1 Magazine (1-8-0-M) 4 01-23-1 FCU-1 DX N/A 70 0.95 0.958 1.58 69.8 55 527 632.4 0 N/A N/A N/A W 154-WPC-512-302 C-2 Pilot house (01-19-0-C) 5 01-21-2 FCU-1 DX N/A 70 0.95 0.958 0.38 69.8 55 190 228.0 0 N/A N/A N/A W 154-WPC-512-302 C-2 Pilot house (01-19-0-C) 6 01-21-1 FCU-1 DX N/A 70 0.95 0.958 0.38 69.8 55 190 228.0 0 N/A N/A N/A W 154-WPC-512-302 C-2 Pilot house (01-19-0-C) 7 2-22-1 FCU-2 DX N/A 80 1 1 2.63 80 60 891 1069.2 0 N/A N/A N/A W 154-WPC-512-302 C-2 C4ISR (2-23-3-Q)

*1) Accommodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-0-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

COOLING COIL LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 4 -

Heater List

COOL HEAT REQ'D ACT

[C] [F] [C] [F] [kW] [kW] [In wg] 1 1-25-1 AC-1 Electrical C 2992 7.3 45.14 26.1 78.98 32.6 36.2 64.4 0.209 W 154-WPC-512-302 N/A N/A N/A *1)Accomodation 2 01-23-1 FCU-1 Electrical R 527 21 69.8 N/A N/A 0.741 1 64.4 N/A W N/A N/A N/A N/A Pilot house (01-19-0-C) 3 01-21-2 FCU-1 Electrical R 190 21 69.8 N/A N/A 0.325 0.425 64.4 N/A W N/A N/A N/A N/A Pilot house (01-19-0-C) 4 01-21-1 FCU-1 Electrical R 190 21 69.8 N/A N/A 0.325 0.425 64.4 N/A W N/A N/A N/A N/A Pilot house (01-19-0-C) 5 1-25-3 AC-1 Electrical N/A 2992 26.1 78.98 26.2 79.16 7.5 7.5 N/A 0.020 W 154-WPC-512-302 N/A N/A N/A *1) Humidifying (Acc.)

6 1-13-2 CE-1 Convection N/A N/A N/A N/A N/A N/A 0.307 0.4 75 N/A Z N/A N/A N/A N/A Head (1-12-0-L) 7 1-15-1 CE-2 Convection N/A N/A N/A N/A N/A N/A 0.423 0.8 75 N/A Z N/A N/A N/A N/A Head (1-15-1-L) 8 1-23-1 CE-3 Convection N/A N/A N/A N/A N/A N/A 0.371 0.8 75 N/A Z N/A N/A N/A N/A Head (1-23-1-L) 9 2-23-1 CE-10 Convection N/A N/A N/A N/A N/A N/A 0.551 0.8 75 N/A Z N/A N/A N/A N/A Head (2-23-1-L) 10 2-12-2 CE-4 Convection N/A N/A N/A N/A N/A N/A 0.286 0.4 75 N/A Z N/A N/A N/A N/A Head (2-12-2-L) 11 2-12-1 CE-5 Convection N/A N/A N/A N/A N/A N/A 0.25 0.4 75 N/A Z N/A N/A N/A N/A SW (2-12-1-L) 12 2-13-2 CE-6 Convection N/A N/A N/A N/A N/A N/A 0.288 0.4 75 N/A Z N/A N/A N/A N/A Head (2-13-2-L) 13 2-13-1 CE-7 Convection N/A N/A N/A N/A N/A N/A 0.25 0.4 75 N/A Z N/A N/A N/A N/A SW (2-13-1-L) 14 2-14-2 CE-8 Convection N/A N/A N/A N/A N/A N/A 0.285 0.4 75 N/A Z N/A N/A N/A N/A Head (2-14-2-L) 15 2-14-1 CE-9 Convection N/A N/A N/A N/A N/A N/A 0.25 0.4 75 N/A Z N/A N/A N/A N/A SW (2-14-1-L) 16 1-10-2 CE-11 Convection N/A N/A N/A N/A N/A N/A 2.35 2.50 40 N/A Z N/A N/A N/A N/A EDG room (1-10-0-E) 17 3-5-2 CE-12 Convection N/A N/A N/A N/A N/A N/A 3.00 4.00 39.1 N/A Z N/A N/A N/A N/A Fwd Aux (3-3-0-E) 18 3-27-1 CE-13 Convection N/A N/A N/A N/A N/A N/A 8.00 50 N/A Z N/A N/A N/A N/A Engine Room (3-27-0-E) 19 3-32-2 CE-14 Convection N/A N/A N/A N/A N/A N/A 8.00 50 N/A Z N/A N/A N/A N/A Engine Room (3-27-0-E) 20 3-36-2 CE-15 Convection N/A N/A N/A N/A N/A N/A 2.25 40 N/A Z N/A N/A N/A N/A Generator Room (3-36-0-E) 21 3-39-1 CE-16 Convection N/A N/A N/A N/A N/A N/A 2.25 40 N/A Z N/A N/A N/A N/A Generator Room (3-36-0-E) 22 3-45-1 CE-17 Convection N/A N/A N/A N/A N/A N/A 1.18 1.50 35 N/A Z N/A N/A N/A N/A Steering Gear Room (3-40-1-E) 23 3-45-2 CE-18 Convection N/A N/A N/A N/A N/A N/A 1.18 1.50 35 N/A Z N/A N/A N/A N/A Steering Gear Room (3-40-2-E)

*1) Accomodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-0-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

HTR

ITEM NO. HTR NO. ENTRANCE

TEMP

D C

CLASS

EXIT

TEMPUSE PL

HEATER LIST

THERMO

OSTAT

SETTING

POWER

SPACES HEATEDTEMP CTRL

ARRGMTTYPE t

CFM TYPE OF

CONTROL

VALVE

THERMOSTAT

TYPE

3.64

SYS NO. ENTRANCE

TEMP

EXIT

TEMPSIZE

13.00

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 5 -

Installed Filter List

SIZE N POWER CLEAN DIRTY

[kW]

1 AC-1 Standard HVAC room 20x35 1 N/A N/A N/A 0.19 0.40 2 FCU-1 Standard Pilot house 30x10 2 N/A N/A N/A N/A N/A 3 FCU-1 Standard Pilot house 23x8 1 N/A N/A N/A N/A N/A 4 FCU-1 Standard Pilot house 23x8 1 N/A N/A N/A N/A N/A 5 FCU-2 Standard C4ISR 30x10 2 N/A N/A N/A N/A N/A 6 FCU-3 Standard Galley 35x8 1 N/A N/A N/A N/A N/A 7 SS-12 Standard Gen Room 24x24 1 N/A N/A N/A N/A N/A

*1) Accomodation Pilot House 01-19-0-C XO Stateroom 1-12-2-L CO Cabin 1-12-1-L

OPS CPO STRM 1-15-2-L

Office 1-16-1-A Galley 1-18-2-Q Mess 1-17-0-Q Cabin 2-10-2-L Cabin 2-15-2-L Cabin 2-15-1-L Cabin 2-17-2-L Cabin 2-20-1-L Cabin 2-21-2-L Cabin 2-17-1-L EPO Stateroom 2-23-2-L

C4ISR 2-23-3-Q

Cabin 2-10-1-L Climate Controlled Store Room 2-23-4-A

*1) Accomodation Pilot house (01-19-0-C) Pilot house (01-19-0-C) Pilot house (01-19-0-C)

Galley (1-18-2-Q) Generator Room (3-36-0-E)

C4ISR (2-23-3-Q)

ESP PL SPACES SERVED

INSTALLED FILTER LIST

SIZE NFLTR

ITEM NO.

SYSTEM

NO. TYPE FILTER

LCTN

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 6 -

Service Filter List

0 10 10

QUANTITY 0 0 0 0 0 0 0 0 0 0 0 0

10AF 11AF 12AF 14AF 15AF 16AF ESP

SERVICE FILTER LIST

13AF HEPA CBR REMARKSSIZE

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 7 -

Total Connected Load

N TYPE SIZE TOTAL

TONS

C-1 1 Cooling coil AC N/A 16.58 N/A N/A N/A W C-1 1 Fan Coil Unit N/A 0.92 N/A N/A N/A Z C-1 1 Gravity Coil N/A 0.13 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 1.58 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 0.38 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 0.38 N/A N/A N/A W C-2 1 Fan Coil Unit N/A 2.63 N/A N/A N/A W

N/A N/A N/A N/A 22.32 N/A N/A N/A W N/A N/A N/A N/A 0.92 N/A N/A N/A Z

Total load Total load

FCU-2

TOTAL CONNECTED LOAD - SUMMARY LIST

TOTAL

GPM

HEAT TRANSFER EQUIP.

APPLICATION NOTESD C

CLASS

CONNECTED

TO PLANT

NO.

t1 t2

FCU-3

FCU-1B

FCU-1B

FCU-1A

GC-1

AC-1

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 8 -

Air Conditioning Plant Summary

LOCATION N TN HP tc te t1 t2 t SIZE HP P N SIZE HP P C-1 Piston compressor Engine room (3-27-0-E) 1 21.1 28.5 115 36 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3-29-1 1101-1105 C-2 Piston compressor Engine room (3-27-0-E) 1 6.68 17.7 115 36 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3-30-2 ALL C-1 Piston compressor Engine room (3-27-0-E) 1 19.3 35.4 109 36 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3-29-1 1106-On

AIR CONDITIONING PLANTS SUMMARY LIST

PLANT

NO. TYPE

REFRIGERATING MACHINES C W PUMPS S W PUMPS

NOTES

APPLICABLE

HULL

NUMBERS

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 9 -

Closures, Dampers and Valve List

ITEM NO. VLV NO. SYS NO. TYP TYP OF

CNTL ACTUATOR SIZE

(mm) CFM LOCATION DC

CLASS

PWR

REQ'S

[W]

SPECIAL

FEATURES SPACES SERVED

1 1-24-1 AC-1 Fire Damper Automatic Motorized 100 164 HVAC Equipment room (1-24-1-Q) W 8 None Supply Galley (1-18-2-Q) 2 1-25-3 AC-1 Shut-off damper Automatic Motorized 300x400 792 HVAC Equipment room (1-24-1-Q) W 1W None Fresh air AC-1 3 01-28-1 ES-1 Closure Manual Manual 200 401 Aft of Pilot House (01-19-0-C) W N/A None Sanitary exhaust outlet 4 1-21-2 ES-2 Shut-off damper Automatic Motorized 200x200 450 Galley (1-18-2-Q) W 1W None Exhaust Galley (1-18-2-Q) 5 1-17-2 ES-2 Shut-off damper Automatic Motorized 200x200 286 Galley (1-18-2-Q) W 1W None Supply Galley (1-18-2-Q) 6 01-26-1 AC-1 Smoke damper Manual Manual 100 781 Pilot House (01-19-0-C) Y N/A None Pilot House (01-19-0-C) 7 1-23-1 AC-1 On-off damper Manual Manual 160 554 Head (1-23-1-L) W N/A None *2) Accommodation 8 2-25-3 AC-1 Smoke damper Manual Manual 100 246 C4ISR (2-23-3-Q) Y N/A None C4ISR (2-23-3-Q) 9 2-25-1 AC-1 Smoke damper Manual Manual 125 246 Passageway (2-25-0-L) W N/A None *1) Accommodation 10 1-24-7 RS-1 Regulation Damper Manual Manual 125 208 HVAC Equipment room (1-24-1-Q) W N/A None Passage (1-23-0-L) 11 1-24-3 RS-1 Regulation Damper Manual Manual 250 1022 HVAC Equipment room (1-24-1-Q) W N/A None Passage (1-23-0-L) 12 1-17-3 RS-1 Regulation Damper Manual Manual 160 520 Office (1-16-1-A) W N/A None Passage (2-17-0-L) 13 1-16-1 RS-1 Regulation Damper Manual Manual 125 195 Office (1-16-1-A) W N/A None Passage (2-10-0-L) 14 1-22-7 AC-1 Regulation Damper Manual Manual 160 780 Mess Deck (1-17-0-Q) W N/A None *3) Accommodation 15 1-22-3 AC-1 Regulation Damper Manual Manual 160 525 Mess Deck (1-17-0-Q) W N/A None *4) Accommodation 16 1-22-1 AC-1 Regulation Damper Manual Manual 100 211 Mess Deck (1-17-0-Q) W N/A None Mess (1-17-0-Q) 17 1-24-5 RS-1 Smoke damper Manual Manual 125 255 HVAC Equipment room (1-24-1-Q) W N/A None *6) Accommodation 18 1-17-1 RS-1 Smoke damper Manual Manual 200 715 Office (1-16-1-A) W N/A None Passage (2-17-0-L) 19 1-25-1 AC-1 Smoke damper Manual Manual 125 321 HVAC Equipment room (1-24-1-Q) W N/A None *5) Accommodation 20 1-27-1 ES-1 Shut-off damper Automatic Motorized 200x200 401 Passage (1-23-0-L) W 1W None *7) Toilets 21 1-3-1 NS-1 Watertight Closure Manual Manual 194 329 Main deck (1-A-0-X) W N/A None Fwd Aux (3-3-0-E) 22 1-9-2 NS-1 Watertight Closure Manual Manual 194 329 Main deck (1-A-0-X) W N/A None Fwd Aux (3-3-0-E)

23 1-10-2 NS-2 Watertight Closure Manual Manual 1005x1665 9406 S 3475 W Main deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

24 1-10-2 NS-2 Demister Manual Manual 686x1676 9406 S 3475 W Main deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

25 1-10-2 NS-2 Fire Damper Automatic Motorized 656x1280 9406 S 3475 W EDG Room (1-10-0-E) W None EDG Room (1-10-0-E)

26 1-10-1 NS-2 Fire Damper Automatic Motorized 829x1508 9000 S 3069 W EDG Room (1-10-0-E) W None EDG Room (1-10-0-E)

27 1-10-1 NS-2 Watertight Closure Manual Manual 715x1600 9000 S 3069 W Main deck (1-A-0-X) W N/A None EDG Room (1-10-0-E)

CLOSURES, DAMPERS, AND VALVE LIST

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 10 -

(mm) CFM LOCATION DC

CLASS

PWR

REQ'S

[W]

SPECIAL

FEATURES SPACES SERVED

28 01-10-2 ES-4 Watertight Closure Manual Manual 100 161 01 Deck (01-08-X) W N/A None EDG Room (1-10-0-E) 29 1-28-2 ES-5 Watertight Closure Manual Manual 905x1018 10000 Main deck (1-A-0-X) W N/A None ER (3-27-0-E) 30 1-28-2 ES-5 Demister Manual Manual 801x912 10000 1-28-2-E W N/A None ER (3-27-0-E) 31 1-28-2 ES-5 Fire Damper Automatic Motorized 648x648 10000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E) 32 1-28-1 ES-6 Watertight Closure Manual Manual 905x1018 10000 Main deck (1-A-0-X) W N/A None ER (3-27-0-E) 33 1-28-1 ES-6 Demister Manual Manul 801x912 10000 1-28-1-E W N/A None ER (3-27-0-E) 34 1-28-1 ES-6 Fire Damper Automatic Motorized 648x648 10000 Exhaust Comp (1-28-0-Q) W 7.2 None ER (3-27-0-E) 35 1-34-2 SS-9 Watertight Closure Manual Manual 1017x1254 10000 Main deck (1-A-0-X) W N/A None ER (3-27-0-E) 36 1-34-2 SS-9 Demister Manual Manual 838x1062 10000 1-34-2-E W N/A None ER (3-27-0-E) 37 3-34-2 SS-9 Fire Damper Automatic Motorized 648x648 10000 ER (3-27-0-E) W 7.2 None ER (3-27-0-E) 38 1-34-1 SS-10 Watertight Closure Manual Manual 1017x1254 10000 Main deck (1-A-0-X) W N/A None ER (3-27-0-E) 39 1-34-1 SS-10 Demister Manual Manual 838x1062 10000 1-34-1-E W N/A None ER (3-27-0-E) 40 3-34-1 SS-10 Fire Damper Automatic Motorized 648x648 10000 ER (3-27-0-E) W 7.2 None ER (3-27-0-E) 41 1-38-2 ES-11 Watertight Closure Manual Manual 1011x1011 6259 Main Deck (1-A-0-X) W N/A None Generator Room (3-36-0-E) 42 1-38-2 ES-11 Demister Manual Manual 814x876 6259 1-37-2-E W N/A None Generator Room (3-36-0-E) 43 3-38-2 ES-11 Fire Damper Automatic Motorized 648x648 6259 Generator Room (3-36-0-E) W 7.2 None Generator Room (3-36-0-E) 44 1-38-1 SS-12 Watertight Closure Manual Manual 1011x1011 7379 Main Deck (1-A-0-X) W N/A None Generator Room (3-36-0-E) 45 1-38-1 SS-12 Demister Manual Manual 814x876 7379 1-37-1-E W N/A None Generator Room (3-36-0-E) 46 3-38-1 SS-12 Fire Damper Automatic Motorized 648x648 7379 Generator Room (3-36-0-E) W 7.2 None Generator Room (3-36-0-E) 47 1-40-2 NS-3 Watertight Closure Manual Manual 146 120 Main deck (1-A-0-X) W N/A None Steering Gear Room (3-40-2-E) 48 1-43-2 NS-3 Watertight Closure Manual Manual 146 120 Main deck (1-A-0-X) W N/A None Steering Gear Room (3-40-2-E) 49 1-40-1 NS-4 Watertight Closure Manual Manual 146 120 Main deck (1-A-0-X) W N/A None Steering Gear Room (3-40-1-E) 50 1-43-1 NS-4 Watertight Closure Manual Manual 146 120 Main deck (1-A-0-X) W N/A None Steering Gear Room (3-40-1-E) 51 1-26-3 AC-1 Regulation Damper Manual Manual 100 227 Passage (1-23-0-L) W N/A None Pilot House (01-19-0-C) 52 1-25-5 RS-1 Demister Manual Manual 406x483 793 Main deck (1-A-0-X) W N/A None HVAC Equipment room (1-24-1-Q) 53 1-21-4 RS-1 Demister Manual Manual 305x330 450 Main deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 54 1-17-4 RS-1 Demister Manual Manual 254x330 286 Main deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 55 1-25-7 RS-1 Watertight Closure Manual Manual 590X390 793 Main deck (1-A-0-X) W N/A None HVAC Equipment room (1-24-1-Q) 56 1-17-6 RS-1 Watertight Closure Manual Manual 390X290 286 Main deck (1-A-0-X) W N/A None Galley (1-18-2-Q) 57 1-21-6 RS-1 Watertight Closure Manual Manual 390X290 450 Main deck (1-A-0-X) W N/A None ER (3-27-0-E)

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 11 -

(mm) CFM LOCATION DC

CLASS

PWR

REQ'S

[W]

SPECIAL

FEATURES SPACES SERVED

58 1-26-1 AC-1 Smoke damper Manual Manual 100 227 Passage (1-23-0-L) W N/A None Pilot House (01-19-0-C) 59 1-23-3 ES-1 Smoke damper Manual Manual 100 66 Head (1-23-1-L) W N/A None Head (2-23-1-L) 60 1-17-5 AC-1 Smoke damper Manual Manual 160 520 Office (1-16-1-A) W N/A None *8) Accommodations 61 1-14-1 AC-1 Smoke damper Manual Manual 160 407 CO Cabin (1-12-1-L) W N/A None *9) Accommodations 62 1-14-5 ES-1 Smoke damper Manual Manual 125 212 CO Cabin (1-12-1-L) W N/A None *10) Toilets 63 2-14-1 ES-1 Regulation Damper Manual Manual 100 31 Shower (2-14-1-L) W N/A None Shower (2-14-1-L) 64 2-14-3 ES-1 Regulation Damper Manual Manual 125 75 Shower (2-14-1-L) W N/A None *11) Toilets 65 2-24-1 RS-1 Regulation Damper Manual Manual 100 77 C4ISR (2-23-3-Q) W N/A None C4ISR (2-23-3-Q) 66 1-14-7 ES-1 Regulation Damper Manual Manual 125 212 CO Cabin (1-12-1-L) W N/A None *10) Toilets 67 1-14-3 AC-1 Regulation Damper Manual Manual 160 407 CO Cabin (1-12-1-L) W N/A None *9) Accommodations 68 1-16-3 RS-1 Smoke damper Manual Manual 125 195 Office (1-16-1-A) W N/A None Passage (2-10-0-L) 69 1-17-7 AC-1 Regulation Damper Manual Manual 160 520 Office (1-16-1-A) W N/A None *8) Accommodations 70 1-22-9 AC-1 Regulation Damper Manual Manual 160 554 Mess Deck (1-17-0-Q) W N/A None *2) Accommodation 71 1-22-11 ES-1 Regulation Damper Manual Manual 100 66 Mess Deck (1-17-0-Q) W N/A None *12) Toilets 72 1-22-5 AC-1 Regulation Damper Manual Manual 200 715 Mess Deck (1-17-0-Q) W N/A None Passage (2-10-0-L)+(2-17-0-L) 73 1-23-5 ES-1 Regulation Damper Manual Manual 100 66 Head (1-23-1-L) W N/A None Head (2-23-1-L) 74 1-30-1 ES-15 Watertight Closure Manual Manual 646X358 1300 Main deck (1-A-0-X) W N/A None Exhaust Comp (1-28-0-Q) 75 1-30-1 ES-15 Demister Manual Manual 646X358 1300 Exhaust Comp (1-28-0-Q) W N/A None Exhaust Comp (1-28-0-Q) 76 1-29-1 ES-15 Fire Damper Manual Manual 646X358 1300 Exhaust Comp (1-28-0-Q) W N/A None Exhaust Comp (1-28-0-Q) 77 1-30-2 ES-16 Watertight Closure Manual Manual 646X358 1300 Main deck (1-A-0-X) W N/A None Exhaust Comp (1-28-0-Q) 78 1-30-2 ES-16 Demister Manual Manual 646X358 1300 Exhaust Comp (1-28-0-Q) W N/A None Exhaust Comp (1-28-0-Q) 79 1-29-2 ES-16 Fire Damper Manual Manual 646X358 1300 Exhaust Comp (1-28-0-Q) W N/A None Exhaust Comp (1-28-0-Q)

*1) Accommodation *3) Accommodation *5) Accommodation *7) Toilets Climate Controlled Store Room 2-23-4-A XO Stateroom 1-12-2-L Eng CPO Stateroom 2-23-2-L Head Main deck front 1-12-0-L EPO Stateroom 2-23-2-L OPS CPO Stateroom 1-15-2-L Climate Controlled Store Room 2-23-4-A Head Main deck 1-15-1-L

Cabin 2-17-1-L C4ISR 2-23-3-Q Head Main deck between AC and Mess 1-23-1-L Cabin 2-20-1-L Head Second deck next to C4ISR 2-23-1-L

*2) Accommodation Cabin 2-21-2-L *6) Accommodation Head Second deck front PS 2-12-2-L Co Cabin 1-12-1-L Cabin 2-17-2-L Climate Controlled Store Room 2-23-4-A Head Second deck front PS 2-13-2-L Cabin 2-15-2-L C4ISR 2-23-3-Q Head Second deck front PS 2-14-2-L Cabin 2-10-2-L *4) Accommodation Shower Second deck front SB 2-12-1-L Cabin 2-10-1-L Mess 1-17-0-Q *10) Toilets Shower Second deck front SB 2-13-1-L Cabin 2-15-1-L Ship's Office 1-16-1-A Head Second deck front PS 2-12-2-L Shower Second deck front SB 2-14-1-L

Head Second deck front PS 2-13-2-L Head Second deck front PS 2-14-2-L *12) Toilets

*8) Accommodation *9) Accommodation Shower Second deck front SB 2-12-1-L Head Main deck front 1-12-0-L Cabin 2-17-1-L Cabin 2-15-1-L Shower Second deck front SB 2-13-1-L Head Main deck 1-15-1-L Cabin 2-20-1-L Cabin 2-10-1-L Shower Second deck front SB 2-14-1-L Head Second deck front PS 2-12-2-L Cabin 2-21-2-L Cabin 2-10-2-L Head Second deck front PS 2-13-2-L Cabin 2-17-2-L Cabin 2-15-2-L *11) Toilets Head Second deck front PS 2-14-2-L

Shower Second deck front SB 2-12-1-L Shower Second deck front SB 2-12-1-L Shower Second deck front SB 2-13-1-L Shower Second deck front SB 2-13-1-L

Shower Second deck front SB 2-14-1-L

Bollinger Shipyards Business Sensitive. This document and the data contained herein may not be disclosed to any third party. Use or disclosure of this

- 12 -

Portable Test Covers List

ITEM NO. PORTABLE TEST

COVER NO. SYSTEM NO. SIZE LOCATION SPACES SERVED

None None None None None None

PORTABLE TEST COVERS LIST

The vessel has no portable test covers.

Revision History
Table of Contents
1.0 Purpose
2.0 References
3.0 HVAC Equipment Lists
Fan List
Cooling Coil List
Heater List
Installed Filter List
Service Filter List
Total Connected Load
Air Conditioning Plant Summary
Closures, Dampers and Valve List
Portable Test Covers List

File details come from the government source that posted it. Updated .