B11_QA_10-3-2024_0001.docx
DOCX document 52 KB Posted
- Attached to
- HEHO Replace Fire and Security Alarm System Federal contract opportunity
- Solicitation number
- 140P6024B0005
About this file
This document is a set of Questions and Answers related to a federal contract opportunity to Replace the Fire and Security Alarm System at the Herbert Hoover National Historic Site.
The key details are:
- The current system includes various components from multiple manufacturers, including Keltron, DSC, Faraday, FireLite, System Sensor, and others.
- The awardee will be responsible for all wiring, including removing the old wiring, devices, and panels.
- The awardee will not be running the cabling; that will be their responsibility.
- The federal agency involved is the National Park Service, Midwest Region.
- The solicitation number is 140P6024B0005.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6024B0005_Amd_0003.pdf | ||
| B11_QA_11-4-2024_0003.docx | DOCX document | |
| B12_MISC_Site_Visit_Questions_0002.docx | DOCX document | |
| B12_MISC_Site_Visit_Attendees_0002.pdf | ||
| Sol_140P6024B0005_Amd_0002.pdf | ||
| Sol_140P6024B0005_Amd_0001.pdf | ||
| Sol_140P6024B0005.pdf | ||
| B08_Sol_-_Att_5_-_Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| B08_Sol_-_Att_2_-_Drawings.pdf | ||
| B08_Sol_-_Att_6_-_Submittal_List.pdf | ||
| B08_Sol_-_Att_4_-_Notice_to_Contractors.pdf | ||
| B08_Sol_-_Att_1_-_Specifications.pdf | ||
| B08_Sol_-_Att_3_-_Wage_Determination.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of the Interior
NATIONAL PARK SERVICE
CONTRACTING OPERATIONS - CENTRAL
1849 C Street NW Washington, DC 20240
Questions/Answers PARK: Herbert Hoover National Historic Site PROJECT TITLE: Replace Fire and Security Alarm System – 140P6024B0005 Questions:
1. Do you have the model numbers for the devices and panels for both the burglary and fire systems?
Answer: The current model numbers are as follows:
· Main system for burglary and fire - Keltron DMP-703 with a Keltron PS740 Power Supply in addition to a Minuteman Enterprise E750 uninterruptable power supply
· Keypads are all MAXSYS DSC - 4501 keypads
· Commercial Fire Control Communicator - MAXSYS DSC PC4020CF with additional Keltron expanders
· Communication from each building to the main system - Keltron Partyline Event Transceiver (PET 404 or 408)
· Fire panels vary throughout the park - Faraday LiefWatch 41, FireLite MS-2, MS-4, or MS-5UD, and DMP Fire Command Center XR150FC/XR550FC
· Power Supply - Potter PSN-64 is at the Birthplace Cottage
· Burglary panels - most buildings have a PC4020 (unknown make)
· Motion detectors vary - multiple brands of addressable to non-addressable
· Smoke detectors - mostly System Sensor i3 Series
· Heat detectors - mostly System Sensor 5600 Series (135 and 194 degrees)
· Fire alarm pull stations - FireLite Alarms at Visitor Center and Post Office
· Multiple makes and models of horn strobes.
· Unknown make and models of hold up alarms at the Visitor Center and Post Office
2. Who is running the cabling for the property?
Answer: The awardee will be responsible for running the cabling.
3. Are we hanging devices and running all cabling? or is a subcontractor running all cabling too where the devices will be installed, and we are connecting the devices?
Answer: The awardee will be responsible for all the wiring, including removing the old wiring, devices, and panels.