Attachment_4_-_Equipment_Schedules.pdf

PDF 3 MB Posted

Attached to
FY24 VAFO HVAC INSPECTIONS & MAINTENANCE
Solicitation number
140P4224Q0122
Issued by

About this file

This document appears to be an equipment schedule for an air cooled chiller and associated HVAC equipment for a federal contract opportunity. The key details include:

The air cooled chiller has a capacity of 100 tons and is specified to meet AHRI efficiency standards. Chilled water system components such as pumps, an expansion tank, and air separator are also detailed. The document includes schedules for air handling units, including supply and return fans, cooling coils, and dimensions/weights. Diffuser and register specifications are also provided.

The related federal contract opportunity is for HVAC inspections and maintenance services at Valley Forge National Historical Park, issued by the Department of the Interior National Park Service Northeast Region. The solicitation number is 140P4224Q0122 and the contract will have a base period plus two option years.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR COOLED CHILLER SCHEDULE

PDEWT

CAPACITY EVAPORATOR

LOCATIONTAG FOULINGFLOW LWT

(°F)

(TONS)

IPLV @

AHRI

(GPM) (°F) (FT) FACTOR MCAHERTZVOLTS PHASE MOCP

ELECTRICAL

REMARKSFLUID

TYPE

FLUID

ELECTRICAL DATA

TEMP.

( F)

FLUID

TAG

PUMP SCHEDULE

SERVICE TYPE FLOW HEAD RPM BASIS OF DESIGNVOLTS/ REMARKS

(GPM) (FT.)

CHILLED WATER SYSTEM VERTICAL INLINE 247 85 1750 44-85CHP-1 208/3 TACO KS301110

MOTOR

HP PHASE MFG. AND MODEL

3X310

(IN. X IN.)(IN.)

DISCHARGEDIA.

IMPELLER SUCTION X

ACC-1 OUTSIDE 100 16.3 EER 247 57 47 10.0 0.0001 WATER 208 3 60 441 500

KW

115.7 DAIKIN# AGZ100

FURNISH WITH LON/ BACNET CARD, COORDINATE WITH DDC CONTROLS CONTRACTOR

FURNISH EACH PUMP WITH END SUCTION DIFFUSER AND TRIPLE DUTY VALVE.

WATER

AMBIENT

TEMP.

NUMBER OF

COMPRESSORS

(°F)

NUMBER OF

CONDENSOR FANS

6 147"L x 88"W x 98" H, 4800 LBS

TYPE

FLUID

UNIT DIMENSIONS

VOLUME

( GAL)

ACCEPTANCE

TAG

EXPANSION TANK

SERVICE UNIT LOCATION

MOUNTING

PRESSURE BASIS OF DESIGN REMARKS

(PSIG)

CHILLED WATER SYSTEM MECH. ROOM FLOOR 40 37ET-1 460/3 TACO CA 14020" DIA., 46" H

INCHES MFG. AND MODEL

37125

(GAL.)(PSIG)

VOLUMESETTING

RELIEF VALVE TANK

WATER

TANK

MIN. FILL

TYPE

FLUID

PIPE CONNECTION

TAG

AIR SEPARATOR

SERVICE UNIT LOCATION PD BASIS OF DESIGN REMARKS

(FT)

CHILLED WATER SYSTEM MECH. ROOM 2.5AS-1 TACO ACT-66

INCHES MFG. AND MODEL

WATER

MAX

MAX.

(GPM)

AIR SEPARATOR WITH STRAINER AND DRAIN VALVE

SIZE

AIR HANDLER SCHEDULE

WHEEL TYPEAREATAG

SIZE (IN.) VOLTS PHASE

ELECTRICAL

REMARKS

AHU-1 ADMIN. 15.75" FC 208 3 DAIKIN MODEL CAH014GDGM

1. FURNISH WITH VFDs (FOR BALANCING) COMPATIBLE WITH CONTROLS, COORDINATE WITH DDC CONTROLS CONTRACTOR AND TAB CONTRACTOR.

2. MAXIMUM DISCHARGE SOUND POWER NOT TO EXCEED NC 65. MAXIMUM RADIATED SOUND POWER NOT TO EXCEED NC 55.

SUPPLY FAN

SERVED

OA

CFM

FAN SPEED

RPM

TOTAL

6,770

CFM

ESP

1.25

(IN. WG)

TOTAL SP

3.10

(IN. WG)

BHP

TOTAL

5.1

HP

(2) 3.0

WHEEL TYPE

SIZE (IN.)

15.75"

RETURN FAN

FAN SPEED

RPM

TOTAL

6,500

CFM

ESP

0.5

(IN. WG)

BHP

3.8

HP

5.0

COOLING COIL

MIN. FACE AREA

(SQ FT)

13.1

MAX AP

1.08

(IN. WG)

TOTAL/SENS.

(MBH)

337/222

EAT

DB (F) WB (F)

LAT

DB (F) WB (F)

83.7 69.5 53.7 53.5

GPM

66.4

WPD

FT (F) (F)

EWT LWT

11.2 47 57

WEIGHT

UNIT

(LBS)

WEIGHT

UNIT

(LBS)

PROVIDE VARIABLE SPEED DRIVE FOR WINTER OPERATION.

TAG

REGISTERS, GRILLES AND DIFFUSERS

TYPE SIZE BASIS OF DESIGN REMARKS

CEILING DIFFUSER 24x24CD-1 NAILOR RNS

NECK SIZE

(IN)

8" Ø

BLOW

PATTERN

4 WAY LAY-IN

FRAME

NONE

DAMPER

<20

MAX NC

CEILING DIFFUSER 24x24CD-2 NAILOR RNS10" Ø 4 WAY LAY-IN NONE <20

CEILING DIFFUSER 24x24CD-3 NAILOR RNS14" Ø 4 WAY LAY-IN NONE <20

RG-1

1. 45 DEGREE DEFLECTION, FIXED BLADE, 3/4" BLADE SPACING, HORIZONTAL BLADES AND STEEL CONTRUCTION

EXPOSED SPIRAL DUCT RETURN - 36x24 FIXED - YES <20 NAILOR 6145HC NOTE 1

CEILING DIFFUSER 24x24CD-4 NAILOR RNS16" Ø 4 WAY LAY-IN NONE <20

MIN. BASIS OF DESIGN

MFG. AND MODEL

BASIS OF DESIGN

MFG. AND MODEL

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEETEYP Inc.

POTOMAC

STREET NW,

WASHINGTON,

DC 20007

OF

HEATING & COOLING SYST. DESIGN

ADMIN BLDG & AUDITORIUM

VALLEY FORGE NATIONAL HISTORICAL PARK

KING OF PRUSSIA, PA 34

VAFO 201534A

DEC. 2, 2016

SCHEDULES

M601

NB

RR

RR

EXISTING AIR HANDLER SCHEDULE

AREATAG REMARKS

AC-2 ADMIN. ATTIC

SUPPLY FAN

SERVED

TOTAL

4,355

CFM

HP

3.0

AC-3 AUDITORIUM MEZZANINE

OUTSIDE AIR

1,000

CFM

9,550 2,750 7.5

GPM

FOR INFO ONLY

FOR INFO ONLY

CONVECTORS

TAG LOCATION

ENCLOSURE

WIDTH (IN.)

ELEMENT

LENGTH (IN.)

CAPACITY

(KW) QUANTITY BOD

C-2 ADMIN - VARIOUS 18 TBD 1.0 3 ATLANTIC F118

C-3 VARIOUS 30 TBD 2.0 10 ATLANTIC F118

NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL

ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.

2. MOUNT AT SAME HEIGHT AS EXISTING.

C-1 ADMIN - BASEMENT 15 TBD 0.5 1 ATLANTIC F118

EXISTING REHEAT COILS

TAG LOCATION

SIZE

(IN.)

CAPACITY

(KW) CFM

NO.

CIRC.

RH-1 ADMIN - BASEMENT 24X8 6.0 500 1

RH-2 ADMIN - BASEMENT 36X12 5.0 1080 1

RH-3 ADMIN - BASEMENT 48X28 21.0 3970 3

RH-4 ADMIN - BASEMENT 12X8 2.0 350 1

RH-5 ADMIN- FIRST FLOOR 24X8 3 530 1

RH-6 ADMIN - ATTIC 12X8 2 410 1

RH-7 ADMIN - ATTIC 24X12 7 900 1

RH-8 ADMIN - ATTIC 24X12 7 885 1

RH-9 ADMIN - ATTIC 24X8 3 540 1

RH-10 ADMIN - ATTIC 18X12 3.5 625 1

RH-11 ADMIN - ATTIC 24X12 3.5 755 1

RH-12 AUDITORIUM - MEZZANINE 40X42 30.0 6500 3

RH-13 AUDITORIUM - MEZZANINE 24X8 2.5 600 1

RH-14 AUDITORIUM - MEZZANINE 12X8 1.5 290 1

RH-15 AUDITORIUM - MEZZANINE 24X12 5.5 1090 1

RH-16 AUDITORIUM - MEZZANINE 27X8 2.5 590 1

SILL LINE HEATERS

TAG LOCATION

ENCLOSURE WIDTH

(IN.)

ELEMENT

LENGTH (IN.)

CAPACITY

(KW) QUANTITY BOD

FTR-1 AUDITORIUM BLDG 120 84 1.75 8 TRANE EWFB

FTR-2 STAGE AREA 132 96 3.00 2 TRANE EWFB

FTR-3 ENTRANCE SEE DWG 72 2.25 1 TRANE EWFB

FTR-4 ENTRANCE 120 84 2.50 2 TRANE EWFB

FTR-5 VARIOUS WALL TO WALL 84 1.75 2 TRANE EWFB

FTR-6 MEZZANINE 72 36 0.56 1 TRANE EWFB

FTR-7 MEZZANINE 96 60 1.25 1 TRANE EWFB

FTR-8 MEZZANINE 96 60 1.88 1 TRANE EWFB

NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL

ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.

2. MOUNT AT SAME HEIGHT AS EXISTING.

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEETEYP Inc.

POTOMAC

STREET NW,

WASHINGTON,

DC 20007

OF

HEATING & COOLING SYST. DESIGN

ADMIN BLDG & AUDITORIUM

VALLEY FORGE NATIONAL HISTORICAL PARK

KING OF PRUSSIA, PA 34

VAFO 201534A

DEC. 2, 2016

SCHEDULES

M602

NB

RR

RR

REFER TO SPECIFICATION SECTION 230993

FOR SEQUENCES OF OPERATION AND

ALARMS.

T

S

T

HWST

HWRT

SV

HV

BPD

ALM

FZ

HCV

AQS

SD

V-#

TSTAT

SP

S/S

SPL

SPH

OAT

SAT

SAD

OAD

DAT

DPS

CS

AFMS

FBD

EAD

D-#

HS

TS

FM

HHL

VFD

WS

ISOD

LRC

STR

OX

DPS-1 FZ-1 TS-2

V-1

D-2

TS-1

CO2D-3

D-1

AFMS-3

VFD

CS

SD-1

SD-1

ES

AFMS-2

CS

VFD

SPL

SPHD-4 ROOM SENSOR

C C

NC

CHWR

CHWS

NO

X

DPS-1 FILTER DIFFERENTIAL PRESSURE X

V-1 COOLING COIL VALVE X

FZ-1 FREEZESTAT

D-1 VENTILATION AIR DAMPER X

AI AO DI DO HI LOW

POINT ALARMSSYSTEM POINT

DDC CONTROL PANEL INPUT/OUTPUT SUMMARY

OFF/NRML

COMMENTS

D-2 RETURN AIR DAMPER X

AFMS-1 OUTSIDE AIR CFM X

AFMS-2 SUPPLY AIR FAN CFM

XSD-1 SMOKE DETECTOR

TS-2 SUPPLY AIR TEMPERATURE X

SUPPLY AIR

RETURN AIR

TS-1 ROOM TEMPERATURE X

X X

START/STOP SUPPLY FAN VFD

XSUPPLY FAN VFD FAULT

CO2 CARBON DIOXIDE SENSOR RETURN AIR DUCT X

NC

NC

OUTSIDE AIR

RELIEF AIR

D-3 RELIEF AIR DAMPER X

AFMS-3 RETURN AIR FAN CFM X

X X

X W/ CURRENT SENSOR

X

XSTART/STOP RETURN FAN VFD

XRETURN FAN VFD FAULT

X X W/ CURRENT SENSOR

X

IN-DUCT SMOKE DETECTOR

IN-DUCT

SMOKE

DETECTOR

HOT WATER SUPPLY TEMPERATURE

HOT WATER RETURN TEMPERATURE

SUPPLY AIR VALVE

HOOD EXHAUST AIR VALVE

BYPASS DAMPER

ALARM

FREEZESTAT

HEATING CONTROL VALVE

AQUASTAT

SMOKE DETECTOR (DUCT)

STATIC PRESSURE SENSOR

START/STOP

STATIC PRESSURE LOW

STATIC PRESSURE HIGH

THERMOSTAT OR TEMPERATURE SENSOR

MOUNT 48" AFF UNLESS OTHERWISE NOTED

THERMOSTAT OR TEMPERATURE SENSOR

OUTSIDE AIR DAMPER

OUTSIDE AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

SUPPLY AIR DAMPER

DISCHARGE AIR TEMPERATURE

CURRENT SENSOR

DIFFERENTIAL PRESSURE SENSOR

AIR FLOW MEASURING STATION

FACE & BYPASS DAMPER

END SWITCH

EXHAUST AIR DAMPER

CONTROL DAMPER

HUMIDITY SENSOR

TEMPERATURE SENSOR

NORMALLY CLOSEDNC

NO NORMALLY OPEN

FLOW METER

HUMIDITY HIGH LIMIT

VARIABLE FREQUENCY DRIVE

WALL SWITCH

ISOLATION DAMPER

SINGLE POINT INPUT/OUTPUT

MULTIPLE PIONTS INPUT/OUTPUT

X

FIRE ALARM CONTROL PANELFACP

FIRE ALARMFA

ZONE PRESENCE SENSORZPS

FUME HOOD SASH SENSORFHSS

FUME HOOD MONITORFHM

FIREFIGHTER SMOKE CONTROL SYSTEMFSCS

HOOD EXHAUST AIR VALVE

LAB ROOM CONTROLLER

MOTOR STARTER

OXYGEN SENSOR

LEGEND

ES

NC

D-4 SUPPLY FAN ISOLATION DAMPER X

SPH HIGH STATIC PRESSURE LIMIT

SPL LOW STATIC PRESSURE LIMIT

3-WAY

MIXING

VALVE

XX

X X

X

AFMS-1

COMMENTS

UNIT CONTROL PANEL INPUT/OUTPUT SUMMARY

SYSTEM POINT POINT

DODIAOAI

T-1 INTEGRAL THERMOSTAT X

REFER TO SPECIFICATION SECTION 230993 FOR

SEQUENCE OF OPERATION AND ALARMS

T R S

T-1

RELAY

SWITCH

POWER FROM

X-CONTACTOR

HEATER

ADJUSTABLE, LINE VOLTAGE

LOCATION T-1 SWITCH

STAIR #2 1 1

T

TS-2

TS-1

SAH

C

SA

ROOM SENSOR

(NEW)

COMMENTS

BAS DDC CONTROL PANEL INPUT/OUTPUT SUMMARY

SYSTEM POINT POINT

DODIAOAI

TS-1 ROOM TEMPERATURE X

TS-2 DISCHARGE AIR TEMPERATURE X

REFER TO SPECIFICATION SECTION 230993 FOR

SEQUENCE OF OPERATION AND ALARMS

R

DO

BAS

POWER

CONTACTOR

AF

DUCT

REHEAT COIL

AIR FLOW

T

TS-E

ROOM SENSOR

PNEUMATIC

DEMO/REMOVE

AF AIRFLOW SWITCH X

R CONTACTOR (EXTG) X

HI LIMIT

BAS WILL ENERGIZE CONTACTOR

REHEAT

COIL T-1 LOCATION

ASSOC.

UNIT

1 NORTH PASSAGE AHU-1

2 AHU-1

6 A\C-2 7 A\C-2

8 A\C-2COMM. READING

MUSEUM

STAIR #1

LIBRARY

3 AHU-1LOBBY

4 AHU-1STAFF LOUNGE

5 AHU-1TOILET (RECEPTION)

9 A\C-2SUPER. OFFICE

10 A\C-2GENERAL OFFICE

11 A\C-2RECEPTION

13 A\C-3PROJ. ROOM

14 A\C-3PASSAGE B51

15 A\C-3LOBBY

16 A\C-3STAIR #3

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEETEYP Inc.

POTOMAC

STREET NW,

WASHINGTON,

DC 20007

OF

HEATING & COOLING SYST. DESIGN

ADMIN BLDG & AUDITORIUM

VALLEY FORGE NATIONAL HISTORICAL PARK

KING OF PRUSSIA, PA 34

VAFO 201534A

DEC. 2, 2016

CONTROL DIAGRAM

M701

NB

RR

RR

NTS1 AHU-1 CONTROLS DIAGRAM

NTS2

ELECTRIC FIN TUBE RADIATION

CONTROL DIAGRAM

NTS3 TYPICAL DUCT MOUNTED REHEAT COIL

VRV TERMINAL UNIT SCHEDULE

DESG SERVES

UNIT

AIRFLOW

[CFM]

OUTDOOR

AIR

[CFM]

COOLING

SETPOINT

(°F)

HEATING

SETPOINT

(°F)

CALCULATED

TOTAL

COOLING CAP

[MBH]

UNIT

MAX

COOLING

CAP

[MBH]

CALCULATED

HEATING

CAP

[MBH]

UNIT

MAX

HEATING

CAP

[MBH]

MAX UNIT DIMENSION

MCA MCOP V/PH/Hz MAX

NC

BASIS OF DESIGN

NOTESLENGTH

(IN)

HEIGHT

(IN)

DEPTH

(IN) MANUFACTURER MODEL

VRF-1 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6

VRF-2 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6

VRF-3 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6

VRF-4 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6

VRF-5 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6

VRF-6 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6

VRF-7 Porch 1,200 - 75 68 33.6 33.5 12.8 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6

VRF-8 Exhibit/Servant Quarters 1,200 - 75 68 36 33.5 38 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6

VRF-9 Restroom - lvl 1 245 - 75 68 7.2 7.0 5.8 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-10 Office 245 - 75 68 7.2 7.0 9.0 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-11 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-12 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-13 Bedroom 2 245 - 75 68 8.4 7.0 9.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-14 Bedroom 3 245 - 75 68 8.4 7.0 7.2 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-15 Restroom - Groom 245 - 75 68 3.6 7.0 2.3 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-16 Stair, Upper 245 - 75 68 8.4 8.8 8.4 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-17 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-18 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-19 Restroom - lvl 3 245 - 75 68 2.4 7.0 2.7 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-20 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-21 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-22 Restroom - Bridal 245 - 75 68 2.4 8.8 2.6 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-23 Servant Quarters - Hall 245 - 75 68 6.0 8.8 6.9 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 4, 6

NOTES:

1. PROVIDE IN SPACE, WALL MOUNTED DIGITAL THERMOSTAT. FINAL LOCATION SHALL BE COORDINATED WITH OWNER.

2. FLOOR MOUNTED, DUCTED UNIT.

3. CONCEALED FLOOR MOUNTED, NON-DUCTED UNIT.

4. UNIT TO BE INSTALLED WITH MANUFACTURER ENCLOSURE. EXISTING ENCLOSURE SHALL BE REMOVED, PROTECTED FOR STORAGE, AND PROVIDED TO OWNER.

5. DESIGN INTENT IS THAT UNIT BE INSTALLED WITHOUT MANUFACTURER ENCLOSURE.

6. INCLUDE MANUFACTURER PROVIDED CONDENSATE PUMP.

VRV OUTDOOR UNIT SCHEDULE

DESG

EQUIPMENT

COOLING CAP

[MBH]

EQUIPMENT

HEATING CAP

[MBH]

MAX

REFRIGERANT

CHARGE [lbs]

MCA MCOP

AMBIENT

TEMP

[°F]

V/PH/HZ

BASIS OF DESIGN

NOTES

MANUFACTURER MODEL

CU-1 192.9 130.0 35.9 63.9 80 95 208/3/60 DAIKIN RXYQ192TTJU

CU-2 97.5 68.3 22.7 36.3 45 95 208/3/60 DAIKIN RXYQ96TTJU

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

AutoCAD SHX Text 2/16/2018

AutoCAD SHX Text

PHILANDER CHASE KNOX HOUSE

AutoCAD SHX Text

HEATING SYSTEM REPLACEMENT

AutoCAD SHX Text 163366

AutoCAD SHX Text

AutoCAD SHX Text 41022B

AutoCAD SHX Text

100%%% CD DRAWINGS

AutoCAD SHX Text

LOUIS BERGER GROUP

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

SCHEDULES

AutoCAD SHX Text

STN

AutoCAD SHX Text

MS

AutoCAD SHX Text M6.1

AutoCAD SHX Text 10/12/17 10:13 SNEWSWANGER R20 P:\PROJECTS\2016 PROJECTS\NPS-CHASE KNOX HOUSE\3. PROJECT INFORMATION\3.2 DRAWINGS\VAFO\163366\DRAWINGS\MECH\M6.1 MECHANICAL SCHEDULES.DWG XREFS: ..\XREF\XG-TITLBLK.DWG;

AutoCAD SHX Text

Pages from 1 VAFO 201534A 100 CD Drawings PDF
Pages from FULL COMBINED SET
PCK
Sheets and Views
M6.1

File details come from the government source that posted it. Updated .