160-127398A_As_Built_Coe_HVAC_0002.pdf
PDF 12 MB Posted
- Attached to
- REPLACE HVAC AT ERNEST COE VC Federal contract opportunity
- Solicitation number
- 140P5425R0010
About this file
The document is a set of Red Line As-Built Drawings for the Ernest Coe Visitor Center HVAC replacement project at Everglades National Park in Homestead, Florida. The technical drawings, associated with Contract #P15PC00432, detail modifications to the existing HVAC system, including specifications for air handling units (AHU-1, AHU-2, AHU-3) and condensing units (CU-1A/1B, CU-2A/2B, CU-3A/3B). The drawings include detailed floor plans, mechanical room layouts, roof construction details, and system service literature, documenting the HVAC system upgrades completed on 06/03/2016. The project was prepared for the National Park Service, with William Shelley listed as the Contracting Officer's Representative (COR), and covers modifications to the visitor center's heating, ventilation, and air conditioning infrastructure.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers_0002.pdf | ||
| Sol_140P5425R0010_Amd_0002.pdf | ||
| Pages_from_1996_EVER-246_Plans_0002.pdf | ||
| Sol_140P5425R0010_Amd_0001.pdf | ||
| Sol_140P5425R0010.pdf | ||
| Wage_Determination.pdf | ||
| Past_Performance_Questionnaire.pdf | ||
| Statement_of_Work.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RED LINE AS-BUILT DRAWINGS
Prepared for:
National Parks Service (NPS) Ernest Coe Visitor Center
40001 SR 9336
Homestead, FL 33034
COR: William Shelley
Location of Project: Ernest Coe Visitor Center Title of Project: Replacing HVAC at Visitor Center
Contract #: P15PC00432 wshelley Typewritten Text Completion Date: 06/03/2016 wshelley
Drawing Number 160/127,398A
TABLE OF CONTENTS
Page
1 RED LINE AS-BUILT DRAWINGS
2 EXHIBIT ROOM SYSTEM SERVICE LITERATURE
3 AUDITORIUM SYSTEM SERVICE LITERATURE
4 MAIN ROOM SYSTEM SERVICE LITERATURE ................................................ 50-102
4.1 AIR HANDLER UNIT
4.2 CONDENSER UNIT
LEGEND
TO
FORT MYERS
PARK BOUNDARY
COUNlY LINE
RANGER STATION
VISITOR CENTER
OBSERVATION TOWER
PUBLIC AIRPORTS
SWAMP OR SLOUGH
--:-:-:-:-:-:-:-:-:-- _- 1 -:-:-:-:-:-- --------- - -- ------
TO- KEY-:-:-- ...: ::: _-:-:-:-:-:---
WEST __ :::::::::---
WATER
LAND OUTSIDE PARK I& EVERGLADES NATIONAL
~" WORLD HERITAGE SITE
I
PARK
SCALE OF MILES
0 5 10
I I I I I I
I
5 0 5 10 15
SCALE OF KILOMETERS
TO FLAMINGO
SHEET
HEADQUARTERS BUILDING
SITE MAP
SUB SHEET
SITE ADDRESS:
40001 STATE ROAD 9336
HOMESTEAD, FL 34139
(j 100
DRAWING INDEX
TITLE
COVER AND INDEX
EXISTING HVAC SYSTEM
MECHANICAL ROOM 1
MECHANICAL ROOM 2
EXHIBIT ROOM AND MAIN LOBBY
0 100
SCALE OF FEET
CONSTRUCTION DRAWINGS
TITLE OF SHEET
MODIFY COE VC HVAC
UNITED STATES
DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
EVERGLADES NATIONAL PARK
LOCATION WITHIN PARK
ERNEST COE VISITOR CENTER
NAME OF PARK
EVERGLADES NATIONAL PARK
REGION
SOUTHEAST
COUNIY
MIAMI-DADE
DRAWING NO.
127,398
PMIS/PKG NO.
203625
SHEET
_1_oF _Q_
CONCRETE BEAMS
TYPICAL BUILDING SECTION
WALKWAY
6X8 OPEN
END DUCT
6X8 OPEN
END DUCT
ZONE 2
1150 SF
SCALE: NO SCALE
D-5
W/8"~NECK
330 CFM
TYP OF 3
CONDENSING UNITS 2A & 2B
CONDENSING UNITS 3A & 3B
SHEET 4 MODIFICATIONS__/"
CONDENSING UNITS ---..~--..1.._.
1A & 1B
0-3 48"-2 SLOT
MAIN
ROOM
140 CFM
VISITOR CENTER FLOOR PLAN
SCALE: SCALE A
EXISTING AIR HANDLING UNIT DESIGN PARAMETERS
SEE SPECIFICATIONS FOR SIZING NEW UNITS. NEW UNITS DD NOT
NECESSARILY MATCH THE OLD.
UNIT COOLING
HEATING
FAN (CFM) CAPACITY
NUMBER CAPACITY {MBH)
(KILOWATIS)
AHU-1 8000
AHU 2 1100
AHU-3 1320
SHEET 3
· MODIFICATIONS
30X84 OA LOUVER WITH
30X12X84 PLENUM
BEHIND tz9UVER
PORCH
260 27
85 9
79 11
EXISTING CONDENSING
UNIT DESIGN
PARAMETERS
SEE SPECIFICATIONS FOR
SIZING NEW UNITS. NEW
UNITS DO NOT NECESSARILY
MATCH THE OLD.
UNIT COOLING
NUMBER CAPACITY (MBH)
CU-1A
CU-1B
CU-2A
CU-2B
CU-3A
CU-3B
130.0
130.0
41 .5
41.5
37.5
COVERED
WALKWAY
r--__,ff-~.--SHEET 5
MODIFICATIONS
24X10 0-4
580 CFM
60X48 RELIEF AIR R-2
ABOVE PRESENTATION
CEILING
TYP ROOF CONSTR STANDING SEAM
METAL ROOF ON ASPHALT RAG FELT
UNDER LAYMENT &
VAPOR RETARDER
WD BLOCKING
TYP WALL-ROOF DETAIL
HORIZ WO SIDING.
AT INTERIOR THEATER
WALL SUBSTITUTE f' TH
CEDAR SHIP LAP SIDING
FOR BEVELED SIDING-
ALIGN COURSING WITH
EXTl~RIOR
SCALE: NO SCALE
1'-3/4"
~" PLWD SHEATHING---------+i.__j
1 1 /2" RIGID INSUL & 2X4 -------j~-~:l§it
WO STUDS «!) 16" QC-PRESS
TRTD @ EXTERIOR
VAPOR RETARDER
8" CMU ----
SHEET ~5
MODIFIC.~TIONS
2 1/2" METAL
STUDS @ 16" OC
24X24 R-1 W/22X22
NECK AIR RELIEF
0 - 5 48"-4 SLOT W/8"~
NECK 330 CFM (TYP OF 4)
i" PLYWD @ SOUTH AND WEST -----<1'111
WALLS IN EXHIBIT/LOBBY
TYP WALL DETAIL
SCALE: NO SCALE
DESIGNED: SUB SH EET NO. TITLE OF SHEET
TOP OF TIE BEAM
EL 10.20' AFF
DRAWING NO
ZONE 3
880 SF
~ W H SHELLEY
DRAWN:
EXISTING HVAC SYSTEM 160
127,398
SCALE A
8 ' 0 8 ' 16'
W H SHELLEY
TECH. REVIEW:
MPS
DATE:
04/2015
ERNEST COE VISITOR CENTER
EVERGLADES NATIONAL PARK
PMI S NO.
203625
SHEET
~of___§_ erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text erik.venergy Typewritten Text 37.5 erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Typewritten Text
REPLACED WITH NEW CU-1
erik.venergy Polygonal Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Typewritten Text
SECTION OF PLENUM DEMO'D
CONVERTED TO OPEN RETURN
erik.venergy Typewritten Text
LOUVER CAPPED
erik.venergy Line erik.venergy Typewritten Text
REPLACED WITH
NEW AHU-1
erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Oval erik.venergy Line erik.venergy Typewritten Text
SHEET 5 MODIFICATIONS
erik.venergy Polygonal Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Typewritten Text
LOUVER CAPPED
erik.venergy
DAMPER DEMO'D
erik.venergy Typewritten Text
PLENUM DEMO'D
CAPPED AT CEILING
erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygon erik.venergy Typewritten Text
EXISTING RE-DESIGNATED AS
CU-2A & CU-2B
erik.venergy Typewritten Text
EXISTING RE-DESIGNATED AS CU-3
erik.venergy Typewritten Text
CONDENSER DE-COMMISSIONED
& RETURNED TO NPS
erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Typewritten Text
REPLACED WITH NEW AHU-2
erik.venergy Typewritten Text
LOUVER
CAPPED
erik.venergy Typewritten Text
REPLACED WITH
NEW AHU-3
erik.venergy Typewritten Text
DEMO'D R/A PLENUM TO CEILING
CONVERTED TO OPEN RETURN
erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Rectangle erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Typewritten Text 10" erik.venergy Oval erik.venergy Line erik.venergy Polygonal Line erik.venergy Line erik.venergy Typewritten Text
SECONDARY 24"X24" RETURN
WITH 10" ROUND DUCT ADDED
TO SERVICE THEATER
erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygon erik.venergy Polygon erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line
Line
DRILL THROUGH WALL NEAR FLOOR. FOR REFRIGERENT LINES.
ELBOW DOWN AND RUN UNDER DECKING. COVER EXPOSED
REFRIGERANT LINES WITH SHEET METAL PAINTED TO MATCH SIDING
COLOR.
PORCH REMOVE EXISTING OUTSIDE AIR
DAMPER AND SEAL PLENUM WITH
SHEET METAL
1------
ADD I
SUPPORTS AS ------I
REQUIRED I
EXISTING\
10'-11 ·x1'-11 •
CONCRETE PAD
I I
L
ABOVEGROUND ROUTE OF
NEW REFRIGERANT LINES.
CONNECT TO EDGE OF
EXISTING PORCH
REPLACE CONDENSING
UNITS 1A & 1B WITH A
NEW CONDENSING
UNITOR UNITS.
CONNECT TO EXISTING
ELECTRICAL BOXES FOR
POWER
CONCRETE
SIDEWALK
II
EXISTING ELE TRICAL BOXES
EACH WITH A 208V 3111, 125
AMP CIRCUIT
RETURN AIR
30x28
ELECTRICAL BOX FOR
AIR HANDLER 208V, 3111,
45 AMP
FIRE
SPRINKLER
ROOM
MECHANICAL ROOM 1 PLAN
SCALE: SCALE A
EXISTING AIR HANDER UNIT
SCALE: NO SCALE EXISTING CONDENSING UNITS
SCALE: NO SCALE
SEAL 30X84 OUTSIDE AIR INTAKE BY PLACING
1/2'" EXTERIOR GRADE PLYWOOD WITH 2X4
FRAME ANO 1 ~ INCH RIGID INSULATION BEHIND
LOUVERS. PAINT PLYWOOD GRAY TO MATCH
EXISTING SIDING COLOR.
REPLACE AIR HANDLER 1 AND DUCT
HEATER CONNECTING TO THE EXISTING
DUCT WORK
BATHROOM
SUPPLY AIR
36X22
ELECTRICAL BOX FOR
DUCT HEATER 208V, 3!11,
90 AMP
SCALE A
i=, !!iiiil!!!!liiiiiil!O !!!!!!!!!1!!!!!1;
,iiiiiiiiiiii
DUCT SMOKE DETECTOR TO REMAIN
REMOVE EXISTING
OUTSIDE AIR DAMPER
ON BACK SIDE OF
PLENUM AND SEAL
PLENUM
PLENUM
SUPPLY AIR
36X22
REPLACE
DUCT HEATER
REPLACE
EXISTING AIR
HANDLER 1
MECHANICAL ROOM 1 SECTION
SCALE: SCALE A
DESIGNED: SUB SHEET NO.
W H SHEllEY
DRAWN:
W H SHELlE.Y
TECH. REVIEW:
MPS
DATE:
04/2015
TITLE OF SHEET
MECHANICAL ROOM 1
ERNEST COE VISITOR CENTER
EVERGLADES NATIONAL PARK
DRAWING NO.
127,398
PMIS NO.
203625
SHEET
3 OF 5 -- --
erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Rectangle erik.venergy Line erik.venergy Rectangle erik.venergy Rectangle erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Rectangle erik.venergy Polygonal Line erik.venergy Oval erik.venergy Oval erik.venergy Line erik.venergy Line erik.venergy Rectangle erik.venergy Rectangle erik.venergy Rectangle erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Rectangle erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Cross-Out erik.venergy Typewritten Text
DE-COMMISSIONED
& MADE SAFE
erik.venergy Typewritten Text
CU-1
erik.venergy Typewritten Text
DE-COMMISSIONED &
MADE SAFE
erik.venergy Typewritten Text
EXISTING DISCONNECT RE-USED
REPLACED FUSES WITH 60A
erik.venergy Line erik.venergy Line erik.venergy Typewritten Text
RE-USED AS MAIN
DISCONNECT FOR AHU-1
erik.venergy Typewritten Text
USED EXISTING UNDERGROUND
PIPE CHASE FOR NEW
REFRIGERANT LINES
erik.venergy Line erik.venergy Typewritten Text
REMOVED SECTION OF R/A PLENUM
CONVERTED TO OPEN RETURN
erik.venergy Line erik.venergy Rectangle erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Typewritten Text
REMOVED SECTION OF R/A PLENUM
CONVERTED TO OPEN RETURN
erik.venergy Line erik.venergy Typewritten Text
REMOVED, INSTALLED
HEATER ON UNIT
erik.venergy Cross-Out erik.venergy Typewritten Text
REMOVED DUCT HEATER
INSTALLED HEATER ON UNIT
Rectangle u z u
CONDENSING UNITS 2A, 28, 3A, AND 38
SCALE: NO SCALE
CONDENSING UNIT 3A NAMEPLATE
CU UNITS 2A, 2B AND 3B IDENTICAL MODELS
SCALE: NO SCALE
CONTRACTOR HAS THE
OPTION TO REPLACE
CONDENSING UNITS 2A
AND 2B WITH NEW UNITS
OR REUSE AND MATCH
TO NEW AIR HANDLING
UNITS
AIR HANDLING UNIT 3
SCALE: NO SCALE
REPLACE AIR HANDLER 2AND
DUCT HEATER RECONNECT TO
EXISTING DUCTS AND ELECTRICAL
POWER
REFRIGERANT LINES
ALONG BUILDING REMOVE
OLD LINES
ELECTRICAL BOX FOR --
DUCT HEATER 2
208V, 3111 30A
REPLA E EXISTING ELECTRICAL
BOXES RECONNECTIONG TO THE
EXISTI WIRES AND CONDUIT. EACH
BOX H S A 208V, 3111, 40A CIRCUIT
CONTRACTOR HAS THE
OPTION TO REPLACE
CONDENSING UNITS 3A
AND 3B WITH NEW UNITS
OR REUSE AND MATCH
TO NEW . NDLING
UNITS
MECHANICAL ROOM 2 PLAN
SCALE: NO SCALE
SCALE A
2' 0 2' 4'
REMOVE EXISTING OUTSIDE AIR
DUCTS. SEAL MIXING PLENUM.
BLOCK EXISTING 34X30 OUTSIDE AIR
GRILLS WITH EXTERIOR GRADE
PLYWOOD AND lr' RIGID INSULATION
PLACED BEHIND EXISTING GRILL.
PAINT PLYWOOD TO MATCH SIDING
COLOR
.. EPLACE AIR HANDLER 3 AND
DUCT HEATER RECONNECT TO
EXISTING DUCTS AND ELECTRICAL
POWER ELECTRICAL BOX FOR
AIR HANDLER 3 208V,
3111 20A
EXISTING OUTSIDE AIR DUCTS AIR HANDLING UNIT 2
SCALE: NO SCALE SCALE: NO SCALE
DESIGNED: SUB SHEET NO.
W H SHELLEY
DRAWN:
W H SHELLEY
TECH. REVIEW:
MPS
DATE:
04/2015
TITLE OF SHEET
MECHANICAL ROOM 2
ERNEST COE VISITOR CENTER
EVERGLADES NATIONAL PARK
DRAWING NO.
127,398
PMIS NO.
203625
SHEET
_±_oF ___§__ erik.venergy Typewritten Text
CU-2A
erik.venergy Typewritten Text
CU-2B
erik.venergy Typewritten Text
CU-3
erik.venergy Rectangle erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Typewritten Text
CONDENSING UNIT
DE-COMMISSIONED
RETURNED TO NPS
erik.venergy Rectangle erik.venergy Line erik.venergy Typewritten Text
DE-COMMISSIONED
& MADE SAFE
erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygonal Line erik.venergy Polygonal Line erik.venergy Typewritten Text
DE-COMMISSIONED
& REMOVED
erik.venergy Typewritten Text
RE-USED AS UNIT
DISCONNECT
erik.venergy Typewritten Text
DECOMMISSIONED
RE-USED AS JUNCTION BOX
FOR MOTOR PROTECTION
erik.venergy Typewritten Text
RE-USED AS UNIT DISCONNECT
erik.venergy Typewritten Text
DEMO'D R/A PLENUM
TO CEILING CONVERTED
TO OPEN RETURN
erik.venergy Typewritten Text
ADDED 10" ROUND SECONDARY
RETURN TO SERVICE THEATER
erik.venergy Cross-Out erik.venergy Typewritten Text
REMOVED DUCT HEATER
INSTALLED NEW HEATER
IN UNIT
erik.venergy Typewritten Text
REMOVED DUCT HEATER
INSTALLED NEW HEATER
IN UNIT
erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Cross-Out erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line
24X24 R-1 W/22X22
NECK AIR RELIEF
EXHIBIT ROOM
SCALE A
2' D
EXHIBIT ROOM
SCALE: SCALE A
2' 4'
48X60 RELIEF
LOUVER
SEAL 48X60 RELIEF VENT
OPENING BY PLACING 1/2'"
EXTERIOR GRADE PLYWOOD WITH
2X4 FRAME AND 1~ INCH RIGID
INSULATION BEHIND LOUVERS.
PAINT PLYWOOD TO MATCH
EXISTING SIDING COLOR.
REMOVE COUNTER
BALANCE RELIEF DAMPER
REMOVE 36X48X60 PLENUM AND
BLOCK OFF OPENING TO DUCT
ABOVE WITH SHEET METAL.
INSTALL 4" -----'oc.
JET NOZZLE
POINT UP
TOWARD
CEILING PEAK
MAIN ROOM
D-3 48"-2 SLOT
140 CFM
MAIN LOBBY
SCALE: SCALE A
DESIGNED: SUB SHEET ND.
W H SHEllEY
DRAWN:
W H SHEllEY
TECH. REVIEW:
MPS
DATE:
D4/2015
TITLE OF SHEET DRAWING NO
EXHIBIT ROOM AND 160
127,398
MAIN LOBBY PMI S ND.
203625
SHEET
ERNEST COE VISITOR CENTER
EVERGLADES NATIONAL PARK 5 OF 5
erik.venergy Oval erik.venergy Typewritten Text
ACTUAL CONDITIONS
REQUIRED INSTALLATION
TO ME MOVED TO MAIN
SUPPLY AIR DUCT NEAR
ENTRANCE
erik.venergy Line erik.venergy Polygon erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Line erik.venergy Polygon erik.venergy Line
2011 Lennox Industries Inc.
Litho U.S.A.
Corp. 0701-L1
CB27UH/
Service Literature Revised September 2012 CBX27UH
CB(X)27 Series Units
IT IS HIGHLY RECOMMENDED IF THE AIR HANDLER IS INSTALLED IN A
UNCONDITIONED SPACE THAT A CIRCUIT BREAKER COVER (ORDERED
SEPARATELY) IS USED. ORDER LENNOX CATALOG # 82W01.
CIRCUIT BREAKER
OPENING
CIRCUIT BREAKER
COVER
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Table of Contents
Specifications / Electrical Data Page 2
Blower Data Page 4
Parts Arrangement Page 6
I Application Page 7
II Unit Components Page 7
III Optional Electric Heat Page 9
IV Start Up Page 27
V Typical Operating Characteristics Page 27. .
VI Maintenance Page 28
VII Wiring Diagrams and Sequence of Operations Page 31
The Elite CB27UH/CBX27UH are high efficiency blower coils. Several models are available in sizes ranging from 1‐1/2 through 5 tons (5.3 through 17.6 kW). The CB27UH is an upflow horizontal unit designed for HFC-22 refrigerant and the CBX27UH is an upflow horizontal unit designed for HCFC-410A refrigerant. See unit installation instructions for more detail. A kit is available for downflow applications.
CB(X)27 units come with a factory installed check and ex pansion valve for cooling or heat pump applications.
CB(X)27 series units are designed to be matched with the 14 SEER air conditioner and heat pump lines. While these blower coil units are designed to be primarily matched with these outdoor units, they may be matched with other air conditioners or heat pumps as noted in the rating informa tion.
ECB29 electric heat, in several voltages and kW sizes, can be field installed in the CB(X)27 cabinets.
Information contained in this manual is intended for use by experienced HVAC service technicians only. All specifica tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
SPECIFICATIONS
General Data
R-22 Model Number CB27UH‐018 CB27UH‐024 CB27UH‐030 CB27UH‐036
R-410A Model Number CBX27UH‐018 CBX27UH‐024 CBX27UH‐030 CBX27UH‐036
Nominal tonnage 1.5 2 2.5 3
Connections Suction (vapor) line (o.d.) - in. sweat 3/4 3/4 3/4 3/4
Liquid line (o.d.) - in. sweat 3/8 3/8 3/8 3/8
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4
Indoor Coil
Net face area - ft.2 4.44 4.44 5.0 5.0
Tube outside diameter - in. 3/8 3/8 3/8 3/8
Number of rows 3 3 3 3
Fins per inch 12 12 12 12
Blower Wheel nominal diameter x width - in. 10 x 8 10 x 8 11 x 8 11 x 8
Blower motor output - hp 1/2 1/2 1/2 1/2
1 Filters Size of filter - in. 20 x 20 x 1 20 x 20 x 1 20 x 20 x 1 20 x 20 x 1
Shipping Data -1 package - lbs. 148 148 159 159
ELECTRICAL DATA
Voltage - 1 phase - 60hz 208/230V-1ph 208/230V-1ph 208/230V-1ph 208/230V-1ph
Voltage - 3 phase - 60hz - - - - - - - - - 3 460V-1ph
2 Maximum Overcurrent Protection (unit only) - All voltages 15 15 15 15
Minimum Circuit Ampacity (unit only) - 208/230V 5 5 5 5
Blower Motor Full Load Amps - 208/230V 4.1 4.1 4.1 4.1
Minimum Circuit Ampacity (unit only) - 460V - - - - - - - - - 2.6
Blower Motor Full Load Amps - 460V - - - - - - - - - 2.1
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
ComfortSense� 7000 Thermostat Y2081 Y2081 Y2081 Y2081
Remote Outdoor Temperature Sensor (for ComfortSense 7000)
X2658 X2658 X2658 X2658
Dehumidification Relay Kit 26W62 26W62 26W62 26W62
Down‐Flow Additive Floor Base 44K15 44K15 44K15 44K15
Down‐Flow Conversion Kit 83M57 83M57 83M57 83M57
Electric Heat - See Electric Heat Data tables 2.5 to 20 kW
Healthy Climate Germicidal Light
UVC-24V (24V) X9423 X9423 X9423 X9423
UVC-41W-S (110/230v-1 ph) X9424 X9424 X9424 X9424
Horizontal Support Frame Kit 56J18 56J18 56J18 56J18
Side Return Unit Stand (Up‐Flow Only) 45K32 45K32 45K32 45K32
Single Point Power Source Control Box 21H39 21H39 21H39 21H39
Wall Hanging Bracket Kit (Up-Flow Only) 45K30 45K30 45K30 45K30
1 Disposable frame type filter.
2 HACR type circuit breaker or fuse.
3 Blower motor is 460V - 1 phase. Optional electric heat is 460V - 3 phase.
SPECIFICATIONS
General Data
R-22 Model Number CB27UH‐042 CB27UH‐048 CB27UH‐060
R-410A Model Number CBX27UH‐042 CBX27UH‐048 CBX27UH‐060
Nominal tonnage 3.5 4 5
Connections Suction (vapor) line (o.d.) - in. sweat 7/8 7/8 7/8
Liquid line (o.d.) - in. sweat 3/8 3/8 3/8
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4
Indoor Coil
Net face area - ft.2 7.22 7.22 8.33
Tube outside diameter - in. 3/8 3/8 3/8
Number of rows 3 3 3
Fins per inch 12 12 12
Blower Wheel nominal diameter x width - in. 12 x 9 12 x 9 12 x 9
Blower motor output - hp 1 1 1
1 Filters Size of filter - in. 20 x 24 x 1 20 x 24 x 1 20 x 24 x 1
Shipping Data -1 package lbs. 194 194 216
ELECTRICAL DATA
Voltage - 1 phase - 60hz 208/230V-1ph 208/230V- 1ph 208/230V- 1ph
Voltage - 3 phase - 60hz - - - 3 460V-1ph 3 460V-1ph
2 Maximum Overcurrent Protection (unit only) - All voltages 15 15 15
Minimum Circuit Ampacity (unit only) - 208/230V 10 10 10
Blower Motor Full Load Amps - 208/230V 7.6 7.6 7.6
Minimum Circuit Ampacity (unit only)V - 460V - - - 5 5
Blower Motor Full Load Amps - 460V - - - 4 4 1 Disposable frame type filter.
2 HACR type circuit breaker or fuse.
3 Blower motor is 460V - 1 phase. Optional electric heat is 460V - 3 phase.
REPLACEMENT CIRCUIT BREAKERS
Voltage Description Catalog No.
208/240V - 1 Phase 25 amp, 2 pole 41K13
30 amp, 2 pole 17K70
35 amp, 2 pole 72K07
40 amp, 2 pole 49K14
45 amp, 2 pole 17K71
50 amp, 2 pole 41K12
60 amp, 2 pole 17K72
208/240V - 3 Phase 30 amp, 3 pole 18M85
40 amp, 3 pole 41K16
45 amp, 3 pole 18M86
50 amp, 3 pole 41K15
60 amp, 3 pole 41K17
BLOWER DATA
CB(X)27UH‐018 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 815 80 810 77 835 86 855 89 1010 137 820 82 815 77 835 84 850 91 1010 140
.10 720 71 700 68 735 76 790 89 980 142 710 71 715 71 735 77 795 89 975 144
.20 580 59 560 58 665 76 755 99 950 153 570 59 580 60 660 77 755 99 950 154
.30 500 63 450 55 610 78 710 101 905 157 505 64 440 58 615 80 715 102 910 160
.40 400 65 350 59 580 87 685 111 870 166 415 67 355 60 89 680 112 875 170
.50 365 74 290 60 505 96 640 114 835 176 355 77 300 64 510 99 630 118 850 179
.60 315 75 280 68 445 100 580 124 800 179 320 77 270 71 450 102 575 129 805 183
.70 N/A N/A 210 71 390 102 515 128 755 187 N/A N/A 220 72 395 106 525 137 780 192
.80 N/A N/A 170 71 355 109 470 136 710 194 N/A N/A 175 76 365 112 485 144 725 200
CB(X)27UH‐024 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 885 89 885 89 930 97 1035 130 1185 184 890 91 895 90 920 99 1040 130 1190 189
.10 755 77 760 77 850 98 995 139 1140 193 785 82 770 78 855 100 1000 142 1145 200
.20 665 73 670 72 820 106 970 148 1100 203 675 76 670 76 820 111 960 152 1110 207
.30 605 77 600 77 775 112 920 154 1070 213 605 80 605 80 780 114 930 156 1085 219
.40 560 84 515 88 725 121 885 165 1025 219 570 88 555 88 745 123 890 166 1035 225
.50 445 95 445 95 675 124 835 171 1000 228 465 99 465 99 670 131 850 172 1010 235
.60 400 98 395 96 570 137 810 179 960 232 405 101 405 101 595 142 815 183 975 246
.70 N/A N/A 345 101 520 143 705 193 920 242 N/A N/A 350 106 530 151 710 197 935 248
.80 N/A N/A 320 106 460 148 625 201 835 254 N/A N/A 330 112 485 155 660 207 895 260
CB(X)27UH‐030 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 1130 128 1175 142 1230 158 1270 177 1345 208 1145 130 1180 142 1235 161 1280 179 1365 212
.10 1045 118 1065 126 1140 151 1240 183 1345 219 1030 118 1085 130 1155 154 1245 183 1345 223
.20 910 103 950 113 1105 160 1205 193 1305 231 915 105 955 116 1120 164 1205 195 1310 237
.30 730 89 870 117 1050 169 1165 202 1250 238 755 91 885 118 1060 171 1170 207 1265 242
.40 605 93 825 120 1020 176 1115 209 1205 248 655 92 830 124 1030 180 1125 213 1230 254
.50 540 101 725 136 980 181 1085 218 1180 257 550 102 745 136 985 184 1090 223 1195 265
.60 470 106 670 145 930 191 1035 224 1140 262 475 107 670 149 945 195 1050 230 1145 270
.70 N/A N/A 605 154 835 207 995 235 1105 273 N/A N/A 620 159 860 213 1005 242 1110 280
.80 N/A N/A 545 159 785 217 950 245 1055 284 N/A N/A 560 163 805 223 915 258 1050 295
CB(X)27UH‐036 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V / 460V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 1185 136 1225 149 1320 184 1430 234 1545 293 1180 139 1230 152 1330 191 1440 238 1555 299
.10 1070 125 1125 137 1280 196 1395 244 1515 303 1085 129 1125 141 1195 201 1405 251 1520 313
.20 960 113 1010 130 1240 201 1360 255 1475 314 955 114 1025 132 1260 213 1365 264 1485 325
.30 815 101 970 136 1195 214 1310 265 1430 322 805 105 975 142 1210 219 1330 275 1445 337
.40 750 106 915 148 1155 225 1275 273 1385 334 770 114 930 153 1170 231 1285 283 1405 345
.50 670 119 870 153 1110 231 1240 284 1345 345 670 128 870 159 1120 243 1250 295 1365 357
.60 605 130 825 163 1160 242 1190 290 1315 355 605 134 810 173 1080 249 1210 307 1330 367
.70 555 137 725 177 1125 251 1145 301 1270 359 565 142 725 185 1040 260 1160 313 1285 378
.80 515 142 670 282 970 262 1100 312 1225 369 525 146 675 195 980 276 1120 324 1245 391
CB(X)27UH‐042 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 1475 198 1530 218 1610 251 1705 295 1805 349 1475 200 1530 222 1615 254 1705 300 1815 350
.10 1370 183 1420 207 1545 251 1660 307 1780 364 1360 184 1435 207 1545 255 1665 310 1775 368
.20 1255 172 1305 189 1515 266 1635 322 1750 378 1245 172 1305 190 1515 269 1630 326 1750 384
.30 1090 153 1250 200 1470 278 1600 336 1705 390 1090 155 1255 203 1470 278 1605 343 1715 395
.40 1010 164 1190 210 1430 295 1560 346 1685 407 1020 165 1200 213 1420 300 1565 351 1680 408
.50 955 177 1145 225 1385 310 1510 373 1640 428 955 178 1150 229 1385 314 1520 373 1650 430
.60 885 183 1090 242 1330 319 1475 384 1590 443 915 183 1095 243 1330 324 1480 390 1595 453
.70 N/A N/A 1005 248 1255 341 1430 401 1565 457 N/A N/A 1000 254 1265 344 1440 408 1565 468
.80 N/A N/A 990 260 1200 355 1365 419 1510 473 N/A N/A 1000 255 1200 362 1375 429 1515 481
CB(X)27UH‐048 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V / 460V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 1440 200 1515 233 1670 304 1690 313 1850 413 1440 202 1525 237 1680 309 1700 319 1860 422
.10 1370 188 1455 224 1650 318 1670 329 1825 421 1370 189 1465 224 1665 324 1685 331 1840 431
.20 1260 173 1425 231 1635 327 1660 337 1825 436 1255 177 1425 235 1650 331 1675 342 1840 443
.30 1120 166 1380 242 1605 343 1630 351 1800 447 1125 167 1380 243 1625 349 1645 358 1815 461
.40 1055 172 1335 260 1565 352 1595 367 1770 462 1055 177 1335 262 1585 358 1605 373 1780 471
.50 960 190 1295 273 1530 372 1555 377 1735 479 970 194 1290 278 1535 378 1570 385 1745 490
.60 895 195 1230 285 1490 389 1510 401 1695 489 890 201 1230 296 1500 396 1525 408 1720 506
.70 N/A N/A 1145 304 1445 407 1470 418 1650 513 N/A N/A 1140 308 1455 415 1490 425 1665 533
.80 N/A N/A 1095 317 1385 416 1430 432 1605 530 N/A N/A 1075 325 1405 435 1430 445 1630 551
CB(X)27UH‐060 BLOWER PERFORMANCE
External Static Pres sure
Air Volume and Motor Watts at 208V Air Volume and Motor Watts at 230V / 460V
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
.00 1490 207 1765 331 1970 455 2010 494 2365 799 1505 212 1775 337 1980 461 2025 497 2365 822
.10 1395 194 1740 344 1930 466 1985 507 2328 810 1400 198 1745 352 1950 475 1990 514 2345 839
.20 1320 192 1700 354 1900 480 1955 522 2300 827 1325 196 1705 361 1910 490 1965 532 2310 850
.30 1275 206 1670 367 1875 487 1915 531 2265 842 1270 211 1675 374 1890 507 1930 540 2285 863
.40 1220 214 1620 378 1825 504 1890 544 2235 850 1230 224 1635 390 1840 516 1905 556 2255 882
.50 1170 226 1575 395 1795 519 1850 555 2205 861 1185 231 1590 402 1815 532 1875 573 2225 891
.60 1135 241 1535 409 1750 529 1810 569 2175 872 1140 239 1545 419 1785 550 1825 585 2190 908
.70 N/A N/A 1490 417 1720 543 1775 585 2135 885 N/A N/A 1510 426 1735 562 1795 602 2155 922
.80 N/A N/A 1470 429 1685 557 1730 592 2085 893 N/A N/A 1480 442 1700 574 1760 619 2120 940
CB27UH & CBX27UH PARTS ARRANGEMENT
FIGURE 1
CONTROL BOX
ELECTRIC HEAT
SECTION
BLOWER
COMPARTMENT
COIL
HORIZONTAL
DRAIN PAN
EXPANSION VALVE
(COMPLETE WITH
SCREEN)
*BLOWER ACCESS
PANEL
*COIL ACCESS
PANEL
FILTER ACCESS
PANEL
FILTER
FIGURE 2
CB27UH & CBX27UH CONTROL BOX
BLOWER RELAY
(K20)
TRANSFORMER
(T1)
TERMINAL STRIP
(TB1)
I-APPLICATION
All major blower coil components must be matched accord ing to Lennox recommendations for the unit to be covered under warranty. Refer to the Engineering Handbook for ap proved system matchups. A misapplied system will cause erratic operation and can result in early unit failure. The units come with factory installed check and expansion valve for all applications. The TXV valve has been installed inter nally for a cleaner installation and is accessible if required.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic com ponents. Take precautions during unit installation and service to protect the unit's electronic con trols. Precautions will help to avoid control expo sure to electrostatic discharge by putting the unit, the control and the technician at the same electro static potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
II-UNIT COMPONENTS
A-Control Box
See figure 2 for CB(X)27UH control box. Line voltage and electric heat connections are made in the control box. Op tional electric heat fits through an opening located in the center of the control box. When electric heat is not used, knock out plates cover the opening. The electric heat con trol arrangement is detailed in the electric heat section of this manual.
B-Terminal Strip (TB1)
CB(X)27UH units are equipped with a low voltage terminal strip (TB1) located in the control box. See figure 2. The strip is used for making up all indoor thermostat wires. The out door unit low voltage wiring connections to TB1 may be spliced with wire nuts inside the CB units.
Y1 to Y2 Jumper
A factory installed jumper will be installed between “Y1 and “Y2” for single-stage stage cooling. Remove the jumper for two-stage cooling.
R to W2 Jumper
A factory installed jumper will be installed between “R“ and “W2” for single-stage heat pump applications. Remove the jumper for two-stage non heat pump application.
C-Transformer (T1)
CB(X)27UH series units use a single line voltage to 24VAC transformer mounted in the control box. The transformer supplies power to the control circuits in the indoor and out door unit. Transformers are rated at 70VA. 208/240VAC single phase transformers use two primary voltage taps as shown in figure 3.
FIGURE 3
BLUE
YELLOW
ORANGE
RED
BLACK
240 VOLTS
208 VOLTS
PRIMARY SECONDARY
208 / 240 VOLT TRANSFORMER
F1
D- Fuse (F1)
All transformers used in the CB(X)27UH series units have a fuse (F1) wired in series on the low secondary side. See fig ure 3. F1 provides secondary voltage overcurrent protec tion and is rated at 3 amps.
E-Blower Relay (K20)
CB(X)27UH units use a DPDT relay to energize the blower motor during a call for electric heat only. When the relay coil is energized on an electric heat call, a set of N.O. contacts closes to energize the blower motor on heating speed.
F-Dehumidification Relay (K183)
Relay K183 is used for dehumidification during cooling de mand. K183 decreases blower speed resulting in an in crease in the amount of moisture taken from the air. See wiring diagram on page Page 43 and operation sequence on Page 43 for more detail.
BLOWER ASSEMBLY
FIGURE 4
Motor Terminals
G-Blower Motor (B3)
IMPORTANT
Blower motor features programmed electronic braking. The integral control brakes the motor near the end of the supply air blower operation, allowing the motor to maintain a more controlled ramping shut-down. Each blower is statically and dynamically balanced as an assembly before installation in the unit.
CB(X)27UH units are equipped with an indoor blower motor that is permanent magnetic with constant torque. The mo tor has 5 signal level speed taps all referenced to the same signal common. Each tap requires 24 volts to energize.
Multiple Taps Energized It is acceptable to have more than one tap energized at once but the micro-controller (integrated in the motor) will default to the highest tap. For example tap five will have pre cedence over tap four.
Input Voltage Requirements The circuit is designed to be operated with AC voltage. To enable a tap requires 12 to 33VAC. Expected current draw will be less than 20mA.
Troubleshooting Troubleshooting the motor is an easy process. Follow steps below.
1- Shut off power to unit.
2- Remove input plug from motor. Turn power back on to unit.
3- Check for 230 volts across terminals “L” and “N” on the input plug. See figure 4. If voltage is present continue. If voltage is not present problem may be may be up stream of the motor input plug.
4- Check for 24 volts across terminals “C” and speed tap used (1, 2, 3, 4 or 5) on the input plug. See figure 4. If 24 volts is not present problem may be up stream of the motor input plug.
If correct voltage is present in steps 3 and 4 and motor is not operating properly, replace motor. The motor is not field re pairable.
H-Coil
CB(X)27UH units have dual slab coils arranged in an “A” configuration. Each coil has two or three rows of copper tubes fitted with ripple-edged aluminum fins. An expansion valve complete with screen, feeds multiple parallel circuits through the coils. The coil is designed to easily slide out of the unit cabinet.
I-Plastic Drain Pans
Both upflow/downflow and horizontal drain pans are pro vided and installed on the CB(X)27UH units. The drain pans are made from fiberglass filled plastic. The drain hole on horizontal pans are used for right‐hand discharge only, and must be plugged when the unit is configured for left‐hand discharge.
III-OPTIONAL ECB29 ELECTRIC HEAT
A-Matchups and Ratings
See Tables 1 through 4 show all approved , and
CB(X)27UH to ECB29 matchups and electrical ratings.
B-Electric Heat Components
ECB29 parts arrangement is shown in figures 5 through 9.
All electric heat sections consist of components mounted to the electric heat vestibule panel and electric heating ele ments exposed directly to the air stream. 208/230V electric heat sections may be equipped with circuit breakers. The circuit breakers are designated by CB in the model number.
The electric heat section is connected to the unit via jack J2, which plugs into plug P2 of the unit.
Electric Heat Sequencer Relays
(K32, K33, K34, K35, K116, K117) (208/230 volt only)
Relays K32, K33, K34, K35, K116 and K117 are N.O.
sequencer relays with a resistive element for a coil and a bi‐metal disk which actuates the contacts. The relays are located on the electric heat vestibule panel and are energized by a 24V heating demand (W1, W2, and W3) via jack/plug 2. When energized, the internal resist ance heats the bi‐metal disk causing the contacts to close. When the relay is de‐energized, the disk cools and the contacts open. The relays energize different stages of heat, as well as the blower. The blower is al ways first on and last off.
Primary(S15) & Secondary(S20) Temperature Limits
Both the primary (S15) and secondary (S20) limits are located on the electric heat vestibule panel and are ex posed directly to the air stream through an opening in the panel. The high temperature limits are SPST N.C.
limits with the primary limit being an auto‐reset limit and the secondary limit being a “one‐time” limit. One‐time limits need to be replaced when opened. The limits are factory set and are not adjustable.
208/230 Volt Electric Heat Sections
Each stage of the 208/230 electric heat is protected by a primary (S15) and secondary (S20) high temperature limit. Both S15 and S20 are located in the same hous ing. Each stage use the same style of limits. Both the primary and secondary limits are wired in series with a heat element. When either S15 or S20 opens, the cor responding heat element is de‐energized. All other heating elements remain energized. The primary high temperature limit opens at 150�F + 5�F (65.5�C + 2.8�C) on a temperature rise and automatically resets at 110�F + 9�F (43.3�C + 5.0�C) on a temperature fall.
The secondary high temperature limit opens at 333�F + 10�F (167.2�C + 5.6�C) on a temperature rise. If the secondary limit opens it will need to be replaced.
Circuit Breaker (CB1, CB2, and CB3)
(208/230 volt only)
Line voltage connections are made to circuit breakers CB1, CB2, and CB3 in the electric heat sections with circuit breakers (designated by CB in the model num bers) then routed to the CB unit through J/P2 . Tables 1 through 4 show the amp rating for each circuit breaker used. Single-phase electric heat uses two-pole circuit breakers; while three-phase electric heat uses three-pole circuit breakers.
Terminal Strip (TB2) 208/230 volt only)
For the electric heat sections without circuit breakers or fuses, line voltage connections are made to terminal strip TB2 then routed to the CB unit through J/P2 The terminal strip is located in the lower left corner of the electric heat vestibule panel. Single-phase electric heat uses two-pole terminal strips; while three-phase electric heat uses three- pole terminal strips.
Heating Elements (HE1 through HE6)
Heating elements are composed of helix wound bare nichrome wire exposed directly to the air stream. The elements are supported by insulators mounted to the wire frame. For single-phase applications, one element is used per stage. Each stage is energized indepen dently by the corresponding relay located on the elec tric heat vestibule panel. All three-phase heating ele ments are arranged in a three-phase delta. Once energized, heat transfer is instantaneous. High tem perature protection is provided by primary and secon dary high temperature limits.
FIGURE 5
ECB29‐2.5, ‐5, ‐5CB, -6, -6CB 208/230 SINGLE-PHASE
ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT
TERMINAL BLOCK
(TB2)
CIRCUIT BREAKER
(CB1)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE1)
ELECTRIC HEAT
VESTIBULE PAN
EL
ELECTRIC HEAT
SEQUENCER RELAY (K32)
FIGURE 6
ECB29‐8, ‐8CB, 9CB, ‐10, ‐10CB 208/230
SINGLE-PHASE
ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT
TERMINAL BLOCK
(TB2)
CIRCUIT BREAKER
(CB1)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE2)
ELECTRIC HEAT
VESTIBULE PAN
EL
ELECTRIC HEAT
SEQUENCER RELAY (K32)
ELECTRIC HEAT
ELEMENT (HE1)
ELECTRIC HEAT
SEQUENCER RELAY (K33)
FIGURE 7
ECB29‐8, ‐10 208/230 THREE-PHASE
ECB29‐12.5CB, ‐15CB 208/230 SINGLE & THREE-PHASE
ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT
TERMINAL BLOCK
(TB2)
CIRCUIT BREAKER
(CB1)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE3)
ELECTRIC HEAT
VESTIBULE PAN
EL
ELECTRIC HEAT
SEQUENCER RELAY (K32)
ELECTRIC HEAT
ELEMENT (HE2)ELECTRIC HEAT
SEQUENCER RELAY (K33)
CIRCUIT BREAKER
(CB2)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE1)
FIGURE 8
ECB29‐20CB 208/230 SINGLE-PHASE
ELECTRIC HEAT VESTIBULE PARTS
ARRANGEMENT
CIRCUIT BREAKER
(CB1)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE4)
ELECTRIC HEAT
VESTIBULE PAN
EL
ELECTRIC HEAT
SEQUENCER RELAY (K32)
ELECTRIC HEAT
ELEMENT (HE3)ELECTRIC HEAT
SEQUENCER RELAY (K33)
CIRCUIT BREAKER
(CB2)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE2)
ELECTRIC HEAT
ELEMENT (HE1)
ELECTRIC HEAT
SEQUENCER RELAY (K34)
FIGURE 9
ECB29‐20CB, ‐25CB 208/230 THREE-PHASE
ECB29‐25CB, ‐30CB 208/230 SINGLE-PHASE
ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT
CIRCUIT BREAKER
(CB1)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE4)
ELECTRIC HEAT
VESTIBULE PAN
EL
ELECTRIC HEAT
SEQUENCER RELAY (K32)
ELECTRIC HEAT
ELEMENT (HE5)
ELECTRIC HEAT
SEQUENCER RELAY (K33)
CIRCUIT BREAKER
(CB3)
PRIMARY LIMIT (S15)
& SECONDARY LIMIT (S20)
ELECTRIC HEAT
ELEMENT (HE1 & HE2)
(not shown)
ELECTRIC HEAT
ELEMENT (HE6)
ELECTRIC HEAT
SEQUENCER RELAY (K34)
CIRCUIT BREAKER
(CB2)
ELECTRIC HEAT
SEQUENCER RELAY (K35)
ELECTRIC HEAT
SEQUENCER RELAY (K116)
ELECTRIC HEAT
ELEMENT (HE3)
TABLE 1
ELECTRIC HEAT DATA - CB(X)27UH-018
Model Number No.
of
Stages
Input 2 Blower Motor Full
Load Amps
3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
Volts kW 1 Btuh
SINGLE PHASE
2.5 kW 4 lbs.
ECB29-2.5 (28K30) Termi nal Block
1 208 1.9 6,400 4.1 16 20
220 2.1 7,200 4.1 18 20
230 2.3 7,800 4.1 18 20
240 2.5 8,500 4.1 18 20
4 kW 4 lbs.
ECB29-4 (55W87)
Terminal Block
ECB29-4CB (55W88)
30A Circuit breaker
1 208 3.0 10,250 4.1 23 4 25
220 3.4 11,450 4.1 26 30
230 3.7 12,550 4.1 26 30
240 4.0 13,650 4.1 26 30
5 kW 4 lbs.
ECB29-5 (28K31)
Terminal Block
ECB29-5CB (28K32)
30A Circuit breaker
1 208 3.8 12,800 4.1 28 30
220 4.2 14,300 4.1 31 4 35
230 4.6 15,700 4.1 31 4 35
240 5.0 17,100 4.1 31 4 35
6 kW 4 lbs.
ECB29-6 (47L22)
Terminal Block
ECB29-6CB (47L23)
35A Circuit breaker
1 208 4.5 15,400 4.1 32 35
220 5.0 17,100 4.1 36 4 40
230 5.5 18,800 4.1 36 4 40
240 6.0 20,500 4.1 36 4 40
8 kW 5 lbs.
ECB29-8 (28K33)
Terminal Block
ECB29-8CB (28K34)
45A Circuit breaker
1 208 6.0 20,500 4.1 41 45
220 6.7 22,900 4.1 47 4 50
230 7.3 25,100 4.1 47 4 50
240 8.0 27,300 4.1 47 4 50
9 kW 5 lbs.
ECB29-9CB (10L11)
ECB29EH-9CB (91K67)
50A Circuit breaker
2 208 6.8 23,100 4.1 46 50
220 7.6 25,800 4.1 52 4 60
230 8.3 28,200 4.1 52 4 60
240 9.0 30,700 4.1 52 4 60
10 kW 6 lbs.
ECB29-10 (28K35)
Terminal Block
ECB29-10CB (28K36)
60A Circuit breaker
2 208 7.5 25,600 4.1 50 4 50
220 8.4 28,700 4.1 57 60
230 9.2 31,400 4.1 57 60
240 10.0 34,100 4.1 57 60
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1 Electric heater capacity only - does not include additional blower motor heat capacity.
2 Amps shown are for blower motor only.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4 Bold text indicates that the circuit breaker on ”CB” circuit breaker models must be replaced with size noted. See Table on Page <?>.
5 HACR type circuit breaker or fuse.
TABLE 2
ELECTRIC HEAT DATA - CB(X)27UH-024
Model Number No.
of
Stages
Input 2 Blower Motor Full
Load Amps
3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
Single Point Power Source
Volts kW 1 Btuh Ckt 1 Ckt 2 Ckt 1 Ckt 2 3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
SINGLE PHASE
4 kW 4 lbs.
ECB29-4 (55W87)
Terminal Block
ECB29-4CB (55W88)
30A Circuit breaker
1 208 3.0 10,250 4.1 23 - - - 4 25 - - - - - - - - -
220 3.4 11,450 4.1 26 - - - 30 - - - - - - - - -
230 3.7 12,550 4.1 26 - - - 30 - - - - - - - - -
240 4.0 13,650 4.1 26 - - - 30 - - - - - - - - -
5 kW 4 lbs.
ECB29-5 (28K31)
Terminal Block
ECB29-5CB (28K32)
30A Circuit breaker
1 208 3.8 12,800 4.1 28 - - - 30 - - - - - - - - -
220 4.2 14,300 4.1 31 - - - 4 35 - - - - - - - - -
230 4.6 15,700 4.1 31 - - - 4 35 - - - - - - - - -
240 5.0 17,100 4.1 31 - - - 4 35 - - - - - - - - -
6 kW 4 lbs.
ECB29-6 (47L22)
Terminal Block
ECB29-6CB (47L23)
35A Circuit breaker
1 208 4.5 15,400 4.1 32 - - - 35 - - - - - - - - -
220 5.0 17,100 4.1 36 - - - 4 40 - - - - - - - - -
230 5.5 18,800 4.1 36 - - - 4 40 - - - - - - - - -
240 6.0 20,500 4.1 36 - - - 4 40 - - - - - - - - -
8 kW 5 lbs.
ECB29-8 (28K33)
Terminal Block
ECB29-8CB (28K34)
45A Circuit breaker
1 208 6.0 20,500 4.1 41 - - - 45 - - - - - - - - -
220 6.7 22,900 4.1 47 - - - 4 50 - - - - - - - - -
230 7.3 25,100 4.1 47 - - - 4 50 - - - - - - - - -
240 8.0 27,300 4.1 47 - - - 4 50 - - - - - - - - -
9 kW 5 lbs.
ECB29-9CB (10L11)
ECB29EH-9CB (91K67)
50A Circuit breaker
2 208 6.8 23,100 4.1 46 - - - 50 - - - - - - - - -
220 7.6 25,800 4.1 52 - - - 4 60 - - - - - - - - -
230 8.3 28,200 4.1 52 - - - 4 60 - - - - - - - - -
240 9.0 30,700 4.1 52 - - - 4 60 - - - - - - - - -
10 kW 6 lbs.
ECB29-10 (28K35)
Terminal Block
ECB29-10CB (28K36)
60A Circuit breaker
2 208 7.5 25,600 4.1 50 - - - 4 50 - - - - - - - - -
220 8.4 28,700 4.1 57 - - - 60 - - - - - - - - -
230 9.2 31,400 4.1 57 - - - 60 - - - - - - - - -
240 10.0 34,100 4.1 57 - - - 60 - - - - - - - - -
12.5 kW
10 lbs.
ECB29-12.5CB (28K37)
ECB29EH-12.5CB (91K68)
(1) 25A Circuit breaker & (1) 50A Circuit breaker
2 208 9.4 32,000 4.1 24 38 25 4 40 70 70
220 10.5 35,800 4.1 27 43 4 30 4 45 70 70
230 11.5 39,200 4.1 27 43 4 30 4 45 70 70
240 12.5 42,600 4.1 27 43 4 30 4 45 70 70
15 kW 12 lbs.
ECB29-15CB (28K38)
ECB29EH-15CB (91K69)
(1) 30A Circuit breaker & (1) 60A Circuit breaker
2 208 11.3 38,400 4.1 28 45 30 4 45 83 90
220 12.6 43,000 4.1 31 52 4 35 60 83 90
230 13.8 47,000 4.1 31 52 4 35 60 83 90
240 15.0 51,200 4.1 31 52 4 35 60 83 90
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1 Electric heater capacity only - does not include additional blower motor heat capacity.
2 Amps shown are for blower motor only.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4 Bold text indicates that the circuit breaker on ”CB” circuit breaker models must be replaced with size noted. See Table on Page <?>.
TABLE 3
ELECTRIC HEAT DATA - CB(X)27UH-030
Model Number No.
of
Stages
Input 2 Blower Motor
Full Load Amps
3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
Single Point Power Source
Volts kW 1 Btuh Ckt 1 Ckt 2 Ckt 1 Ckt 2 3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
SINGLE PHASE
4 kW 4 lbs.
ECB29-4 (55W87)
Terminal Block
ECB29-4CB (55W88)
30A Circuit breaker
1 208 3.0 10,250 4.1 23 - - - 4 25 - - - - - - - - -
220 3.4 11,450 4.1 26 - - - 30 - - - - - - - - -
230 3.7 12,550 4.1 26 - - - 30 - - - - - - - - -
240 4.0 13,650 4.1 26 - - - 30 - - - - - - - - -
5 kW 4 lbs.
ECB29-5 (28K31)
Terminal Block
ECB29-5CB (28K32)
30A Circuit breaker
1 208 3.8 12,800 4.1 28 - - - 30 - - - - - - - - -
220 4.2 14,300 4.1 31 - - - 4 35 - - - - - - - - -
230 4.6 15,700 4.1 31 - - - 4 35 - - - - - - - - -
240 5.0 17,100 4.1 31 - - - 4 35 - - - - - - - - -
6 kW 4 lbs.
ECB29-6 (47L22)
Terminal Block
ECB29-6CB (47L23)
35A Circuit breaker
1 208 4.5 15,400 4.1 32 - - - 35 - - - - - - - - -
220 5.0 17,100 4.1 36 - - - 4 40 - - - - - - - - -
230 5.5 18,800 4.1 36 - - - 4 40 - - - - - - - - -
240 6.0 20,500 4.1 36 - - - 4 40 - - - - - - - - -
8 kW 5 lbs.
ECB29-8 (28K33)
Terminal Block
ECB29-8CB (28K34)
45A Circuit breaker
1 208 6.0 20,500 4.1 41 - - - 45 - - - - - - - - -
220 6.7 22,900 4.1 47 - - - 4 50 - - - - - - - - -
230 7.3 25,100 4.1 47 - - - 4 50 - - - - - - - - -
240 8.0 27,300 4.1 47 - - - 4 50 - - - - - - - - -
9 kW 5 lbs.
ECB29-9CB (10L11)
50A Circuit breaker
ECB29EH-9CB (91K67)
50A Circuit breaker
2 208 6.8 25,600 4.1 46 - - - 50 - - - - - - - - -
220 7.6 28,700 4.1 52 - - - 4 60 - - - - - - - - -
230 8.3 31,400 4.1 52 - - - 4 60 - - - - - - - - -
240 9.0 34,100 4.1 52 - - - 4 60 - - - - - - - - -
10 kW 6 lbs.
ECB29-10 (28K35)
Terminal Block
ECB29-10CB (28K36)
60A Circuit breaker
2 208 7.5 25,600 4.1 50 - - - 4 50 - - - - - - - - -
220 8.4 28,700 4.1 57 - - - 60 - - - - - - - - -
230 9.2 31,400 4.1 57 - - - 60 - - - - - - - - -
240 10.0 34,100 4.1 57 - - - 60 - - - - - - - - -
12.5 kW 10 lbs.
ECB29-12.5CB (28K37)
ECB29EH-12.5CB (91K68)
(1) 25A Circuit breaker & (1) 50A Circuit breaker
2 208 9.4 32,000 4.1 24 38 25 4 40 70 70
220 10.5 35,800 4.1 27 43 4 30 4 45 70 70
230 11.5 39,200 4.1 27 43 4 30 4 45 70 70
240 12.5 42,600 4.1 27 43 4 30 4 45 70 70
15 kW 12 lbs.
ECB29-15CB (28K38)
ECB29EH-15CB (91K69)
(1) 30A Circuit breaker & (1) 60A Circuit Breaker
2 208 11.3 38,400 4.1 28 45 30 4 45 83 90
220 12.6 43,000 4.1 31 52 4 35 60 83 90
230 13.8 47,000 4.1 31 52 4 35 60 83 90
240 15.0 51,200 4.1 31 52 4 35 60 83 90
THREE PHASE
8 kW 5 lbs.
ECB29-8 (28K42)
Terminal Block
1 208 6.0 20,500 4.1 26 - - - 30 - - - - - - - - -
220 6.7 22,900 4.1 29 - - - 30 - - - - - - - - -
230 7.3 25,100 4.1 29 - - - 30 - - - - - - - - -
240 8.0 27,300 4.1 29 - - - 30 - - - - - - - - -
10 kW 6 lbs.
ECB29-10 (28K43)
Terminal Block
1 208 7.5 25,600 4.1 31 - - - 35 - - - - - - - - -
220 8.4 28,700 4.1 35 - - - 35 - - - - - - - - -
230 9.2 31,400 4.1 35 - - - 35 - - - - - - - - -
240 10.0 34,100 4.1 35 - - - 35 - - - - - - - - -
15 kW 12 lbs.
ECB29-15CB (28K44)
(1) 50A Circuit breaker
1 208 11.3 38,400 4.1 44 - - - 45 - - - - - - - - -
220 12.6 43,000 4.1 50 - - - 50 - - - - - - - - -
230 13.5 47,000 4.1 50 - - - 50 - - - - - - - - -
240 15.0 51,200 4.1 50 - - - 50 - - - - - - - - -
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1 Electric heater capacity only - does not include additional blower motor heat capacity.
2 Amps shown are for blower motor only.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4 Bold text indicates that the circuit breaker on ”CB” circuit breaker models must be replaced with size noted. See Table on Page <?>.
TABLE 4
ELECTRIC HEAT DATA - CB(X)27UH-042
SINGLE PHASE
Model Number No.
of
Stages
Volts Input kW Input
1 Btuh Input
2 Blower Motor Full
Load Amps
3 Minimum Circuit
Ampacity
5 Maximum Overcurrent Protection
Single Point Power Source
Ckt
Ckt
Ckt
Ckt
Ckt
Ckt
3 Mini mum
Circuit Ampacity
5 Maximum Overcurrent Protection
4 kW 4 lbs.
ECB29-4 (55W87)
Terminal Block
ECB29-4CB (55W88)
30A Circuit breaker
1 208 3.0 10,25
7.6 28 - - - - - - 30 - - - - - - - - - - - -
220 3.4 11,45
7.6 30 - - - - - - 30 - - - - - - - - - - - -
230 3.7 12,55
7.6 30 - - - - - - 30 - - - - - - - - - - - -
240 4.0 13,65
7.6 30 - - - - - - 30 - - - - - - - - - - - -
5 kW 4 lbs.
ECB29-5 (28K31)
Terminal Block
ECB29-5CB (28K32)
30A Circuit breaker
1 208 3.8 12,80
7.6 32 - - - - - - 4 35 - - - - - - - - - - - -
220 4.2 14,30
7.6 36 - - - - - - 4 40 - - - - - - - - - - - -
230 4.6 15,70
7.6 36 - - - - - - 4 40 - - - - - - - - - - - -
240 5.0 17,10
7.6 36 - - - - - - 4 40…