This document appears to be a set of drawings and specifications related to a federal contract opportunity. The drawings depict the details of a Variable Refrigerant Flow (VRF) HVAC system, including outdoor units, indoor units, refrigerant piping, and schedules for the equipment. The related federal contract opportunity is for HVAC inspections and maintenance services at Valley Forge National Historical Park. The contract is for a base period plus two option years. The solicitation number is 140P4224Q0122 and the contracting agency is the Department of the Interior National Park Service Northeast Region. The document provides technical specifications and design details for the VRF system that will be maintained under the resulting contract.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5/8x1 1/8" 3/8x5/8"
5/8x1 1/8"
3/8x5/8"
1/2x1 1/8"
1/4x1/2"
1/2x1 1/8"
1/4x1/2"
1/2x1 1/8"
3/8x5/8"
1/2x1 1/8"
3/8x5/8"
3/8x7/8"
3/8x5/8"
3/8x5/8"
3/8x5/8"
1/4x1/2"
1/2x1 1/8" 3/8x3/4"
BHFP22P100U
CU-1
RXYQ192TTJU
KHRP26M72TU9
VRF 1
KHRP26M72TU9
VRF 2
KHRP26M72TU9
VRF 3
KHRP26M72TU9
VRF 4
KHRP26M72TU9
VRF 5
KHRP26M72TU9
VRF 6
KHRP26A33T9
VRF 7
KHRP26A22T9
KHRP26A22T9
VRF 10
3/8x5/8"
VRF 8
1/4x1/2"
VRF 9
3/8x7/8" 1/4x1/2"
3/8x7/8"
1/4x1/2"
3/8x7/8"
1/4x1/2"
3/8x7/8"
1/4x1/2"
3/8x7/8"
1/4x1/2"
3/8x7/8"
1/4x1/2"
3/8x3/4"
1/4x1/2"
3/8x3/4"
1/4x1/2"
3/8x5/8"
1/4x1/2"
3/8x5/8"
3/8x5/8"
CU-2
RXYQ96TTJU
KHRP26A33T9
FCU 11
KHRP26A33T9
FCU 12
KHRP26A33T9
FCU 13
KHRP26A33T9
FCU 14
KHRP26A33T9
FCU 15
KHRP26A33T9
FCU 16
KHRP26A22T9
FCU 17
KHRP26A22T9
FCU 18
KHRP26A22T9
FCU 19
1/4x1/2"
FCU 20
1/4x1/2"
FCU 21
KHRP26A22T9
KHRP26A22T9
3/8x5/8"
1/4x1/2"
FCU 22
KHRP26A22T9
1/4x1/2"
FCU 23
VRV TERMINAL UNIT SCHEDULE
DESG SERVES
UNIT
AIRFLOW
[CFM]
OUTDOOR
AIR
[CFM]
COOLING
SETPOINT
(°F)
HEATING
SETPOINT
(°F)
CALCULATED
TOTAL
COOLING CAP
[MBH]
UNIT
MAX
COOLING
CAP
[MBH]
CALCULATED
HEATING
CAP
[MBH]
UNIT
MAX
HEATING
CAP
[MBH]
MAX UNIT DIMENSION
MCA MCOP V/PH/Hz MAX
NC
BASIS OF DESIGN
NOTESLENGTH
(IN)
HEIGHT
(IN)
DEPTH
(IN) MANUFACTURER MODEL
VRF-1 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6
VRF-2 Library 1,000 - 75 68 20.4 27.8 30 35.3 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ30TAVJUD 1, 2, 6
VRF-3 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6
VRF-4 Reception 400 - 75 68 9.0 11.1 9.3 14.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ12TAVJUD 1, 2, 6
VRF-5 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6
VRF-6 Conference/Stair 800 - 75 68 22.2 22.3 26.3 28.0 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ24TAVJUD 1, 2, 6
VRF-7 Porch 1,200 - 75 68 33.6 33.5 12.8 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6
VRF-8 Exhibit/Servant Quarters 1,200 - 75 68 36 33.5 38 41.5 17.5 45.0 21.0 4.9 15 208/1/60 30 DAIKIN FXTQ36TAVJUD 1, 2, 6
VRF-9 Restroom - lvl 1 245 - 75 68 7.2 7.0 5.8 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-10 Office 245 - 75 68 7.2 7.0 9.0 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-11 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-12 Bedroom 1 245 - 75 68 6.6 7.0 8.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-13 Bedroom 2 245 - 75 68 8.4 7.0 9.6 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-14 Bedroom 3 245 - 75 68 8.4 7.0 7.2 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-15 Restroom - Groom 245 - 75 68 3.6 7.0 2.3 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 4, 6
VRF-16 Stair, Upper 245 - 75 68 8.4 8.8 8.4 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-17 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-18 Storage 1 245 - 75 68 7.8 8.8 8.5 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-19 Restroom - lvl 3 245 - 75 68 2.4 7.0 2.7 8.8 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ07MVJU9 1, 3, 5, 6
VRF-20 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-21 Storage 2 245 - 75 68 7.8 8.8 8.7 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-22 Restroom - Bridal 245 - 75 68 2.4 8.8 2.6 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 5, 6
VRF-23 Servant Quarters - Hall 245 - 75 68 6.0 8.8 6.9 10.9 40.0 24.0 9.0 0.3 15 208/1/60 30 DAIKIN FXLQ09MVJU9 1, 3, 4, 6
NOTES:
1. PROVIDE IN SPACE, WALL MOUNTED DIGITAL THERMOSTAT. FINAL LOCATION SHALL BE COORDINATED WITH OWNER.
2. FLOOR MOUNTED, DUCTED UNIT.
3. CONCEALED FLOOR MOUNTED, NON-DUCTED UNIT.
4. UNIT TO BE INSTALLED WITH MANUFACTURER ENCLOSURE. EXISTING ENCLOSURE SHALL BE REMOVED, PROTECTED FOR STORAGE, AND PROVIDED TO OWNER.
5. DESIGN INTENT IS THAT UNIT BE INSTALLED WITHOUT MANUFACTURER ENCLOSURE.
6. INCLUDE MANUFACTURER PROVIDED CONDENSATE PUMP.
VRV OUTDOOR UNIT SCHEDULE
DESG
EQUIPMENT
COOLING CAP
[MBH]
EQUIPMENT
HEATING CAP
[MBH]
MAX
REFRIGERANT
CHARGE [lbs]
MCA MCOP
AMBIENT
TEMP
[°F]
V/PH/HZ
BASIS OF DESIGN
NOTES
MANUFACTURER MODEL
CU-1 192.9 130.0 35.9 63.9 80 95 208/3/60 DAIKIN RXYQ192TTJU
CU-2 97.5 68.3 22.7 36.3 45 95 208/3/60 DAIKIN RXYQ96TTJU