Amendment_0002_Attachment_06_VAFO_VC_201534A_100_CD_Drawings_PDF_0002.pdf
PDF 2 MB Posted
- Attached to
- FY24 VAFO HVAC INSPECTIONS & MAINTENANCE
- Solicitation number
- 140P4224Q0122
About this file
This document contains design and construction drawings for the HVAC system of the administrative building and auditorium at Valley Forge National Historical Park. The drawings include floor plans, sections, elevations, and details for the new heating, cooling, and ventilation system. Key details include:
The administrative building will have a new air handling unit (AHU-1) serving the basement and first floor. The auditorium building will have a new air-cooled chiller (ACC-1) and associated piping and equipment. The drawings indicate the locations of new ductwork, grilles, diffusers, and other HVAC components. Specifications are provided for the major equipment such as the air handler, chiller, and pumps. The drawings also show modifications to the existing ductwork and HVAC systems in the buildings.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E
SheetMark REVISION Date Initial
OR
OR
Design (Title I)
Prepared in Accordance with Preliminary by Preliminary Design (Title I) Construction Drawing Not Preceded
Approved by Superintendent on Variance from Preliminary Design (Title I)
Project Manager
Drawing No.
Date
Date
QUALITY DESIGN CERTIFICATION
BASIC DATA:
STATEREGION COUNTY
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF PROJECT DRAWING NO.EYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007 DEPARTMENT OF THE INTERIOR
UNITED STATES
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
OF
PKG.
NO.
SHEET
CHESTER PENNSYLVANIANORTHEAST
VISITOR CENTER
VALLEY FORGE NATIONAL HISTORICAL PARK
DESIGN AND CONSTRUCTION DOCUMENTS
HEATING & COOLING SYSTEM DESIGN
ADMINISTRATIVE BUILDING & AUDITORIUM
PMIS NO. VAFO 201534A
DESIGN AND CONSTRUCTION DOCUMENTS
FOR HEATING & COOLING SYSTEM DESIGN
ADMINISTRATIVE BUILDING & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
VALLEY FORGE NATIONAL HISTORICAL PARK
PENNSYLVANIA
Benjamin Franklin HW Y
Valley Forge Park Rd
N Gulph Rd
U/S NATIONAL
PARK SERVICE
Valley Forge National Park Visitor Center
N.Outer Line Dr
N.Outer Line Dr
N.Outer Line Dr
Sheet # Sheet Discipline Sheet Set Sheet Name
2016.05.16 - Schematic Designs (90%) Review
2016.06.24- Final Design Review
2016.08.12 - 100% Contruction Documents
2012.12.02 Final Construction
Documents
G101 1 - Cover G101 COVER X X X X
A001 9 - Architectural A001 TYPICAL SYMBOLS AND ABBREVIATIONS X X
A101 9 - Architectural A100 ADMIN BUILDING FLOOR PLAN & RCP PLAN X X X X A102 9 - Architectural A100 AUDITORIUM BLDG FIRST AND MEZZ. FLOOR X X X X
A201 9 - Architectural A200 SECTIONS ADMINISTRATIVE BLDG X X X X A 202 9 - Architectural A200 SECTIONS AUDITORIUM BLDG X X X X
A301 9 - Architectural A300 ELEVATIONS X X X X
A501 9 - Architectural A500 DETAILS X X X
M001 14-Mechanical M001 HVAC LEGEND AND GENERAL NOTES X X X X
M101 14-Mechanical M100 HVAC PLAN - ADMIN BASEMENT & FIRST FLOOR X X X X M102 14-Mechanical M100 HVAC PLAN - AUDITORIUM FLOOR PLANS X X X
M201 14-Mechanical M200 PIPING PLAN - ADMIN BASEMENT & FIRST FLOOR X X X X
M301 14-Mechanical M300 ENLARGED PLANS X X M302 14-Mechanical M300 SECTIONS-ADMINISTRATIONS X X
M401 14-Mechanical M400 FLOW DIAGRAMS X X X X
M501 14-Mechanical M500 DETAILS X X X
M601 14-Mechanical M600 SCHEDULES X X X X M602 14-Mechanical M600 SCHEDULES X X X
M701 14-Mechanical M700 CONTROL DIAGRAM X X M702 14-Mechanical M700 CONTROL DIAGRAM X X M703 14-Mechanical M700 AS-BUILT CONTROLS X M704 14-Mechanical M700 AS-BUILT CONTROLS X M705 14-Mechanical M700 AS-BUILT CONTROLS X M706 14-Mechanical M700 AS-BUILT CONTROLS X M707 14-Mechanical M700 AS-BUILT CONTROLS X
MD001 14-Mechanical MD001 DEMO - ADMINISTRATION X X X X MD002 14-Mechanical MD001 DEMO-AUDITORIUM X
E001 15 - Electrical E001 ELECTRICAL LEGEND X X X X
E101 15 - Electrical E100 POWER PLAN - ADIMINSTRATION X E102 15 - Electrical E100 POWER PLAN - AUDITORIUM X
E201 15 - Electrical E200 ELECTRICAL POWER PLAN X X X
E401 15 - Electrical E400 ELECTRICAL RISER DIAGRAM & SCHEDULE X X X
E601 15 - Electrical E600 PARTIAL SINGLE LINE DIAGRAM & SCHEDULES X E602 15 - Electrical E600 ELECTRICAL PANEL SCHEDULES X
ED101 15 - Electrical ED101 DEMO - ADMINISTRATION X ED102 15 - Electrical ED101 DEMO - AUDITORIUM X
2' x 2' ACOUSTICAL
PANEL CEILING AND
SUSPENSION SYSTEM
1' X 4' LED SURFACE
MOUNTED LIGHT
FIXTUREGWB CEILING
NO CEILING
RECESSED DOWN
LIGHT CENTERED IN
CEILING GRID
SUPPLY AIR DIFFUSER
RETURN AIR REGISTER
2' X 4' LED LAY-IN
LIGHT FIXTURE
RCP LEGEND
2' X 2' LED LAY-IN
LIGHT FIXTURE
EXHAUST FAN
CONCEALED SPRINKLER
UPRIGHT SPRINKLER
SIDE WALL SPRINKLER
EXIT LIGHT
EMERGENCY LIGHTING UNIT
DAYLIGHT SENSOR
MOTION SENSOR
STROBE
SMOKE DECTECTOR
ROOM NAME & NUMBERS
DOOR NUMBERS
COLUMN NUMBERS
ELEVATION TARGET
REVISION NUMBER
WALL/ PARTITION TYPES
CONSTRUCTION KEY NOTE
FLOOR BOX
FLOOR DRAIN
CASEWORK TAG
MATERIAL KEY NOTE
OFFICE
100A
00.00
B60A
WINDOW/ LOUVER TYPE2
WB36E30
EQUIPMENT TAG00000-00
FB
FD
?CPT-1
PLAN SYMBOLS
EXIST TO BE
REMOVED
EXIST TO REMAIN
OPENING
CASEWORK
DOOR
WALL
SINK
WINDOW
NEW
MILLWORK
PLAN LEGEND
ALUMINUM
BATT INSULATION
BRICK
COMPACTED BACKFILL
EARTH
FINISH WOOD
GLASS IN ELEVATION
GRANULAR FILL
GYPSUM WALL BOARD OR GROUT
PARTICLE BOARD/ FIBER BOARD
PLYWOOD
RIGID INSULATION / ROOF INSULATION
ROUGH WOOD BLOCKING (CONTINUOUS)
ROUGH WOOD BLOCKING (INTERRUPTED)
STEEL
STONE (CUT OR CAST)
CONCRETE
CONCRETE MASONRY UNITS
MATERIAL LEGEND
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
TYPICAL SYMBOLS AND
ABBREVIATIONS
A001
ASP
SS
1/8" = 1'-0"
RCP LEGEND
1/8" = 1'-0"
PLAN SYMBOLS
1/8" = 1'-0"
DEMOLITION LEGEND
1 : 11 MATERIAL INDICATIONS
ARCHITECTURAL ABBREVIATIONS
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAINTED
PTN PARTION
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
QTY QUANTITY
R_ RISER LINE
RAD RADIUS
RB RUBBER BASE
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCED
REQ'D REQUIRED
RESIL RESILIENT
RLE RELOCATE EXISTING
RM ROOM
RTU ROOF TOP UNIT
S&R SHELF & ROD
SB SMART BOARD
SC SPECIAL COATING, SOLID CORE
SD SOAP DISPENSER
SF SQUARE FOOT/FEET
SG SAFTEY GLASS
SHT SHEET
SIM SIMILAR
SLD SEALED
SOG SLAB ON GRADE
SP SUMP PUMP
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
ST STORM SEWER, STONE, STAIN
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCUR(E, AL)
SUSP SUSPEND(ED)
SYS SYSTEM
T THREAD
T&B TOP & BOTTOM
T&G TOUNGE & GROOVE
T/ TOP OF
T/C TOP OF CONCRETE
T/F TOP OF FRAME
T/S TOP OF STEEL
T/W TOP OF WALL
TB TACKBOARD
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZO
THK THICK
THR THRESHOLD
TOIL TOILET
TV TELEVISION
TYP TYPICAL
UC UNDERCUT
UG UNDERGROUND
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UPS UNINTERUPTABLE POWER SUPPLY
UTIL UTILITY
VAR VARIABLE
VB VINYL BASE
VCT VINYL COMPOSITE TILE
VEN VENEER
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FEILD
VIN VINYL
VT VAPOR TIGHT
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WIDE, WIDTH, WATER
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WH WATER HEATER
WP WATERPROOF
WT WEIGHT
WTC WATER COOLER
WTR WATER
ARCHITECTURAL ABBREVIATIONS
ETRL EXISTING TO BE RELOCATED
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXP EXPANSION
F/C FLOOR TO CEILING
FAI FRESH AIR INTAKE
FB FOILBACKED
FBR FABRIC
FD FLOOR DRAIN, FIRE DAMPER
FDN, FOUND FOUNDATION
FDVC FIRE DEPT. VALVE CABINET
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FIN FINISH(ED)
FL, FLR FLOOR
FLAM FLAMMABLE
FLOUR FLOURECENT
FO FIBER OPTIC(S)
FOB FACE OF BRICK
FOC FACE OF CONCRETE
FOP FACE OF PILASTER
FP FIRE PROTECTION, FILLER PANEL
FRT FIRE RETARDANT TREAT(ED,MENT)
FS FLOOR SINK
FSACCP FLAT SEAM ALLOY - COATED COPPER PANEL
FT FEET, FOOT, FULL TIME
FTG FOOTING
GC GENERAL CONTRACTOR
HTR HEATER
HVAC HEATING,VENTILATION, AIR CONDITIONING
HW HOT WATER
HWD HARDWOOD
HWR HOT WATER RETURN
I.E. THAT IS
ID INSIDE DIAMETER
IN INTERIOR
INV INVERT(ED)
JB JUNCTION BOX
JC JANITOR'S CLOSET
JG JAMB GUARD
JT JOINT
JTS JOINTS
KS KNEE SPACE, KICK SPACE
LAM LAMINATED
LAV LAVATORY
LGMF LIGHT GAUGE METAL FRAMING
LIN LINEN
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
MB MARKER BOARD
MEJ MASONRY EXPANSION JOINT
MTD MOUNT(ED)
MTL METAL
N.I.C. NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OH OVERHEAD
OPG OPENING
OPP OPPOSITE
OZ OUNCE
P POLE
PB PULL BOX
PCC PRECAST CONCRETE
PD PRESSURE DROP
PH PHASE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLMB PLUMBING
PLYWD PLYWOOD
PNL PANEL
POLY POLYCARBONATE
ARCHITECTURAL ABBREVIATIONS
A
AAF ABOVE ACCESS FLOOR
ABV ABOVE
ACCES ACCESSIBLE
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN, ACCESS DOOR
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFL ACCESS FLOOR(ING)
AGGR AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACCESS PANEL
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURE (URE,URAL)
AS ABOVE SLAB
ASPH ASPHALT
AUTO AUTOMATIC
AUX AUXILIARY
AVG AVERAGE
B/C BOTTOM OF CURB
BALC BALCONY
BD BOARD
BEL BELOW
BET BETWEEN
BKBD BACKBOARD
BLDG BUILDING
BLKG BLOCKING
BLKHD BULKHEAD
BM BEAM
BOD BASIS OF DESIGN
BOT BOTTOM
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BUR BYD BUILT-UP ROOF BEYOND
C CONDUIT
CAB CABINET
CAP CAPACITY
CAT CATALOG
CB CATCH BASIN
CEM CEMENT
CF CUBIC FOOT
CI CAST IRON
CJ CONTROL JOINT
CLG CEILING (SEE ALSO MECH ABBREVIATIONS)
CLL CONTRACT LIMIT LINE
CLOS CLOSET
CLR CLEAR(ANCE)
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
COND CONDENS(ATE,ER,ING,ATION)
CONF CONFERENCE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINU(OUS,ATION)
CONTR CONTRACTOR
COORD COORDINATE
CPT CARPET
CRS COURSE
CT CERAMIC TILE
CW COLD WATER
CWR COLD WATER RETURN
CY CUBIC YARD
CYL CYLINDER
DET DETAIL
DRWR DRAWER
DS DOWNSPOUT
DWGS DRAWINGS
EF EXHAUST FAN
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLO(ES,SURE)
EOS EDGE OF SLAB
EP ELECTRICAL PANEL
EPX EPOXY
EQ EQUAL
EQUIP/EQPT EQUIPMENT
ETR EXISTING TO REMAIN
UPDN
UP
DN
DN
DN
DN
UP
UP
DN
DN
STAIR 1
MUSEUM
STORAGE
COMPUTER
SPECIALIST
104A
MAIL ROOM
104D
ADMINISTRATIVE
CLERK
104C
PURCHASING
AGENT
105B
CONTRACT
SPECIALIST
105C
PERSONNEL
MANAGEMENT
SPECIALIST
105D
ADMIN
105E
ADMINISTRATION
OFFICER
105F
ENTRY FOYER
105A
NORTH PASSAGE
A201
A201
A201
A201
104-1
111-2
105-3
105-1
105-2
MEN'S TOILET
VEST
SOUTH
PASSAGE
JAN
BUDGET ANALYST
NEW
CHILLER
PAD, 1/A501
LAN ROOM
104B
WOMEN'S REST
ROOM
WALL PENETRATION
BY HOSE BIBB
WALL PENETRATION BY
HOSE BIBB
WALL PENETRATION BY
HOSE BIBB
LIGHT FIXTURE ON THE
EXT. WALL
ELEC. CONDUIT WALL
PENETRATION
LIGHT FIXTURE ON
THE EXT. WALL
LIGHT FIXTURE ON THE
EXT. WALL
PATCH ABANDOND OUTDOOR
A/C UNIT PIPE WALL
PENETRATION, BASE BID
NEW
ENCLOSURE
NEW
ENCLOSURE
NEW
ENCLOSURE
NEW
DUCT
EXISTING
AIRWAY
A501
A501
CHILLER
20' - 0"
4'
- 8
1/ 8"
4'
- 1
1"
4' - 6" 4' - 8"
STAIR 2
SUPPORT
PROGRAM
ASSISTANT
LIBRARY
STORAGE
STAIR 1
VAULT
CONFERENCE
ROOM
PARK SUP.
MANAGER
ASSISTANT
WOMEN
MEN
JAN.
COATS
PASSAGE
SECRETARY
SUP. PARK
RANGER
SUP. PERK
RANGER
215A
DEPUTY SUP.
215B
SUP. SECRETARY
205A
A201
A201
A201
A201
A501
A201
A201
A201
A201
NEW PLYWOOD
SHEATHING ATTACHED
TO ROOF STRUCTURE,
ENTIRE FLOOR SEE
2/A501
NEW GASKETED &
INSULATED ACCESS HATCH
36"X30" ADD ALT 01
NEW GASKETED &
INSULATED ACCESS
HATCH 36"X30" ADD
ALT 01
REMOVE AND
REINSTALL EXISTING
ACOUSTIC CEILING
TILE SYSTEM, ENTIRE
FLOOR SEE 2/A501
REMOVE EXISTING
GYPSUM CEILING
AND REPLACE IT
WITH NEW GYPSUM
CEILING
REMOVE EXISTING
GYPSUM CEILING
AND REPLACE IT
WITH NEW GYPSUM
CEILING
ADD ALT 3
REMOVE AND
REINSTALL EXISTING
ACOUSTIC CEILING
TILE SYSTEM,
ENTIRE FLOOR
REMOVE EXISTING
GYPSUM CEILING
AND REPLACE IT
WITH NEW GYPSUM
CEILING
ADD ALT 3
NEW PLYWOOD
SHEATHING ATTACHED
TO ROOF STRUCTURE,
ENTIRE FLOOR SEE
2/A501
A201
A201
A201
A201
NEW
SUSPENDED
ACOUSTIC
CEILING
NEW
SUSPENDED
ACOUSTIC
CEILING
NEW
SUSPENDED
ACOUSTIC
CEILING
NEW
SUSPENDED
ACOUSTIC
CEILING
NEW
SUSPENDED
ACOUSTIC
CEILING
EXISTING GYPSUM
CEILING TO REMAIN
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
ADMIN BUILDING FLOOR
PLAN & RCP PLAN
A101
ASP
SS
1/8" = 1'-0"1 FIRST FLOOR PLAN - BASE BID
1/8" = 1'-0"2 SECOND FLOOR PLAN - ADD ALT 01
1/8" = 1'-0"4
REFLECTED CEILING PLAN SECOND
FLOOR - ADD ALT 03
NOTE:
1.SEAL INTERIOR PENETRATIONS AT EXTERIOR WALLS SEE 3/A501, ADD ALT 02
NOTE: REMOVE, CLEAN AND STORE FOR
REINSTALLATION ALL LIGHT FIXTURES, MECHANICAL
GRILLES AND OTHER CEILING MOUNTED EQUIPMENT.
REINSTALL IN EXISTING LOCATIONS
1/8" = 1'-0"3
REFLECTED CEILING PLAN FIRST
FLOOR-BASE BID
NOTE: REMOVE, CLEAN AND STORE FOR
REINSTALLATION ALL LIGHT FIXTURES, MECHANICAL
GRILLES AND OTHER CEILING MOUNTED EQUIPMENT.
REINSTALL IN EXISTING LOCATIONS
DNUP DN
DN
DN
DN
DN
DN
DN
DN
UP
UP
MECHANICAL
ROOM
M-6
PROJECTION
ROOM
M-4
STAIR 33
M-1PASSAGE
M-2
PROJ TOIL
M-5
STORAGE
M-3
A 202
A 202
REMOVE AND
REINSTALL SCREEN
REMOVE AND
REINSTALL CURTAINS
REMOVE AND
REINSTALL CURTAINS
NEW 6" STEEL STUD WALL, 5/8" GYPSUM
BOARD, R-19 BATT INSULATION, PAINT
A501
ETR AC-3
NEW EXPOSED SPIRAL DUCT AND
GRILLES,
PAINT FLAT OFF WHITE COLOR,
BASE BID
CUT & PATCH WALL FINISH TO
MATCH EXISTING
RG-1, 36"X18"
1100 CFM
TYP OF 6
STAIR #3
LOBBY
A 202
A 202
STAGE
153A
AUDITORIUM
151-2
151-3
151-1
153-2153-1
NEW 6" STEEL STUD WALL, 5/8" GYPSUM
BOARD, R-19 BATT INSULATION, PAINT
REMOVE AND
REINSTALL SCREEN
REMOVE AND
REINSTALL CURTAINS
REMOVE AND
REINSTALL CURTAINS
16' - 0"
6' - 4" 25' - 8"
A501
WALL PENETRATION
BY HOSE BIBB
LIGHT FIXTURE ON THE
EXT. WALL
LIGHT FIXTURE ON THE
EXT. WALL
LIGHT FIXTURE ON THE
EXT. WALL
PVC CONDUIT PENETRATION
THROUGH THE WALL
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
AUDITORIUM BLDG FIRST
AND MEZZ. FLOOR
A102
ASP
SS
1/8" = 1'-0"2 MEZZANINE FLOOR - ADD ALT 01
1/8" = 1'-0"3 FIRST FLOOR - ADD ALT 01
NOTE:
1.SEAL PENETRATIONS AT EXTERIOR WALLS SEE 3/A501
SECOND FLOOR PLAN 2A
179' - 2"
BASEMENT PLAN 1A
157' - 8"
FIRST FLOOR PLAN 1A
168' - 6"
ROOF 1A
188' - 3 3/8"
A501
NEW DUCT
THROUGH WALL,
SEE MECH DWG
SECOND FLOOR PLAN 2A
179' - 2"
BASEMENT PLAN 1A
157' - 8"
FIRST FLOOR PLAN 1A
168' - 6"
ROOF 1A
188' - 3 3/8"
A501
NEW
ENCLOSURE
CHILLER
DUCT, PAINT WHITE
SEAL
AROUND
DUCT
SECOND FLOOR PLAN 2A
179' - 2"
BASEMENT PLAN 1A
157' - 8"
FIRST FLOOR PLAN 1A
168' - 6"
ROOF 1A
188' - 3 3/8"
A501
NEW
ENCLOSURE
CHILLER
DUCT, PAINT WHITE
SECOND FLOOR PLAN 2A
179' - 2"
BASEMENT PLAN 1A
157' - 8"
FIRST FLOOR PLAN 1A
168' - 6"
ROOF 1A
188' - 3 3/8"
A501
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
SECTIONS
ADMINISTRATIVE BLDG
A201
ASP
SS
1/8" = 1'-0"1 SECTION 1
1/8" = 1'-0"2 SECTION 2
1/8" = 1'-0"3 SECTION 3
1/8" = 1'-0"4 SECTION 4
DUCT, PAINT WHITE
NEW ENCLOSURE
NEW ENCLOSURE
DUCT, PAINT WHITE
A501
DUCT, PAINT WHITE
NEW
ENCLOSURE
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
ELEVATIONS
A301
ASP
SS
3/32" = 1'-0"4 EAST ELEVATION
3/32" = 1'-0"3 WEST ELEVATION
3/32" = 1'-0"1 SOUTH ELEVATION
3/32" = 1'-0"2 NORTH ELEVATION
FOIL FACED R-19 BATT
INSULATION, TAPE ALL
SEAMS EXISTING
STONE WALL
AIR GAP
6" STEEL STUD WALL,
5/8" GYPSUM BOARD,
PAINT
METAL TRACK TOP AND
BOTTOM
REMOVE AND
REINSTALL CURTAIN
EXISTING ROOF
DECKING
REMOVE & REINSTALL
SCREEN
ADD BLOCKING FOR
MOUNTING SCREEN, AS
REQUIRED
ELECTRICAL FIN TUBE
HEATING SEE MECH DWG
PAINTED WOOD WALL
BASEBOARD, MATCH
EXISTING
BRIDGING AS REQUIRED
PER STUD
MANUFACTURER
RECOMMENDATION
SEALANT TOP AND
BOTTOM
TAPE ALL SEAMS IN PLYWOOD
R30 12" FOILED FACED INSULATION
1/2" TONGUE AND
GROOVE PLYWOOD
EXISTING ROOF FRAMING
REINSTALLED ACOUSTICAL
TILE CEILING SYSTEM
FINISHED GRADES
#5 @ 12" ON CENTER
EACH WAY WITH 90°
HOOKS AT ENDS
CL
R
0'
- 2
NOTES:
1. COORDINATE HOUSE KEEPING PAD AND LOCATION WITH MECHANICAL DRAWINGS AND ACTUAL UNIT SELECTED
2. PROVIDE A MINIMIUM 6" CLEAR DISTANCE BETWEEN EQUIPMENT AND EDGE OF CURB.
#57 STONE OR NON-FROST
SUSCEPTIBLE MATERIAL
MIN
1' - 0"
0'
- 6
0'
- 8
0' - 6" 0' - 6"
0'
- 6
" M
IN
MI
N
3'
- 0
0'
- 6
" 1'
- 2
EQUIPMENT
0' - 6"
EQUIPMENT EDGE
0' - 6"
EXISTING
FLUE CAP
INFILL FLUE WITH
NON SHRINK
GROUT, 6" MIN
CLOSE EXISTING
DAMPER
EXISTING
8" CMU
EXISTING 13"X13"
TC FLUE LINING
EXISTING
4" BRICK
R-20 6" FOIL FACED
INSULATION
SEALANT ALL
EDGES
EXISTING SLAB
STEEL ANGLE
STEEL PLATE
EXISTING WALL FUROUT
EXISTING EXTERIOR
MASONRY WALL
EXISTING BATT INSULATION
SPRAY FOAM
INSULATION IN
CAVITIES
EXISTING
ELECTRICAL
DEVICE & BOX
SEALANT ALL EDGES
UNDER FACE PLATE
PENETRATION SCHEDULE
ADMIN:
(3) HOSE BIB WALL PENETRATION
(3) LIGHT FIXTURE WALL PENETRATION
(1) ELEC CONDUIT WALL PENETRATION
(1) A/C CONDUIT WALL PENETRATION
AUDITORIUM:
(1) HOSE BIB WALL PENETRATION
(3) LIGHT FIXTURE WALL PENETRATION
(1) ELEC CONDUIT WALL PENETRATION
7'
- 0
VINYL GATE
VINYL POSTS
8'
- 0
3' - 6"
6"X6"VINYL
POST
VINYL
ENCLOSURE
VINYL
POST
8'
- 0
0'
- 4
TY
P
0'
- 3
3/ 4"
1"X6" CONT.
VINYL CAP.
MITER CUT
@CORNERS
1"X4" CONT.
VINYL RAILS
MITER CUT
@CORNERS
6" X 6" VINYL
POST
PI
PE
E
MB
ED
M E
NT
3'
- 0
1' - 4"
2'
- 7
CHAMFER
2%
8'
- 0
8'
- 0
GRADE
0'
- 4
0'
- 4
" C
LR
8 - #4 BARS,
VERT
#4 TIES, TYP
AT 12" O.C. ,
U.N.O
0' - 3" CLR, TYP
0'
- 3
" C
LR
0'
- 5
FIRST TWO TIES
SPACED IN TOP 5"
(AS SHOWN)
PI
ER
E
MB
ED
ME
NT
2'
- 1
1"
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
DETAILS
A501
ASP
SS
08 1/2" = 1'-0"8 WALL SECTION AT STAGE ADD ALT01
1 1/2" = 1'-0"2 CEILING DETAIL ADD ALT 03
3/4" = 1'-0"1 CHILLER EQUIPMENT PAD
3/4" = 1'-0"4 FIRE PLACE DETAIL ADD ALT 01
3" = 1'-0"3
TYPICAL INTERIOR PENETRATION ETAIL
ADD ALT 02
Door Schedule (ADD ALT 01)
DOOR NUMBER DOOR DIMENSION NEW EQUIPMENT
104-1 (2) 3'-0"X7'-2" 1,2,3,4 105-1 (2) 3'-0"X7'-2" 1,2,3,4 105-2 (2) 3'-0"X7'-2" 1,2,3,4 105-3 3'-0"x7'-2" 2,4 111-2 3'-0"x7'-2" 2,4 151-1 (2) 3'-0"X7'-2" 1,2,3,4 151-2 (2) 3'-0"X7'-2" 1,2,3,4 151-3 (2) 3'-0"X7'-2" 1,2,3,4 153-1 (2) 3'-0"X7'-2" 1,2,3,4 153-2 (2) 3'-0"X7'-2" 1,2,3,4 M-6 (2)4'-0"X7'-2" 1,2,3,4
1. NEW ASTRASAL
2. NEW ADA COMPATIBLE THRESHOLD
3. NEW COORDINATOR
4. NEW WEATHER SEALS
3/8" = 1'-0"6 VINYL GATE ELEVATION
3/8" = 1'-0"5 VINYL GATE PLAN
1 1/2" = 1'-0"7 NEW ENCLOSURE SECTION
1ST FL ADT
162' - 0"
A0M-MZN AUDT
172' - 8"
BSMT ADT
151' - 2"
LVL 1A ADT
160' - 0"
ROOF ADT
180' - 6"
NEW 6" STEEL STUD WALL, 5/8" GYPSUM
BOARD, R-19 BATT INSULATION, PAINT
NEW SPIRAL
DUCT, BASE BID
A0M-MZN AUDT
172' - 8"
BSMT ADT
151' - 2"
LVL 1A ADT
160' - 0"
ROOF ADT
180' - 6"
STAGE ADT
163' - 0"
NEW 6" STEEL STUD WALL, 5/8" GYPSUM
BOARD, R-19 BATT INSULATION, PAINT
REMOVE AND
REINSTALL SCREEN
REMOVE AND
REINSTALL CURTAINS
REMOVE AND
REINSTALL CURTAINS
NEW SPIRAL DUCT, BASE BID
H
WE
AL
G
CT
TCH
A I
IN
IA
R
C
OM
M
ON
VI
OFT
STEVEN H. SHAFFER
Lic. No.012871
R E DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
12/02/2016
SECTIONS AUDITORIUM
BLDG
A 202
ASP
SS
1/8" = 1'-0"5 SECTION 5 - ADD ALT 01
1/8" = 1'-0"1 SECTION 7 - ADD ALT 01
Abbreviation Description
P PUMP
PD PRESSURE DROP, PRESSURE DIFFERENCE
PDS PRESSURE DIFFERENTIAL SWITCH
PERF PERFORATED
PF PREFILTER
PH PHASE (ELECTRIC)
PHC PREHEAT COIL
POS POSITIVE, POSITION
PPM PARTS PER MILLION
PRESS PRESSURE
PSI(A, G) POUNDS PER SQUARE INCH (ABSOLUTE, GAUGE)
PVC POLYVINYL CHLORIDE
R RISE, RADIUS, REFRIGERANT SENSOR
RA RETURN AIR
RAD RADIATOR
RCP REFLECTED CEILING PLAN
REQD REQUIRED
RF RETURN OR RELIEF AIR FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RLA RATED LOAD AMPS
RM ROOM
RPM REVOLUTIONS PER MINUTE
RV RELIEF VALVE
SA SUPPLY AIR
SCH SCHEDULE
SD SMOKE DAMPER, SUPPLY DIFFUSER
SDET SMOKE DETECTOR
SENS SENSIBLE (HEAT)
SF SUPPLY AIR FAN, SQUARE FEET, SAFETY FACTOR
SG SPECIFIC GRAVITY, SUPPLY GRILLE
SHR SENSIBLE HEAT RATIO
SM SHEET METAL
SP STATIC PRESSURE
SPEC SPECIFICATIONS
SPS STATIC PRESSURE SENSOR
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
SV SUPPLY AIR VALVE OR TERMINAL UNIT
T THERMOSTAT, TEMPERATURE SENSOR
TA TRANSFER AIR, THROW AWAY
TAB TESTING AND BALANCING
TAV THERMOSTATIC AIR VENT
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE, TEMPORARY
TG TRANSFER GRILLE
TO TRANSFER OPENING
TOD TOP OF DUCT
TOP TOP OF PIPE
TOS TOP OF STEEL OR SLAB
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UNOCC UNOCCUPIED
V VOLT, VALVE, VENT
VAR VARI(ABLE, ES)
VD VOLUME DAMPER (MANUAL)
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VOL VOLUME
W/ WITH
W/O WITHOUT
W WATT, WIDTH
WBT WET BULB TEMPERATURE
WG WATER GAUGE
WMS WIRE MESH SCREEN
WPD WATER PRESSURE DROP
Abbreviation Description
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FPS FEET PER SECOND
FTR FINNED TUBE RADIATION
FRPM FAN RPM
FS FLOW SWITCH
FSD COMBINATION FIRE/SMOKE DAMPER
FT FEET, FLASH TANK
FVEL FACE VELOCITY
FZ FREEZESTAT
G GAS
GA GAUGE, GAGE
GAL GALLONS
GALV GALVANIZED
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRAINS (OF MOISTURE)
GWB GYPSUM WALL BOARD
HC HEATING COIL
HD HEAD
HOA HAND OFF AUTO
HORIZ HORIZONTAL
HP HORSEPOWER, HEAT PUMP
HPC HIGH PRESSURE STEAM CONDENSATE RETURN
HPS HIGH PRESSURE STEAM (ABOVE 15 PSIG)
HT HEIGHT
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HZ HERTZ
ID INSIDE DIAMETER
IN INCHES
INCL INCLUD (E, ES, ING)
INWC INCHES WATER COLUMN
KW KILOWATT
KWH KILOWATT HOUR
L LOW
LAT LEAVING AIR TEMPERATURE, LATENT (HEAT)
LBS POUNDS
LD LINEAR DIFFUSER
LF LINEAR FOOT
LG LENGTH, LONG
LRA LOCKED ROTOR AMPS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MB MIXING BOX
MBH ONE THOUSAND BRITISH THERMAL UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MOD MOTOR OPERATED DAMPER
MOV MOTOR OPERATED VALVE
MS MOTOR STARTER
M/S METERS PER SECOND
MU MAKE UP WATER
MV MANUAL AIR VENT
N/A NOT APPLICABLE
NC NOISE CRITERIA, NORMALLY CLOSED (I.E. FAIL CLOSED)
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NUMBER, NORMALLY OPEN (I.E. FAIL OPEN)
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OAT OUTSIDE AIR TEMPERATURE
OBD OPPOSED BLADE DAMPER
OCC OCCUP(IED, ANCY)
OD OUTSIDE DIAMETER
OED OPEN ENDED DUCT WITH WIRE MESH SCREEN
OPNG OPENING
OS&Y OUTSIDE SCREW AND YOKE
OV OUTLET VELOCITY
Abbreviation Description
ACC AIR COOLED CHILLER
ACU AIR COOLED CONDENSING UNIT
AD ACCESS DOOR
ADJ ADJUSTABLE
AF AIR FILTER, AIR FOIL
AFF ABOVE FINISHED FLOOR
AFM AIR FLOW MEASURING DEVICE
AHJ AUTHORITY HAVING JURISDICTION AIR HANDLING UNIT
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
AS AIR SEPARATOR
ATV ATMOSPHERIC VENT
AV AUTOMATIC AIR VENT
AVG AVERAGE
BAS BUILDING AUTOMATION SYSTEM
BD BELT DRIVE
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER, BOILER HORSEPOWER
BI BACKWARD INCLINE
BLDG BUILDING
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTUH BRITISH THERMAL UNITS PER HOUR
C/W COMPLETE WITH
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCW COUNTERCLOCKWISE
CD CONDENSATE DRAIN, CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
ACH CHILLER
CHWR CHILLED WATER RETURN (TO CHILLER)
CHWS CHILLED WATER SUPPLY (FROM CHILLER)
CLG COOLING, CEILING
CO CLEAN OUT, CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENS(ATE, ER, ING, ATION)
CONT CONTIN(UED, UES, UOUS, UATION)
CONV CONVECTOR
CUH CABINET UNIT HEATER
CW COLD WATER, CLOCKWISE
D DROP, DRAIN
DB DECIBELS, DRY BULB
DBT DRY BULB TEMPERATURE
DD DIRECT DRIVE
DDC DIRECT DIGITAL CONTROL
DG DOOR GRILLE
DIA DIAMETER
DN DOWN
DPT DEW POINT TEMPERATURE
DS DUCT SILENCER
DWG DRAWING
EA EXHAUST AIR, EACH
EAT ENTERING AIR TEMPERATURE
EBB ELECTRIC BASEBOARD
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EFT ENTERING FLUID TEMPERATURE
EG EXHAUST GRILLE
EHC ELECTRIC HEATING COIL
EL ELEVATION
EMER EMERGENCY
EOA EMERGENCY OUTSIDE AIR
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EV EXHAUST AIR VALVE OR TERMINAL UNIT
EVAP EVAPORAT(E, ING, ED, OR)
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
°F DEGREES FAHRENHEIT
F FAN
FA FREE AREA, FACE AREA
FC FLEXIBLE CONNECTION, FORWARD CURVED
FCV FLOW CONTROL VALVE
FD FIRE DAMPER, FLOOR DRAIN
FG FIBERGLASS
FL FLOOR
FLA FULL LOAD AMPS
FLTR FILTER
FM FLOW METER
FO FLAT OVAL
NEW RETURN PIPING
EXISTING RETURN PIPING TO REMAIN
EXISTING RETURN PIPING TO BE REMOVED
EXISTING SUPPLY PIPING TO REMAIN
E SERVICE
EXISTING SUPPLY PIPING TO BE REMOVED
NEW SUPPLY PIPING
FLOW DIRECTION WITHIN PIPE
SERVICE
SERVICE
PITCH: RISE (R) OR DROP (D)
E SERVICE
E SERVICE
E SERVICE
R/D
MV
THERMOMETER AND WELL
TEMPERATURE AND PRESSURE TEST PORT
MANUAL AIR VENT
STRAINER
PRESSURE GAUGE AND SHUT-OFF COCK
PUMP (SHOWN WITH FLOW FROM LEFT TO RIGHT)
TEE (SIDE)
90 DEGREE ELBOW (SIDE)
TEE TURNED DOWN
TEE TURNED UP
RISE OR DROP IN PIPE
FLANGE
ELBOW TURNED DOWN
ELBOW TURNED UP
PIPE CONTINUES
THREE WAY CONTROL VALVE
BUTTERFLY VALVE
SHUT-OFF VALVE (REFER TO SPECS FOR TYPE)
CHECK VALVE (REFER TO SPECS FOR TYPE)
GLOBE VALVE
BALL VALVE
INSERTION TYPE FLOW METER
FM
FLOW SWITCH
FS
UNION
AIR SEPARATORAS
AV
AUTOMATIC AIR VENT
CALIBRATED BALANCING VALVE
CAP
BLIND FLANGE
CONCENTRIC REDUCER
OR
ECCENTRIC REDUCER
FLAT ON BOTTOM OR
FLAT ON TOP
THERMOWELL
UNDERCUT DOOR (3/4" UNO)
UC
DG
DOOR GRILLE
RETURN GRILLE OR EXHAUST GRILLE WITH TAG
(TAG INCLUDES DIFFUSER TYPE,
CFM, AND QUANTITY)
CFM, AND QUANTITY)
(TAG INCLUDES GRILLE TYPE,
EG-1
200 CFM
200 CFM
SUPPLY DIFFUSER WITH TAG
RETURN GRILLE WITH ACOUSTICALLY LINED BOOT
SIDE WALL GRILLE
ACCESS DOOR IN DUCTWORK
SD-1
FIRE DAMPER (FD),
SMOKE DAMPER (SD), OR
COMBINATION FIRE SMOKE DAMPER (FSD)
WITH ACCESS DOOR
FLEXIBLE CONNECTOR
FLEXIBLE DUCTWORK
RECTANGULAR DUCTWORK (WIDTH x DEPTH)
ROUND DUCTWORK (SIZE, DIAMETER)
FLAT OVAL DUCTWORK (WIDTH x DEPTH)
ACOUSTICALLY LINED DUCTWORK
FD
SD
FSD
SD
FD
FSD
10x8 FO
8Ø
10x8
(TYP ....)
(TYP ....)
10x8 FO
8Ø
10x8
AD
AD
EXHAUST / RETURN AIRFLOW
SUPPLY AIRFLOW
OPEN END DUCT W/ WMS
EXISTING DUCTWORK TO BE REMOVED
EXISTING DUCTWORK TO REMAIN
SUPPLY DUCT DN
SUPPLY DUCT UP
DOUBLE LINESINGLE LINE
RETURN DUCT DN
RETURN DUCT UP
SUPPLY DUCT UP
SUPPLY DUCT DN
RETURN DUCT UP
RETURN DUCT DN
NEW DUCTWORK
GENERAL NOTES, LEGENDS AND DETAILS ARE APPLICABLE TO ALL M-SERIES DRAWINGS.
THE WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS, CODES AND STANDARDS, INCLUDING BUT NOT LIMITED TO LOCAL, STATE AND FEDERAL REGULATIONS, CODES AND STANDARDS.
THE WORK AND EQUIPMENT SHOWN IS DIAGRAMMATIC AND IN ITS APPROXIMATE LOCATION. DETERMINE AND COORDINATE
EXACT LOCATIONS OF SYSTEMS, EQUIPMENT AND COMPONENTS IN THE FIELD.
ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS SPECIFICALLY INDICATED OTHERWISE.
COORDINATE WORK OF THIS DIVISION WITH THAT OF ALL OTHER DIVISIONS.
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS PERTAINING TO THESE DOCUMENTS.
PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND STEEL PLATFORMS
REQUIRED FOR WORK OF THIS DIVISION.
ALL FLOOR MOUNTED MECHANICAL EQUIPMENT SHALL HAVE A 6-INCH TALL CONCRETE HOUSEKEEPING PAD THAT EXTENDS 6-INCHES BEYOND THE EQUIPMENT FOOTPRINT ON ALL SIDES. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
DETAILS.
COORDINATE ROOF AND EXTERIOR WALL PENETRATIONS WITH WORK OF OTHER DIVISIONS AND WITH PROJECT FLASHING
REQUIREMENTS.
EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY. DETAILED DESCRIPTIONS AND DIMENSIONS ARE PROVIDED
IN THE SPECIFICATIONS AND ARCHITECTURAL DRAWINGS.
RUN DUCTS AND PIPING CONCEALED, UNLESS NOTED OTHERWISE. ALL DUCTWORK SHALL BE INSTALLED AS CLOSE AS
POSSIBLE TO UNDERSIDE OF BEAMS AND JOISTS.
OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS AND TRANSITIONS) AROUND OBSTRUCTIONS SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER’S CERTIFIED DRAWINGS AND INSTALLATION INSTRUCTIONS.
VERIFY AND PROVIDE DUCT TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONS
BEFORE FABRICATION.
ACCESS PANELS SHALL BE PROVIDED, WHERE REQUIRED, TO SERVICE DAMPERS, HEATERS, VALVES, MOTORS, AND ALL
CONCEALED MECHANICAL EQUIPMENT.
SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE AND PROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS OF SUPPORT.
SHEET METAL DUCTWORK AND FITTINGS SHALL BE SECURELY INSTALLED, STEEL ANGLE REINFORCED AND SUPPORTED IN
ACCORDANCE WITH THE LATEST SMACNA STANDARDS.
REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION, SEAL AND LEAKAGE CLASSES.
PROVIDE ACCESS DOORS IN THE DUCTWORK NEAR FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS OR
ANY OTHER DEVICE REQUIRING DUCT ACCESS FOR ROUTINE INSPECTION AND MAINTENANCE.
PROVIDE FIRE DAMPERS WHERE SHOWN ON THE DRAWINGS AND WHERE REQUIRED BY CODE FOR DUCTS THAT
PENETRATE RATED CONSTRUCTION.
ALL FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH SMACNA AND THEIR UL LISTING.
DUCT SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM UNDER DIVISIONS 26 AND 28.
UNDER DIVISION 23, MOUNT THE DETECTORS IN THE DUCTWORK AND WIRE THE DETECTORS TO THE BAS AND FAN
STARTERS FOR SHUTDOWN.
INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE SIZE TO ACCOMMODATE DUCT LINER WHERE LINER
IS PROVIDED.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF AIR TERMINAL DEVICES.
DIFFUSER SIZES SHOWN ARE NECK SIZES. REGISTER AND GRILLE SIZES ARE NOMINAL.
BRANCH DUCT SIZES TO INDIVIDUAL AIR TERMINAL DEVICES SHALL BE THE SAME SIZE AS THE NECK OF THE AIR TERMINAL
DEVICE UNLESS NOTED OTHERWISE. SEE AIR TERMINAL DEVICE SCHEDULE FOR NECK SIZE.
PROVIDE VOLUME DAMPERS OR OTHER APPROVED BALANCING DEVICES AT ALL DUCT BRANCH CONNECTIONS AND IN RUN- OUTS TO INDIVIDUAL AIR TERMINAL DEVICES. WHERE CEILING CONSTRUCTION DOES NOT ALLOW DIRECT ACCESS FOR BALANCING, PROVIDE REMOTE OPERATED BALANCING DAMPERS ADJUSTABLE FROM AIR TERMINAL DEVICE FACE.
THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH AN AIR TERMINAL DEVICE SHALL BE PAINTED FLAT BLACK.
ALL RETURN, TRANSFER AND EXHAUST AIR OPENINGS ABOVE THE CEILING SHALL BE PROVIDED WITH A 1/2-INCH WIRE
MESH SCREEN.
INSTALL THERMOSTATS 48 INCHES ABOVE THE FINISHED FLOOR OR AS DIRECTED OTHERWISE HEREIN. COORDINATE
EXACT MOUNTING LOCATION WITH THE ARCHITECT.
ALL CONTROL AND BAS WIRING SHALL COMPLY WITH NEC AND DIVISION 26.
PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS
ON PIPING.
PROVIDE VENTS AT ALL HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT ALL LOW POINTS.
PROVIDE AT LEAST THREE ELBOW SWING FOR PIPING TAKE-OFFS TO RISERS AND EQUIPMENT.
ALL CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH “P”-TRAP, AND CONNECTED TO
PLUMBING SYSTEM AS INDICATED.
ALL EXISTING BUILDING CONSTRUCTION, DUCTWORK, PIPING, CONDUITS, ETC. ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ROUTING THE NEW DUCTWORK AND PIPING WITH ALL NECESSARY DROPS, OFFSETS, RISERS AND TRANSITIONS AS REQUIRED FOR A COMPLETE INSTALLATION.
EQUIPMENT SHUTDOWNS OR CONNECTIONS TO EXISTING EQUIPMENT SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF
THE OWNER.
NEW WORK SHALL NOT ENCROACH UPON SERVICE ACCESS AND CLEARANCES FOR EXISTING EQUIPMENT.
THE CONTRACTOR SHALL CONFIRM THE SIZE OF CONNECTIONS TO EXISTING EQUIPMENT, DUCTWORK AND PIPING IN THE
FIELD PRIOR TO FABRICATION.
PROVIDE TEMPORARY PARTITIONS FOR DUST CONTROL AND TO SEPARATE WORK AREAS FROM OCCUPIED AREAS.
PROVIDE DUST PROTECTION FOR ALL NEW AND EXISTING TO REMAIN DUCTWORK AND EQUIPMENT.
EXISTING DUCTWORK AND AIR HANDLING EQUIPMENT SHALL NOT BE USED TO SERVE THE WORK AREA DURING CONSTRUCTION WITHOUT WRITTEN PERMISSION FROM THE OWNER. IF THEIR USE IS ALLOWED, THE CONTRACTOR SHALL PROVIDE CONSTRUCTION FILTERS AT ALL RETURN AND EXHAUST AIR OPENINGS AND WITHIN AIR HANDLING EQUIPMENT.
AT COMPLETION OF WORK, ALL TEMPORARY FILTERS SHALL BE REMOVED AND NEW FILTERS INSTALLED.
ALL EXISTING SMOKE DETECTORS WITHIN THE WORK AREA SHALL BE PROTECTED FROM DUST, ETC. BY ENCAPSULATION IN A PLASTIC BAG DURING AT THE START OF THE WORK DAY AND UNCOVERED AT THE END OF EACH WORK DAY.
ALL MEANS OF EGRESS SHALL BE MAINTAINED FREE AND CLEAR OF OBSTRUCTIONS AND EXISTING LIFE SAFETY SYSTEMS
SHALL REMAIN OPERATIONAL AT ALL TIMES.
DUCTWORK, PIPING, AND EQUIPMENT INDICATED TO BE REMOVED, SHALL BE REMOVED IN THEIR ENTIRETY, INCLUDING ALL
ASSOCIATED WIRING AND SUPPORTS.
ALL MATERIAL INDICATED TO BE REMOVED, INCLUDING LIQUIDS, SHALL BECOME THE PROPERTY OF THE CONTRACTOR UNLESS OTHERWISE NOTED, AND SHALL BE REMOVED FROM THE SITE. REMOVALS AND DISPOSAL SHALL COMPLY WITH
THE RULES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
COORDINATE REMOVALS WITH ALL OTHER TRADES AND WITH ANY REMEDIATION ACTIVITIES.
REMOVE PIPING AND DUCTWORK BACK TO THE POINTS INDICATED AND CAP. WHERE NO SPECIFIC POINT IS INDICATED, REMOVE BACK TO THE NEAREST MAIN DUCT OR PIPE.
WHERE REMOVALS EXTEND THROUGH THE ROOF OR EXTERIOR WALL, PROVIDE TEMPORARY WEATHER PROTECTION OF
THE OPENING AFTER REMOVAL.
PROTECT ITEMS IDENTIFIED FOR SALVAGE FROM WEATHER AND PHYSICAL DAMAGE. COORDINATE DELIVERY OF THESE
ITEMS TO THE OWNER.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
M501
DETAIL NUMBER
CONNECT TO EXISTING
POINT OF DISCONNECTION
DRAWING NUMBER WHERE
DETAIL OR ENLARGED PLAN
IS DRAWN
DRAWING NUMBER WHERE
SECTION IS DRAWN
DIRECTION OF VIEW
KEYED NOTE TAG1
REVISION NUMBER1
M301
FLOOR ELEVATION
SECTION NUMBER
XXX - 101
UNIT NUMBER
MECHANICAL
EQUIPMENT TAG
XXX - 101OR:
M 0 01 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, & SITE PLANS
MD 1 01 FLOOR PLANS, DEMOLITION
HVAC DISCIPLINE PREFIX
M 4 01 RISER DIAGRAMS
M 3 01 LARGE SCALE PLANS & SECTIONS
M 5 01 DETAILS & MISCELLANEOUS
M 1 01 FLOOR PLANS, DUCTWORK
M 6 01 SCHEDULES
M 2 01 FLOOR PLANS, PIPING
GROUP DESIGNATION
DRAWING NUMBER
M 7 01 CONTROL DIAGRAM
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
HVAC LEGEND AND
GENERAL NOTES
M001
NB
RR
RR
NTS1 HVAC ABBREVIATIONS
NTS5
PIPE FITTINGS, SPECIALTIES AND
VALVES
NTS3 SHEET METAL
NTS6 GENERAL NOTES
NTS4 GENERAL SYMBOLS
NTS2 DRAWING GROUP ORGANIZATION
UPDN
UP
DN
DN
M302
M301
T
C-2
C-3
C-1
VD
VD
VD
12x5 SA
14x5 SA
16x5 SA
26x5 SA
36x5 SA
36x6 SA
36x6 SA
26x5 SA
26x5 SA
18x5 SA
26x5 SA
CD-3
550 CFM
14"Ø NECK CD-2
335 CFM
10"Ø NECK
CD-3
550 CFM
14"Ø NECK
CD-3
550 CFM
14"Ø NECK
CD-4
742 CFM
16"Ø NECK
CD-3
500 CFM
14"Ø NECK
36x6 SA
CD-1
215 CFM
8"Ø NECK
CD-2
325 CFM
10"Ø NECK
CD-1
240 CFM
8"Ø NECK
CD-2
300 CFM
10"Ø NECK
12x5 SA
36x6 SA DN
ETR
M302
CD-4
742 CFM
16"Ø NECK 36x5 SA
36x6 SA
ACC-1
60x24 OA BIRDSCREEN
NEW END CAP
RG, 15x80
500 CFM
ETR
36x6 SA DN
ETR
78x6 SA DN
ETR
78x6 SA
78x6 SA
ETR
C-3
C-2
C-3
C-3
C-3
T T1 2
T
TYP. OF 2
T
H
VD
VD VD
VD
VD
VD
VD VD
VD
VD
VD
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
DEC. 2, 2016
HVAC PLAN - ADMIN
BASEMENT & FIRST FLOOR
M101
NB
RR
RR
1/8" = 1'-0"1 HVAC PLAN - ADMIN BASEMENT
1/8" = 1'-0"2 HVAC PLAN - ADMIN FIRST FLOOR
KEYED NOTES:
1 REMOVE AND CLEAN EXISTING ELECTRIC DUCT MOUNT HEATERS AND REINSTALL - REFER TO SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
2 REUSE EXISTING 36X6 SUPPLY DUCT BRANCH ABOVE CEILING. INSTALL NEW DUCTWORK AS SHOWN ABOVE CEILING.
3 CONNECT NEW DUCT WORK TO EXISTING OPEN ENDED DUCTWORK AND INSTALL NEW DUCTWORK ABOVE CEILING.
GENERAL NOTES:
1 CONTRACTOR TO REBALANCE ALL NEW AND EXISTING BRANCHES OF DUCTWORK SERVED BY THE NEW AHU-1 UNIT.
2 ALL NEW SUPPLY DUCTS TO BE LINED WITH 1" ACOUSTIC LINING. INCREASE DUCT SIZES TO GET CLEAR SIZES SHOWN.
4 NEW WIRELESS ELECTRONIC THERMOSTAT TO REPLACE REMOVED PNEUMATIC THERMOSTAT.
5 NEW WIRELESS ELECTRONIC HUMIDISTAT TO REPLACE REMOVED PNEUMATIC THERMOSTAT.
UP DN
DN
DN
DN
DN
DN
DN
DN
DN UP
UP
FTR-3 FTR-4
FTR-1
FTR-1
FTR-1
FTR-1FTR-1
FTR-1
FTR-1
NEW TOTAL ENCLOSURE
LENGTH 18'-0"
NEW BLANK OFF PLATE
BEHIND EXISTING RAG
34X60
FTR-2 FTR-2
T
T
T
T
FTR-4
C-3 TYP.
OF 2
C-3 TYP.
OF 2
ETR AC-3
EXISTING SUPPLY DUCTWORK
AND ASSOCIATED DUCT
REHEAT COILS TO REMAIN.
RETURN DUCTWORK
TIE-IN POINT IN VERT RISER
36Ø RA
32x32 RA
EXPOSED SPIRAL DUCTWORK AND GRILLES TO BE
PAINTED IN COLOR APPROVED BY OWNER
FTR-5FTR-8
FTR-7
FTR-6
RG-1, 36x18
1,100 CFM
TYP OF 6
X - ELECTRICAL PANEL
TYP. OF 4
T
RH-12
RH-13 RH-14
RH-15
RH-16
FTR-1 FTR-5T
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
DEC. 2, 2016
HVAC PLAN - AUDITORIUM
FLOOR PLANS
M102
NB
RR
RR
1/8" = 1'-0"2 AUDITORIUM - FIRST FLOOR
1/8" = 1'-0"3 AUDITORIUM MEZZANINE
KEYED NOTES:
1 CONNECT NEW DUCTWORK TO EXISTING 50x18 RETURN VERTICAL RISER MAIN.
1/8" = 1'-0"1 AUDITORIUM - BASEMENT
2 NEW WIRELESS ELECTRONIC THERMOSTAT TO REPLACE REMOVED PNEUMATIC THERMOSTAT.
UPDN
UP
DN
DN
2"
CHWR
CHWP-1
4" CONCRETE PAD
4"
CHWS
4"
CHWR
SHOT FEEDER
EXPANSION TANK
ET-1
2" CHWS
4" CHWR
HEADER
3/4" MAKE UP
WATER
M302
M302
ACU
ETR
AHU-11
4NEW
BAS PANEL
ETR 3" CHILLED WATER SUPPLY
AND RETURN TO AC-3 IN AUDITORIUM
BUILDING
ACC-1
4"
CHWS
4"
CHWR
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
1/8" = 1'-0" 0 4 12
SCALE OF FEET
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
8 164
DEC. 2, 2016
PIPING PLAN - ADMIN
BASEMENT & FIRST FLOOR
M201
NB
RR
RR
1/8" = 1'-0"1 PIPING PLAN - ADMIN BASEMENT
1/8" = 1'-0"2 PIPING PLAN - ADMIN FIRST FLOOR
KEYED NOTES:
1 CONDENSATE DRAIN FROM AHU-1 ROUTE TO NEAREST EXTG. FLOOR DRAIN.
2 DRILLING NEW CORE HOLES IN EXT. WALLS WITH LINK SEALS AT EACH OPENING.
3 EXPOSED CHW PIPES TO BE HEAT TRACED.
4 CHW PIPES ARE BURIED. SEE SPECS FOR DETAILS.
M302
M302
40x14 EA
E-EAL, 48x18
6,500 CFM
ETR
70x14 EA
SAR-2, 18x12
500 CFM
22x16 RA
36x29 RA
34x20 SA
7x15 SA
38x14 SA
40x28 RA
60x24 OA 24x80 OA
14x70 EA
14x15 SA
1 VFD
36x29 RA
CONCRETE
FOUNDATION
14x82 SA
2 2
C-2 ACU
ETR
NEW
BAS PANEL
X-ELECT
DISTRIBUTION
3 3
VD
VD
VD
VD
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
ENLARGED PLANS
M301
NB
RR
RR
1/4" = 1'-0"1 MECHANICAL ROOM ENLARGED PLAN
1 REMOVE AND CLEAN EXISTING ELECTRIC DUCT HEATERS AND REINSTALL - REFER TO SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES:
1. INSTALL NEW BRANCH VCD AT CONNECTION TO EXISTING DUCTS.
2 EXISTING TO REMAIN DUCT REHEAT COIL.
KEYED NOTES:
3 DUCT WITH 1" LINING. OUTER DUCT DIMENSIONS SHOWN.
M-ADMIN
BASEMENT -MECH
RM
156' - 2"
M-FIRST FLOOR
167' - 0"
14x70 EA
40x14 EA
24x80 OA
14x70 OA
36x29 RA
14x38 SA
14x82 SA
M302
M-A01-LVL 2
177' - 8"
PROVIDE
BIRDSCREEN
24x60 OA
15x7 SA
26x38 RA
4"
CHWR
2 1/2"
CHWR
2"
CHWR
3"
CHWR
M-HVAC PLAN -
ADMIN BASEMENT
156' - 2"
M-FIRST FLOOR
167' - 0"
M302
29x36 RA
82x14 SA
40x28 RA
28x40 RA
14x38 SA
38x26 RA
AHU-1
CHWS
CHWR
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
SECTIONS -
ADMINISTRATION
M302
NB
RR
RR
1/2" = 1'-0"1 AHU-1 SECTION 1
1/2" = 1'-0"2 AHU-1 SECTION 2
KEYED NOTES:
1 CUT OPENING IN EXTG. GRATING FOR NEW OA DUCT.
MECH ROOM FLOOR
ET-1
ME
CH
. R
OO
M W
AL
L
AS-1
ESD
CHWP-1
GRADE
4" CHWS ACC-1
100 TON
6"
3/4"
SYSTEM STRAINER,
ORIVAL# ORM, RATED FOR
1.0 PSIG WPD AT 350 GPM
SINGLE WALL WELDED
SCH 40 STEEL PIPE
INSIDE BUILDING
AIR-COOLED CHILLER
W12x15 GALVANIZED STEEL BEAM, ANCHOR TO CONCRETE PAD
TDV
SINGLE WALL INSULATED SCH 40 WELDED
STEEL PIPE WITH 3" OF CLOSED CELL FOAM
INSULATION, COVER WITH METAL JACKET.
EXPOSED PIPES TO BE HEAT TRACED.
3/4" MAKE-UP WATER
HIGH CAPACITY AIR VENT
NEW CONCRETE PAD
PITCH 1/8" PER FT
4" CHWR
2-1/2" TO AHU-1
3" TO EXISTING 3" BRANCH LINES2" TO EXISTING
2" BRANCH LINES
1"1"
5.O GAL SHOT FEEDER
NO
CONCRETE PAD
ANCHOR CHILLER LEG TO STEEL WITH 1/2" GALVANIZED BOLTS
(TYPICAL FOR EACH LEG SUPPORT)
4" CHWS
4" CHWS
4" CHWR
AHU-1
BASEMENT
FIRST FLOOR
28x813x8
SUPPLY DUCT
(425 CFM)
25x6
SUPPLY DUCT
(530 CFM)
32x18
SUPPLY DUCT
(1985 CFM)
36x12
24x6
24x6
SUPPLY DUCT
(540 CFM)
SUPPLY DUCT
(540 CFM)
80x12
20x4 20x4
SUPPLY DUCT
(250 CFM)
SUPPLY DUCT
(250 CFM)
RETURN DUCT
(255 CFM)
34x27
6x14
24x4
14x6
14x6
24x4
14x6
RETURN DUCT
(250 CFM)
RETURN DUCT
(255 CFM)
RETURN DUCT
(255 CFM)
RETURN DUCT
(250 CFM)
RETURN DUCT
(255 CFM)
60x24
OUTSIDE AIR DUCT
6500 MAX CFM
500 MIN CFM
34x27 38x26
RETURN DUCT
(4000 CFM)
E-EAL
6000 MAX CFM
450 MIN CFM
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
FLOW DIAGRAMS
M401
NB
RR
RR
NO SCALE1 CHILLED WATER FLOW DIAGRAM
1/4" = 1'-0"2 AIR FLOW DIAGRAM
BUTTERFLY VALVE
UNION
VENT
DIRECTION OF FLOW
BALANCING VALVE
MODULATING THREE-WAY VALVE
COOLING COIL
THERMOMETER
DRAIN VALVE
STRAINER
6"
12"
UNEXCAVATED EARTH
FLOWABLE BACK FILL MATERIAL
EXISTING TURF
HDPE JACKET PIPE (PRE-INSULATED PIPING SYSTEM)
STEEL CARRIER PIPE(PRE-INSULATED PIPING SYSTEM)
CONTINUOUS PIPE MARKER TAPE BELOW SOD
NEW SOD/TURF TO MATCH EXISTING
CUT EXISTING SOD/TURF
SAND BACKFILL, MIN 6" ABOVE PIPE JACKET
ELECTRICAL CONDUIT, KEEP CONDUIT 12" AWAY FROM PIPING
3 8 7
8 3
1 2
4 5
STEEL WALL SLEEVE
HDPE JACKET PIPE
STEEL CARRIER PIPE
LINK SEAL
FOUNDATION WALL
INSULATION
STEEL PIPE INSIDE BUILDING
MASTIC END SEAL
1 5
EXISTING CONCRETE PAD
DROP IN 1 / 2" ZINC PLATED CONCRETE ANCHOR
BOLT, GSA FF-325, TYPE I, WITH EXPANDER PLUG
4" DEEP HOLE, SEAL WITH EPOXY
W FLANGE/EQUIPMENT ANCHOR TAB, CHILLER AND
BUFFER TANK.
CHWR CHWR
BUTTERFLY VALVE
THERMOMETER
PUMP
PRESSURE GAUGE
END SUCTION DIFFUSER
TRIPLE DUTY VALVE
THREADED ROD
FLOOR
24"
AV
STRAINER
AUTOMATIC AIR VENT (TYP)
DRAIN VALVE W/ HOSE END (TYP)
PRESSURE GAUGE (TYP)
AIR SEPARATOR
FROM HYDRONIC SYSTEM
MAKE-UP WATER PIPING
PRESSURIZED EXPANSION TANK
HOUSEKEEPING PAD
FLOOR
SHUT-OFF VALVE (TYP)
UNION (TYP)
PRESSURE REGULATING VALVE
THROTTLING BYPASS VALVE
TO SYSTEM PUMP SUCTION
SHUT-OFF VALVE W/ LOCKING HANDLE
SEE NOTE 1
SEE NOTE 2
SEE NOTE 3
NOTES:
1. CONNECT TO SIDE OF MAIN TO PREVENT AIR OR DEBRIS FROM ENTERING PIPE TO TANK. TOP OR BOTTOM CONNECTION NOT PERMITED.
2. LOCK VALVE IN OPEN POSITION.
3. PROVIDE ANTI-THERMOSYPHON LOOP ON SYSTEMS WITH > 150°F OPERATING TEMPERATURE ONLY.
1"
12"
SUPPORT FROM STRUCTURE
MAKE-UP SIZE
TOTAL SYSTEM
FLOW (GPM)
MAKE-UP LINE
SIZE (INCHES)
PRU MINIMUM
FLOW (GPM)
UP TO 500
500-1200 1200-3000 3001-5000 5001-12000
3/4
1 1/4 1 1/2
SEE NOTE 4
4. FOR SYSTEMS CONTAINING GLYCOL OMIT MAKE-UP ASSEMBLY AND CONNECT GLYCOL FEED AT THIS LOCATION.
6 7 8 9
AV
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
DETAILS
M501
NB
RR
RR
NO SCALE1 CHILLED WATER COIL DETAIL
NO SCALE4
CHILLED WATER PIPING TRENCH
DETAIL
NO SCALE5
CHILLED WATER PIPING WALL
PENETRATION DETAIL
NO SCALE2 CHILLER ANCHOR DETAIL
NO SCALE3 CHILLED WATER PUMP DETAIL
NO SCALE6
AIR SEPARATOR / EXPANSION TANK
PIPING DETAIL
AIR COOLED CHILLER SCHEDULE
PDEWT
CAPACITY EVAPORATOR
LOCATIONTAG FOULINGFLOW LWT
(°F)
(TONS)
IPLV @
AHRI
(GPM) (°F) (FT) FACTOR MCAHERTZVOLTS PHASE MOCP
ELECTRICAL
REMARKSFLUID
TYPE
FLUID
ELECTRICAL DATA
TEMP.
( F)
FLUID
TAG
PUMP SCHEDULE
SERVICE TYPE FLOW HEAD RPM BASIS OF DESIGNVOLTS/ REMARKS
(GPM) (FT.)
CHILLED WATER SYSTEM VERTICAL INLINE 247 85 1750 44-85CHP-1 208/3 TACO KS301110
MOTOR
HP PHASE MFG. AND MODEL
3X310
(IN. X IN.)(IN.)
DISCHARGEDIA.
IMPELLER SUCTION X
ACC-1 OUTSIDE 100 16.3 EER 247 57 47 10.0 0.0001 WATER 208 3 60 441 500
KW
115.7 DAIKIN# AGZ100
FURNISH WITH LON/ BACNET CARD, COORDINATE WITH DDC CONTROLS CONTRACTOR
FURNISH EACH PUMP WITH END SUCTION DIFFUSER AND TRIPLE DUTY VALVE.
WATER
AMBIENT
TEMP.
NUMBER OF
COMPRESSORS
(°F)
NUMBER OF
CONDENSOR FANS
6 147"L x 88"W x 98" H, 4800 LBS
TYPE
FLUID
UNIT DIMENSIONS
VOLUME
( GAL)
ACCEPTANCE
TAG
EXPANSION TANK
SERVICE UNIT LOCATION
MOUNTING
PRESSURE BASIS OF DESIGN REMARKS
(PSIG)
CHILLED WATER SYSTEM MECH. ROOM FLOOR 40 37ET-1 460/3 TACO CA 14020" DIA., 46" H
INCHES MFG. AND MODEL
37125
(GAL.)(PSIG)
VOLUMESETTING
RELIEF VALVE TANK
WATER
TANK
MIN. FILL
TYPE
FLUID
PIPE CONNECTION
TAG
AIR SEPARATOR
SERVICE UNIT LOCATION PD BASIS OF DESIGN REMARKS
(FT)
CHILLED WATER SYSTEM MECH. ROOM 2.5AS-1 TACO ACT-66
INCHES MFG. AND MODEL
WATER
MAX
MAX.
(GPM)
AIR SEPARATOR WITH STRAINER AND DRAIN VALVE
SIZE
AIR HANDLER SCHEDULE
WHEEL TYPEAREATAG
SIZE (IN.) VOLTS PHASE
ELECTRICAL
REMARKS
AHU-1 ADMIN. 15.75" FC 208 3 DAIKIN MODEL CAH014GDGM
1. FURNISH WITH VFDs (FOR BALANCING) COMPATIBLE WITH CONTROLS, COORDINATE WITH DDC CONTROLS CONTRACTOR AND TAB CONTRACTOR.
2. MAXIMUM DISCHARGE SOUND POWER NOT TO EXCEED NC 65. MAXIMUM RADIATED SOUND POWER NOT TO EXCEED NC 55.
SUPPLY FAN
SERVED
OA
CFM
FAN SPEED
RPM
TOTAL
6,770
CFM
ESP
1.25
(IN. WG)
TOTAL SP
3.10
(IN. WG)
BHP
TOTAL
5.1
HP
(2) 3.0
WHEEL TYPE
SIZE (IN.)
15.75"
RETURN FAN
FAN SPEED
RPM
TOTAL
6,500
CFM
ESP
0.5
(IN. WG)
BHP
3.8
HP
5.0
COOLING COIL
MIN. FACE AREA
(SQ FT)
13.1
MAX AP
1.08
(IN. WG)
TOTAL/SENS.
(MBH)
337/222
EAT
DB (F) WB (F)
LAT
DB (F) WB (F)
83.7 69.5 53.7 53.5
GPM
66.4
WPD
FT (F) (F)
EWT LWT
11.2 47 57
WEIGHT
UNIT
(LBS)
WEIGHT
UNIT
(LBS)
PROVIDE VARIABLE SPEED DRIVE FOR WINTER OPERATION.
TAG
REGISTERS, GRILLES AND DIFFUSERS
TYPE SIZE BASIS OF DESIGN REMARKS
CEILING DIFFUSER 24x24CD-1 NAILOR RNS
NECK SIZE
(IN)
8" Ø
BLOW
PATTERN
4 WAY LAY-IN
FRAME
NONE
DAMPER
<20
MAX NC
CEILING DIFFUSER 24x24CD-2 NAILOR RNS10" Ø 4 WAY LAY-IN NONE <20
CEILING DIFFUSER 24x24CD-3 NAILOR RNS14" Ø 4 WAY LAY-IN NONE <20
RG-1
1. 45 DEGREE DEFLECTION, FIXED BLADE, 3/4" BLADE SPACING, HORIZONTAL BLADES AND STEEL CONTRUCTION
EXPOSED SPIRAL DUCT RETURN - 36x24 FIXED - YES <20 NAILOR 6145HC NOTE 1
CEILING DIFFUSER 24x24CD-4 NAILOR RNS16" Ø 4 WAY LAY-IN NONE <20
MIN. BASIS OF DESIGN
MFG. AND MODEL
BASIS OF DESIGN
MFG. AND MODEL
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
SCHEDULES
M601
NB
RR
RR
EXISTING AIR HANDLER SCHEDULE
AREATAG REMARKS
AC-2 ADMIN. ATTIC
SUPPLY FAN
SERVED
TOTAL
4,355
CFM
HP
3.0
AC-3 AUDITORIUM MEZZANINE
OUTSIDE AIR
1,000
CFM
9,550 2,750 7.5
GPM
FOR INFO ONLY
FOR INFO ONLY
CONVECTORS
TAG LOCATION
ENCLOSURE
WIDTH (IN.)
ELEMENT
LENGTH (IN.)
CAPACITY
(KW) QUANTITY BOD
C-2 ADMIN - VARIOUS 18 TBD 1.0 3 ATLANTIC F118
C-3 VARIOUS 30 TBD 2.0 10 ATLANTIC F118
NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL
ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.
2. MOUNT AT SAME HEIGHT AS EXISTING.
C-1 ADMIN - BASEMENT 15 TBD 0.5 1 ATLANTIC F118
EXISTING REHEAT COILS
TAG LOCATION
SIZE
(IN.)
CAPACITY
(KW) CFM
NO.
CIRC.
RH-1 ADMIN - BASEMENT 24X8 6.0 500 1
RH-2 ADMIN - BASEMENT 36X12 5.0 1080 1
RH-3 ADMIN - BASEMENT 48X28 21.0 3970 3
RH-4 ADMIN - BASEMENT 12X8 2.0 350 1
RH-5 ADMIN- FIRST FLOOR 24X8 3 530 1
RH-6 ADMIN - ATTIC 12X8 2 410 1
RH-7 ADMIN - ATTIC 24X12 7 900 1
RH-8 ADMIN - ATTIC 24X12 7 885 1
RH-9 ADMIN - ATTIC 24X8 3 540 1
RH-10 ADMIN - ATTIC 18X12 3.5 625 1
RH-11 ADMIN - ATTIC 24X12 3.5 755 1
RH-12 AUDITORIUM - MEZZANINE 40X42 30.0 6500 3
RH-13 AUDITORIUM - MEZZANINE 24X8 2.5 600 1
RH-14 AUDITORIUM - MEZZANINE 12X8 1.5 290 1
RH-15 AUDITORIUM - MEZZANINE 24X12 5.5 1090 1
RH-16 AUDITORIUM - MEZZANINE 27X8 2.5 590 1
SILL LINE HEATERS
TAG LOCATION
ENCLOSURE WIDTH
(IN.)
ELEMENT
LENGTH (IN.)
CAPACITY
(KW) QUANTITY BOD
FTR-1 AUDITORIUM BLDG 120 84 1.75 8 TRANE EWFB
FTR-2 STAGE AREA 132 96 3.00 2 TRANE EWFB
FTR-3 ENTRANCE SEE DWG 72 2.25 1 TRANE EWFB
FTR-4 ENTRANCE 120 84 2.50 2 TRANE EWFB
FTR-5 VARIOUS WALL TO WALL 84 1.75 2 TRANE EWFB
FTR-6 MEZZANINE 72 36 0.56 1 TRANE EWFB
FTR-7 MEZZANINE 96 60 1.25 1 TRANE EWFB
FTR-8 MEZZANINE 96 60 1.88 1 TRANE EWFB
NOTES: 1. PROVIDE SELF CONTAINED THERMOSTAT CONTROL, DISCONNECT SWITCH FOR EACH ACTIVE LENGTH, COLOR WHITE AND ALL
ASSOCIATED TRIM ACCESSORIES TO ENCLOSE ENCLOSURE.
2. MOUNT AT SAME HEIGHT AS EXISTING.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETEYP Inc.
POTOMAC
STREET NW,
WASHINGTON,
DC 20007
OF
HEATING & COOLING SYST. DESIGN
ADMIN BLDG & AUDITORIUM
VALLEY FORGE NATIONAL HISTORICAL PARK
KING OF PRUSSIA, PA 34
VAFO 201534A
DEC. 2, 2016
SCHEDULES
M602
NB
RR
RR
REFER TO SPECIFICATION SECTION 230993
FOR SEQUENCES OF OPERATION AND
ALARMS.
T
S
T
HWST
HWRT
SV
HV
BPD
ALM
FZ
HCV
AQS
SD
V-#
TSTAT
SP
S/S
SPL
SPH
OAT
SAT
SAD
OAD
DAT
DPS
CS
AFMS
FBD
EAD
D-#
HS
TS
FM
HHL
VFD
WS
ISOD
LRC
STR
OX
DPS-1 FZ-1 TS-2
V-1
D-2
TS-1
CO2D-3
D-1
AFMS-3
VFD
CS
SD-1
SD-1
ES
AFMS-2
CS
VFD
SPL
SPHD-4 ROOM SENSOR
C C
NC
CHWR
CHWS
NO
X
DPS-1 FILTER DIFFERENTIAL PRESSURE X
V-1 COOLING COIL VALVE X
FZ-1 FREEZESTAT
D-1 VENTILATION AIR DAMPER X
AI AO DI DO HI LOW
POINT ALARMSSYSTEM POINT
DDC CONTROL PANEL INPUT/OUTPUT SUMMARY
OFF/NRML
COMMENTS
D-2 RETURN AIR DAMPER X
AFMS-1 OUTSIDE AIR CFM X
AFMS-2 SUPPLY AIR FAN CFM
XSD-1 SMOKE DETECTOR
TS-2 SUPPLY AIR TEMPERATURE X
SUPPLY AIR
RETURN AIR
TS-1 ROOM TEMPERATURE X
X X
START/STOP SUPPLY FAN VFD
XSUPPLY FAN VFD FAULT
CO2 CARBON DIOXIDE SENSOR RETURN AIR DUCT X
NC
NC
OUTSIDE AIR
RELIEF AIR
D-3 RELIEF AIR DAMPER X
AFMS-3 RETURN AIR FAN CFM X
X X
X W/ CURRENT SENSOR
X
XSTART/STOP RETURN FAN VFD
XRETURN FAN VFD FAULT
X X W/ CURRENT SENSOR
X
IN-DUCT SMOKE DETECTOR
IN-DUCT
SMOKE
DETECTOR
HOT WATER SUPPLY TEMPERATURE
HOT WATER RETURN TEMPERATURE
SUPPLY AIR VALVE
HOOD EXHAUST AIR VALVE
BYPASS DAMPER
ALARM
FREEZESTAT
HEATING CONTROL VALVE
AQUASTAT
SMOKE DETECTOR (DUCT)
STATIC PRESSURE SENSOR
START/STOP
STATIC PRESSURE LOW
STATIC PRESSURE HIGH
THERMOSTAT OR TEMPERATURE SENSOR
MOUNT 48" AFF UNLESS OTHERWISE NOTED
THERMOSTAT OR TEMPERATURE SENSOR
OUTSIDE AIR DAMPER
OUTSIDE AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
SUPPLY AIR DAMPER
DISCHARGE AIR TEMPERATURE
CURRENT SENSOR
DIFFERENTIAL PRESSURE SENSOR
AIR FLOW MEASURING STATION
FACE & BYPASS DAMPER
END SWITCH
EXHAUST AIR DAMPER
CONTROL DAMPER
HUMIDITY SENSOR
TEMPERATURE SENSOR
NORMALLY CLOSEDNC
NO NORMALLY OPEN
FLOW METER
HUMIDITY HIGH LIMIT
VARIABLE FREQUENCY DRIVE
WALL SWITCH
ISOLATION DAMPER
SINGLE POINT INPUT/OUTPUT
MULTIPLE PIONTS INPUT/OUTPUT
X
FIRE ALARM CONTROL PANELFACP
FIRE ALARMFA
ZONE PRESENCE SENSORZPS
FUME HOOD SASH SENSORFHSS
FUME HOOD MONITORFHM
FIREFIGHTER SMOKE CONTROL SYSTEMFSCS
HOOD EXHAUST AIR VALVE
LAB ROOM CONTROLLER
MOTOR STARTER
OXYGEN SENSOR
LEGEND
ES
NC
D-4 SUPPLY FAN ISOLATION DAMPER X
SPH HIGH STATIC PRESSURE LIMIT
SPL LOW STATIC PRESSURE LIMIT
3-WAY
MIXING
VALVE
XX
X X
X
AFMS-1
COMMENTS
UNIT CONTROL PANEL INPUT/OUTPUT SUMMARY
SYSTEM POINT POINT
DODIAOAI
T-1 INTEGRAL THERMOSTAT X
REFER TO SPECIFICATION SECTION 230993 FOR
SEQUENCE OF OPERATION AND ALARMS
T R S
T-1
RE…