This document is an Asbestos Survey Report for the Canaveral National Seashore Facility located at 7611 South Atlantic Avenue in New Smyrna Beach, Florida. Conducted by Professional Service Industries, Inc. (PSI) on May 5, 2025, the survey investigated the presence of asbestos-containing materials (ACM) in the facility's approximately 1,587 square foot residential-type structure.

The survey identified three homogeneous areas with asbestos-containing materials: gray siding containing 25% chrysotile asbestos across approximately 1,587 square feet, exterior window caulk containing 5% chrysotile asbestos across less than 500 square feet, and soffit caulking with no asbestos detected. The report recommends that all Category I & II non-friable ACMs must be properly removed by a licensed asbestos abatement contractor prior to renovation, following federal, state, and local regulations. The survey was performed in accordance with EPA AHERA and NESHAP guidelines, with samples analyzed by PSI's NVLAP-accredited laboratory using polarized light microscopy.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NESHAP Renovation Asbestos Survey Report

Canaveral National Seashore Facility 7611 South Atlantic Avenue

New Smyrna Beach, Florida 32169

Prepared for:

Canaveral National Seashore 212 South Washington Avenue

Titusville, Florida 32796

Prepared by:

Professional Service Industries, Inc.

1748 33rd Street

Orlando, Florida 32839 407-304-5560

May 14, 2025

PSI Project Number: 06637114-1

Kyle Pratt Asbestos Inspector Lic. or Cert. #: 139350681

Jeremy Jernigan, CIH, CSP, CHMM Principal Consultant-FLAC #AX73

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 PURPOSE AND SCOPE OF SERVICES

1.2 AUTHORIZATION AND ACCESS

1.3 LIMITATIONS

2.0 GENERAL PROPERTY, BUILDING, AND SURVEY INFORMATION

2.1 PROPERTY AND BUILDING INFORMATION

2.2 SURVEY INFORMATION

3.0 METHODOLOGY

3.1 GENERAL REFERENCES

3.2 RECORD DOCUMENT REVIEW

3.3 VISUAL INSPECTION PROCEDURES

3.4 ASBESTOS SAMPLING PROCEDURES

3.5 ASBESTOS ANALYSIS PROCEDURES

3.6 QUANTIFICATION

3.7 PHOTOGRAPHIC DOCUMENTATION

4.0 FINDINGS

4.1 INACCESSIBLE AND/OR UNACCESSED AREAS

5.0 CONCLUSIONS AND RECOMMENDATIONS

5.1 CONCLUSIONS

5.2 RECOMMENDATIONS AND OTHER CONSIDERATIONS

6.0 WARRANTY AND THIRD PARTY RELIANCE

6.1 STANDARD OF CARE AND WARRANTIES

6.2 RELIANCE

6.3 THIRD PARTY RELIANCE

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025 Page i www.intertek.com/ building/psi

LIST OF APPENDICES

PHOTOGRAPHS

BULK SAMPLE ANALYSIS AND CHAIN-OF-CUSTODY DOCUMENTATION

LABORATORY ACCREDITATION DOCUMENTATION

COMPANY LICENSE DOCUMENTATION

PERSONNEL ACCREDITATION DOCUMENTATION

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025 Page ii

LIST OF ACRONYMS OR ABBREVIATIONS

Acronym or Abbreviation Definition

ACM Asbestos-Containing Material

ACBM Asbestos-Containing Building Material

AHERA Asbestos Hazard Emergency Response Act

AIHA American Industrial Hygiene Association

CAT. I NF Category I Non-Friable

CAT. II NF Category II Non-Friable

CFR Code of Federal Regulations

CMU Concrete Masonry Unit

EPA Environmental Protection Agency

HA Homogeneous Area

HVAC Heating, Ventilation, and Air Conditioning

MJP Mudded Joint Packing

NESHAP National Emission Standards for Hazardous Air Pollutants

NVLAP National Voluntary Laboratory Accreditation Program

O&M Operations & Maintenance

OSHA Occupational Safety and Health Administration

PACM Presumed Asbestos-Containing Material

PLM Polarized Light Microscopy

PSI Professional Service Industries, Inc., an Intertek company

PT Point Count

RACM Regulated Asbestos-Containing Material

TEM Transmission Electron Microscopy

TSI Thermal System Insulation

VFT Vinyl Floor Tile

VJC Vibration Joint Cloth

VSF Vinyl Sheet Flooring

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025 Page iii

1.0 INTRODUCTION

PSI was retained by Canaveral National Seashore to perform a survey for suspect ACM at the Canaveral National Seashore Facility, located at 7611 South Atlantic Avenue in New Smyrna Beach, Florida 32169.

This project encompassed the exterior siding of an approximately, 1,587 SF residential type structure, hereinafter referred to as the Project Area. The field work was conducted on May 5, 2025.

1.1 PURPOSE AND SCOPE OF SERVICES

The purpose of this survey was to provide general information for the Project Area regarding the presence, condition, and quantity of accessible and/or exposed friable and non-friable materials suspected to contain asbestos.

The survey of the Project Area was conducted in general accordance with the EPA AHERA and the NESHAP sampling guidelines to determine the presence and general locations of exposed and/or physically accessible suspect ACM, and provide photographic documentation of each homogeneous area.

Each suspect material was touched, where possible, to determine the friability of the material. Samples were obtained only from suspect ACM that were readily exposed and/or physically accessible during the survey

Samples were sent to the PSI NVLAP accredited laboratory located at 850 Poplar Street, in Pittsburgh, PA, for analysis. Each sample underwent PLM analysis for detection of asbestos fibers in the building materials on a “positive stop” basis, which is defined as follows: if one sample in the sample group has an analysis indicating that the material contains asbestos at a concentration greater than 1%, then the remaining samples in the group are not analyzed.

1.1.1 INFORMATION PROVIDED BY THE CLIENT

No documents were provided by the client during the course of this survey.

1.2 AUTHORIZATION AND ACCESS

Authorization to perform the survey was given on April 21, 2025, by the receipt of a signed copy by PSI of PSI Proposal Number 0663-450177, between Canaveral National Seashore and PSI.

Access to the property was provided by Leonardo Da Silva. PSI was escorted by Leonardo Da Silva during the field work for this project.

1.3 LIMITATIONS

This asbestos survey was intended to meet the requirements of the NESHAP for Asbestos renovation. The survey included a thorough inspection of the reported areas of planned renovation.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025 www.intertek.com/building/psi

Roof Systems were not included in the scope of this survey.

Destructive sampling, such as behind finished surfaces (plaster/drywall walls, above hard ceilings, etc.) inside mechanical chases, behind mirrored walls, under carpet or tiled floors, etc., was not generally conducted to assess inaccessible or concealed materials.

Although PSI made an attempt to identify all areas of ACM, an exhaustive investigation of void spaces was not included in the scope of services for this project. There may exist conditions which were unable to be identified within the scope of this survey.

Inaccessible is defined as areas of the building that were locked, or where admittance was not permitted.

It also includes areas/materials that could not be tested (sampled) without destruction of the structure or a portion of the structure, and areas/materials that could not be safely reached by the inspector or inspection team. In the event that access to a portion of the building was not obtained (which otherwise would have been tested), such limitations specifically are identified in the Findings Section of this report.

PSI did not inspect for or sample materials in areas or locations which presented a hazard to the inspection team, such as those associated with energized electrical systems or within confined spaces.

PSI did not collect samples from building elements where the intended use would be compromised by testing, such as fire rated doors, vapor barriers, mirror mastics, etc. If observed, such materials were assumed to be asbestos-containing.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

2.0 GENERAL PROPERTY, BUILDING, AND SURVEY INFORMATION

2.1 PROPERTY AND BUILDING INFORMATION

SUBJECT PROPERTY: Canaveral National Seashore Facility 7611 South Atlantic Avenue New Smyrna Beach, Florida 32169

CONSTRUCTION DATE: 1965

PREVIOUS RENOVATION DATE OR

DATES:

Not Reported

NUMBER OF FLOORS: One

ESTIMATED SQUARE FOOTAGE: 1,587 SF

CONSTRUCTION TYPE: Residential

VACANT? (YES/NO) Yes

ADDITIONAL INFORMATION: None Provided

2.2 SURVEY INFORMATION

NAME OF INSPECTOR: Kyle Pratt

LICENSE/CERTIFICATION NUMBER: 139350681

DATE OF SURVEY AND SAMPLING: May 5, 2025

ESCORT: Leonardo Da Silva

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

3.0 METHODOLOGY

3.1 GENERAL REFERENCES

Survey, sampling, and analysis, procedures were performed in general accordance with the guidelines published by the EPA in 40 CFR Part 763 Subpart E, October 30, 1987, the OSHA Asbestos Construction Standard, found in 29 CFR 1926.1101, and in the NESHAP regulation (40 CFR Part 61, April 6, 1973, revised 1990).

3.2 RECORD DOCUMENT REVIEW

If available, prior to conducting the visual inspection, PSI reviewed documents provided by the client including: drawings, floor plans, historical data, maintenance records, previous survey reports, laboratory reports, etc. for information regarding construction history and building materials. This data was used to focus the walk through and scope of work to be followed over the course of our visual inspection and sampling. Information obtained from the references was incorporated into the Findings Section of the report.

3.3 VISUAL INSPECTION PROCEDURES

An initial walkthrough of the Project Area was conducted to determine the presence and condition of suspect materials which were physically accessible and/or exposed. Materials which were similar in general appearance were grouped into HAs. In addition, the friability of the suspect material was determined. A material is defined as friable (F) if the material can be reduced to a powder by hand pressure when dry.

Non-Friable (NF) materials that are damaged can also be considered friable.

3.3.1 HOMOGENEOUS AREA CLASSIFICATIONS

A walk-through of the Project Area was conducted to determine areas of materials which were visually similar in color, texture, general appearance, and which appeared to have been installed at the same time. Such materials are termed HAs by the EPA AHERA regulation. During this walk-through, the approximate locations of these HAs were also noted. Only materials which were physically accessible and/or exposed and suspected to contain asbestos were identified and placed in homogeneous areas.

Following the EPA AHERA inspection protocol, each identified HA was placed in one of the following AHERA classifications for the purposes of determining the number of samples to collect:

• Surfacing Materials: spray or trowel applied to building members;

• TSI: materials generally applied to various mechanical systems; or

• Miscellaneous Materials: any materials which do not fit either of the above categories.

Following the EPA NESHAP inspection protocol, each identified suspect homogeneous material that was confirmed as an ACM was also placed in one of the following NESHAP classifications:

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

• Friable Materials: NESHAP defines a friable ACM as any material containing more than one percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

• Category I Non-Friable (Cat. I NF): NESHAP defines a Category I non-friable ACM as packing, gaskets, resilient floor covering (except vinyl sheet flooring products which are considered friable), and asphalt roofing products which contain more than one percent asbestos.

• Category II Non-Friable (Cat. II NF): NESHAP defines a Category II non-friable ACM as any material, except for a Category I non-friable ACM, which contains more than one percent asbestos and cannot be reduced to a powder by hand pressure when dry.

In the NESHAP regulation, a regulated asbestos-containing material (RACM) is defined as any (a) friable asbestos material; (b) Category I Non-Friable ACM that has become friable; (c) Cat. I NF ACM that will be or has been subjected to sanding, grinding, cutting, or abrading; or (d) Category II Non-Friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations.

3.4 ASBESTOS SAMPLING PROCEDURES

Following the walk-through, the inspector collected selected samples of exposed and/or physically accessible materials identified as suspect ACM. Sampling was limited to those physically accessible materials not involving the destruction of walls, other building elements, physical barriers, or the structural integrity of the item being tested.

EPA guidelines were used to determine the sampling protocol. Sampling locations were chosen to be representative of the homogeneous area.

Where possible, samples of surfacing material, if present, were collected in general accordance with the EPA random sampling protocol outlined in the EPA publication, "Asbestos in Buildings: Simplified Sampling Scheme for Friable Surfacing Materials" (EPA 560/5-85-030a, October, 1985). The homogeneous area was divided into a grid of nine sub-areas. If nine samples were taken, one sample was taken from each sub-area.

If less than nine samples were taken, the EPA random numbering diagram was used to determine which sub-areas would be sampled. While an effort was made to extract the samples from approximately the middle of the sub-area, samples were taken preferentially from already damaged areas or areas which were the least visible.

Samples of TSI and miscellaneous materials were taken as randomly as possible while again attempting to sample already damaged areas so as to minimize disturbance of the material.

After each sample was extracted, where applicable, a spray encapsulant and/or tape covering was applied to the sampled area to prevent potential fiber release.

In accordance with the agreement between PSI and the client, roofing materials were not sampled as part of this survey.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

3.5 ASBESTOS ANALYSIS PROCEDURES

The samples were analyzed at PSI's Asbestos Laboratory, located in Pittsburgh, PA. The PSI Asbestos Laboratory is a NVLAP Accredited (ID number 101350-0) Laboratory. A copy of the Laboratory’s Accreditation Certificate is included in the Appendix.

The samples were analyzed for asbestos on a “positive-stop” basis by PLM in accordance with the "Interim Method for the Determination of Asbestos in Bulk Insulation Samples" (EPA 600/M4-82-020). Analysis was performed by visually observing the bulk samples with a stereoscope, followed by slide preparation(s) for microscopic examination and identification.

Using a stereoscope, the microscopist visually estimated relative amounts of each constituent by determining the volume of each constituent in proportion to the total volume of the sample. Next, the samples were mounted on slides and analyzed by PLM for asbestos (chrysotile, amosite, crocidolite, anthophyllite, actinolite/tremolite), and fibrous non-asbestos constituents (mineral wool, fiberglass, cellulose, etc.).

Asbestos was identified by refractive indices, morphology, color, pleochroism, birefringence, extinction characteristics, and signs of elongation. The same characteristics were used to identify the non-asbestos constituents.

It should be noted that some ACM might not be accurately identified or quantified by PLM. As an example, the original fabrication of vinyl floor tiles routinely involved milling of asbestos fibers to extremely small sizes.

As a result, these fibers may go undetected under the standard PLM method. TEM is another method that can provide a more definitive analysis of these materials, but was not in the scope of work for this project.

3.5.1 LABORATORY QUALITY CONTROL PROGRAM

The PSI Laboratory in Pittsburgh, PA, maintains an in-house quality control program. This program involves blind reanalysis of ten percent of all samples, precision and accuracy controls, and use of standard bulk reference materials. In addition, the laboratory is accredited by NVLAP, which also has quality control procedures inherent in its program.

3.6 QUANTIFICATION

Quantities of physically accessible and/or exposed confirmed ACM were estimated. This estimation was performed by taking approximate measurements in the field or estimating quantities based on as-built mechanical or structural drawings. Materials such as pipe insulation and associated MJP were categorized according to the outside diameter of the insulation. Pipe insulation was quantified by linear footage of the insulation while the actual number of MJPs was counted. Insulation on mechanical equipment such as boilers and duct work was quantified by the square footage of the surface area of suspect insulation. Similarly, fireproofings, plasters, ceiling and floor tiles, and cementitious panels were measured in square feet of surface area. The quantities of confirmed ACM that were identified during this investigation are reported in the Tables later in this report.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

Quantities identified in this report are estimates, are intended as order of magnitude information or for general policy discussions, and should be confirmed by an abatement contractor when renovation or demolition is contemplated.

3.7 PHOTOGRAPHIC DOCUMENTATION

Photographs of HAs were taken during the course of this survey. While these photographs were not intended to provide a complete record of the survey, they do provide a visual description of the HA . Photographs of HAs are intended to depict a representative portion of that HA. The captioned photographs taken during this survey are appended.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

4.0 FINDINGS

A total of 6 samples were collected from 3 suspect HAs during the asbestos survey.

The tables below list the suspect ACM observed in the Project Area. Table 1 lists the materials that were sampled, along with the results of the inspection and laboratory analysis.

The table or tables provide a description of the materials, their general locations, condition, friability, and, if applicable and/or within the scope of work, EPA NESHAP Category, and estimated quantities.

In the following table or tables, items that are confirmed or assumed to be ACM are indicated in bold and items that contain less than 1% asbestos, but are not 'no asbestos detected' are indicated by italics.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

TABLE 1 - SUSPECT ACM - SAMPLED

HA

# of

Samples Material Description Material Location Sample Locations F/NF Condition % Asbestos & Type EPA NESHAP Category Estimated Quantity

1 2 Gray Siding Exterior Northeast Corner & Southwest Corner NF Good 25% Chrysotile Cat. I NF ~1,587 SF

2 2 Exterior Window Caulk Exterior Northeast Corner Window & West Central Window NF Good 5% Chrysotile Cat. I NF <500 SF

3 2 Soffit Caulking Exterior Southeast Corner & Northwest Corner NF Good NAD NAD NAD

NOTES: F=Friable, NF=Non-Friable; Dam.=Damaged, Sig. Dam.=Significantly Damaged; NAD=No Asbestos Detected, CH=Chrysotile, AM=Amosite, CR=Crocidolite, TR=Tremolite, AC=Actinolite, AN=Anthophyllite, PT=Point Count Analysis; RACM=Regulated ACM, Cat. I NF=Category I Non-Friable ACM, Cat. II

NF=Category II Non-Friable ACM; SF=square feet; LF=lineal feet; EA=each; N/A=Not Applicable

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

4.1 INACCESSIBLE AND/OR UNACCESSED AREAS

PSI did not encounter areas where access was denied or prohibited at the time of the field activities.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

5.0 CONCLUSIONS AND RECOMMENDATIONS

5.1 CONCLUSIONS

ACM (>1% asbestos) was identified based on the samples collected from the materials in the Project Area at the Canaveral National Seashore Facility.

Assumed ACM was not identified in the Project Area at the Canaveral National Seashore Facility.

5.2 RECOMMENDATIONS AND OTHER CONSIDERATIONS

Category I & II non-friable ACMs, must be properly removed by a licensed asbestos abatement contractor prior to renovations that would disturb the material. Federal, State and Local regulations and guidelines should be strictly adhered to when removing the ACM.

If additional suspect materials not documented in this report are encountered during work activities, the material should be considered asbestos-containing unless bulk sampling is performed and laboratory analysis proves otherwise. The renovation and/or demolition contractor should provide oversight to ensure that additional found suspect ACM is properly tested, if practical, or treated as asbestos-containing.

The client should consult the EPA’s NESHAP standard, the State of Florida’s asbestos regulations, and any local regulations for additional details regarding asbestos-related demolition or renovation procedures and requirements.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

6.0 WARRANTY AND THIRD PARTY RELIANCE

6.1 STANDARD OF CARE AND WARRANTIES

The field and laboratory results reported herein are considered sufficient in detail and scope to determine the presence of accessible and/or exposed suspect ACM for the Project Area. PSI warrants that the findings contained herein have been prepared in general accordance with accepted professional practices at the time of its preparation as applied by professionals in the community. Changes in the state of the art or in applicable regulations cannot be anticipated and have not been addressed in this report.

The scope of work addressed readily accessible and exposed locations within the Project Area. Observation or sampling of inaccessible areas such as behind walls or within ductwork was not performed unless otherwise noted in this report. The survey and analytical methods have been used to provide the client with information regarding the presence of accessible and/or exposed suspect ACM existing at the time of the survey. Test results are valid only for the material or materials tested. There is a distinct possibility that conditions may exist which could not be identified within the scope of the survey or which were not apparent during the on-site work. The survey is also limited to the information available from the client at the time it was conducted.

The methodologies may include reviewing information provided by other sources. PSI treats information obtained from interviews or other sources as reliable, complete and accurate. The scope of work did not require PSI to independently verify the information provided. Therefore, PSI cannot and does not warrant or guarantee that the information provided by these other sources is reliable, complete or accurate.

Our services were not intended to be technically exhaustive. There is a possibility that with the proper application of methodologies, conditions may exist on the property that could not be identified within the scope of the survey or that were not reasonably identifiable from the available information. The report may not represent all conditions at the subject property or project area as it only reflects the information gathered from specific locations on the date of the survey. No inspection can wholly eliminate uncertainty regarding the potential for asbestos in connection with the subject property.

The observations and/or recommendations presented in this report are time dependent, and conditions will change. This report speaks only as of its date.

As directed by the client, PSI did not provide any service to investigate or detect the presence of moisture, mold or other biological contaminants in or around any structure, or any service that was designed or intended to prevent or lower the risk of the occurrence of the amplification of the same. Client acknowledges that mold is ubiquitous to the environment with mold amplification occurring when building materials are impacted by moisture. Client further acknowledges that site conditions are outside of PSI’s control, and that mold amplification will likely occur, or continue to occur, in the presence of moisture. As such, PSI cannot and shall not be held responsible for the occurrence or recurrence of mold amplification.

No other warranties are implied or expressed.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

6.2 RELIANCE

Canaveral National Seashore, PSI's client, may rely on this report.

6.3 THIRD PARTY RELIANCE

This report was prepared pursuant to a contract between PSI and its client. That contractual relationship included an exchange of information about the property that was unique and serves as the basis upon which this report was prepared. Because of the importance of these understandings, our survey may not be sufficient for the intended purposes of another party.

Reliance or any use of this report by anyone other than those parties identified above for which it was prepared, except with express written permission, is prohibited and therefore not foreseeable to PSI. Any unauthorized reliance on or use of this report, including any of the information or conclusions contained herein, will be at the third party's risk. No warranties or representations expressed or implied in this report are made to any such third party.

Third party reliance letters may be issued:

• upon timely request;

• subject to the permission of our original client; and

• payment of the then-current fee for such letters.

All third parties relying on our report, by such reliance, agree that such reliance is limited by our proposal and/or General Conditions, as applicable.

Work Order Number 06637114-1 Canaveral National Seashore Facility

May 14, 2025

PHOTOGRAPHS

Photo 1: Site Photo

Photo 2: Representative photo of HA1

Photo 3: Representative photo of HA2

Photo 4: Representative photo of HA3

BULK SAMPLE ANALYSIS AND

CHAIN-OF-CUSTODY

DOCUMENTATION

REPORT OF BULK SAMPLE ANALYSIS FOR ASBESTOS

TESTED FOR: PSI, Inc.

Canaveral National Seashore Facility

Date Received: 5/6/2025 Date Completed: 5/9/2025

1748 33rd Street Orlando, FL 32839 Attn: Kyle Pratt

Project ID: 06637114-1

Orlando, Florida

Date Reported: 5/9/2025

Page: 1 of 1Analyst: Chris Kopar Work Order: 2505135

Lab ID (Layer)

Asbestos Content

(Percent and Type)

Non-asbestos Fibers

(Percent and Type)

Client ID Sample Description (Color, Texture, Etc.)

Analyst's Comment

001A1A (1) Gray, Siding, Homogeneous Chrysotile25% None Reported

(2) Black, Tar Paper, Homogeneous 85% Cellulose FiberNO ASBESTOS DETECTED

002A1B (1) Gray, Siding, Homogeneous Chrysotile25% None Reported

(2) Black, Tar Paper, Homogeneous 85% Cellulose FiberNO ASBESTOS DETECTED

003A2A (1) White, Caulking, Homogeneous NO ASBESTOS DETECTED None Reported

004A2B (1) White, Caulking, Homogeneous NO ASBESTOS DETECTED None Reported

(2) Green, Caulking, Homogeneous Chrysotile5% None Reported

005A3A (1) White, Caulking, Homogeneous NO ASBESTOS DETECTED None Reported

006A3B (1) White, Caulking, Homogeneous NO ASBESTOS DETECTED None Reported

Report Notes: (PT) Point Count Results

Quantitation is based on a visual estimation of the relative area of bulk sample components, unless otherwise noted in the "Comments" section of this report. The results are valid only for the item tested as received. This report may not be used to claim product endorsement by NVLAP or any agency of the U.S. Government. Method used: E.P.A.

Interim Method for the Determination of Asbestos in Bulk Insulation Samples (EPA 600/M4-82-020). Polarized Light Microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative Transmission Electron Microscopy is currently the only method that can be used to determine if the material can be considered or treated as non-asbestos containing. Samples will be disposed of within 30 days unless notified in writing by the client. No part of this report may reproduced, except in full, without written permission of the laboratory. The reporting limit is 1% by weight. NVLAP Lab Code 101350-0.

Respectfully submitted, Approved Signatory

PSI, Inc.

Professional Service Industries, Inc. 850 Poplar Street, Pittsburgh, PA 15220 Phone 412/922-4010 Fax 412/922-4014

George Skarupa

LABORATORY ACCREDITATION

COMPANY LICENSE

Melanie S. Griffin, SecretaryRon DeSantis, Governor

STATE OF FLORIDA

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

THE ASBESTOS BUSINESS ORGANIZATION HEREIN IS LICENSED UNDER THE

PROVISIONS OF CHAPTER 469, FLORIDA STATUTES

PROFESSIONAL SERVICE INDUSTRIES, INC.

Do not alter this document in any form.

545 EAST ALGONQUIN ROAD

LICENSE NUMBER: ZA101

EXPIRATION DATE: NOVEMBER 30, 2025

This is your license. It is unlawful for anyone other than the licensee to use this document.

ARLINGTON HEIGHTS IL 60005

Always verify licenses online at MyFloridaLicense.com

PERSONNEL ACCREDITATION

Certificate: 139350681

Date of Course Completion April 7, 2025

William H. Goulet, Instructor

Kyle Pratt

Building Inspector Annual Refresher - Florida

Has attended and completed Refresher training in accordance with Title II of TSCA, 40 CFR Part 763 Appendix C to Subpart E as revised

Certificate of Completion info@asbestosonlinetraining.com

Expiration Date April 7, 2026

Date of Course Examination April 7, 2025 with Passing Score of 70% or Higher via online course

Course # FL-490006359 Provider # FL-490005406

This is to certify that

Asbestos Online Training, LLC 7452 2nd Street E

Redington Shores, Florida 33708

727-873-6442

Melanie S. Griffin, SecretaryRon DeSantis, Governor

STATE OF FLORIDA

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

THE ASBESTOS CONSULTANT HEREIN IS LICENSED UNDER THE

PROVISIONS OF CHAPTER 469, FLORIDA STATUTES

JERNIGAN, JEREMY RYAN

Do not alter this document in any form.

PROFESSIONAL SERVICE INDUSTRIES, INC.

LICENSE NUMBER: AX73

EXPIRATION DATE: NOVEMBER 30, 2026

This is your license. It is unlawful for anyone other than the licensee to use this document.

545 EAST ALGONQUIN ROAD

ARLINGTON HEIGHTS IL 60005

Always verify licenses online at MyFloridaLicense.com

ISSUED: 09/06/2024

https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=bdbf6ec9ffe891a69dcc0f823fafbd4e https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=bdbf6ec9ffe891a69dcc0f823fafbd4e

Title Page
1.0 INTRODUCTION
1.1 PURPOSE AND SCOPE OF SERVICES
1.1.1 Information Provided by the Client
1.2 AUTHORIZATION AND ACCESS
1.3 LIMITATIONS
2.0 GENERAL PROPERTY, BUILDING, AND SURVEY INFORMATION
2.1 PROPERTY AND BUILDING INFORMATION
2.2 SURVEY INFORMATION
3.0 METHODOLOGY
3.1 GENERAL REFERENCES
3.2 RECORD DOCUMENT REVIEW
3.3 VISUAL INSPECTION PROCEDURES
3.3.1 Homogeneous Area Classifications
3.4 ASBESTOS SAMPLING PROCEDURES
3.5 ASBESTOS ANALYSIS PROCEDURES
3.5.1 Laboratory Quality Control Program
3.6 QUANTIFICATION
3.7 PHOTOGRAPHIC DOCUMENTATION
4.0 FINDINGS
4.1 INACCESSIBLE AND/OR UNACCESSED AREAS
5.0 CONCLUSIONS AND RECOMMENDATIONS
5.1 CONCLUSIONS
5.2 RECOMMENDATIONS AND OTHER CONSIDERATIONS
6.0 WARRANTY AND THIRD PARTY RELIANCE
6.1 STANDARD OF CARE AND WARRANTIES
6.2 RELIANCE
6.3 THIRD PARTY RELIANCE
PHOTOGRAPHS
BULK SAMPLE ANALYSIS AND CHAIN-OF-CUSTODY DOCUMENTATION
LABORATORY ACCREDITATION DOCUMENTATION