TOWABLE DIESEL GENERATOR Federal contract opportunity
Solicitation number
140R3024Q0050
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document is a product specification sheet for the Cat XQ125 Tier 4 final rental generator set. The 110 kW, 137 kVA standby and 100 kW, 125 kVA prime generator set is powered by a Caterpillar C4.4 diesel engine and meets U.S. EPA Tier 4 Final emission standards. Key features include a Cat Clean Emissions Module, Diesel Exhaust Fluid (DEF) system, automatic voltage regulator, sound-attenuated enclosure, and 24-hour runtime at 75% load. Optional equipment includes a trailer, battery charger, generator space heater, and 600V generator. The document provides detailed technical specifications on the engine, generator, fuel system, cooling system, and dimensions/weights.

The related federal contract opportunity is for a Towable Diesel Generator, solicitation number 140R3024Q0050 issued by the Department of the Interior Bureau of Reclamation. This appears to be a request for the type of generator described in the product specification.

View the file

Other files for this federal contract opportunity

Other files attached to TOWABLE DIESEL GENERATOR, newest first.
File Type Posted
Sol_140R3024Q0050.pdf PDF
C05_Combined_Synopsis.pdf PDF
C05_Clauses___Provisions.pdf PDF
C05_Salient_Characteristics_-_Attach_002.pdf PDF
C05_SOW_-_Attach_001.pdf PDF
C05_140R3024Q0050_RFQ.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cat® XQ125 Rental Generator Set

Page 1 of 7 LEHX0035-08 Caterpillar: Confidential Green

Standby 110 kW, 137 kVA

Prime 100 kW, 125 kVA

U.S. EPA Tier 4 Final

60 Hz

1800 RPM

Specifications

Generator Frequency Voltage Standby kW (kVA)

Prime kW (kVA)

Phase Amp (A)

Standard

60 Hz 480/277V 110 (137) 100 (125) 3-phase 150.35

60 Hz 208/120V 110 (137) 100 (125) 3-phase 346.97

60 Hz 240/120V 65 (65) 65 (65) 1-phase 270.83

Optional

60 Hz 600V/349V 110 (137) 100 (125) 3-phase 120.28

60 Hz 480V/277V 110 (137) 100 (125) 3-phase 150.35

60 Hz 208/120V 110 (137) 100 (125) 3-phase 346.97

60 Hz 240/120V 64 (64) 64 (64) 1-phase 266.67

Cat® C4.4 Diesel Engine Metric Imperial (English)

Configuration I-4, 4-Stroke - Water Cooled Diesel

Bore 105 mm 4.13 in

Stroke 127 mm 5 in

Displacement 4.4 L 268.5 in3

Aspiration Turbocharged-Aftercooled

Compression Ratio 16.5:1

Engine rpm 1800

Governor Type ADEM™ A4

Image shown may not reflect actual configuration

Page 2 of 7 LEHX0035-08 Caterpillar: Confidential Green

Features & Benefits

Fuel/Emissions Strategy

• Meets U.S. EPA Tier 4 Final emission standards and CARB certified for non-road mobile applications at all 60 Hz ratings

Design Criteria

• Meets ISO 8528 transient response and linear vibration

• Canadian Standards Association (CSA) Certified

Single-source Supplier

• Package is factory designed and production tested

• Manufactured in ISO 9001:2000 certified

Caterpillar facility

Cat C4.4 Diesel Engine

• Four-stroke diesel engine with ACERT technology combined with electronic engine controller offers consistent performance and excellent fuel economy

• Series turbocharged with smart wastegate

• Low ownership costs enabled by a 3,000 hrs service interval for multi-vee belts and service free tappets

• Oil and fuel filter change intervals: 500 hrs

Cat Clean Emissions Module (CEM)

• Engine mounted Aftertreatment module contains of

Diesel Oxidation Catalyst (DOC) and Selective

Catalytic Reduction (SCR)

• Aftertreatment remains invisible to the equipment operator when in use

• No requirement for ash servicing

• Service free for life of the engine

Diesel Exhaust Fluid (DEF) System

• DEF tank provides more than 24 hrs run time@

75% load.

• Electrically heated DEF lines

Cat Generator

• Matched to the performance and output characteristics of Cat engines

• Integrated voltage selector switch

• UL 1446 Recognized Class H insulation

Automatic Voltage Regulator (AVR)

• D350 excitation module

• Three-phase sensing

• Adjustable volts-per-hertz regulation

• Provides precise control, excellent block loading, and constant voltage in the normal operating range

XQCP Control Panel

• Electronic control panel provides power metering, protective relaying, engine, and generator parameter viewing, and expanded AC metering

• Four lines back-lit LCD text display

• Simple, user-friendly interface and navigation

• Integrates with the Automatic Voltage Regulator

(AVR) to provide precise control, excellent block loading, and constant voltage

Sound-attenuated Enclosure

• Provides excellent weather protection and allows for a quiet package operation with less than 66 dBA sound levels at full load, while offering excellent service access with multiple doors and access panels

• Galvanized sheet steel body panels for improved corrosion resistance

• Coolant and oil drains along with auxiliary fuel connections are all conveniently located at one location on the exterior of the enclosure for easy access

• Single point lifting

Fuel System

• Provides 24-hour runtime @ 75% prime

• Meets UL 142, ULC 601

• OPTIONAL: Meets Transport Canada (UN31A) requirements with factory-installed, optional vent kit

Reduced Environmental Impact

• 110% spill containment of onboard engine fluids

Cooling System

• Provides 50°C ambient capability @ full rating

• Coolant low-level shutdown switch

• Coolant recovery system for easy top off

Charging System

• Charging alternator; 12V-100A, heavy duty with integral regulator and belt guards

• 10-Watt Solar maintainer for batteries

Asset Monitoring and Management

• Product Link™ Generation (PLG) hardware provides two-way communication for remote control and equipment monitoring via cellular network

• Customer-defined, equipment-based, real-time status updates and alerts

• Flexible and customer-configurable user interface

• GPS provides asset location and geo-fencing

Page 3 of 7 LEHX0035-08 Caterpillar: Confidential Green

Factory-installed Standard Equipment

Engine

• Cat C4.4 heavy-duty diesel engine meets

Tier 4 Final emission standards

Engine Air Inlet

• Heavy-duty air cleaner with dust cup and service indicator

• Turbocharger and air-to-air after cooler

Cat CEM

• Engine mounted CEM

• Robust operation in cold weather and low loads

• Includes DOC and SCR

DEF System

• 8-gal (30 L) plastic DEF tank provides capacity to meet or exceed fuel tank runtime at any given load.

• DEF tank is equipped with integrated level sensor and heating element to aid in cold weather operation.

• Electrically heated DEF lines

• DEF level gauge located on the control panel

• Equipped with low and critically-low level alarms and a critically-low shutdown

Fuel System

• 150-gal (568 L) double-wall fuel tank

• Fuel fill located in an isolated enclosed space away from the engine compartment with a lockable door

• Designed to meet UL 142, ULC 601

• Provides 24-hour runtime @ 75% prime

• Engine mounted electric priming pump

• Auxiliary connections for customer-supplied fuel transfer system with 3-way fuel transfer valve

• Engine mounted primary fuel filter with integral water separator

• Engine-mounted secondary fuel filter

Cooling System

• Provides 50°C ambient capability @ full rating

• Vertically mounted radiator with engine mounted cooling fan

• 50/50 Extended Life Coolant

• Coolant low-level shutdown switch

• Coolant recovery system

• Coolant drain line with valve

Mounting System

• Engine, generator and radiator soft mounted to the heavy duty, fabricated steel base frame

Sound-attenuated Enclosure

• Provides excellent weather protection

• Offers a quiet package with 66 dBA sound levels

• Rugged, corrosion-resistant construction:

o Galvanealed, sheet steel body panels with zinc phosphate pre-treatment prior to polyester powder coating

• Excellent access for service and maintenance:

o Two doors on each side of the enclosure provides clear access to routine service and maintenance needs.

o Two rear doors provide access to power distribution and control panel access o Separate door for DEF and Diesel fill access o Access panel on the front provides access to clean radiator cores and to service DEF tank.

o Lube oil drain, coolant drain, external fuel supply and return lines are all piped to exterior of the enclosure and located on one panel for easy access.

• Security and safety features:

o Pad lockable latches on all access doors o Exterior emergency stop (E-stop) button

Lube System

• Open crankcase breather with filter

• Oil drain line with internal valve routed to connection point accessible from exterior

• 500-hour engine oil change interval

Starting System

• Single electric starting motor, 12VDC

• Single 12V (850 CCA) maintenance-free battery with disconnect switch, battery rack, and cables

• 120V single-phase block heater

Quality

• Factory testing of standard generator set and complete power module

• UL, NEMA, ISO, and IEEE standards

• O&M manuals

• CSA Certified

• Full manufacturer’s warranty

Shore Power

• One 110V shore power connection for powering engine block heater and generator space heater (optional), battery charger (optional), and single duplex service receptacle

• Includes controls to de-energize block and generator space heaters when the engine is running

Page 4 of 7 LEHX0035-08 Caterpillar: Confidential Green

Factory-installed Optional Equipment

Vent Kit

• Provides necessary vents and films to upgrade the standard UL142 certified tank to meet Transport

Canada (UN31A) certification

Trailer Electric

• Two-axle trailer with Electric brakes

Trailer Hydraulic

• Two-axle trailer with Hydraulic brakes

Battery Charger

• 10A, 12 VDC output

• UL & CSA listed

Hitches

• 3" Pintle OR 2-5/16" Ball

Generator Space Heater

• 110 VAC Anti-condensation heater

Permanent Magnet Generator (PMG)

• Adds independent source of excitation to generator

NEMA Receptacles

• 208 Volt locking NEMA receptacles, quantity 2

600V Generator

• Includes 600V generator and 4-position rotary switch for easy selection of desired output

• Available voltages include:

o 3-phase (600/347 Volt, 480/277 Volt, 208/120 Volt) o 1-phase (240/120 Volt)

Page 5 of 7 LEHX0035-08 Caterpillar: Confidential Green

Technical Data

Cat Generator

Frame size LC3114F

Pitch 2/3

No. of poles 4

No. of leads 12

Excitation Self Excited

Number of bearings Single bearing, close coupled

Insulation Class H

Enclosure Drip proof IP23

Alignment Pilot shaft

Overspeed capability – % of rated 125% of rated

Voltage regulator 3-phase sensing with volts-per-hertz

Voltage regulation (adjustable to compensate for engine speed droop and line loss)

Less than ± 1⁄2% voltage gain

Wave form deviation 3%

Telephone Influence Factor (TIF) Less than 50

Harmonic Distortion (THD) Less than 5%

Cat Generator Set

Units 60 Hz — Standby 60 Hz — Prime

Power Rating kW (kVA) 110 (137) 100 (125)

Performance Specification

Lubricating System

Oil pan capacity L (gal) 9.4 (2.5) 9.4 (2.5)

Fuel System

Fuel consumption — 100% Load L/hr (gal/hr) 31.3 (8.27) 28.4 (7.49)

75% Load L/hr (gal/hr) - 20.9 (5.51)

50% Load L/hr (gal/hr) - 14.4 (3.80)

25% Load L/hr (gal/hr) - 7.5 (1.97)

Fuel tank capacity L (gal) 568 (150) 568 (150)

Run time @ 75% rating Hr 28

DEF System

DEF consumption — 100% Load L/hr (gal/hr) 1.2 (0.31) 0.47 (0.12)

75% Load L/hr (gal/hr) - 0.72 (0.19)

50% Load L/hr (gal/hr) - 0.39 (0.10)

25% Load L/hr (gal/hr) - 0.45 (0.12)

DEF tank capacity L (gal) 30 (7.92) 30 (7.92)

Run time @ 75% rating Hr 24

Cooling System

Ambient capability °C (°F) 55 (131) 55 (131)

Engine & radiator coolant capacity L (gal) 18.3 (4.8) 18.3 (4.8)

Noise Rating (with enclosure)

@ 7 meters (23 feet) @ 75% rating dB(A) 66 65

Page 6 of 7 LEHX0035-08

Caterpillar: Confidential Green

Technical Data (continued)

General Layout Dimensions

Dimensions in millimeters (inches).

Shown with optional trailer.

Dimensions and Weights

Model Length mm (in)

(A)

Width mm (in)

(B)

Height mm (in)

(C)

With Lube Oil

& Coolant

Kg (lb.)

With all fluids

Kg (lb.)

XQ125 3,261 (128.4) 1,243 (48.9) 1,856 (73) 2,372 (5,230) 2,876 (6,341)

XQ125 with trailer (electric brakes)

4,475 (176) 1,981 (78) 2,174 (85.5) 2,812 (6,200) 3,316 (7,311)

XQ125 with trailer

(hydraulic brakes) 4,495 (177) 1,981 (78) 2,174 (85.5) 2,821 (6,220) 3,325 (7,331)

(A) (B)

(C)

LEHX0035-08 (12/21)

Caterpillar: Confidential Green

Item Description

Steel enclosure with hinged, lockable doors (not shown)

2 Circuit breakers for receptacles

3 Emergency stop

2X Single-phase GFCI duplex receptacles (20A @ 120V)

5 Two-wire remote start terminals

3X Single-phase, California-style, twist-lock receptacles, 50A @ 208V phase-to-phase, 120V phase to neutral, or 240/120 single-phase when in that voltage position

Single-phase, NEMA locking input receptacle, (30A @ 120V) to power block heater, battery charger and generator space heater

8 HEST and DPF lamp

9 Glow plug lamp

10 XQCP digital generator set controller

11 Potentiometer for voltage adjustment

12 Cat ET service tool connector

13 Generator main circuit breaker

Main bus connection (bus bars with 13 mm holes) behind hinged cover with safety switch

15 Breaker trip door switch

Control Panel and Power Distribution Layout

Ratings Definitions and Conditions

Meets or Exceeds International Specifications: AS1359, CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-33.

Prime — Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year. Prime power in accordance with

ISO3046. Prime ambient shown indicate ambient temperature at 100% load which results in a coolant top tank temperature below the alarm temperature.

Standby — Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.

Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.

Fuel rates are based on fuel oil of 35º API [16ºC (60ºF)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29ºC (85ºF) and weighing 838.9 g/liter (7.001 lbs/U.S.

gal).

Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information regarding low sulfur fuel and biodiesel capability, please consult your Cat dealer.

www.Cat.com/rentalpower ©2022 Caterpillar

All rights reserved.

Materials and specifications are subject to change without notice.

The International System of Units (SI) is used in this publication.

CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, "Caterpillar Corporate Yellow", the "Power Edge" and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission

11 12 http://www.cat.com/rentalpower

File details come from the government source that posted it. Updated .