This document appears to be a set of drawings and specifications related to a federal contract opportunity. The drawings depict the details of a Variable Refrigerant Flow (VRF) HVAC system, including outdoor units, indoor units, refrigerant piping, and schedules for the equipment. The related federal contract opportunity is for HVAC inspections and maintenance services at Valley Forge National Historical Park. The contract is for a base period plus two option years. The solicitation number is 140P4224Q0122 and the contracting agency is the Department of the Interior National Park Service Northeast Region. The document provides technical specifications and design details for the VRF system that will be maintained under the resulting contract.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5/8x1 1/8" 3/8x5/8"

5/8x1 1/8"

3/8x5/8"

1/2x1 1/8"

1/4x1/2"

1/2x1 1/8"

1/4x1/2"

1/2x1 1/8"

3/8x5/8"

1/2x1 1/8"

3/8x5/8"

3/8x7/8"

3/8x5/8"

3/8x5/8"

3/8x5/8"

1/4x1/2"

1/2x1 1/8" 3/8x3/4"

BHFP22P100U

CU-1

RXYQ192TTJU

KHRP26M72TU9

VRF 1

KHRP26M72TU9

VRF 2

KHRP26M72TU9

VRF 3

KHRP26M72TU9

VRF 4

KHRP26M72TU9

VRF 5

KHRP26M72TU9

VRF 6

KHRP26A33T9

VRF 7

KHRP26A22T9

KHRP26A22T9

VRF 10

3/8x5/8"

VRF 8

1/4x1/2"

VRF 9

3/8x7/8" 1/4x1/2"

3/8x7/8"

1/4x1/2"

3/8x7/8"

1/4x1/2"

3/8x7/8"

1/4x1/2"

3/8x7/8"

1/4x1/2"

3/8x7/8"

1/4x1/2"

3/8x3/4"

1/4x1/2"

3/8x3/4"

1/4x1/2"

3/8x5/8"

1/4x1/2"

3/8x5/8"

3/8x5/8"

CU-2

RXYQ96TTJU

KHRP26A33T9

FCU 11

KHRP26A33T9

FCU 12

KHRP26A33T9

FCU 13

KHRP26A33T9

FCU 14

KHRP26A33T9

FCU 15

KHRP26A33T9

FCU 16

KHRP26A22T9

FCU 17

KHRP26A22T9

FCU 18

KHRP26A22T9

FCU 19

1/4x1/2"

FCU 20

1/4x1/2"

FCU 21

KHRP26A22T9

KHRP26A22T9

3/8x5/8"

1/4x1/2"

FCU 22

KHRP26A22T9

1/4x1/2"

FCU 23

VRV TERMINAL UNIT SCHEDULE

DESG SERVES

UNIT

AIRFLOW

[CFM]

OUTDOOR

AIR

[CFM]

COOLING

SETPOINT

(°F)

HEATING

SETPOINT

(°F)

CALCULATED

TOTAL

COOLING CAP

[MBH]

UNIT

MAX

COOLING

CAP

[MBH]

CALCULATED

HEATING

CAP

[MBH]

UNIT

MAX

HEATING

CAP

[MBH]

MAX UNIT DIMENSION

MCA MCOP V/PH/Hz MAX

NC

BASIS OF DESIGN

NOTESLENGTH

(IN)

HEIGHT

(IN)

DEPTH

(IN) MANUFACTURER MODEL

VRF-1 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6

VRF-2 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6

VRF-3 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6

VRF-4 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6

VRF-5 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6

VRF-6 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6

VRF-7 Porch 1,200 - 75 68 33.6 33.5 12.8 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6

VRF-8 Exhibit/Servant Quarters 1,200 - 75 68 36 33.5 38 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6

VRF-9 Restroom - lvl 1 245 - 75 68 7.2 7.0 5.8 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-10 Office 245 - 75 68 7.2 7.0 9.0 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-11 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-12 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-13 Bedroom 2 245 - 75 68 8.4 7.0 9.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-14 Bedroom 3 245 - 75 68 8.4 7.0 7.2 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-15 Restroom - Groom 245 - 75 68 3.6 7.0 2.3 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6

VRF-16 Stair, Upper 245 - 75 68 8.4 8.8 8.4 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-17 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-18 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-19 Restroom - lvl 3 245 - 75 68 2.4 7.0 2.7 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6

VRF-20 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-21 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-22 Restroom - Bridal 245 - 75 68 2.4 8.8 2.6 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6

VRF-23 Servant Quarters - Hall 245 - 75 68 6.0 8.8 6.9 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 4, 6

NOTES:

1. PROVIDE IN SPACE, WALL MOUNTED DIGITAL THERMOSTAT. FINAL LOCATION SHALL BE COORDINATED WITH OWNER.

2. FLOOR MOUNTED, DUCTED UNIT.

3. CONCEALED FLOOR MOUNTED, NON-DUCTED UNIT.

4. UNIT TO BE INSTALLED WITH MANUFACTURER ENCLOSURE. EXISTING ENCLOSURE SHALL BE REMOVED, PROTECTED FOR STORAGE, AND PROVIDED TO OWNER.

5. DESIGN INTENT IS THAT UNIT BE INSTALLED WITHOUT MANUFACTURER ENCLOSURE.

6. INCLUDE MANUFACTURER PROVIDED CONDENSATE PUMP.

VRV OUTDOOR UNIT SCHEDULE

DESG

EQUIPMENT

COOLING CAP

[MBH]

EQUIPMENT

HEATING CAP

[MBH]

MAX

REFRIGERANT

CHARGE [lbs]

MCA MCOP

AMBIENT

TEMP

[°F]

V/PH/HZ

BASIS OF DESIGN

NOTES

MANUFACTURER MODEL

CU-1 192.9 130.0 35.9 63.9 80 95 208/3/60 DAIKIN RXYQ192TTJU

CU-2 97.5 68.3 22.7 36.3 45 95 208/3/60 DAIKIN RXYQ96TTJU

Sheets and Views
Layout1