Attachment_4_-_Equipment_Schedules.pdf
PDF 3 MB Posted
- Attached to
- FY24 VAFO HVAC INSPECTIONS & MAINTENANCE
- Solicitation number
- 140P4224Q0122
About this file
This document appears to be an equipment schedule for an air cooled chiller and associated HVAC equipment for a federal contract opportunity. The key details include:
The air cooled chiller has a capacity of 100 tons and is specified to meet AHRI efficiency standards. Chilled water system components such as pumps, an expansion tank, and air separator are also detailed. The document includes schedules for air handling units, including supply and return fans, cooling coils, and dimensions/weights. Diffuser and register specifications are also provided.
The related federal contract opportunity is for HVAC inspections and maintenance services at Valley Forge National Historical Park, issued by the Department of the Interior National Park Service Northeast Region. The solicitation number is 140P4224Q0122 and the contract will have a base period plus two option years.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR COOLED CHILLER SCHEDULE
PDEWT
CAPACITY EVAPORATOR
LOCATIONTAG FOULINGFLOW LWT
(°F)
(TONS)
IPLV @
AHRI
(GPM) (°F) (FT) FACTOR MCAHERTZVOLTS PHASE MOCP
ELECTRICAL
REMARKSFLUID
TYPE
FLUID
ELECTRICAL DATA
TEMP.
( F)
FLUID
TAG
PUMP SCHEDULE
SERVICE TYPE FLOW HEAD RPM BASIS OF DESIGNVOLTS/ REMARKS
(GPM) (FT.)
CHILLED WATER SYSTEM VERTICAL INLINE 247 85 1750 44-85CHP-1 208/3 TACO KS301110
MOTOR
HP PHASE MFG. AND MODEL
3X310
(IN. X IN.)(IN.)
DISCHARGEDIA.
IMPELLER SUCTION X
ACC-1 OUTSIDE 100 16.3 EER 247 57 47 10.0 0.0001 WATER 208 3 60 441 500
KW
115.7 DAIKIN# AGZ100
FURNISH WITH LON/ BACNET CARD, COORDINATE WITH DDC CONTROLS CONTRACTOR
FURNISH EACH PUMP WITH END SUCTION DIFFUSER AND TRIPLE DUTY VALVE.
WATER
AMBIENT
TEMP.
NUMBER OF
COMPRESSORS
(°F)
NUMBER OF
CONDENSOR FANS
6 147"L x 88"W x 98" H, 4800 LBS
TYPE
FLUID
UNIT DIMENSIONS
VOLUME
( GAL)
ACCEPTANCE
TAG
EXPANSION TANK
SERVICE UNIT LOCATION
MOUNTING
PRESSURE BASIS OF DESIGN REMARKS
(PSIG)
CHILLED WATER SYSTEM MECH. ROOM FLOOR 40 37ET-1 460/3 TACO CA 14020" DIA., 46" H
INCHES MFG. AND MODEL
37125
(GAL.)(PSIG)
VOLUMESETTING
RELIEF VALVE TANK
WATER
TANK
MIN. FILL
TYPE
FLUID
PIPE CONNECTION
TAG
AIR SEPARATOR
SERVICE UNIT LOCATION PD BASIS OF DESIGN REMARKS
(FT)
CHILLED WATER SYSTEM MECH. ROOM 2.5AS-1 TACO ACT-66
INCHES MFG. AND MODEL
WATER
MAX
MAX.
(GPM)
AIR SEPARATOR WITH STRAINER AND DRAIN VALVE
SIZE
AIR HANDLER SCHEDULE
WHEEL TYPEAREATAG
SIZE (IN.) VOLTS PHASE
ELECTRICAL
REMARKS
AHU-1 ADMIN. 15.75" FC 208 3 DAIKIN MODEL CAH014GDGM
1. FURNISH WITH VFDs (FOR BALANCING) COMPATIBLE WITH CONTROLS, COORDINATE WITH DDC CONTROLS CONTRACTOR AND TAB CONTRACTOR.
2. MAXIMUM DISCHARGE SOUND POWER NOT TO EXCEED NC 65. MAXIMUM RADIATED SOUND POWER NOT TO EXCEED NC 55.
SUPPLY FAN
SERVED
OA
CFM
FAN SPEED
RPM
TOTAL
6,770
CFM
ESP
1.25
(IN. WG)
TOTAL SP
3.10
(IN. WG)
BHP
TOTAL
5.1
HP
(2) 3.0
WHEEL TYPE
SIZE (IN.)
15.75"
RETURN FAN
FAN SPEED
RPM
TOTAL
6,500
CFM
ESP
0.5
(IN. WG)
BHP
3.8
HP
5.0
COOLING COIL
MIN. FACE AREA
(SQ FT)
13.1
MAX AP
1.08
(IN. WG)
TOTAL/SENS.
(MBH)
337/222
EAT
DB (F) WB (F)
LAT
DB (F) WB (F)
83.7 69.5 53.7 53.5
GPM
66.4
WPD
FT (F) (F)
EWT LWT
11.2 47 57
WEIGHT
UNIT
(LBS)
WEIGHT
UNIT
(LBS)
PROVIDE VARIABLE SPEED DRIVE FOR WINTER OPERATION.
TAG
REGISTERS, GRILLES AND DIFFUSERS
TYPE SIZE BASIS OF DESIGN REMARKS
CEILING DIFFUSER 24x24CD-1 NAILOR RNS
NECK SIZE
(IN)
8" Ø
BLOW
PATTERN
4 WAY LAY-IN
FRAME
NONE
DAMPER
<20
MAX NC
CEILING DIFFUSER 24x24CD-2 NAILOR RNS10" Ø 4 WAY LAY-IN NONE <20
CEILING DIFFUSER 24x24CD-3 NAILOR RNS14" Ø 4 WAY LAY-IN NONE <20
RG-1
1. 45 DEGREE DEFLECTION, FIXED BLADE, 3/4" BLADE SPACING, HORIZONTAL BLADES AND STEEL CONTRUCTION
EXPOSED SPIRAL DUCT RETURN - 36x24 FIXED - YES <20 NAILOR 6145HC NOTE 1
CEILING DIFFUSER 24x24CD-4 NAILOR RNS16" Ø 4 WAY LAY-IN NONE <20
MIN. BASIS OF DESIGN
MFG. AND MODEL
BASIS OF DESIGN
MFG. AND MODEL
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
SCHEDULES
M601
NB
RR
RR
EXISTING AIR HANDLER SCHEDULE
AREATAG REMARKS
AC-2 ADMIN. ATTIC
SUPPLY FAN
SERVED
TOTAL
4,355
CFM
HP
3.0
AC-3 AUDITORIUM MEZZANINE
OUTSIDE AIR
1,000
CFM
9,550 2,750 7.5
GPM
FOR INFO ONLY
FOR INFO ONLY
CONVECTORS
TAG LOCATION
ENCLOSURE
WIDTH (IN.)
ELEMENT
LENGTH (IN.)
CAPACITY
(KW) QUANTITY BOD
C-2 ADMIN - VARIOUS 18 TBD 1.0 3 ATLANTIC F118
C-3 VARIOUS 30 TBD 2.0 10 ATLANTIC F118
NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL
ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.
2. MOUNT AT SAME HEIGHT AS EXISTING.
C-1 ADMIN - BASEMENT 15 TBD 0.5 1 ATLANTIC F118
EXISTING REHEAT COILS
TAG LOCATION
SIZE
(IN.)
CAPACITY
(KW) CFM
NO.
CIRC.
RH-1 ADMIN - BASEMENT 24X8 6.0 500 1
RH-2 ADMIN - BASEMENT 36X12 5.0 1080 1
RH-3 ADMIN - BASEMENT 48X28 21.0 3970 3
RH-4 ADMIN - BASEMENT 12X8 2.0 350 1
RH-5 ADMIN- FIRST FLOOR 24X8 3 530 1
RH-6 ADMIN - ATTIC 12X8 2 410 1
RH-7 ADMIN - ATTIC 24X12 7 900 1
RH-8 ADMIN - ATTIC 24X12 7 885 1
RH-9 ADMIN - ATTIC 24X8 3 540 1
RH-10 ADMIN - ATTIC 18X12 3.5 625 1
RH-11 ADMIN - ATTIC 24X12 3.5 755 1
RH-12 AUDITORIUM - MEZZANINE 40X42 30.0 6500 3
RH-13 AUDITORIUM - MEZZANINE 24X8 2.5 600 1
RH-14 AUDITORIUM - MEZZANINE 12X8 1.5 290 1
RH-15 AUDITORIUM - MEZZANINE 24X12 5.5 1090 1
RH-16 AUDITORIUM - MEZZANINE 27X8 2.5 590 1
SILL LINE HEATERS
TAG LOCATION
ENCLOSURE WIDTH
(IN.)
ELEMENT
LENGTH (IN.)
CAPACITY
(KW) QUANTITY BOD
FTR-1 AUDITORIUM BLDG 120 84 1.75 8 TRANE EWFB
FTR-2 STAGE AREA 132 96 3.00 2 TRANE EWFB
FTR-3 ENTRANCE SEE DWG 72 2.25 1 TRANE EWFB
FTR-4 ENTRANCE 120 84 2.50 2 TRANE EWFB
FTR-5 VARIOUS WALL TO WALL 84 1.75 2 TRANE EWFB
FTR-6 MEZZANINE 72 36 0.56 1 TRANE EWFB
FTR-7 MEZZANINE 96 60 1.25 1 TRANE EWFB
FTR-8 MEZZANINE 96 60 1.88 1 TRANE EWFB
NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL
ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.
2. MOUNT AT SAME HEIGHT AS EXISTING.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
SCHEDULES
M602
NB
RR
RR
REFER TO SPECIFICATION SECTION 230993
FOR SEQUENCES OF OPERATION AND
ALARMS.
T
S
T
HWST
HWRT
SV
HV
BPD
ALM
FZ
HCV
AQS
SD
V-#
TSTAT
SP
S/S
SPL
SPH
OAT
SAT
SAD
OAD
DAT
DPS
CS
AFMS
FBD
EAD
D-#
HS
TS
FM
HHL
VFD
WS
ISOD
LRC
STR
OX
DPS-1 FZ-1 TS-2
V-1
D-2
TS-1
CO2D-3
D-1
AFMS-3
VFD
CS
SD-1
SD-1
ES
AFMS-2
CS
VFD
SPL
SPHD-4 ROOM SENSOR
C C
NC
CHWR
CHWS
NO
X
DPS-1 FILTER DIFFERENTIAL PRESSURE X
V-1 COOLING COIL VALVE X
FZ-1 FREEZESTAT
D-1 VENTILATION AIR DAMPER X
AI AO DI DO HI LOW
POINT ALARMSSYSTEM POINT
DDC CONTROL PANEL INPUT/OUTPUT SUMMARY
OFF/NRML
COMMENTS
D-2 RETURN AIR DAMPER X
AFMS-1 OUTSIDE AIR CFM X
AFMS-2 SUPPLY AIR FAN CFM
XSD-1 SMOKE DETECTOR
TS-2 SUPPLY AIR TEMPERATURE X
SUPPLY AIR
RETURN AIR
TS-1 ROOM TEMPERATURE X
X X
START/STOP SUPPLY FAN VFD
XSUPPLY FAN VFD FAULT
CO2 CARBON DIOXIDE SENSOR RETURN AIR DUCT X
NC
NC
OUTSIDE AIR
RELIEF AIR
D-3 RELIEF AIR DAMPER X
AFMS-3 RETURN AIR FAN CFM X
X X
X W/ CURRENT SENSOR
X
XSTART/STOP RETURN FAN VFD
XRETURN FAN VFD FAULT
X X W/ CURRENT SENSOR
X
IN-DUCT SMOKE DETECTOR
IN-DUCT
SMOKE
DETECTOR
HOT WATER SUPPLY TEMPERATURE
HOT WATER RETURN TEMPERATURE
SUPPLY AIR VALVE
HOOD EXHAUST AIR VALVE
BYPASS DAMPER
ALARM
FREEZESTAT
HEATING CONTROL VALVE
AQUASTAT
SMOKE DETECTOR (DUCT)
STATIC PRESSURE SENSOR
START/STOP
STATIC PRESSURE LOW
STATIC PRESSURE HIGH
THERMOSTAT OR TEMPERATURE SENSOR
MOUNT 48" AFF UNLESS OTHERWISE NOTED
THERMOSTAT OR TEMPERATURE SENSOR
OUTSIDE AIR DAMPER
OUTSIDE AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
SUPPLY AIR DAMPER
DISCHARGE AIR TEMPERATURE
CURRENT SENSOR
DIFFERENTIAL PRESSURE SENSOR
AIR FLOW MEASURING STATION
FACE & BYPASS DAMPER
END SWITCH
EXHAUST AIR DAMPER
CONTROL DAMPER
HUMIDITY SENSOR
TEMPERATURE SENSOR
NORMALLY CLOSEDNC
NO NORMALLY OPEN
FLOW METER
HUMIDITY HIGH LIMIT
VARIABLE FREQUENCY DRIVE
WALL SWITCH
ISOLATION DAMPER
SINGLE POINT INPUT/OUTPUT
MULTIPLE PIONTS INPUT/OUTPUT
X
FIRE ALARM CONTROL PANELFACP
FIRE ALARMFA
ZONE PRESENCE SENSORZPS
FUME HOOD SASH SENSORFHSS
FUME HOOD MONITORFHM
FIREFIGHTER SMOKE CONTROL SYSTEMFSCS
HOOD EXHAUST AIR VALVE
LAB ROOM CONTROLLER
MOTOR STARTER
OXYGEN SENSOR
LEGEND
ES
NC
D-4 SUPPLY FAN ISOLATION DAMPER X
SPH HIGH STATIC PRESSURE LIMIT
SPL LOW STATIC PRESSURE LIMIT
3-WAY
MIXING
VALVE
XX
X X
X
AFMS-1
COMMENTS
UNIT CONTROL PANEL INPUT/OUTPUT SUMMARY
SYSTEM POINT POINT
DODIAOAI
T-1 INTEGRAL THERMOSTAT X
REFER TO SPECIFICATION SECTION 230993 FOR
SEQUENCE OF OPERATION AND ALARMS
T R S
T-1
RELAY
SWITCH
POWER FROM
X-CONTACTOR
HEATER
ADJUSTABLE, LINE VOLTAGE
LOCATION T-1 SWITCH
STAIR #2 1 1
T
TS-2
TS-1
SAH
C
SA
ROOM SENSOR
(NEW)
COMMENTS
BAS DDC CONTROL PANEL INPUT/OUTPUT SUMMARY
SYSTEM POINT POINT
DODIAOAI
TS-1 ROOM TEMPERATURE X
TS-2 DISCHARGE AIR TEMPERATURE X
REFER TO SPECIFICATION SECTION 230993 FOR
SEQUENCE OF OPERATION AND ALARMS
R
DO
BAS
POWER
CONTACTOR
AF
DUCT
REHEAT COIL
AIR FLOW
T
TS-E
ROOM SENSOR
PNEUMATIC
DEMO/REMOVE
AF AIRFLOW SWITCH X
R CONTACTOR (EXTG) X
HI LIMIT
BAS WILL ENERGIZE CONTACTOR
REHEAT
COIL T-1 LOCATION
ASSOC.
UNIT
1 NORTH PASSAGE AHU-1
2 AHU-1
6 A\C-2 7 A\C-2
8 A\C-2COMM. READING
MUSEUM
STAIR #1
LIBRARY
3 AHU-1LOBBY
4 AHU-1STAFF LOUNGE
5 AHU-1TOILET (RECEPTION)
9 A\C-2SUPER. OFFICE
10 A\C-2GENERAL OFFICE
11 A\C-2RECEPTION
13 A\C-3PROJ. ROOM
14 A\C-3PASSAGE B51
15 A\C-3LOBBY
16 A\C-3STAIR #3
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
CONTROL DIAGRAM
M701
NB
RR
RR
NTS1 AHU-1 CONTROLS DIAGRAM
NTS2
ELECTRIC FIN TUBE RADIATION
CONTROL DIAGRAM
NTS3 TYPICAL DUCT MOUNTED REHEAT COIL
VRV TERMINAL UNIT SCHEDULE
DESG SERVES
UNIT
AIRFLOW
[CFM]
OUTDOOR
AIR
[CFM]
COOLING
SETPOINT
(°F)
HEATING
SETPOINT
(°F)
CALCULATED
TOTAL
COOLING CAP
[MBH]
UNIT
MAX
COOLING
CAP
[MBH]
CALCULATED
HEATING
CAP
[MBH]
UNIT
MAX
HEATING
CAP
[MBH]
MAX UNIT DIMENSION
MCA MCOP V/PH/Hz MAX
NC
BASIS OF DESIGN
NOTESLENGTH
(IN)
HEIGHT
(IN)
DEPTH
(IN) MANUFACTURER MODEL
VRF-1 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6
VRF-2 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6
VRF-3 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6
VRF-4 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6
VRF-5 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6
VRF-6 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6
VRF-7 Porch 1,200 - 75 68 33.6 33.5 12.8 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6
VRF-8 Exhibit/Servant Quarters 1,200 - 75 68 36 33.5 38 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6
VRF-9 Restroom - lvl 1 245 - 75 68 7.2 7.0 5.8 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-10 Office 245 - 75 68 7.2 7.0 9.0 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-11 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-12 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-13 Bedroom 2 245 - 75 68 8.4 7.0 9.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-14 Bedroom 3 245 - 75 68 8.4 7.0 7.2 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-15 Restroom - Groom 245 - 75 68 3.6 7.0 2.3 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-16 Stair, Upper 245 - 75 68 8.4 8.8 8.4 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-17 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-18 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-19 Restroom - lvl 3 245 - 75 68 2.4 7.0 2.7 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-20 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-21 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-22 Restroom - Bridal 245 - 75 68 2.4 8.8 2.6 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-23 Servant Quarters - Hall 245 - 75 68 6.0 8.8 6.9 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 4, 6
NOTES:
1. PROVIDE IN SPACE, WALL MOUNTED DIGITAL THERMOSTAT. FINAL LOCATION SHALL BE COORDINATED WITH OWNER.
2. FLOOR MOUNTED, DUCTED UNIT.
3. CONCEALED FLOOR MOUNTED, NON-DUCTED UNIT.
4. UNIT TO BE INSTALLED WITH MANUFACTURER ENCLOSURE. EXISTING ENCLOSURE SHALL BE REMOVED, PROTECTED FOR STORAGE, AND PROVIDED TO OWNER.
5. DESIGN INTENT IS THAT UNIT BE INSTALLED WITHOUT MANUFACTURER ENCLOSURE.
6. INCLUDE MANUFACTURER PROVIDED CONDENSATE PUMP.
VRV OUTDOOR UNIT SCHEDULE
DESG
EQUIPMENT
COOLING CAP
[MBH]
EQUIPMENT
HEATING CAP
[MBH]
MAX
REFRIGERANT
CHARGE [lbs]
MCA MCOP
AMBIENT
TEMP
[°F]
V/PH/HZ
BASIS OF DESIGN
NOTES
MANUFACTURER MODEL
CU-1 192.9 130.0 35.9 63.9 80 95 208/3/60 DAIKIN RXYQ192TTJU
CU-2 97.5 68.3 22.7 36.3 45 95 208/3/60 DAIKIN RXYQ96TTJU
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
AutoCAD SHX Text 2/16/2018
AutoCAD SHX Text
PHILANDER CHASE KNOX HOUSE
AutoCAD SHX Text
HEATING SYSTEM REPLACEMENT
AutoCAD SHX Text 163366
AutoCAD SHX Text
AutoCAD SHX Text 41022B
AutoCAD SHX Text
100%%% CD DRAWINGS
AutoCAD SHX Text
LOUIS BERGER GROUP
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text
STN
AutoCAD SHX Text
MS
AutoCAD SHX Text M6.1
AutoCAD SHX Text 10/12/17 10:13 SNEWSWANGER R20 P:\PROJECTS\2016 PROJECTS\NPS-CHASE KNOX HOUSE\3. PROJECT INFORMATION\3.2 DRAWINGS\VAFO\163366\DRAWINGS\MECH\M6.1 MECHANICAL SCHEDULES.DWG XREFS: ..\XREF\XG-TITLBLK.DWG;
AutoCAD SHX Text
| Pages from 1 VAFO 201534A 100 CD Drawings PDF |
| Pages from FULL COMBINED SET |
| PCK |
| Sheets and Views |
| M6.1 |
File details come from the government source that posted it. Updated .