Independence_Hall_Points_9_4_2026_0002.xlsx
XLSX spreadsheet 23 KB Posted
- Solicitation number
- 140P4226Q0046
About this file
This file is a spreadsheet containing scoring points and evaluation criteria for the Independence Hall Fire Alarm Inspection, Testing, and Maintenance (ITM) and As-Needed Repair Services solicitation. The document appears to be an evaluation matrix or scoring template used by the National Park Service (NPS) to assess contractor proposals for annual fire alarm services at Independence National Historical Park in Philadelphia, Pennsylvania.
The spreadsheet includes point allocations and evaluation categories that the NPS will use to rank competing proposals. The evaluation framework is designed to assess contractor qualifications and capabilities for providing comprehensive fire alarm inspection, testing, maintenance, and emergency repair services at the historic site. Site visits for interested contractors are scheduled for August 31, 2026, at 9:30 AM EDT at 143 S. 3rd Street, Philadelphia, PA 19106, with attendees responsible for arranging their own street parking. This is a solicitation issued by the Department of the Interior National Park Service Northeast Region, with solicitation number 140P4226Q0046.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P4226Q0046_Amd_0002.pdf | ||
| First_Bank_ROC_0002.pdf | ||
| 140P4226Q0046_QnA_0001.pdf | ||
| 2025_Inspection_Reports_0001.pdf | ||
| Sol_140P4226Q0046_Amd_0001.pdf | ||
| Sol_140P4226Q0046.pdf | ||
| Attachment_2_Locations_and_Equipment_Lists.xlsx | XLSX spreadsheet | |
| Attachment_3_Quote_Submission_Package.docx | DOCX document | |
| Attachment_1_Wage_Determination_2015-4233_Rev_37_effective_7_30_2026.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Node 1
| Node 1 (NGA): Independence Hall | ||||
| Loop | Address | DACT | Type | Description |
Node 2
| Node 2 (ILI-MB): IH ILI | ||||
| Loop | Address | DACT | Type | Description |
| 1 | S1 | 17 | Multi Criteria | IH Bsmt Near AHU-4 |
| 1 | M1 | 0 | Form C AOM NS | IH Bsmt AHU-4 Supply Shutdown Relay |
| 1 | S2 | 3 | Photo Duct Supv | IH Bsmt AHU-4 Supply |
| 1 | M2 | 1 | Addr. Manual Station | IH Bsmt Entrance to East Wing |
| 1 | S3 | 3 | Photo Duct Supv | IH Bsmt AHU-4 Return |
| 1 | M3 | 0 | Form C AOM NS | IH Bsmt AHU-4 Return Shutdown Relay |
| 1 | S4 | 17 | Multi Criteria | IH Bsmt at Stairs to East Wing |
| 1 | M4 | 0 | Form C AOM NS | IH Bsmt AHU-8 Supply Shutdown Relay |
| 1 | S5 | 17 | Multi Criteria | IH Bsmt Near AHU-4 |
| 1 | M5 | 0 | Form C AOM NS | IH Bmst AHU-5 Supply Shutdown Relay |
| 1 | M6 | 1 | Addr. Manual Station | IH Bsmt Near Stairs to West Wing |
| 1 | M7 | 1 | Addr. Manual Station | IH 1FL FACP Room |
| 1 | S8 | 17 | Multi Criteria | IH Bsmt at AHU-4 |
| 1 | M8 | 0 | Form C AOM NS | IH Bsmt AHU-5 Return Shutdown Relay |
| 1 | S9 | 3 | Photo Duct Supv | IH Bsmt AHU-8 Supply |
| 1 | M9 | 1 | Addr. Manual Station | IH 1FL Central Hall Chestnut Street Exit |
| 1 | S10 | 3 | Photo Duct Supv | IH Bsmt AHU-8 Return |
| 1 | M10 | 0 | Beam Smk Alarm | IH 1FL Central Hall BSD Alarm |
| 1 | S11 | 17 | Multi Criteria | IH Bsmt Tunnel |
| 1 | M11 | 20 | Beam Smk Trbl | IH 1FL Central Hall BSD Trouble |
| 1 | S12 | 17 | Multi Criteria | IH Bsmt Near AHU-5 |
| 1 | M12 | 1 | Addr. Manual Station | IH 2FL Assembly Chamber Hallway |
| 1 | S13 | 3 | Photo Duct Supv | IH Bsmt AHU-5 Supply |
| 1 | M13 | 2 | Tamper NonL | IH 2FL Attic Left Side V/T |
| 1 | S14 | 3 | Photo Duct Supv | IH Bsmt AHU-5 Return |
| 1 | M14 | 2 | Tamper NonL | IH 2FL Attic Right Side V/T |
| 1 | S15 | 17 | Multi Criteria | IH Bsmt Right of Stairs to West Wing |
| 1 | M15 | 2 | Tamper NonL | IH Roof Hydrant V/T (Bsmt by Fire Pump) |
| 1 | S16 | 17 | Multi Criteria | IH Bsmt at AHU-5 & Stairs to West Wing |
| 1 | M16 | 1 | Addr. Manual Station | IH 2FL Landing to Attic & Tower |
| 1 | S17 | 17 | Multi Criteria | IH Bsmt Left of Stairs to West Wing |
| 1 | M17 | 1 | Addr. Manual Station | IH Tower L2 at Stairs |
| 1 | S18 | 17 | Multi Criteria | IH Bsmt at AHU-8 |
| 1 | M18 | 1 | Addr. Manual Station | IH Tower L3 at Stairs |
| 1 | S19 | 5 | Photo Detector | IH 1FL Above FACP |
| 1 | M19 | 1 | Addr. Manual Station | IH Tower L4 Across from Stairs |
| 1 | S20 | 5 | Photo Detector | IH 1FL Main Entrance |
| 1 | M20 | 1 | Addr. Manual Station | IH Tower L5 Across from Stairs |
| 1 | S21 | 5 | Photo Detector | IH 1FL Storage Room by FACP |
| 1 | M21 | 1 | Addr. Manual Station | IH Tower L6 at Stairs |
| 1 | S22 | 5 | Photo Detector | IH 1FL Near Central Hall Entrance |
| 1 | M22 | 20 | Pwr Supply Tbl | IH PS1 Fault |
| 1 | S23 | 5 | Photo Detector | IH 1FL Supreme Court Rm Left Arch Chase |
| 1 | M23 | 0 | Beam Smk Alarm | 1FL Assembly Room Near Hall BSD Alarm |
| 1 | S24 | 5 | Photo Detector | IH 1FL Supreme Court Room Left Rear |
| 1 | M24 | 20 | Beam Smk Trbl | 1FL Assembly Room Near Hall BSD Trouble |
| 1 | S25 | 5 | Photo Detector | IH 1FL Supreme Court Room Left Front |
| 1 | M25 | 0 | Beam Smk Alarm | 1FL Assembly Room by Fire Place BSD Alm |
| 1 | S26 | 5 | Photo Detector | IH 1FL Supreme Court Room Under Stage |
| 1 | M26 | 20 | Beam Smk Trbl | 1FL Assembly Room by Fire Place BSD Trbl |
| 1 | S27 | 5 | Photo Detector | IH 1FL Supreme Court Room Center Front |
| 1 | M27 | 0 | Beam Smk Alarm | 2FL Committee of Assembly Chmbr BSD Alm |
| 1 | S28 | 5 | Photo Detector | IH 1FL Supreme Court Room Center Rear |
| 1 | M28 | 20 | Beam Smk Trbl | 2FL Committee of Assembly Chmbr BSD Trbl |
| 1 | S29 | 5 | Photo Detector | IH 1FL Supreme Court Room Front Right |
| 1 | M29 | 0 | Beam Smk Alarm | 2FL Long Gallery BSD Alarm |
| 1 | S30 | 5 | Photo Detector | IH 1FL Supreme Court Room Right Rear |
| 1 | M30 | 20 | Beam Smk Trbl | 2FL Long Gallery BSD Trouble |
| 1 | S31 | 5 | Photo Detector | IH 1FL Supreme Court Rm Right Arch Chase |
| 1 | M31 | 0 | Beam Smk Alarm | 2FL Governors Council Chamber BSD Alarm |
| 1 | S32 | 5 | Photo Detector | IH 1FL Assembly Room Left Closet |
| 1 | M32 | 20 | Beam Smk Trbl | 2FL Governors Council Chamber BSD Trbl |
| 1 | S33 | 5 | Photo Detector | IH 1FL Assembly Room Right Closet |
| 1 | S34 | 5 | Photo Detector | IH 2FL Ceiling Right Rear |
| 1 | S35 | 5 | Photo Detector | IH 2FL Ceiling Left Rear |
| 1 | S36 | 5 | Photo Detector | IH 2FL Ceiling Front Left |
| 1 | S37 | 5 | Photo Detector | IH 2FL Ceiling Front Right |
| 1 | S38 | 5 | Photo Detector | IH 2FL Committee of Assembly Chmbr Hall |
| 1 | S39 | 5 | Photo Detector | IH 2FL CAC Hall Closet Left |
| 1 | S40 | 5 | Photo Detector | IH 2FL CAC Hall Closet Right |
| 1 | S41 | 5 | Photo Detector | IH 2FL Stairs to Attic |
| 1 | S44 | 17 | Multi Criteria | IH Tower L2 Under Stairs |
| 1 | S45 | 17 | Multi Criteria | IH 2FL Landing to Attic & Tower |
| 1 | S46 | 17 | Multi Criteria | IH Attic Far Right Side Cat Walk |
| 1 | S47 | 17 | Multi Criteria | IH Attic Right Side Cat Walk |
| 1 | S48 | 17 | Multi Criteria | IH Attic Center Cat Walk |
| 1 | S49 | 17 | Multi Criteria | IH Attic Left Side Cat Walk |
| 1 | S50 | 17 | Multi Criteria | IH Attic Far Left Side Cat Walk |
| 1 | S51 | 17 | Multi Criteria | IH Tower L2 Clock Pendulum Room |
| 1 | S52 | 17 | Multi Criteria | IH Tower L2 Front |
| 1 | S53 | 17 | Multi Criteria | IH Tower L2 Rear |
| 1 | S54 | 17 | Multi Criteria | IH Tower L3 |
| 1 | S55 | 17 | Multi Criteria | IH Tower L3 Near Stairs |
| 1 | S56 | 17 | Multi Criteria | IH Tower L3 Clockworks Room |
| 1 | S57 | 17 | Multi Criteria | IH Tower L3 Rear |
| 1 | S58 | 17 | Multi Criteria | IH Tower L4 Near Stairs |
| 1 | S59 | 17 | Multi Criteria | IH Tower L4 Center |
| 1 | S60 | 17 | Multi Criteria | IH Tower L5 Near Stairs |
| 1 | S61 | 17 | Multi Criteria | IH Tower L5 Center |
| 1 | S62 | 17 | Multi Criteria | IH Tower L6 Near Stairs |
| 1 | S63 | 17 | Multi Criteria | IH Tower L6 Center |
| 1 | S64 | 17 | Multi Criteria | IH Tower L8 |
| 1 | S66 | 17 | Multi Criteria | IH Attic Far Left in Clock Area |
| 1 | S67 | 17 | Multi Criteria | IH Attic Far Left at Wall (Low Right) |
| 1 | S68 | 17 | Multi Criteria | IH Attic Far Left at Wall (Low Left) |
| 1 | S69 | 17 | Multi Criteria | IH Attic Catwalk Right Side |
| 1 | S70 | 17 | Multi Criteria | IH Attic Far Right at Wall (Low Left) |
| 1 | S71 | 17 | Multi Criteria | IH Attic Far Right at Wall (Low Right) |
| 1 | S72 | 17 | Multi Criteria | IH Attic Far Left at Wall (Low Right) |
| 1 | S73 | 17 | Multi Criteria | IH Attic Far Left at Wall (Low Left) |
| 1 | S74 | 17 | Multi Criteria | IH Attic Far Right at Wall (Low Left) |
| 1 | S75 | 17 | Multi Criteria | IH Attic Far Right at Wall (Low Right) |
Node 3
| Node 3 (SLP-SS): IH S3 | ||||
| Loop | Address | DACT | Type | Description |
Node 4
| Node 4 (ILI-MB): EW ILI | ||||
| Loop | Address | DACT | Type | Description |
| 1 | S1 | 17 | Multi Criteria | EW Bsmt at Stairs to 1FL |
| 1 | M1 | 1 | Addr. Manual Station | EW Bsmt at Stairs to 1FL |
| 1 | S2 | 17 | Multi Criteria | EW Bsmt Near Electric Panels |
| 1 | M2 | 0 | Form C AOM NS | EW Bsmt RF-6 Shutdown Relay |
| 1 | S3 | 17 | Multi Criteria | EW Bsmt Above RF-6 Near Stairs |
| 1 | M3 | 2 | Supervisory Sw | EW Bsmt Room 10 ATS #1 Power Transfer |
| 1 | S4 | 3 | Photo Duct Supv | EW Bsmt RF-6 Return DSD |
| 1 | M4 | 2 | Supervisory Sw | EW Bsmt Room 10 ATS #2 Power Transfer |
| 1 | S5 | 3 | Photo Duct Supv | EW Bsmt AHU-6 Supply DSD |
| 1 | S6 | 17 | Multi Criteria | EW Bsmt Inside Substation Front |
| 1 | M6 | 1 | Addr. Manual Station | EW Bsmt Inside Substation |
| 1 | S7 | 17 | Multi Criteria | EW Bsmt Inside Substation Rear |
| 1 | M7 | 2 | Supervisory Sw | EW Bsmt Substation TraceTek Moisture Det |
| 1 | S8 | 17 | Multi Criteria | EW Bsmt Above AHU-6 Near Stairs |
| 1 | M8 | 0 | Form C AOM NS | EW Bsmt AHU-6 Shutdown Relay |
| 1 | S9 | 17 | Multi Criteria | EW Bsmt Inside Substation Middle |
| 1 | M9 | 1 | Addr. Manual Station | EW Bsmt Stairs to Fire Pump |
| 1 | M10 | 2 | Tamper NonL | EW Bsmt Room 005 Sprinkler Main Shutoff |
| 1 | S11 | 17 | Multi Criteria | EW Bsmt South Room 002 Sub-Basement |
| 1 | M11 | 0 | Waterflow Sil | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | S12 | 17 | Multi Criteria | EW Bsmt North Room 005 |
| 1 | M12 | 2 | Tamper NonL | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | S13 | 17 | Multi Criteria | EW Bsmt Above Fire Pump |
| 1 | M13 | 0 | Waterflow Sil | EW Bsmt Pre-Action Serving WW Attic |
| 1 | S14 | 17 | Multi Criteria | EW Bsmt South Room 009 |
| 1 | M14 | 2 | Tamper NonL | EW Bsmt Pre-Action Serving WW Attic |
| 1 | S15 | 17 | Multi Criteria | EW Bsmt Walkway Between Rooms 007 & 009 |
| 1 | M15 | 0 | Waterflow Sil | EW Bsmt Wet System Serving WW Bsmt |
| 1 | S16 | 17 | Multi Criteria | EW Bsmt South Room 010 |
| 1 | M16 | 2 | Tamper NonL | EW Bsmt Wet System Serving WW Bsmt |
| 1 | S17 | 5 | Photo Detector | EW 1FL O/S Gift Shop Entrance |
| 1 | M17 | 0 | Waterflow Sil | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | S18 | 5 | Photo Detector | EW 1FL Gift Shop Rear |
| 1 | M18 | 2 | Tamper NonL | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | S19 | 5 | Photo Detector | EW 1FL Gift Shop Middle |
| 1 | M19 | 0 | Waterflow Sil | EW Bsmt Pre-Act Serving IH Attic + Tower |
| 1 | S20 | 5 | Photo Detector | EW 1FL Gift Shop Front |
| 1 | M20 | 2 | Tamper NonL | EW Bsmt Pre-Act Serving IH Attic + Tower |
| 1 | S21 | 5 | Photo Detector | EW 1FL at Door to Chestnut Street |
| 1 | M21 | 0 | Waterflow Sil | EW Bsmt Wet System Serving IH Bsmt |
| 1 | S22 | 5 | Photo Detector | EW 2FL O/S Security Break Room |
| 1 | M22 | 2 | Tamper NonL | EW Bsmt Wet System Serving IH Bsmt |
| 1 | S23 | 5 | Photo Detector | EW 2FL Security Break Room Front Right |
| 1 | M23 | 0 | Waterflow Sil | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | S24 | 5 | Photo Detector | EW 2FL Security Break Room Storage Room |
| 1 | M24 | 2 | Tamper NonL | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | S25 | 5 | Photo Detector | EW 2FL Security Break Room Rear Left |
| 1 | M25 | 0 | Waterflow Sil | EW Bsmt Pre-Action Serving EW Attic |
| 1 | S26 | 5 | Photo Detector | EW 2FL Security Break Room Front Left |
| 1 | M26 | 2 | Tamper NonL | EW Bsmt Pre-Action Serving EW Attic |
| 1 | S27 | 5 | Photo Detector | EW 2FL Security Break Room O/S Restroom |
| 1 | M27 | 0 | Waterflow Sil | EW Bsmt Wet System Serving EW Bsmt |
| 1 | S28 | 17 | Multi Criteria | EW Attic Near Hatch |
| 1 | M28 | 2 | Tamper NonL | EW Bsmt Wet System Serving EW Bsmt |
| 1 | S29 | 17 | Multi Criteria | EW Attic Left Rear |
| 1 | M29 | 2 | Tamper NonL | EW Bsmt Fire Pump Bypass Left V/T |
| 1 | S30 | 17 | Multi Criteria | EW Attic Right Rear |
| 1 | M30 | 2 | Tamper NonL | EW Bsmt Fire Pump Bypass Right V/T |
| 1 | S31 | 17 | Multi Criteria | EW Attic Right Front |
| 1 | M31 | 2 | Tamper NonL | EW Bsmt Jocket Pump Suction V/T |
| 1 | S32 | 17 | Multi Criteria | EW Bsmt South Room 002 Sub-Basement |
| 1 | M32 | 2 | Supervisory Sw | EW Bsmt Jockey Pump Power Loss |
| 1 | S33 | 17 | Multi Criteria | EW Bsmt Above RF-6 Right Side |
| 1 | M33 | 2 | Tamper NonL | EW Bsmt Jocket Pump Discharge V/T |
| 1 | M34 | 2 | Tamper NonL | EW Bsmt Fire Pump Test Header V/T |
| 1 | M35 | 2 | Tamper NonL | EW Bsmt Fire Pump Discharge V/T |
| 1 | M36 | 2 | Tamper NonL | EW Bsmt Fire Pump Suction V/T |
| 1 | M37 | 2 | Supervisory Sw | EW Bsmt Fire Pump Run |
| 1 | M38 | 2 | Supervisory Sw | EW Bsmt Fire Pump Power Loss |
| 1 | M39 | 2 | Supervisory Sw | EW Bsmt Fire Pump Phase Reverse |
| 1 | M40 | 2 | Supervisory Sw | EW Bsmt Fire Pump ATS #3 Power Transfer |
| 1 | M45 | 1 | Addr. Manual Station | EW 1FL Entrance to Gift Shop |
| 1 | M46 | 1 | Addr. Manual Station | EW 1FL Exit to Chestnut Street |
| 1 | M47 | 1 | Addr. Manual Station | EW 1FL Gift Shop Rear Exit |
| 1 | M48 | 1 | Addr. Manual Station | EW 2FL O/S Security Break Room |
| 1 | M49 | 1 | Addr. Manual Station | EW Attic Near Hatch |
| 1 | M50 | 0 | Form C AOM NS | EW Bsmt Door Release Realy at FACP |
| 1 | M51 | 1 | Addr. Manual Station | EW Bsmt at Stairs to IH |
| 1 | M52 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | M53 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving EW Attic |
| 1 | M54 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | M55 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving EW Attic |
| 1 | M56 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | M57 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving EW Attic |
| 1 | M58 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving EW 1FL + 2FL |
| 1 | M59 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving EW Attic |
| 1 | M60 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | M61 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving IH Attic |
| 1 | M62 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | M63 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving IH Attic |
| 1 | M64 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | M65 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving IH Attic |
| 1 | M66 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving IH 1FL + 2FL |
| 1 | M67 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving IH Attic |
| 1 | M68 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | M69 | 0 | Pre-Action Alm | EW Bsmt Pre-Action Serving WW Attic |
| 1 | M70 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | M71 | 20 | Pre-Action Tbl | EW Bsmt Pre-Action Serving WW Attic |
| 1 | M72 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | M73 | 2 | Pre-Action Sup | EW Bsmt Pre-Action Serving WW Attic |
| 1 | M74 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving WW 1FL + 2FL |
| 1 | M75 | 2 | Low Air NonL | EW Bsmt Pre-Action Serving WW Attic |
| 2 | M1 | 20 | Pwr Supply Tbl | EW-PS1 Fault |
Node 5
| Node 5 (ILI-MB): OCH ILI | ||||
| Loop | Address | DACT | Type | Description |
| 1 | S1 | 5 | Photo Detector | OCH Bsmt Womens Locker Room |
| 1 | M1 | 1 | Addr. Manual Station | OCH Bsmt at Stairs to 1FL |
| 1 | S2 | 5 | Photo Detector | OCH Bsmt Hall at Stairs to 1FL |
| 1 | M2 | 1 | Addr. Manual Station | OCH Bsmt at Mech Area Door to Lockers |
| 1 | S3 | 5 | Photo Detector | OCH Bsmt Mens Restroom |
| 1 | M3 | 1 | Addr. Manual Station | OCH Bsmt Near RF-7 and Stairs to EW |
| 1 | S4 | 5 | Photo Detector | OCH Bsmt Womens Restroom |
| 1 | M4 | 0 | Form C AOM NS | OCH Bsmt AHU-7 Supply Shutdown Relay |
| 1 | S5 | 5 | Photo Detector | OCH Bsmt Mens Locker Room |
| 1 | M5 | 0 | Form C AOM NS | OCH Bsmt AHU-7 Return Shutdown Relay |
| 1 | S6 | 17 | Multi Criteria | OCH Bsmt OS Door to Mens Locker Room |
| 1 | M6 | 0 | Waterflow Sil | OCH Bsmt Wet System W/F |
| 1 | S7 | 17 | Multi Criteria | OCH Bsmt Front Right Between Duct Work |
| 1 | M7 | 2 | Tamper NonL | OCH Bsmt Wet System V/T |
| 1 | M8 | 0 | Waterflow Sil | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S9 | 3 | Photo Duct Supv | OCH Bsmt RF-7 Return DSD |
| 1 | M9 | 2 | Tamper NonL | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S10 | 17 | Multi Criteria | OCH Bsmt Near Stairs to EW |
| 1 | M10 | 2 | Low Air NonL | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S11 | 3 | Photo Duct Supv | OCH Bsmt AHU-7 Supply DSD |
| 1 | M11 | 2 | Low Air NonL | OCH Bsmt Pre-Action Serving Attic |
| 1 | S12 | 3 | Photo Duct Supv | OCH Bsmt AHU-7 Return DSD |
| 1 | M12 | 0 | Waterflow Sil | OCH Bsmt Pre-Action Serving Attic |
| 1 | S13 | 17 | Multi Criteria | OCH Bsmt Near AHU-7 |
| 1 | M13 | 2 | Tamper NonL | OCH Bsmt Pre-Action Serving Attic |
| 1 | S14 | 17 | Multi Criteria | OCH Bsmt Near Sprinkler Riser |
| 1 | M14 | 2 | Tamper NonL | OCH Bsmt Rear Hall Main V/T |
| 1 | S15 | 17 | Multi Criteria | OCH Bsmt Rear Hall Near OS&Y |
| 1 | M15 | 0 | Waterflow Sil | OCH Bsmt Rear Hall Main W/F |
| 1 | S16 | 17 | Multi Criteria | OCH Bsmt Rear Hall Middle |
| 1 | M16 | 1 | Addr. Manual Station | OCH 1FL O/S FACP Room |
| 1 | S17 | 17 | Multi Criteria | OCH Bsmt O/S Door to EW Electrical Room |
| 1 | M17 | 0 | Beam Smk Alarm | OCH 1FL Entrance BSD Alarm |
| 1 | S18 | 17 | Multi Criteria | OCH Bsmt Alcove Near EW Electrical Room |
| 1 | M18 | 20 | Beam Smk Trbl | OCH 1FL Entrance BSD Trouble |
| 1 | S19 | 17 | Multi Criteria | OCH Bsmt Hall to Rear Hallway |
| 1 | M19 | 0 | Beam Smk Alarm | OCH 1FL Gift Shop BSD Alarm |
| 1 | S20 | 5 | Photo Detector | OCH 1FL at FACP |
| 1 | M20 | 20 | Beam Smk Trbl | OCH 1FL Gift Shop BSD Trouble |
| 1 | S21 | 5 | Photo Detector | OCH 1FL O/S FACP Room |
| 1 | M21 | 0 | Beam Smk Alarm | OCH 1FL Court Room Hall BSD Alarm |
| 1 | S22 | 5 | Photo Detector | OCH 1FL Mayors Courtroom On Stage |
| 1 | M22 | 20 | Beam Smk Trbl | OCH 1FL Court Room Hall BSD Trouble |
| 1 | S23 | 5 | Photo Detector | OCH 1FL Gallery Front |
| 1 | M23 | 0 | Beam Smk Alarm | OCH 1FL Court Room Front BSD Alarm |
| 1 | S24 | 5 | Photo Detector | OCH 1FL Gallery Middle |
| 1 | M24 | 20 | Beam Smk Trbl | OCH 1FL Court Room Front BSD Trouble |
| 1 | S25 | 5 | Photo Detector | OCH 1FL Gallery Rear |
| 1 | M25 | 0 | Beam Smk Alarm | OCH 1FL Court Room Read BSD Alarm |
| 1 | S26 | 5 | Photo Detector | OCH 2FL Office 205 |
| 1 | M26 | 20 | Beam Smk Trbl | OCH 1FL Court Room Read BSD Trouble |
| 1 | S27 | 5 | Photo Detector | OCH 2FL Office 202 Rear |
| 1 | M27 | 1 | Addr. Manual Station | OCH 2FL at Stairs |
| 1 | S28 | 5 | Photo Detector | OCH 2FL Office 202 Middle |
| 1 | M28 | 0 | Beam Smk Alarm | OCH 2FL Hall BSD Alarm |
| 1 | S29 | 5 | Photo Detector | OCH 2FL Office 202 Front |
| 1 | M29 | 20 | Beam Smk Trbl | OCH 2FL Hall BSD Trouble |
| 1 | S30 | 5 | Photo Detector | OCH 2FL Mayors Office at Bay Window |
| 1 | M30 | 0 | Beam Smk Alarm | OCH 2FL Mayors Office Front BSD Alarm |
| 1 | S31 | 5 | Photo Detector | OCH 2FL Office 204 |
| 1 | M31 | 20 | Beam Smk Trbl | OCH 2FL Mayors Office Front BSD Trouble |
| 1 | S32 | 5 | Photo Detector | OCH 3FL Stairs to Attic |
| 1 | M32 | 0 | Beam Smk Alarm | OCH 2FL Mayors Office Rear BSD Alarm |
| 1 | S33 | 17 | Multi Criteria | OCH Attic Near Door to Stairs |
| 1 | M33 | 20 | Beam Smk Trbl | OCH 2FL Mayors Office Rear BSD Trouble |
| 1 | S34 | 17 | Multi Criteria | OCH Attic Left of Door - Front |
| 1 | M34 | 1 | Addr. Manual Station | OCH Attic at Door to Stairs |
| 1 | S35 | 17 | Multi Criteria | OCH Attic Right Side Front |
| 1 | M35 | 0 | Form C AOM NS | OCH 1FL FACP Door Release Relay |
| 1 | S36 | 17 | Multi Criteria | OCH Attic Right Side Rear |
| 1 | M36 | 20 | Pwr Supply Tbl | OCH PS1 Fault |
| 1 | S37 | 17 | Multi Criteria | OCH Attic Right Side Rear - Middle |
| 1 | M37 | 0 | Pre-Action Alm | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | M38 | 0 | Pre-Action Alm | OCH Bsmt Pre-Action Serving Attic |
| 1 | M39 | 20 | Pre-Action Tbl | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | M40 | 20 | Pre-Action Tbl | OCH Bsmt Pre-Action Serving Attic |
| 1 | M41 | 2 | Pre-Action Sup | OCH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | M42 | 2 | Pre-Action Sup | OCH Bsmt Pre-Action Serving Attic |
| 1 | M43 | 0 | Form C AOM NS | OCH 1FL FACP Beam Smoke Reset Relay |
| 1 | M44 | 0 | FACP | OCH Honeywell Vista by FACP Alarm |
| 1 | M45 | 2 | Supervisory Sw | OCH Honeywell Vista by FACP Trouble |
Node 6
| Node 6 (ILI-MB): WW ILI | ||||
| Loop | Address | DACT | Type | Description |
| 1 | S1 | 17 | Multi Criteria | WW Bsmt at FACP |
| 1 | M1 | 1 | Addr. Manual Station | WW Bsmt at FACP and Stairs |
| 1 | S2 | 3 | Photo Duct Supv | WW Bsmt AHU-3 Supply DSD |
| 1 | M2 | 0 | Form C AOM NS | WW Bsmt AHU-3 Supply Shutdown Relay |
| 1 | S3 | 3 | Photo Duct Supv | WW Bsmt AHU-3 Return DSD |
| 1 | M3 | 0 | Form C AOM NS | WW Bsmt AHU-3 Return Shutdown Relay |
| 1 | S4 | 17 | Multi Criteria | WW Bsmt Near Slop Sink |
| 1 | M4 | 1 | Addr. Manual Station | WW Bsmt Hall to IH |
| 1 | S5 | 17 | Multi Criteria | WW Bsmt South Room 002 |
| 1 | M5 | 1 | Addr. Manual Station | WW Bsmt North Wall Near CH |
| 1 | S6 | 17 | Multi Criteria | WW Bsmt South Room 003 |
| 1 | M6 | 1 | Addr. Manual Station | WW 1FL at Stairs and Chestnut St Exit |
| 1 | S7 | 17 | Multi Criteria | WW Bsmt North Room 004 Front |
| 1 | M7 | 1 | Addr. Manual Station | WW 1FL Show Rm Rear Exit to Chestnut St |
| 1 | S8 | 17 | Multi Criteria | WW Bsmt North Room 004 Rear |
| 1 | M8 | 1 | Addr. Manual Station | WW 1FL at Ramp to Show Room |
| 1 | S9 | 17 | Multi Criteria | WW Bsmt North Room 006 Front |
| 1 | M9 | 1 | Addr. Manual Station | WW 2FL at Stairs to 1FL |
| 1 | S10 | 17 | Multi Criteria | WW Bsmt Near Bulk Head Door Stairs |
| 1 | M10 | 1 | Addr. Manual Station | WW Attic Near Entrance |
| 1 | S11 | 17 | Multi Criteria | WW Bsmt Above AHU-3 Duct Work |
| 1 | M11 | 0 | Form C AOM NS | WW Bsmt Door Release Relay at FACP |
| 1 | S12 | 17 | Multi Criteria | WW Bsmt South Wall Near Electrical Pnls |
| 1 | M12 | 2 | Supervisory Sw | WW Bsmt N Rm 004 TraceTek Moisture Det |
| 1 | S13 | 17 | Multi Criteria | WW Bsmt Near Hall to CH |
| 1 | S15 | 5 | Photo Detector | WW 1FL at Ramp to Show Room |
| 1 | S16 | 5 | Photo Detector | WW 1FL Inside Closet Near Ramp |
| 1 | S17 | 5 | Photo Detector | WW 1FL Right Side of Display Case |
| 1 | S18 | 5 | Photo Detector | WW 1FL Left Side of Display Case |
| 1 | S19 | 5 | Photo Detector | WW 1FL Inside Closet Near Chestnut St |
| 1 | S20 | 5 | Photo Detector | WW 1FL at Stairs and Chestnut St Exit |
| 1 | S21 | 5 | Photo Detector | WW 2FL at Stairs to 1FL |
| 1 | S22 | 5 | Photo Detector | WW 2FL Inside Closet Near Entrance |
| 1 | S23 | 5 | Photo Detector | WW 2FL Womens Restroom |
| 1 | S24 | 5 | Photo Detector | WW 2FL Restroom Hallway |
| 1 | S25 | 5 | Photo Detector | WW 2FL VIP Room North |
| 1 | S26 | 5 | Photo Detector | WW 2FL VIP Room South |
| 1 | S27 | 5 | Photo Detector | WW 2FL Kitchenette |
| 1 | S28 | 5 | Photo Detector | WW 2FL Mens Restroom |
| 1 | S29 | 5 | Photo Detector | WW 2FL Custodial Closet |
| 1 | S30 | 5 | Photo Detector | WW 2FL O/S Custodial Closet |
| 1 | S31 | 17 | Multi Criteria | WW Bsmt North Room 006 Rear |
| 1 | S32 | 17 | Multi Criteria | WW Attic at Entrance |
| 1 | S33 | 17 | Multi Criteria | WW Attic South East Side |
| 1 | S34 | 17 | Multi Criteria | WW Attic North East Side |
| 1 | S35 | 17 | Multi Criteria | WW Attic North West Side |
| 2 | M1 | 20 | Pwr Supply Tbl | WW Bsmt PS1 Fault |
Node 7
| Node 7 (ILI-MB): CH ILI | ||||
| Loop | Address | DACT | Type | Description |
| 1 | S1 | 17 | Multi Criteria | CH Bsmt Near FACP |
| 1 | M1 | 1 | Addr. Manual Station | CH Bsmt at FACP |
| 1 | S2 | 3 | Photo Duct Supv | CH RF-1 Return DSD |
| 1 | M2 | 0 | Form C AOM NS | CH Bsmt RF-1 Shutdown Relay |
| 1 | M3 | 0 | Form C AOM NS | CH Bsmt Door Release Relay at FACP |
| 1 | S4 | 17 | Multi Criteria | CH Bsmt at Door to West Wing |
| 1 | M4 | 1 | Addr. Manual Station | CH Bsmt Near AHU-1 DSD |
| 1 | S5 | 3 | Photo Duct Supv | CH Bsmt AHU-1 Supply DSD |
| 1 | M5 | 0 | Form C AOM NS | CH Bsmt AHU-1 Supply Shutdown Relay |
| 1 | S6 | 17 | Multi Criteria | CH Bsmt Above AHU-1 Center |
| 1 | M6 | 1 | Addr. Manual Station | CH Bsmt at Bulkhead Doors |
| 1 | S7 | 17 | Multi Criteria | CH Bsmt Behind AHU-1 |
| 1 | M7 | 1 | Addr. Manual Station | CH Bsmt at Pre-Action Panels |
| 1 | S8 | 17 | Multi Criteria | CH Bsmt Room 008 Left Side |
| 1 | M8 | 0 | Waterflow Sil | CH Bsmt Wet System W/F |
| 1 | S9 | 17 | Multi Criteria | CH Bsmt Room 009 Left Side |
| 1 | M9 | 2 | Tamper NonL | CH Bsmt Wet System V/T |
| 1 | S10 | 17 | Multi Criteria | CH Bsmt Room 009 Center |
| 1 | M10 | 0 | Waterflow Sil | CH Bsmt Pre-Action Serving CH 1FL+2FL |
| 1 | S11 | 17 | Multi Criteria | CH Bsmt Room 009 Right Side |
| 1 | M11 | 2 | Tamper NonL | CH Bsmt Pre-Action Serving CH 1FL+2FL |
| 1 | S12 | 17 | Multi Criteria | CH Bsmt Room 008 at Bulkhead Doors |
| 1 | M12 | 0 | Waterflow Sil | CH Bsmt Pre-Action Serving CH Attic |
| 1 | S13 | 17 | Multi Criteria | CH Bsmt Room 008 Center |
| 1 | M13 | 2 | Tamper NonL | CH Bsmt Pre-Action Serving CH Attic |
| 1 | S14 | 17 | Multi Criteria | CH Bsmt Above AHU-1 Right Side |
| 1 | M14 | 2 | Low Air NonL | CH Bsmt Pre-Action Serving CH 1FL+2FL |
| 1 | S15 | 17 | Multi Criteria | CH Bsmt Right of FACP |
| 1 | M15 | 2 | Low Air NonL | CH Bsmt Pre-Action Serving CH Attic |
| 1 | S16 | 17 | Multi Criteria | CH Bsmt Sump Pump Closet |
| 1 | M16 | 1 | Addr. Manual Station | CH 1FL at Stairs to Basement |
| 1 | S17 | 17 | Multi Criteria | CH Bsmt Outside Sump Pump Closet |
| 1 | M17 | 1 | Addr. Manual Station | CH 1FL Main Entrance on Letterbox |
| 1 | S18 | 17 | Multi Criteria | CH Bsmt Room 005 Center |
| 1 | M18 | 1 | Addr. Manual Station | CH 2FL East Committee Rm Janitor Closet |
| 1 | S19 | 17 | Multi Criteria | CH Bsmt Rm 005 Left of Pre-Action Risers |
| 1 | M19 | 1 | Addr. Manual Station | CH Attic Near Hatch |
| 1 | S20 | 5 | Photo Detector | CH Bsmt Womens Restroom |
| 1 | M20 | 0 | Form C AOM NS | CH Attic AHU-2 Return Shutdown Relay |
| 1 | S21 | 17 | Multi Criteria | CH Bsmt Womens Restroom Mop Closet |
| 1 | M21 | 0 | Form C AOM NS | CH Attic AHU-2 Supply Shutdown Relay |
| 1 | S22 | 5 | Photo Detector | CH Bmst Near Steps to First Floor |
| 1 | M22 | 0 | Pre-Action Alm | CH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S23 | 5 | Photo Detector | CH Bsmt Mens Restroom |
| 1 | M23 | 0 | Pre-Action Alm | CH Bsmt Pre-Action Serving Attic |
| 1 | S24 | 5 | Photo Detector | CH 1FL at Stairs to Basement |
| 1 | M24 | 20 | Pre-Action Tbl | CH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S25 | 5 | Photo Detector | CH 1FL at Double Door to Chestnut Street |
| 1 | M25 | 20 | Pre-Action Tbl | CH Bsmt Pre-Action Serving Attic |
| 1 | M26 | 2 | Pre-Action Sup | CH Bsmt Pre-Action Serving 1FL + 2FL |
| 1 | S27 | 17 | Multi Criteria | CH Bsmt In WW Near Entrance to CH |
| 1 | M27 | 2 | Pre-Action Sup | CH Bsmt Pre-Action Serving Attic |
| 1 | S28 | 5 | Photo Detector | CH 1FL IT Room Under East Stairs |
| 1 | S29 | 5 | Photo Detector | CH 1FL Under Gallery |
| 1 | S30 | 5 | Photo Detector | CH 1FL Under Gallery |
| 1 | S31 | 5 | Photo Detector | CH 1FL Above Stage |
| 1 | S32 | 5 | Photo Detector | CH 1FL at Main Entrance |
| 1 | S33 | 5 | Photo Detector | CH 1FL Rear Left |
| 1 | S34 | 5 | Photo Detector | CH 1FL Center Left |
| 1 | S35 | 5 | Photo Detector | CH 1FL Front Left |
| 1 | S37 | 5 | Photo Detector | CH 1FL Gallery Right Side |
| 1 | S38 | 5 | Photo Detector | CH 1FL Gallery Left Side |
| 1 | S44 | 5 | Photo Detector | CH 2FL Top of West Stairs |
| 1 | S46 | 5 | Photo Detector | CH 2FL Joint Committee Room |
| 1 | S47 | 5 | Photo Detector | CH 2FL West Committee Room |
| 1 | S49 | 5 | Photo Detector | CH 2FL Senate Chamber Gallery Right |
| 1 | S50 | 5 | Photo Detector | CH 2FL Senate Chamber Right Rear |
| 1 | S51 | 5 | Photo Detector | CH 2FL Senate Chamber Front Right |
| 1 | S52 | 5 | Photo Detector | CH 2FL Senate Chamber Front Middle |
| 1 | S53 | 5 | Photo Detector | CH 2FL Senate Chamber In Chair On Stage |
| 1 | S54 | 5 | Photo Detector | CH 2FL Senate Chamber Rear Middle |
| 1 | S55 | 5 | Photo Detector | CH 2FL Senate Chamber Front Left |
| 1 | S56 | 5 | Photo Detector | CH 2FL Senate Chamber Rear Left |
| 1 | S57 | 5 | Photo Detector | CH 2FL Senate Chamber Gallery Left |
| 1 | S58 | 5 | Photo Detector | CH 2FL East Committee Room Mop Closet |
| 1 | S60 | 5 | Photo Detector | CH 2FL East Committee Room |
| 1 | S61 | 5 | Photo Detector | CH 2FL Hall O/S East + West Committee Rm |
| 1 | S62 | 5 | Photo Detector | CH 2FL Hall O/S Joint Committee Room |
| 1 | S63 | 5 | Photo Detector | CH 2FL Senate Secretarys Office |
| 1 | S65 | 5 | Photo Detector | CH 2FL Top of East Stairs |
| 1 | S66 | 3 | Photo Duct Supv | CH Attic AHU-2 Return DSD |
| 1 | S67 | 17 | Multi Criteria | CH Attic Behind Hatch |
| 1 | S68 | 17 | Multi Criteria | CH Attic Behind Hatch |
| 1 | S69 | 17 | Multi Criteria | CH Attic Near Hatch |
| 1 | S70 | 17 | Multi Criteria | CH Attic Left of Hatch |
| 1 | S72 | 17 | Multi Criteria | CH Attic Behind AHU-2 Supply DSD |
| 1 | S73 | 17 | Multi Criteria | CH Attic Behind AHU-2 Supply DSD |
| 1 | S74 | 17 | Multi Criteria | CH Attic Right of AHU-2 Supply DSD |
| 1 | S75 | 17 | Multi Criteria | CH Attic Left of AHU-2 Supply DSD |
| 1 | S76 | 3 | Photo Duct Supv | CH Attic AHU-2 Supply DSD |
| 2 | M1 | 20 | Pwr Supply Tbl | CH-PS1 Fault |
File details come from the government source that posted it. Updated .