B08_Solicitation_ATT_9_Questions_and_Answers_0002.pdf

PDF 28 KB Posted

Attached to
PORE RANGER HQ: REPLACE PROPANE FURNACE
Solicitation number
140P8425Q0013
Issued by

About this file

This document is a Questions and Answers file for a federal contract opportunity involving a heat pump installation at Point Reyes National Seashore. The Q&A provides critical details about the project scope, including confirmation that electrical work should be included in the proposal, the building size of 1,950 square feet (excluding unheated basement), and specific requirements about ductwork. Notably, the document clarifies that only ductwork necessary to connect the new system to existing ductwork will be required, and while the current solar system is non-functional, its breakers should be preserved for future repair.

The Q&A supports the broader solicitation for replacing a propane furnace with an electric heating system, which is a total small business set-aside under NAICS code 238220. The project involves removing the existing furnace, installing a high-efficiency heat pump, and integrating it into the current heating infrastructure at the Point Reyes National Seashore Ranger Headquarters in Marin County, California.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

Question: Should the electrical work be included in the proposal?

Answer: Yes, the electrical work required for installing the system should be included in the proposal.

Question: What size system should be installed?

Answer: The system is specified in the specifications. Please include in your proposal the system specified.

Question: What is the size of the building to be heated?

Answer: The building is 1,950 square feet not including the unheated basement space.

Question: Does the work include replacing the duct work in the building?

Answer: The ductwork in the building will not be replaced in this project. The only duct work required will be that necessary to connect the new system into the existing duct work.

Question: Is the solar system for the building working? Can the breakers for the solar system be used for the new heat pump?

Answer: The solar system is not working currently, but we want to keep the breakers for use when the system is repaired in the future.