This is a Hazardous/Regulated Materials Survey & Inspection Report prepared by Environmental Testing & Consulting, Inc. for the City of Detroit Demolition Department regarding the property at 14635 Bentler Street, Detroit, MI 48223. The inspection was conducted on August 3, 2026, with the report issued on August 12, 2026, in support of a planned residential demolition project (Group 9.3.26). The single-story residential structure, built in 1948 with a concrete slab foundation and 572 square feet of total area, was surveyed for asbestos-containing materials, hazardous materials, and structural conditions. The engineering survey identified significant fire and structural damage, including a completely burned roof and absent attic space. Laboratory analysis using Polarized Light Microscopy identified asbestos-containing materials in two product categories: 9x9 brown floor tile containing 3% chrysotile asbestos (199 square feet located in functional spaces FS-1 and FS-5) and white exterior caulk containing 5% chrysotile asbestos (190 linear feet located in exterior areas EA-1 through EA-4). All other tested materials, including drywall board, stack cement, window glazing, tile mastic, cinderblock, mortar, concrete, roofing shingles, and tar paper, tested negative for asbestos or contained trace amounts below the 1% threshold for classification as asbestos-containing materials.

The report establishes baseline conditions for the demolition contractor, who bears responsibility for verifying all quantities of identified asbestos during the bidding process and ensuring compliance with OSHA and EPA regulations for removal and disposal of the detected asbestos-containing materials. No other hazardous materials or regulated substances were detected at the property. The inspection documentation includes detailed chain of custody records, site drawings, photographic evidence of structural damage, and comprehensive laboratory certification from Environmental Testing Laboratories, Inc., with analysis conducted by qualified Michigan Asbestos Inspectors and reviewed by licensed professionals. The findings serve as the basis for preparation of the demolition scope of work and contractor bid requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Hazardous/Regulated Materials Survey & Inspection Report

14635 Bentler Street, Detroit, MI 48223 Parcel #: 22110990.

Date of Inspection: 08/03/2026 Date of Report: 08/12/2026

Prepared For:

City of Detroit Demolition Department

1301 3rd Avenue, 6th Floor

Detroit, MI 48226

Project #: 2026 BPO 7.20.2026

Fieldwork conducted by: Report Reviewed and Approved by:

Andre Richardson Mark Smith Michigan Asbestos Inspector License #: A45125 Michigan Asbestos Inspector License #: A55707 Inspector’s E-Mail: Andre.Richardson@2etc.com E-Mail: Mark.Smith@2etc.com

38900 West Huron River Drive Romulus, MI 48174

734-955-6600 www.2etc.com

Hazardous/Regulated Materials Survey & Inspection Report ETC Job #: 293125

14635 Bentler Street, Detroit, MI 48223 Parcel #: 22110990.

Asbestos Containing Materials

TABLE 1: ASBESTOS CONTAINING MATERIALS

Category Material Description Location Quantity

M 9x9 Floor Tile, Brown FS 1,5 199 SF

M Exterior Caulk, White EA 1-4 190 LF TSI = Thermal System Insulation; S = Surfacing; M = Miscellaneous; SF= Square Feet; LF = Linear Feet;

CY = Cubic Yards; CF = Cubic Feet

Quantities that are listed are estimates only. It is the contractor’s responsibility to verify all amounts of asbestos identified during the bid process.

Hazardous Materials & Tires

TABLE 2: HAZARDOUS MATERIALS

Material Description Location Quantity

None Detected

Engineering Survey

14635 Bentler Street

Reviewed 08/2025

Pre-Demolition Engineering Survey Report

Detroit, MI 48223

Prepared for City of Detroit Demolition Department

1301 Third Street, 6th Floor Detroit, Michigan 48226

Prepared by Environmental Testing & Consulting, Inc.

38900 West Huron River Drive Romulus, MI 48174

Report Date July 31, 2026

Reviewed 08/2025

Survey Details and Site Information Date(s) of Engineering Survey: July 29, 2026

Engineering Survey Inspector name: Jeremy Westcott

Engineering Survey Inspector #: INSP01045

Engineering Survey Inspector email: Jeremy.Westcott@2etc.com

Engineering Survey Inspector phone #: 734-955-6600

Engineering Survey Inspector signature:

Reviewing PE/Architect name:

Reviewing PE/Architect license state/#:

Reviewing PE/Architect email:

Reviewing PE/Architect phone #:

Reviewing PE/Architect signature:

Property Address: 14635 Bentler Street, Detroit, MI 48223

# and types of structure(s): 1 House

Foundation type Concrete Slab

Year built: 1948

# of floors: 1

Total square footage: 572 ft2

William Earle, P.E. (WI)

WI 35407-6

William.Earle@oneatlas.com

847-971-0979

Reviewed 08/2025

Engineering Survey Findings – Exterior Areas Designation Inaccessible Reason Description/Notes

EA-1

EA-2

EA-3

EA-4

EA-5

Key:

• Inaccessible: “P” = Partially inaccessible; “C” = Completely inaccessible

• Reason: “F” = Fire damage, “W” = Water damage, “S” = Structural damage, “T” = Termite damage, “O” = Other damage

C F, S Roof has burned

Reviewed 08/2025

Engineering Survey Findings – Functional Spaces Designation Inaccessible Reason Description/Notes

FS-1

FS-2

FS-3

FS-4

FS-5

FS-6 C F Attic is burned away

Key:

• Inaccessible: “P” = Partially inaccessible; “C” = Completely inaccessible

• Reason: “F” = Fire damage, “W” = Water damage, “S” = Structural damage, “T” = Termite damage, “O” = Other damage

Reviewed 08/2025

Site Drawings

Reviewed 08/2025

Site Photographs

EA1 EA2

EA3 EA4

Reviewed 08/2025

EA5 FS1

FS2 FS3

Reviewed 08/2025

FS4 FS5

FS6 – Attic Gone

Electronic Chain of Custody

Submitting Client:

Detroit, MI - 48226

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Environmental Testing Laboratories, Inc.

City of Detroit - Demolition Department

1301 Third Street - Suite 606

Asbestos-Bulk

72 Hours

Yes

Yes, 400.00 Points

DETROIT DEMO

Sample Type:

Turn Around:

Positive Stop:

Point Counting:

P.C. Criteria:

Sample ID Client Sample ID

ETL Project :Project Location: 29312514635 Bentler St, Detroit, MI 48223

Collection DateSample Location Sample Description

1915215 2026-08-031A FS3 Ceiling / Wall / Drywall Board - White - HA(1)

1915216 2026-08-031B FS3 Ceiling / Wall / Drywall Board - White - HA(1)

1915217 2026-08-031C FS3 Ceiling / Wall / Drywall Board - White - HA(1)

1915218 2026-08-032A FS3 Mortar / Stack Cement - Grey - HA(2)

1915219 2026-08-032B FS3 Mortar / Stack Cement - Grey - HA(2)

1915220 2026-08-032C FS3 Mortar / Stack Cement - Grey - HA(2)

1915221 2026-08-033A EA1 Wall (Ext.) / Window (Glazing) - White - HA(3)

1915222 2026-08-033B EA2 Wall (Ext.) / Window (Glazing) - White - HA(3)

1915223 2026-08-033C EA3 Wall (Ext.) / Window (Glazing) - White - HA(3)

1915224 2026-08-034A FS1 Floor / Tile - 9x9 - Brown - HA(4)

1915225 2026-08-034B FS5 Floor / Tile - 9x9 - Brown - HA(4)

1915226 2026-08-034C FS1 Floor / Tile - 9x9 - Brown - HA(4)

1915227 2026-08-035A FS1 Floor / Tile Mastic - Black - HA(5)

1915228 2026-08-035B FS5 Floor / Tile Mastic - Black - HA(5)

1915229 2026-08-035C FS1 Floor / Tile Mastic - Black - HA(5)

1915230 2026-08-036A EA1 Cinderblock - Grey - HA(6)

1915231 2026-08-036B EA2 Cinderblock - Grey - HA(6)

1915232 2026-08-036C EA3 Cinderblock - Grey - HA(6)

1915233 2026-08-037A EA1 Mortar / Block - Grey - HA(7)

1915234 2026-08-037B EA2 Mortar / Block - Grey - HA(7)

Sample ID Client Sample ID

ETL Project :Project Location: 29312514635 Bentler St, Detroit, MI 48223

Collection DateSample Location Sample Description

1915235 2026-08-037C EA3 Mortar / Block - Grey - HA(7)

1915236 2026-08-038A EA1 Caulk / Exterior - White - HA(8)

1915237 2026-08-038B EA2 Caulk / Exterior - White - HA(8)

1915238 2026-08-038C EA3 Caulk / Exterior - White - HA(8)

1915239 2026-08-039A EA1 Concrete / Walkway - Grey - HA(9)

1915240 2026-08-039B EA2 Concrete / Walkway - Grey - HA(9)

1915241 2026-08-039C EA3 Concrete / Walkway - Grey - HA(9)

1915242 2026-08-0310A FS1 Concrete / Floor - Grey - HA(10)

1915243 2026-08-0310B FS2 Concrete / Floor - Grey - HA(10)

1915244 2026-08-0310C FS3 Concrete / Floor - Grey - HA(10)

1915245 2026-08-0311A EA5 Roofing / Asphalt (Shingles) - Grey - HA(11)

1915246 2026-08-0311B EA5 Roofing / Asphalt (Shingles) - Grey - HA(11)

1915247 2026-08-0311C EA5 Roofing / Asphalt (Shingles) - Grey - HA(11)

1915248 2026-08-0312A EA5 Roofing / Asphalt (Shingles) - Black - HA(12)

1915249 2026-08-0312B EA5 Roofing / Asphalt (Shingles) - Black - HA(12)

1915250 2026-08-0312C EA5 Roofing / Asphalt (Shingles) - Black - HA(12)

1915251 2026-08-0313A EA5 Roofing / Tar Paper - Black - HA(13)

1915252 2026-08-0313B EA5 Roofing / Tar Paper - Black - HA(13)

1915253 2026-08-0313C EA5 Roofing / Tar Paper - Black - HA(13)

Seal Intact:

Preservative (if required):

Containers Labled :

Yes

Yes

Analyst

Yes

Sample ID Client Sample ID

ETL Project :Project Location: 29312514635 Bentler St, Detroit, MI 48223

Collection DateSample Location Sample Description

Received By:

Received Date:

Relinquished By:

Relinquished Date:

Bella Rossi

2026-08-04 12:00 AM

Andre Richardson

Aug 4 2026 12:00AM Chris Canilao

OJ Ivey

Material List

Client : City of Detroit - Demolition Department 1301 Third Street - Suite 606 Detroit, MI - 48226

Project Location: 14635 Bentler st. Detroit Mi. Job #:293125

Material Id Material Description Material Sub Classification Size Quantity Locations

1 Ceiling / Wall/D rywall Board-White Drywall Board M 20 S F F S-03

2 Mortar/S tack Cement-Grey Stack Cement M 5 S F F S-03

3 Wall (Ext.)/Window (Glazing)-White Window (Glazing) M 6 Unit E A-01,E A-02,E A-03,E A-04

4 F loor/Ti le-9x9-Brown Tile M 9x9 199 S F F S-01,F S-05

5 F loor/Ti le Mastic-B lack Tile Mastic M 199 S F F S-01,F S-05

6 C inderblock-Grey M 1580 S F E A-01,E A-02,E A-03,E A-04

7 Mortar/B lock-Grey B lock M 1580 S F E A-01,E A-02,E A-03,E A-04

8 Caulk/Exterior-White Exterior M 190 LF E A-01,E A-02,E A-03,E A-04

9 Concrete/Walkway-Grey Walkway M 185 S F E A-01,E A-02,E A-03,E A-04

10 Concrete/F loor-Grey F loor M 550 S F F S-01,F S-02,F S-03,F S-04,F S-05

11 Roofing/Asphalt (Shingles)-Grey Asphalt (Shingles) M 650 S F E A-05

12 Roofing/Asphalt (Shingles)-B lack Asphalt (Shingles) M 650 S F E A-05

13 Roofing/Tar Paper-B lack Tar Paper M 650 S F E A-05

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive Romulus, Michigan 48174

(734) 955-6600

Fax: (734) 955-6604

To:

Attention:

Environmental Testing And Consulting Inc.

38900 Huron River Drive

Romulus, MI 48174

Project Location: 14635 Bentler St, Detroit, MI 48223

Client Project: 293125

293125ETL Job:

Al Dyer

Report Issued: 08/07/2026

Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst

1915215 Asbestos1A 08/07/2026 OJ Ivey08/03/2026

1915216 Asbestos1B 08/07/2026 OJ Ivey08/03/2026

1915217 Asbestos1C 08/07/2026 OJ Ivey08/03/2026

1915218 Asbestos2A 08/07/2026 OJ Ivey08/03/2026

1915219 Asbestos2B 08/07/2026 OJ Ivey08/03/2026

1915220 Asbestos2C 08/07/2026 OJ Ivey08/03/2026

1915221 Asbestos3A 08/07/2026 OJ Ivey08/03/2026

1915222 Asbestos3B 08/07/2026 OJ Ivey08/03/2026

1915223 Asbestos3C 08/07/2026 OJ Ivey08/03/2026

1915224 Asbestos4A 08/07/2026 OJ Ivey08/03/2026

1915225 Asbestos4B 08/07/2026 OJ Ivey08/03/2026

1915226 Asbestos4C 08/07/2026 OJ Ivey08/03/2026

1915227 Asbestos5A 08/07/2026 OJ Ivey08/03/2026

1915228 Asbestos5B 08/07/2026 OJ Ivey08/03/2026

1915229 Asbestos5C 08/07/2026 OJ Ivey08/03/2026

1915230 Asbestos6A 08/07/2026 OJ Ivey08/03/2026

This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.

Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst

1915231 Asbestos6B 08/07/2026 OJ Ivey08/03/2026

1915232 Asbestos6C 08/07/2026 OJ Ivey08/03/2026

1915233 Asbestos7A 08/07/2026 OJ Ivey08/03/2026

1915234 Asbestos7B 08/07/2026 OJ Ivey08/03/2026

1915235 Asbestos7C 08/07/2026 OJ Ivey08/03/2026

1915236 Asbestos8A 08/07/2026 OJ Ivey08/03/2026

1915237 Asbestos8B 08/07/2026 OJ Ivey08/03/2026

1915238 Asbestos8C 08/07/2026 OJ Ivey08/03/2026

1915239 Asbestos9A 08/07/2026 Chris Canilao08/03/2026

1915240 Asbestos9B 08/07/2026 Chris Canilao08/03/2026

1915241 Asbestos9C 08/07/2026 Chris Canilao08/03/2026

1915242 Asbestos10A 08/07/2026 Chris Canilao08/03/2026

1915243 Asbestos10B 08/07/2026 Chris Canilao08/03/2026

1915244 Asbestos10C 08/07/2026 Chris Canilao08/03/2026

1915245 Asbestos11A 08/07/2026 Chris Canilao08/03/2026

1915246 Asbestos11B 08/07/2026 Chris Canilao08/03/2026

1915247 Asbestos11C 08/07/2026 Chris Canilao08/03/2026

1915248 Asbestos12A 08/07/2026 Chris Canilao08/03/2026

1915249 Asbestos12B 08/07/2026 Chris Canilao08/03/2026

1915250 Asbestos12C 08/07/2026 Chris Canilao08/03/2026

1915251 Asbestos13A 08/07/2026 Chris Canilao08/03/2026

1915252 Asbestos13B 08/07/2026 Chris Canilao08/03/2026

1915253 Asbestos13C 08/07/2026 Chris Canilao08/03/2026

This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this

Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst

Reviewed by:

Summary

Sample Layer MasticMethod

PLM 35Dawson Bradley

This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this

Certificate of Analysis

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915215

1A PLM 90% OtherPLM 10% CelluloseWhiteCeiling / Wall / Drywall Board -

White - HA(1) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915216

1B PLM 90% OtherPLM 10% CelluloseWhiteCeiling / Wall / Drywall Board -

White - HA(1) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915217

1C PLM 90% OtherPLM 10% CelluloseWhiteCeiling / Wall / Drywall Board -

White - HA(1) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915218

2A PLM 97% OtherPLM 3% CelluloseGreyMortar / Stack Cement - Grey -

HA(2) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915219

2B PLM 97% OtherPLM 3% CelluloseGreyMortar / Stack Cement - Grey -

HA(2) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915220

2C PLM 97% OtherPLM 3% CelluloseGreyMortar / Stack Cement - Grey -

HA(2) Non-Fibrous

HomogenousFS3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915221

3A PLM 98% OtherPLM 2% CelluloseWhiteWall (Ext.) / Window (Glazing) -

White - HA(3) Non-Fibrous

HomogenousEA1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915222

3B PLM 98% OtherPLM 2% CelluloseWhiteWall (Ext.) / Window (Glazing) -

White - HA(3) Non-Fibrous

HomogenousEA2

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915223

3C PLM 98% OtherPLM 2% CelluloseWhiteWall (Ext.) / Window (Glazing) -

White - HA(3) Non-Fibrous

HomogenousEA3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM 3% Chrysotile1915224

4A PLM 92% OtherPLM 5% CelluloseBrownFloor / Tile - 9x9 - Brown - HA(4)

Non-Fibrous

HomogenousFS1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

1915225

4B

Positive Stop

FS5

Analyst: OJ Ivey

Date Analyzed : 08/07/2026

Sample Not Analyzed

1915226

4C

Positive Stop

FS1

Analyst: OJ Ivey

Date Analyzed : 08/07/2026

Sample Not Analyzed

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915227

5A PLM 95% OtherPLM 5% CelluloseBlackFloor / Tile Mastic - Black -

HA(5) Non-Fibrous

HomogenousFS1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915228

5B PLM 95% OtherPLM 5% CelluloseBlackFloor / Tile Mastic - Black -

HA(5) Non-Fibrous

HomogenousFS5

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915229

5C PLM 95% OtherPLM 5% CelluloseBlackFloor / Tile Mastic - Black -

HA(5) Non-Fibrous

HomogenousFS1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915230

6A PLM 99% OtherPLM 1% CelluloseGreyCinderblock - Grey - HA(6)

Non-Fibrous

HomogenousEA1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915231

6B PLM 99% OtherPLM 1% CelluloseGreyCinderblock - Grey - HA(6)

Non-Fibrous

HomogenousEA2

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915232

6C PLM 99% OtherPLM 1% CelluloseGreyCinderblock - Grey - HA(6)

Non-Fibrous

HomogenousEA3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915233

7A PLM 99% OtherPLM 1% CelluloseGreyMortar / Block - Grey - HA(7)

Non-Fibrous

HomogenousEA1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915234

7B PLM 99% OtherPLM 1% CelluloseGreyMortar / Block - Grey - HA(7)

Non-Fibrous

HomogenousEA2

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM None Detected 1915235

7C PLM 99% OtherPLM 1% CelluloseGreyMortar / Block - Grey - HA(7)

Non-Fibrous

HomogenousEA3

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

PLM 5% Chrysotile1915236

8A PLM 92% OtherPLM 3% CelluloseWhiteCaulk / Exterior - White - HA(8)

Non-Fibrous

HomogenousEA1

Layer-1 Analyst: OJ Ivey

Date Analyzed : 08/07/2026

1915237

8B

Positive Stop

EA2

Analyst: OJ Ivey

Date Analyzed : 08/07/2026

Sample Not Analyzed

1915238

8C

Positive Stop

EA3

Analyst: OJ Ivey

Date Analyzed : 08/07/2026

Sample Not Analyzed

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915239

9A PLM 100% OtherPLM Trace CelluloseGreyConcrete / Walkway - Grey -

HA(9) Non-Fibrous

HomogenousEA1

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915240

9B PLM 100% OtherPLM Trace CelluloseGreyConcrete / Walkway - Grey -

HA(9) Non-Fibrous

HomogenousEA2

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915241

9C PLM 100% OtherPLM Trace CelluloseGreyConcrete / Walkway - Grey -

HA(9) Non-Fibrous

HomogenousEA3

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915242

10A PLM 100% OtherPLM Trace CelluloseGreyConcrete / Floor - Grey - HA(10)

Non-Fibrous

HomogenousFS1

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915243

10B PLM 100% OtherPLM Trace CelluloseGreyConcrete / Floor - Grey - HA(10)

Non-Fibrous

HomogenousFS2

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915244

10C PLM 100% OtherPLM Trace CelluloseGreyConcrete / Floor - Grey - HA(10)

Non-Fibrous

HomogenousFS3

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915245

11A PLM 100% OtherPLM Trace FiberglassGreyRoofing / Asphalt (Shingles) -

Grey - HA(11) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915246

11B PLM 100% OtherPLM Trace FiberglassGreyRoofing / Asphalt (Shingles) -

Grey - HA(11) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915247

11C PLM 100% OtherPLM Trace FiberglassGreyRoofing / Asphalt (Shingles) -

Grey - HA(11) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915248

12A PLM 100% OtherPLM Trace FiberglassBlackRoofing / Asphalt (Shingles) -

Black - HA(12) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915249

12B PLM 100% OtherPLM Trace FiberglassBlackRoofing / Asphalt (Shingles) -

Black - HA(12) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915250

12C PLM 100% OtherPLM Trace FiberglassBlackRoofing / Asphalt (Shingles) -

Black - HA(12) Non-Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.

Polarized Light Microscopy Asbestos Analysis Report

Location :

To :

Romulus,MI 48174

Environmental Testing And Consulting Inc.

38900 Huron River Drive

14635 Bentler St, Detroit, MI 48223

ETL Job :

Client Project :

293125

293125

Environmental Testing Laboratories, Inc.

37575 W Huron River Drive

Romulus, Michigan 48174

(734) 955-6600, Fax: (734) 955-6604

Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos

08/03/2026

08/04/2026

Date Collected :

Date Received :

PLM None Detected 1915251

13A PLM 90% OtherPLM 10% CelluloseBlackRoofing / Tar Paper - Black -

HA(13) Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915252

13B PLM 90% OtherPLM 10% CelluloseBlackRoofing / Tar Paper - Black -

HA(13) Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

PLM None Detected 1915253

13C PLM 90% OtherPLM 10% CelluloseBlackRoofing / Tar Paper - Black -

HA(13) Fibrous

HomogenousEA5

Layer-1 Analyst: Chris Canilao

Date Analyzed : 08/07/2026

Lab Supervisor/Other Signatory

Chris Canilao

OJ Ivey

Analyst:

400 Point Count Results by EPA 600/R-93/116 PLM (denoted by "PC")

Item 198.1: PLM Methods for Identifying and Quantitating Asbestos in Bulk Samples

Item 198.6: PLM Methods for Identifying and Quantitating Asbestos in Non-Friable Organically Bound Bulk Samples

EPA 600/R-93/116: Method for Determination of Asbestos in Bulk Building Materials

EPA 600/M4-82-020: Interim Method for Determination of Asbestos in Bulk Insulation Samples

A % Asbestos result of "Trace" indicates that the analyzed material was found to contain less than 1% asbestos and would not be considered an Asbestos Containing Material (ACM).

ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any

PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.