2025_Inspection_Reports_0001.pdf
PDF 1 MB Posted
- Solicitation number
- 140P4226Q0046
About this file
These are NFPA 72 annual fire alarm inspection, testing, and maintenance reports for the National Park Service property at 143 S 3rd Street, Philadelphia, PA 19106-2818 (Independence National Historical Park), conducted between July 28-31, 2025 by Hiller Philadelphia technician Christoper Benedetto (Cert/License 24404). The reports document comprehensive testing of five separate fire alarm control systems across multiple buildings and structures on the property.
The inspections identified multiple significant deficiencies requiring immediate attention. System-wide issues include: four backup battery failures (out-of-date Simplex batteries, low charging voltage in one unit); one heat detector damaged by pipe burst; wiring failures affecting multiple photoelectric smoke detectors on the third floor and second floor of the 339-341 Walnut building; nine non-restorable heat detectors dated 1982 requiring replacement; four malfunctioning notification bells in one building with only one operational bell system-wide; and temporary wire bypasses used to circumvent broken detector lines. Other deficiencies include one heat detector with no power access to test, three heat detectors inaccessible due to locked dumbwaiter doors, and one heat detector over 15 years old. Alarm signal transmission times to NPS Security monitoring ranged from 15-21 seconds, all within the 90-second requirement. Of the systems inspected, the Gamewell-FCI S3 systems (K-House Basement and Maintenance Shop) and Notifier SFP-1024 (Declaration House) passed with minimal deficiencies, while the Simplex 4100U (City Tavern), Notifier 4800-A (339-341 Walnut), and related systems showed extensive failures requiring component replacement and system repairs before full compliance with NFPA 72 standards can be achieved.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P4226Q0046_Amd_0002.pdf | ||
| Independence_Hall_Points_9_4_2026_0002.xlsx | XLSX spreadsheet | |
| First_Bank_ROC_0002.pdf | ||
| 140P4226Q0046_QnA_0001.pdf | ||
| Sol_140P4226Q0046_Amd_0001.pdf | ||
| Sol_140P4226Q0046.pdf | ||
| Attachment_2_Locations_and_Equipment_Lists.xlsx | XLSX spreadsheet | |
| Attachment_3_Quote_Submission_Package.docx | DOCX document | |
| Attachment_1_Wage_Determination_2015-4233_Rev_37_effective_7_30_2026.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hiller Philadelphia 21 Bellecor Drive
New Castle, DE 19720
DESP 24-331; DE FAL-0403; FSL-0344
FEL; NJCBP P01705; NJ CRA 744485
Inspection, Testing, & Maintenance Report For
NATIONAL PARK SERVICE
143 S 3rd St
Philadelphia, PA 19106-2818 07-28-2025
COMPACT - NFPA 72 VISUAL AND FUNCTIONAL
INSPECTION OF FIRE ALARM SYSTEMS
Required Inspection Frequency: ANNUAL Information on this form covers the minimum requirements of the current edition of NFPA 72 (unless otherwise directed by the authority having jurisdiction).
Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Monitoring Entity Is location monitored? Yes
Name: NPS Security
Phone Number: 2155977077
Account Number: N/A
Approving Agency Name: NPS Security
Phone Number: 2155977077
Control Unit Information Manufacturer: Simplex
Model: 4020
Panel/Node Identifier: City Tavern
Software Revision: N/A
Type of Communicator: Fiber Network
Circuit Style: B
Number of SLC Circuits (if Applicable): 1
Number of Zones (if Applicable): N/A
Number of NAC Circuits (if Applicable): 4
If there are more than two visual notification appliances in the same room or adjacent space within view of the flash do these visual notification appliances synchronize?
N/A
Did notification appliance circuits operate properly? Yes
Primary Power Supply Information Nominal Input Voltage: 120
Amp Rating: Unknown
Location of Panelboard: Cellar Electrical Room
Overcurrent Protection Type: Circuit Breaker
Overcurrent Amp Rating: 20
Panelboard ID Number: RP-1
Fuse ID or Breaker Number: 11
Engine-Driven Generator Information Location of Generator: N/A
Location of Fuel Storage: N/A
Fuel Type: N/A
Energy Storage System (ESS) Information Equipment Powered by ESS: N/A
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Zip: 19106-2818 Periodicity: Annual
Location of ESS: N/A
Hours of Operation in Standby Mode: N/A
Minutes of Operation in Alarm Mode: N/A
Secondary Power Supply Information (Batteries) Type: Sealed Lead-Acid
Nominal Voltage: 12
Amp Rating: 35
Location: FACP
Hours of operation in Standby Mode: 24
Minutes of operation in Alarm Mode: 5
PART I - OWNER'S SECTION
Is the building occupied? No
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
PART II - INSPECTION AND TESTING
ANNUAL
Control Panel & Power Supplies:
Control unit and power supplies are free of physical damage? Yes
Control unit trouble signal functional? Yes
All lamps, LEDs, and/or LCDs are functional? Yes
Notification appliance circuit power extender lamps and LEDs indicate normal operating status of the equipment? Yes
Remote power supplies, lamps, and LEDs indicate normal operating status of the equipment? Yes
Surge protective devices are in good operating condition? Yes
Optical fiber cable connections are in good operating condition? Yes
All fuses are functional? N/A
All fuses are supervised and ratings verified? N/A
All disconnect switches and buttons are functional? Yes
A trouble signal was received when a supervised function was disconnected? Yes
Ground-fault monitoring is functional? Yes
Circuits properly monitored for integrity? Yes
Local & Remote Annunciators:
All annunciators pass visual inspection? N/A
All annunciators pass functional test? N/A
Offsite Responders Alarm signal received by monitoring within 90 seconds?
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Alarm signal time (seconds): 15
Trouble signal received by monitoring within 90 seconds? Yes
Trouble signal time (seconds): 15
Supervisory signal received by monitoring within 90 seconds? N/A
Supervisory signal time (seconds): N/A
A document cabinet is present at the system control unit or other approved location? N/A
A copy of the site specific software is available? N/A
Are copies of as-built drawings available? N/A
PART III - NOTIFICATIONS THAT TESTING IS COMPLETE
Entities Notified:
Monitoring Organization Contact Name: NPS Security
Record time of contact (HH:MM)): 3:15 pm
Building Management Contact Name: Ken Flannigan
Record time of contact (HH:MM)): 3:15 pm
Building Occupants Contact Name: N/A
Record time of contact (HH:MM)): N/A
Authority Having Jurisdiction Contact Name: Philadelphia Fire Board
Record time of contact (HH:MM)): 3:25 pm
Other if required (specify): N/A
Contact Name: NPS Security
Record time of contact (HH:MM)): N/A
Current Component Counts Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed BELL Annual 6 6 0 6 0 PHOTOELECTRIC SMOKE DETECTOR Annual 6 6 0 6 0 DUCT SMOKE DETECTOR Annual 6 6 0 6 0 HEAT DETECTOR Annual 45 42 3 41 1 MANUAL STATION Annual 9 9 0 9 0 STROBE Annual 1 1 0 1 0 BATTERIES (INDIVIDUAL OR PAIR) Semi-Annual 2 2 0 0 2 OUTSIDE STEM AND YOKE-CONTROL VALVE WITH TAMPER SWITCH Semi-Annual 1 0 1 0 0 VANE-TYPE WATERFLOW SWITCH Semi-Annual 1 0 1 0 0 RELAY Annual 2 2 0 2 0
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Semi-Annual Inspection, Test and Maintenance for Batteries (Individual or Pair) Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
IN FACP Batteries (Individual or Pair)
07-28-2025 Christoper Benedetto
Tested Failed
Power Supply Make: Simplex
Power Supply Model: 4100U
Breaker Panel Location: Basement Wine Storage
Breaker Panel: RP-1
Circuit Breaker: 11
Amp Hour Rating (AH): 35
Charger Test Voltage (VDC): 25.48
Load Voltage: 12.54
Load Amperage: 26
Discharge Voltage: N/A
Load Voltage: 12.54
Load Amperage: 24
Discharge Voltage: N/A
Was the charger voltage within parameters? Yes
Was the load voltage of both batteries within required parameters? Yes
Was the load amperage of both batteries within required parameters? No
Was the discharge voltage of both batteries within required parameters? Yes
Install Date (MM/YY) 2024
Record the ambient temperature of the enclosure (F): 75.9
Record the ambient temperature of the battery at the negative terminal(F): 73.2
All batteries are marked with the month and year of manufacture? Yes
All batteries are within equipment manufacturer's replace date? Yes
All connections to batteries are tight? Yes
All terminals are free of corrosion? Yes
All batteries are free of distortion, cracks, and leakage? Yes
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Can the batteries remain in service considering manufacturers recommendations (such as date of manufacture, service temperature (less than 18 degrees F above ambient), and integrity of the casing)?
Yes
Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
BOOSTER IN CELLAR WINE STORAGE Batteries (Individual or Pair)
07-28-2025 Christoper Benedetto
Tested Failed
Power Supply Make: Simplex
Power Supply Model: 4009
Breaker Panel Location: Basement Wine Storage
Breaker Panel: RP-1
Circuit Breaker: 11
Amp Hour Rating (AH): 12
Charger Test Voltage (VDC): N/A
Load Voltage: N/A
Load Amperage: N/A
Discharge Voltage: N/A
Load Voltage: N/A
Load Amperage: N/A
Discharge Voltage: N/A
Was the charger voltage within parameters? Yes
Was the load voltage of both batteries within required parameters? Yes
Was the load amperage of both batteries within required parameters? Yes
Was the discharge voltage of both batteries within required parameters? Yes
Install Date (MM/YY) 2020
Record the ambient temperature of the enclosure (F): N/A
Record the ambient temperature of the battery at the negative terminal(F): N/A
All batteries are marked with the month and year of manufacture? Yes
All batteries are within equipment manufacturer's replace date? Yes
All connections to batteries are tight? Yes
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
All terminals are free of corrosion? Yes
All batteries are free of distortion, cracks, and leakage? Yes
Can the batteries remain in service considering manufacturers recommendations (such as date of manufacture, service temperature (less than 18 degrees F above ambient), and integrity of the casing)?
No
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Heat Detector
CT M2-33 CELLAR MEN'S ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Failed
CT M2-20 CELLAR FIRE PANEL ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-21 CELLAR HALL BY FIRE PANEL ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-22 CELLAR BAKERY ABOVE CEILING HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-23 CELLAR DISHWASH ABOVE CEILING HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-25 CELLAR LARDER DINING RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-28 CELLAR WINE COOLER AREA HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-29 CELLAR HALL BY FRONT EMERG EXIT HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-30 CELLAR COGNAC DINING RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-31 CELLAR CHEMICAL STORG. RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-32 CELLAR BEER ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-34 CELLAR WOMEN'S ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-35 1FL KITCHEN STORAGE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-36 1FL KITCHEN ABOVE CEILING REAR HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-37 1FL KITCHEN ABOVE CEILING FRONT HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-38 1FL KITCHEN OFFICE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-39 1FL REAR COFFEE RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-4 1FL ADA REST ROOM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-40 1FL FRONT COFFEE RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-41 1FL HALL BY FRONT COFFEE RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-42 1FL TOP OF REAR STAIRS HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-43 LANDING BETWEEN FLOORS 1&2 HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-44 1FL SUBSCRIPTION RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-45 1FL TAVERN ABOVE BOOTH HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
CT M2-46 1FL TAVERN ABOVE BAR HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-48 2FL CENTER OF KITCHEN HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-5 CELLAR WINE STORAGE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-50 2FL TOP OF KITCHEN STAIR HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-51 2FL SOUTH SIDE OF LONG RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-52 2FL CHARTER DINING RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-53 2FL NORTH END OF LONG RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-54 2FL CINCINATTI DINING RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-56 3FL LAUNDRY RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-57 3FL WOMEN'S RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-59 3FL SPECIAL EVENTS OFFICE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-60 3FL CHEF STAIB'S OFFICE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-61 3FL LIQUOR CLOSET HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-62 3FL MAIN OFFICE HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-63 4FL MECHANICAL RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-64 4FL MECHANICAL RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-65 4FL MECHANICAL RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-66 4FL MECHANICAL RM HEAT Heat Detector 07-28-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Bell
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-28-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Photoelectric Smoke Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
CT M2-55 3FL WOMEN'S LOCKER RM SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
CT M2-58 3FL MEN'S LOCKER RM SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
CT M2-71 CELLAR ABOVE FIRE PANEL SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
CT M2-72 CELLAR LINEN CLOSET SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
CT M2-74 4FL TOP OF STAIRS SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
CT M2-75 4FL MECHANICAL ROOM SMOKE Photoelectric Smoke Detector
07-28-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Duct Smoke Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
CT M2-67 4FL MECH RM HV-1 SUPPLY DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-68 4FL MECH RM HV-1 SUPPLY DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-69 4FL MECH RM HV-1 RETURN DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-76 4FL MECH RM AC-1 SUPPLY DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-77 4FL MECH RM AC-1 SUPPLY DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-78 4FL MECH RM AC-1 RETURN DUCT Duct Smoke Detector 07-28-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Manual Station
CT M2-1 CELLAR REAR EXIT PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-2 CELLAR KITCHEN CENTER PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-3 CELLAR KITCHEN FRONT STAIRS PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-6 1FL KITCHEN BY REAR COFFEE RM PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-7 1FL IN KITCHEN STAIRWELL PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-10 2FL KITCHEN EXIT TO CHARTER RM PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-11 2FL TOP OF KITCHEN STAIR PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-12 3FL HALL BY COAT RACK PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-13 4FL MECH RM PULL Manual Station 07-28-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Strobe Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Strobe Strobe 07-28-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Relay Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
CT M2-70 4FL MECH RM HV-1 SHUTDOWN RELAY Relay 07-28-2025 Christoper Benedetto
Tested Passed
CT M2-79 4FL MECH RM AC-1 SHUTDOWN RELAY Relay 07-28-2025 Christoper Benedetto
Tested Passed
Identifier Location Description Device Type Reason Not Tested
CT M2-26 CELLAR SHELF DINING RM HEAT Heat Detector No Access
CT M2-47 2FL TOP OF DUBWAITER #1 HEAT Heat Detector No power to dumbwaiter doors to gain access.
CT M2-49 2FL TOP OF DUBWAITER #2 HEAT Heat Detector No power to dumbwaiter doors to gain access.
CT M2-84 CELLAR SPRINKLER TAMPER Outside Stem and Yoke-Control Valve with Tamper Switch
Tied to a system no longer in use. Point is still in panel programming but resisted out
CT M2-83 1FL KITCHEN WATERFLOW Vane-Type Waterflow Switch
Tested by JCI
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Deficiencies
Identifier Address Location Description Device Type Date of Failure
N/A IN FACP Batteries (Individual or Pair)
07-28-2025
Reason for Failure Batteries (Individual or Pair), IN FACP , Manufacturer: Simplex 4100U , Model: (2) 12v35ah
Code Reference NFPA 72 2022 Table 14.4.3.2 (9)
Identifier Address Location Description Device Type Date of Failure
N/A BOOSTER IN CELLAR WINE STORAGE Batteries (Individual or Pair)
07-28-2025
Reason for Failure Batteries (Individual or Pair), BOOSTER IN CELLAR WINE STORAGE , Manufacturer: Simplex 4009 , Model: (2) 12v12ah -Batteries out of date
Code Reference NFPA 72 2022 Table 14.4.3.2 (9)
Identifier Address Location Description Device Type Date of Failure
CT M2-33 CELLAR MEN'S ROOM HEAT Heat Detector 07-28-2025
Reason for Failure CT M2-33 Heat Detector, CELLAR MEN'S ROOM HEAT , Manufacturer: Simplex , Model: 4098-9733 -Heat detector in "No Answer" trouble upon arrival. Device got wet when a pipe burst. Device needs to be replaced
Code Reference NFPA 72 2022 Table 14.4.3.2 (17) (4) (a) ,NFPA 72 2022 Table 14.4.3.2 (17) (4) (a)
Identifier Address Location Description Device Type Date of Failure
System N/A Simplex 4100U City Tavern Cellar near Linen Storage
Alarm System 07-28-2025
Reason for Failure -FACP had 38 troubles on it upon arrival, including several devices on Bsmt and 1st floors. This did clear about 10 mins after arriving, but not sure what exactly caused the issue.
-(3) troubles left on FACP upon departure. They are as follows:
-Card 3 Ground Fault -Heat detector in "No Answer" trouble. Device got wet when a pipe burst -Card 1 battery depleted/missing trouble. Batteries were replaced in 2024 and tested weak. Charging circuit voltage was a a little low at 25.48vDC. Charging Circuit may be failing
Code Reference NFPA 72
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-28-2025
System ID: Simplex 4100U City Tavern Cellar near
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
New Castle, DE 19720
DESP 24-331; DE FAL-0403; FSL-0344
FEL; NJCBP P01705; NJ CRA 744485
Inspection, Testing, & Maintenance Report For
NATIONAL PARK SERVICE
143 S 3rd St
Philadelphia, PA 19106-2818 07-29-2025
COMPACT - NFPA 72 VISUAL AND FUNCTIONAL
INSPECTION OF FIRE ALARM SYSTEMS
Required Inspection Frequency: ANNUAL Information on this form covers the minimum requirements of the current edition of NFPA 72 (unless otherwise directed by the authority having jurisdiction).
Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable
Name: N/A
Phone Number: N/A
Account Number: N/A
Approving Agency Name:
Phone Number:
Control Unit Information Manufacturer: Notifier
Model: SFP-1024
Panel/Node Identifier: Dec House
Software Revision: N/A
Type of Communicator: N/A
Circuit Style: B
Number of SLC Circuits (if Applicable): N/A
Number of Zones (if Applicable): 7
Number of NAC Circuits (if Applicable): 1
If there are more than two visual notification appliances in the same room or adjacent space within view of the flash do these visual notification appliances synchronize?
N/A
Did notification appliance circuits operate properly? N/A
Primary Power Supply Information Nominal Input Voltage: 120
Amp Rating: 1
Location of Panelboard: Basement Mechanical Rm.
Overcurrent Protection Type: Knife Switch
Overcurrent Amp Rating: N/A
Panelboard ID Number: N/A
Fuse ID or Breaker Number: N/A
Engine-Driven Generator Information Location of Generator: N/A
Location of Fuel Storage: N/A
Fuel Type: N/A
Energy Storage System (ESS) Information Equipment Powered by ESS: N/A
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Minutes of Operation in Alarm Mode: N/A
Secondary Power Supply Information (Batteries) Type: Sealed Lead-Acid
Nominal Voltage: 12
Amp Rating: 7
Location: FACP
Hours of operation in Standby Mode: 24
Minutes of operation in Alarm Mode: 5
PART I - OWNER'S SECTION
Is the building occupied? Yes
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
PART II - INSPECTION AND TESTING
ANNUAL
Control Panel & Power Supplies:
Control unit and power supplies are free of physical damage? Yes
Control unit trouble signal functional? Yes
All lamps, LEDs, and/or LCDs are functional? Yes
Notification appliance circuit power extender lamps and LEDs indicate normal operating status of the equipment? N/A
Remote power supplies, lamps, and LEDs indicate normal operating status of the equipment? N/A
Surge protective devices are in good operating condition? Yes
Optical fiber cable connections are in good operating condition? N/A
All fuses are functional? N/A
All fuses are supervised and ratings verified? N/A
All disconnect switches and buttons are functional? Yes
A trouble signal was received when a supervised function was disconnected? Yes
Ground-fault monitoring is functional? Yes
Circuits properly monitored for integrity? Yes
Local & Remote Annunciators:
All annunciators pass visual inspection? N/A
All annunciators pass functional test? N/A
Offsite Responders Alarm signal received by monitoring within 90 seconds?
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Alarm signal time (seconds): Local Alarm Only
Trouble signal received by monitoring within 90 seconds? N/A
Trouble signal time (seconds): Local Alarm Only
Supervisory signal received by monitoring within 90 seconds? N/A
Supervisory signal time (seconds): Local Alarm Only
A document cabinet is present at the system control unit or other approved location? N/A
A copy of the site specific software is available? N/A
Are copies of as-built drawings available? N/A
PART III - NOTIFICATIONS THAT TESTING IS COMPLETE
Entities Notified:
Monitoring Organization Contact Name: N/A
Record time of contact (HH:MM)): N/A
Building Management Contact Name: Ken Flannigan
Record time of contact (HH:MM)): 11:15 am
Building Occupants Contact Name: N/A
Record time of contact (HH:MM)): N/A
Authority Having Jurisdiction Contact Name: Philadelphia Fire Board
Record time of contact (HH:MM)): 11:20 am
Other if required (specify): N/A
Contact Name: N/A
Record time of contact (HH:MM)): N/A
Current Component Counts Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed BELL Annual 5 5 0 5 0 PHOTOELECTRIC SMOKE DETECTOR Annual 16 15 1 15 0 DUCT SMOKE DETECTOR Annual 2 2 0 2 0 NON-RESTORABLE HEAT DETECTOR Annual 1 1 0 0 1 MANUAL STATION Annual 10 9 1 9 0 BATTERIES (INDIVIDUAL OR PAIR) Semi-Annual 1 1 0 1 0
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Photoelectric Smoke Detector
ZN 1-1 1FL @ FRONT DESK Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-7 1FL REAR EXHIBIT AREA SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 2-1 1FL THEATER ROOM Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-4 1FL BY FRONT ENTRANCE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-8 1FL THEATER PROJECTION RM Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 5-1 2FL TOP REAR OF STAIRS SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 2-3 2FL REAR LEFT EXHIBIT RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 2-4 2FL REAR RIGHT EXHIBIT RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 2-5 2FL AT FRONT STAIRS SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 4-1 3FL TOP OF FRONT STAIRS SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 3-2 3FL MECHANICAL RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 3-3 3FL MIDDLE RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 3-4 3FL END RM W/ ATTIC ACCESSSMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 7-4 BSMT MECHANICAL RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ZN 7-5 BSMT MECHANICAL RM SMOKE Photoelectric Smoke Detector
07-29-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
ZN 1-2 1FL BY FRONT DESK PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-3 1FL BY ENTRANCE PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-5 1FL THEATER RM EXIT PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-6 1FL BY FRONT ENTRANCE PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 2-2 2FL TOP OF REAR STAIRS PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 3-1 3FL TOP OF FRONT STAIRS PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 7-1 BSMT ENTRANCE PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 7-3 BSMT REAR EXIT PULL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
ZN 1-9 REAR LANDING BETWEEN 1ST & 2ND FL Manual Station 07-29-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Duct Smoke Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
ZN 6-1 3FL MECHANICAL RM DUCT Duct Smoke Detector 07-29-2025 Christoper Benedetto
Tested Passed
ZN 6-2 3FL MECHANICAL RM DUCT Duct Smoke Detector 07-29-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Non-Restorable Heat Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
ZN 7-2 BSMT JANITORS CLOSET HEAT Non-Restorable Heat Detector
07-29-2025 Christoper Benedetto
Tested Failed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
IN FACP Batteries (Individual or Pair)
07-29-2025 Christoper Benedetto
Tested Passed
Power Supply Make: Notifier
Power Supply Model: SFP-1024
Breaker Panel Location: Basement Mech. Rm
Breaker Panel: N/A
Circuit Breaker: Knife Switch
Amp Hour Rating (AH): 7
Charger Test Voltage (VDC): 27.16
Load Voltage: 12.65
Load Amperage: 6.4
Discharge Voltage: N/A
Load Voltage: 12.65
Load Amperage: 7.0
Discharge Voltage: N/A
Was the charger voltage within parameters? Yes
Was the load voltage of both batteries within required parameters? Yes
Was the load amperage of both batteries within required parameters? Yes
Was the discharge voltage of both batteries within required parameters? Yes
Install Date (MM/YY) 07/23
Record the ambient temperature of the enclosure (F): 86.5
Record the ambient temperature of the battery at the negative terminal(F): 87.1
All batteries are marked with the month and year of manufacture? Yes
All batteries are within equipment manufacturer's replace date? Yes
All connections to batteries are tight? Yes
All terminals are free of corrosion? Yes
All batteries are free of distortion, cracks, and leakage? Yes
Can the batteries remain in service considering manufacturers recommendations (such as date of manufacture, service temperature (less than 18 degrees F above ambient), and integrity of the casing)?
Yes
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Bell
Bell Bell 07-29-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-29-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-29-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-29-2025 Christoper Benedetto
Tested Passed
Bell Bell 07-29-2025 Christoper Benedetto
Tested Passed
Identifier Location Description Device Type Reason Not Tested
ZN 7-6 BSMT ELECTRICAL RM ABOVE
TRANSFORMER SMK
Photoelectric Smoke Detector
No Access. Need an electrician to enter
ZN 2-6 2FL TOP OF FRONT STAIRS PULL Manual Station Pull station is covered in old wooden box. Would need to remove entire box, not just front cover to test
Deficiencies
Identifier Address Location Description Device Type Date of Failure
ZN 7-2 BSMT JANITORS CLOSET HEAT Non-Restorable Heat Detector
07-29-2025
Reason for Failure ZN 7-2 Non-Restorable Heat Detector, BSMT JANITORS CLOSET HEAT , Manufacturer: Edwards-EST , Model: 283B -Heat detector over 15 years old. Should be replaced
Code Reference NFPA 72 2013 Table 14.4.3.2 (17) (d) (3)
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-29-2025
System ID: Notifier SFP-1024 Declaration Hse- Main
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
New Castle, DE 19720
DESP 24-331; DE FAL-0403; FSL-0344
FEL; NJCBP P01705; NJ CRA 744485
Inspection, Testing, & Maintenance Report For
NATIONAL PARK SERVICE
143 S 3rd St
Philadelphia, PA 19106-2818 07-30-2025
COMPACT - NFPA 72 VISUAL AND FUNCTIONAL
INSPECTION OF FIRE ALARM SYSTEMS
Required Inspection Frequency: ANNUAL Information on this form covers the minimum requirements of the current edition of NFPA 72 (unless otherwise directed by the authority having jurisdiction).
Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable
Name: NPS Security
Phone Number: (215) 597-7077
Account Number: N/A
Approving Agency Name:
Phone Number:
Control Unit Information Manufacturer: Gamewell-FCI
Model: S3
Panel/Node Identifier: K-House
Software Revision: N/A
Type of Communicator: Network
Circuit Style: B
Number of SLC Circuits (if Applicable): 1
Number of Zones (if Applicable): N/A
Number of NAC Circuits (if Applicable): 2
If there are more than two visual notification appliances in the same room or adjacent space within view of the flash do these visual notification appliances synchronize?
N/A
Did notification appliance circuits operate properly? Yes
Primary Power Supply Information Nominal Input Voltage: 120
Amp Rating: 3.6
Location of Panelboard: Basement Mechanical Rm
Overcurrent Protection Type: Circuit Breaker
Overcurrent Amp Rating: 20
Panelboard ID Number: L-DP
Fuse ID or Breaker Number: 19
Engine-Driven Generator Information Location of Generator: N/A
Location of Fuel Storage: N/A
Fuel Type: N/A
Energy Storage System (ESS) Information Equipment Powered by ESS: N/A
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Minutes of Operation in Alarm Mode: N/A
Secondary Power Supply Information (Batteries) Type: Sealed Lead-Acid
Nominal Voltage: 12
Amp Rating: 12
Location: FACP
Hours of operation in Standby Mode: 24
Minutes of operation in Alarm Mode: 5
PART I - OWNER'S SECTION
Is the building occupied? Yes
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
PART II - INSPECTION AND TESTING
ANNUAL
Control Panel & Power Supplies:
Control unit and power supplies are free of physical damage? Yes
Control unit trouble signal functional? Yes
All lamps, LEDs, and/or LCDs are functional? Yes
Notification appliance circuit power extender lamps and LEDs indicate normal operating status of the equipment? N/A
Remote power supplies, lamps, and LEDs indicate normal operating status of the equipment? N/A
Surge protective devices are in good operating condition? Yes
Optical fiber cable connections are in good operating condition? Yes
All fuses are functional? N/A
All fuses are supervised and ratings verified? N/A
All disconnect switches and buttons are functional? Yes
A trouble signal was received when a supervised function was disconnected? Yes
Ground-fault monitoring is functional? Yes
Circuits properly monitored for integrity? Yes
Local & Remote Annunciators:
All annunciators pass visual inspection? N/A
All annunciators pass functional test? N/A
Offsite Responders Alarm signal received by monitoring within 90 seconds?
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Alarm signal time (seconds): 20
Trouble signal time (seconds): 21
Supervisory signal received by monitoring within 90 seconds? Yes
Supervisory signal time (seconds): 20
A document cabinet is present at the system control unit or other approved location? Yes
A copy of the site specific software is available? Yes
Are copies of as-built drawings available? Yes
PART III - NOTIFICATIONS THAT TESTING IS COMPLETE
Entities Notified:
Monitoring Organization Contact Name: NPS Security
Record time of contact (HH:MM)): 1:30 pm
Building Management Contact Name: Ken Flannigan
Record time of contact (HH:MM)): 1:30 pm
Building Occupants Contact Name: N/A
Record time of contact (HH:MM)): N/A
Authority Having Jurisdiction Contact Name: Philadelphia Fire Board
Record time of contact (HH:MM)): 1:45 pm
Other if required (specify): N/A
Contact Name: N/A
Record time of contact (HH:MM)): N/A
Current Component Counts Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed PRESSURE-TYPE WATERFLOW SWITCH Semi-Annual 1 0 1 0 0 INTERNAL BUTTERFLY VALVE-CONTROL VALVE WITH TAMPER SWITCH Semi-Annual 1 0 1 0 0 OUTSIDE STEM AND YOKE-CONTROL VALVE WITH TAMPER SWITCH Semi-Annual 2 0 2 0 0 BATTERIES (INDIVIDUAL OR PAIR) Semi-Annual 1 1 0 1 0 HEAT DETECTOR Annual 2 2 0 2 0 HORN/STROBE Annual 2 2 0 2 0 STROBE Annual 2 2 0 2 0 PHOTOELECTRIC SMOKE DETECTOR Annual 12 12 0 12 0 MANUAL STATION Annual 3 3 0 3 0 DUCT SMOKE DETECTOR Annual 1 1 0 1 0
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed LOW AIR PRESSURE SWITCH Quarterly 1 0 1 0 0
Annual Inspection, Test and Maintenance for Duct Smoke Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
TK L1S015 Basement AHU Duct Smoke Detector 07-30-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Heat Detector Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
TK L1S013 Basement Mechanical Room Heat Detector 07-30-2025 Christoper Benedetto
Tested Passed
TK L1S012 3rd Floor O/S Attic Entrance Heat Detector 07-30-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
IN FACP Batteries (Individual or Pair)
07-30-2025 Christoper Benedetto
Tested Passed
Power Supply Make: Gamewell-FCI
Power Supply Model: S3
Breaker Panel Location: Basement
Breaker Panel: L-DP
Circuit Breaker: 19
Amp Hour Rating (AH): 12
Charger Test Voltage (VDC): 26.72
Load Voltage: 12.65
Load Amperage: 11.9
Discharge Voltage: N/A
Load Voltage: 12.63
Load Amperage: 12.0
Discharge Voltage: N/A
Was the charger voltage within parameters? Yes
Was the load voltage of both batteries within required parameters? Yes
Was the load amperage of both batteries within required parameters? Yes
Was the discharge voltage of both batteries within required parameters? Yes
Install Date (MM/YY) 08/24
Record the ambient temperature of the enclosure (F): 79.3
Record the ambient temperature of the battery at the negative terminal(F): 79.9
All batteries are marked with the month and year of manufacture? Yes
All batteries are within equipment manufacturer's replace date? Yes
All connections to batteries are tight? Yes
All terminals are free of corrosion? Yes
All batteries are free of distortion, cracks, and leakage? Yes
Can the batteries remain in service considering manufacturers recommendations (such as date of manufacture, service temperature (less than 18 degrees F above ambient), and integrity of the casing)?
Yes
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
TK L1S001 1st Floor Reception Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S002 1st Floor Exhibit Room Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S003 2nd Floor Bedroom Exhibit Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S004 2nd Floor O/S Bedroom Exhibit Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S005 2nd Floor Exhibit Room Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S006 2nd Floor Exhibit Room Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S007 3rd Floor Top of Stairs Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S008 3rd Floor Storage by Stairs Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S009 3rd Floor Behind Attic Entrance Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK T1S010 Attic Crawlspace Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK T1S011 Attic Storage Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
TK L1S014 Basement O/S Bathrooms Photoelectric Smoke Detector
07-30-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Manual Station Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
TK L1M007 1st Floor Pine Street Exit Manual Station 07-30-2025 Christoper Benedetto
Tested Passed
TK L1M008 1st Floor 3rd Street Exit Manual Station 07-30-2025 Christoper Benedetto
Tested Passed
TK L1M009 1st Floor Alley Exit Manual Station 07-30-2025 Christoper Benedetto
Tested Passed
Annual Inspection, Test and Maintenance for Strobe Identifier Location Description Device Type Date of Test Tested By: Tested? Passed?
Bsmt Men's Rm Strobe Strobe 07-30-2025 Christoper Benedetto
Tested Passed
Bsmt. Women's Rm Strobe Strobe 07-30-2025 Christoper Benedetto
Tested Passed
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Annual Inspection, Test and Maintenance for Horn/Strobe
1FL Horn Strobe Horn/Strobe 07-30-2025 Christoper Benedetto
Tested Passed
2FL Horn Strobe Horn/Strobe 07-30-2025 Christoper Benedetto
Tested Passed
Identifier Location Description Device Type Reason Not Tested
TK L1M006 Sprinkler Dry Valve Isolation Internal Butterfly Valve-Control Valve with Tamper Switch
Tested by JCI. Sprinkler system was out of service at time of inspection. Tamper and low air in active supervisory during inspection
TK L1M004 Sprinkler Main Shutoff Outside Stem and Yoke-Control Valve with Tamper Switch
Tested by JCI.
TK L1M005 Sprinkler Back Flow Isolation Outside Stem and Yoke-Control Valve with Tamper Switch
Tested by JCI.
TK L1M003 Sprinkler Waterflow Pressure-Type Waterflow Switch
Tested by JCI. Sprinkler system was out of service at time of inspection. Tamper and low air in active supervisory during inspection
TK L1M001 Dry System Low Air Low Air Pressure Switch
Tested by JCI. Sprinkler system was out of service at time of inspection. Tamper and low air in active supervisory during inspection
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 K-House Basement
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
New Castle, DE 19720
DESP 24-331; DE FAL-0403; FSL-0344
FEL; NJCBP P01705; NJ CRA 744485
Inspection, Testing, & Maintenance Report For
NATIONAL PARK SERVICE
143 S 3rd St
Philadelphia, PA 19106-2818 07-30-2025
COMPACT - NFPA 72 VISUAL AND FUNCTIONAL
INSPECTION OF FIRE ALARM SYSTEMS
Required Inspection Frequency: ANNUAL Information on this form covers the minimum requirements of the current edition of NFPA 72 (unless otherwise directed by the authority having jurisdiction).
Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable
Name: NPS Security
Phone Number: (215) 597-7077
Account Number: N/A
Approving Agency Name:
Phone Number:
Control Unit Information Manufacturer: Gamewell-FCI
Model: S3
Panel/Node Identifier: Maintenance Shop
Software Revision: N/A
Type of Communicator: Network
Circuit Style: B
Number of SLC Circuits (if Applicable): 1
Number of Zones (if Applicable): N/A
Number of NAC Circuits (if Applicable): 4
If there are more than two visual notification appliances in the same room or adjacent space within view of the flash do these visual notification appliances synchronize?
Yes
Did notification appliance circuits operate properly? Yes
Primary Power Supply Information Nominal Input Voltage: 120
Amp Rating: 3.6
Location of Panelboard: Basement FACP Rm.
Overcurrent Protection Type: Circuit Breaker
Overcurrent Amp Rating: 20
Panelboard ID Number: Emergency
Fuse ID or Breaker Number: 19
Engine-Driven Generator Information Location of Generator: N/A
Location of Fuel Storage: N/A
Fuel Type: N/A
Energy Storage System (ESS) Information Equipment Powered by ESS: N/A
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 Maint. Shop Elec. Rm.
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Minutes of Operation in Alarm Mode: N/A
Secondary Power Supply Information (Batteries) Type: Sealed Lead-Acid
Nominal Voltage: 12
Amp Rating: 12
Location: FACP
Hours of operation in Standby Mode: 24
Minutes of operation in Alarm Mode: 5
PART I - OWNER'S SECTION
Is the building occupied? Yes
Has the occupancy classification and hazard of contents remained the same since the last inspection? Yes
Are all fire protection systems in service? Yes
PART II - INSPECTION AND TESTING
ANNUAL
Control Panel & Power Supplies:
Control unit and power supplies are free of physical damage? Yes
Control unit trouble signal functional? Yes
All lamps, LEDs, and/or LCDs are functional? Yes
Notification appliance circuit power extender lamps and LEDs indicate normal operating status of the equipment? N/A
Remote power supplies, lamps, and LEDs indicate normal operating status of the equipment? N/A
Surge protective devices are in good operating condition? Yes
Optical fiber cable connections are in good operating condition? Yes
All fuses are functional? N/A
All fuses are supervised and ratings verified? N/A
All disconnect switches and buttons are functional? Yes
A trouble signal was received when a supervised function was disconnected? Yes
Ground-fault monitoring is functional? Yes
Circuits properly monitored for integrity? Yes
Local & Remote Annunciators:
All annunciators pass visual inspection? Yes
All annunciators pass functional test? Yes
Offsite Responders Alarm signal received by monitoring within 90 seconds?
ANNUAL COMPACT - NFPA 72 VISUAL AND FUNCTIONAL INSPECTION OF FIRE
Job ID: 42186744
Date: 07-30-2025
System ID: Gamewell-FCI S3 Maint. Shop Elec. Rm.
Service Tech: Christoper Benedetto
Tech Cert/License: 24404
Property Name: NATIONAL PARK SERVICE Property Address: 143 S 3rd St
City: Philadelphia State: PA
Alarm signal time (seconds): 19
Trouble signal time (seconds): 19
Supervisory signal received by monitoring within 90 seconds? Yes
Supervisory signal time (seconds): 20
A document cabinet is present at the system control unit or other approved location? Yes
A copy of the site specific software is available? Yes
Are copies of as-built drawings available? Yes
PART III - NOTIFICATIONS THAT TESTING IS COMPLETE
Entities Notified:
Monitoring Organization Contact Name: NPS Security
Record time of contact (HH:MM)): 11:30 am
Building Management Contact Name: Ken Flannigan
Record time of contact (HH:MM)): 11:30 am
Building Occupants Contact Name: N/A
Record time of contact (HH:MM)): N/A
Authority Having Jurisdiction Contact Name: Philadelphia Fire Board
Record time of contact (HH:MM)): 11:40
Other if required (specify): N/A
Contact Name: N/A
Record time of contact (HH:MM)): N/A
Current Component Counts Device Type Frequency QTY Inventoried QTY Tested QTY Not Tested QTY Passed QTY Failed VANE-TYPE WATERFLOW SWITCH Semi-Annual 1 0 1 0 0 PRESSURE-TYPE WATERFLOW SWITCH Semi-Annual 1 0 1 0 0 INTERNAL BUTTERFLY VALVE-CONTROL VALVE WITH TAMPER SWITCH Semi-Annual 4 0 4 0 0 OUTSIDE STEM AND YOKE-CONTROL VALVE WITH TAMPER SWITCH Semi-Annual 2 0 2 0 0 BATTERIES (INDIVIDUAL OR PAIR) Semi-Annual 1 1 0 1 0 HEAT DETECTOR Annual 38 38 0 38 0 HORN/STROBE Annual 21 21 0 21 0 STROBE Annual 11 11 0…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .