This document appears to be an amendment to a solicitation for the replacement of the main underwater high voltage cable and multiple transformer boxes that run from the mainland to the Kettle Falls district. The project will also install an improved level of emergency backup generation for critical loads at the Kettle Falls Area. The solicitation number is 140P2024R0130, and the project is being procured by the Department of the Interior National Park Service National Office. The document contains figures related to the project, but does not provide details on the required products or services, response dates, award dates, pricing terms, set asides, or other salient information. This appears to be an appendix to the solicitation rather than the full solicitation document.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared/Date: NES 12/20/23 Checked/Date: JWP 12/20/23 Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Site_Vicinity_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 01_Vicinity Map.pdf 12/20/2023 10:05 AM nathan.soule

Figure 1 Site Vicinity Map

NPS VOYA - Kettle Falls Voyageurs National Park, MN

A B

C D

E

F

G

H

I

J

K L M N

O

P & Q R & S

T

U V & WX

Y & Z

AA

BB

CC

DD

Ash River Boat Launch

Kettle Falls Historical District

Hoist BayÍ wABC

Í w

Í w

Í wÍ w

Í w

Í w

Í w

Í w

Í w

Í w

"AM

%UJ %UJ %UJ

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ %UJ %UJ

%UJ

%UJ%U

J

2 2

2 2

!î

CANADA

UNITED STATES

Legend

!î Ash River Boat Launch %UJ Junction Box "AM CT Metering Junction Box 2 2Recloser

Í w

UG Transformer

Í wABC 3UG Transformer

Approximate Existing 3-Phase Transmission Line Approximate Existing 1-Phase Transmission Line United States - Canada Border

0 4,0002,000 Feet

Prepared/Date: NES 04/02/24 Checked/Date: JWP 04/02/24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Overview_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 02_Project Overview Map.pdf 04/02/24 2:01 PM nathan.soule

Figure 2 Project Overview Map

NPS VOYA - Kettle Falls

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

Staging Area

Barge & Boat Docking

Staging Area

Figure 3 Ash River Contractor Area

NPS VOYA - Kettle Falls Voyageurs National Park, MN¯ 0 7537.5

Feet

Do cu me nt:

X:

\U

S\U

SP

WM

0-P

LD

2\P roj ec t\P roj ec ts\

NP

S V

OY

A G

IS\

NP

S_

VO

YA

_G

IS\

Ma pD oc um en ts\

NP

S_

VO

YA

_W ork

Ar ea s_ x1 7L

S.m xd

PD

F:

X:

\U S\

US

PW

M1

-P

LD

2\P roj ec t\P roj ec ts\

NP

S V

OY

A

GI

S\

NP

S_

VO

YA

_G

IS

\Fi gu res

\Fi gu re 3 -

A sh

R ive r C on tra cto r A rea

.pd f

/15

/20

1:4

5 A M n ath an .so ule

Legend Work and Staging Area

Prepared/Date: NES 03/15/24 Checked/Date: JWP 03/15/24

"AA

"AA

NPS Side

Barge Launch Area

Boat Docking Overnight

Legend "AA Work and Staging Location

Work and Staging Area 0 7537.5

Feet

Prepared/Date: NES 03/15/24 Checked/Date: JWP 03/15/24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 4 - Alternate Docking Area.pdf 03/15/2024 11:45 AM nathan.soule

Figure 4 Alternate Docking Area

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

"AA

"AA

"AA

Kettle Falls Docking Area

Alternative Docking Area

Ash River Docking Area

0 42 Miles

Index Map

Active working area for NPS.

Can't block bays or left side.

Can't close road.

NPS Staff & Concessions use this road daily during the season.

"Road Closed to Public" Sign

Barge Offload & Fueling

Concession House Used During the Season

Concession Garage & Work Area by Road

"Road Closed to Public" Sign

Road to Staging & Storage Area

Storage Area, Limited Parking Area, Work Zone

Barge, Fueling, & Docking Area - Concession Owned -

Need permission to use docks.

More slips are missing (winter image)

Approved Houseboat Docking Area for Barge

Legend

AA

Docking and Staging Areas 0 15075

Feet

Prepared/Date: NES 03/15/24 Checked/Date: JWP 03/15/24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 5 - Kettle Falls Contractor Area.pdf 03/15/2024 11:45 AM nathan.soule

Figure 5 Kettle Falls Contractor Area

NPS VOYA - Kettle Falls

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

A

B

C

D

E

Hoist Bay

%UJ

%UJ

%UJ

Í wABC

"AM

2 2

Legend %UJ Junction Box "AM CT Metering Junction Box 2 2Recloser

Í wABC 3PH Pad Mounted Transformer Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Approximate Existing 1-Phase Transmission Line0 1,100550

Feet

Prepared/Date: MCB 08-15-24 Checked/Date: 08-15-24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_TLine_Route_Fig4_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 06_Locations A-E.pdf 08-15-2024 5:39 PM madison.bolduc

Figure 6 Locations A-E

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

0 31.5 Miles

* Bathymetric data source: Minnesota Geospatial Information Office

E

F

G

H

%UJ

%UJ

%UJ

%UJ

CANADA

UNITED STATES

Legend %UJ Junction Box Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line United States - Canada Border

0 1,100550 Feet

Prepared/Date: NES 01/24/24 Checked/Date: JWP 01/24/24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 05_Locations E-H.pdf 01/24/2024 8:05 AM nathan.soule

Figure 7 Locations E-H

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

0 31.5 Miles

H

I

J

%UJ

%UJ

2 2

30 20

10 20

20 10

CANADA

UNITED STATES

Legend %UJ Junction Box 2 2Recloser

Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Approximate Existing 3-Phase Transmission Line Replaced CIRCA 2021 Note: Replaced Damaged 1-Phase Line

United States - Canada Border

0 1,100550 Feet

Prepared/Date: MCB 08-15-24 Checked/Date: 08-15-24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 08_Locations H-J.pdf 08-15-2024 4:58 PM madison.bolduc

Figure 8 Locations H-J

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

0 31.5 Miles

J

K

L M

N

O

P & Q

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

Í w

Í w

60 50

CANADA

UNITED STATES

Legend %UJ Junction Box Í w

Pad Mounted Transformer Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls

United States - Canada Border

0 1,100550 Feet

Prepared/Date: MCB 08-15-24 Checked/Date: 08-15-24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 09_Locations J-Q.pdf 08-15-2024 4:54 PM madison.bolduc

Figure 9 Locations J-Q

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

0 31.5 Miles

N

O

P & Q

R & S

T

U V & W

X

Y & Z

AA

BB

CC

DD

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

Í w

Í w

Í w

Í w

Í w

Í w

Í w

Í wÍ w

Í w

4251083

CANADA

UNITED STATES

Legend %UJ Junction Box Í w

Pad Mounted Transformer Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls

United States - Canada Border

0 300150 Feet

Prepared/Date: MCB 08-15-24 Checked/Date: 08-15-24

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_KF_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 10_Kettle_Falls_District.pdf 08-15-2024 4:45 PM madison.bolduc

Figure 10 Kettle Falls District

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

0 31.5 Miles

LOCATION "O"

FACILITY MAINTENANCE SHOP SHED:

EXISTING PAD MOUNT 3-SINGLE PHASE, 7.5KVA

TRANSFORMERS, ELECTRIC METER, LV POWER

DISCONNECT (2 POLE, 100A, 240/120V RATED).

SUPPLY POWER TO FACILITY MAINTENANCE

SHOP BUILDING.

LOCATION "N" - EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX

PAD MOUNTED.

EXIST. MV 3-PH MAIN

SERVICE FEEDER ENTERS

KF DISTRICT MAIN LAND

O

N

P & Q

LOCATION"Q": 1PH, 37.5KVA TRANSFORMER

SUPPLY POWER TO:

- COMPANY HOUSE

- NPS GARAGE

- TRADING POST BUILDING

- BOAT HOUSE

- DIESEL FUEL STORAGE TANKS PUMPS

- DIESEL FUEL DISPENSING PUMP STATION

LOCATION "P" EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX,

PAD MOUNTED (TO BE DEMOLISHED)

HISTORIC

HOUSE

R & S

SHARED

TRENCH

CROSS

LOCATION "V"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

LOCATION "S"

EXIST. 15KVA , 1PH

TRANSFORMER

SUPPLY POWER

TO:

- STORAGE SHED

V & W

X

U

LOCATION LOCATION "W"

EXIST. 75KVA, 3PH TRANSFORMER POWER SUPPLIES TO:

- GUEST VILLA HOUSE #109 (LEANING PINE LODGE) (3PH,

200A SERVICE)

- SEWAGE WATER LIFT PUMPS STATION

LOCATION "Z"

EXIST. 1PH, 37.5KVA TRANSFORMER, PAD MOUNTED PROVIDES

POWER TO:

- FUEL DIESEL TANK PUMP (1PH, 20A)

- FUEL DISPENSER PUMP STATION AT BOAT LANDING (1PH, 20A)

- DOCK POWER (1PH, 20A)

- DOCK HOUSE/ SHED (1PH,100A)

Y & Z

AA

BB

CC

DD

LINE CROSSES

INTO WETLAND

LOCATION "AA"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

LOCATION "T"

KETTLE FALLS HOTEL, EXIST. 3-1 PH,

100KVA TRANSFORMER, PAD

MOUNTED, SUPPLY POWER TO:

- HOTEL

- OUTDOOR PUMP STATIONS

- WATER PUMP HOUSE

- GENERATOR SHED

- FISH CLEANING SHED

T

LOCATION "CC"

EXISTING 75KVA, 3PH TRANSFORMER, PAD

MOUNTED, PROVIDES POWER TO:

- BUILDING 108 (HOTEL EMPLOYEE HOUSING)

LOCATION "DD"

EXIST. KF MAIN LAND POTTING

WATER PUMP HOUSE (BUILDING 112),

45KVA, 3 PH TRANSFORMER FEEDS

PUMP HOUSE BUILDING

BOAT

HOUSE

TRADING

POST

EXIST. MV 3-PH SERVICE FEEDER IN

DUCTBANK ABOVE GROUND AND

UNDERGROUND RUN

SEWAGE PUMPS

STATION AREA

EXIST. MV 3PH SERVICE

FEEDER RUN IN RIVER

EXIST. MV 3PH SERVICE

FEEDER ENTER KF DISTRICT

MAIN LAND HERE

DIESEL FUEL

PUMPING STATION

DIESEL FUEL

STORAGE TANKS

(2 QTY)

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

EXIST. MV 3PH SERVICE

FEEDER ENTER KF

DISTRICT MAIN LAND HERE

EXIST. MV 3PH SERVICE

FEEDER IN RIVER

EXIST. MV 3PH SERVICE

FEEDER ENTER KF

DISTRICT MAIN LAND HERE

LOCATION "U"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

LOCATION "R"

EXIST. MV SERVICE

FEEDER

SECTIONALIZED

JUNCTION BOX,

PAD MOUNTED

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

LOCATION "Y"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

EXIST. MV 3PH SERVICE FEEDER ENTER

KF DISTRICT MAIN LAND HERE

LIFT PUMPS STATION AREA

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

MV

MV

MV

MV

MV

MV

MV

MV MV MV MV

MV

MV

MV

MV

MV

MV MV MV MV MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

EXIST. FACILITY MAINTENANCE SHOP SHED

EXIST. MV 3-PH SERVICE

FEEDER IN DUCTBANK RUN

UNDERGROUND TO

LOCATION "P" SECTIONALIZED

JUNCTION BOX

EXIST. MV SERVICE FEEDER IN DUCTBANK RUN

UNDERGROUND UNDER CRIBBED WALKWAY PATH

LOCATION "BB"

EXIST. LIFT PUMPS STATION 3PH, 45KVA PAD MOUNTED

TRANSFORMER PROVIDES POWER TO LIFT PUMPS.

J

J

J

J

J

J

J

LV

LV

LV

LV

LV

MV

MV

MV

MV

MV

MV

LOCATION "X"

75KVA, 3PH TRANSFORMER, PAD MOUNTED POWER SUPPLY TO:

- GUEST VILLA HOUSE #110 (JESSIE HOUSE) (3PH, 125A SERVICE)

- GUEST VILLA HOUSE #111 (BEAR POINT LODGE LEARNING

CENTER) (3PH, 200A SERVICE)

- WASTE WATER LIFT PUMPS STATION

MV

MV

LOCATION "N" - DISCONNECT EXISTING INCOMING

KF DISTRICT POWER SUPPLY MV SERVICE FEEDER

ENTERING FROM UNDERWATER AND LANDING TO

KF DISTRICT AT SECT. JB

EXIST. MV 3-PHASE MAIN

UTILITY SERVICE FEEDER

RUN IN RIVER FROM

SECTIONALIZED JUNCTION

BOX "M" (TO BE DEMOLISHED)

MV

MV

J

MV

Prepared/Date: NES 1/23/24 Checked/Date: AKD 1/23/24

N

SCALE IN FEET

NPS VOYA - Voyageurs National Park, MN

0 100 200

LEGEND VOYA WAYPOINTS

PAD MOUNTED JUNCTION BOX

PAD MOUNTED TRANSFORMER

GROUND ELEVATION CONTOUR

5 FOOT

1 FOOT

ABOVE GROUND

RUN IN RIVER

DEMOLISH

J

EXISTING ELECTRICAL LOCATIONS:

3 PHASE LEG - A

3 PHASE LEG - B

3 PHASE LEG - C

3 PHASE TRANSMISSION LINE

ABBREVIATIONS:

MV - MEDIUM VOLTAGE

LV - LOW VOLTAGE

PROPOSED ELECTRICAL LOCATIONS:

PROPOSED PATH (NEW) - A

Figure 11

Kettle Falls District Existing & Demolition Plan

MV Cable Replacement Waterline Only

LOCATION "EE"

PROPOSED 3PH MV MAIN

SERVICE FEEDER PAD

MOUNT SECTIONALIZED

JUNCTION BOX "1A" (4 WAY)

LOCATION "O"

FACILITY MAINTENANCE SHOP SHED:

EXISTING PAD MOUNT 3-SINGLE PHASE, 7.5KVA

TRANSFORMERS, ELECTRIC METER, LV POWER

DISCONNECT (2 POLE, 100A, 240/120V RATED).

SUPPLY POWER TO FACILITY MAINTENANCE

SHOP BUILDING.

PROPOSED NEW MAIN MV

SERVICE FEEDER 3PH, 12.4KV

RATED TO KF DISTRICT MAIN

LAND FROM RIVER FROM NEW

SECTIONALIZED JUNCTION BOX

AT LOCATION "L".

LOCATION "O"

PROPOSED LOCATION FOR 3PH NEW MV SERVICE FEEDER

SECTIONALIZED JUNCTION BOX (4-WAY), PAD MOUNTED

LOCATION "N" - EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX

PAD MOUNTED.

O

N

P & Q

LOCATION"Q": 1PH, 37.5KVA TRANSFORMER

SUPPLY POWER TO:

- COMPANY HOUSE

- NPS GARAGE

- TRADING POST BUILDING

- BOAT HOUSE

- DIESEL FUEL STORAGE TANKS PUMPS

- DIESEL FUEL DISPENSING PUMP STATION

LOCATION "P" EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX,

PAD MOUNTED (TO BE DEMOLISHED)

HISTORIC

HOUSE

R & S

SHARED

TRENCH

CROSS

LOCATION "V"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

LOCATION "S"

EXIST. 15KVA , 1PH

TRANSFORMER

SUPPLY POWER

TO:

- STORAGE SHED

V & W

X

U

LOCATION LOCATION "W"

EXIST. 75KVA, 3PH TRANSFORMER POWER SUPPLIES TO:

- GUEST VILLA HOUSE #109 (LEANING PINE LODGE) (3PH,

200A SERVICE)

- SEWAGE WATER LIFT PUMPS STATION

LOCATION "Z"

EXIST. 1PH, 37.5KVA TRANSFORMER, PAD MOUNTED PROVIDES

POWER TO:

- FUEL DIESEL TANK PUMP (1PH, 20A)

- FUEL DISPENSER PUMP STATION AT BOAT LANDING (1PH, 20A)

- DOCK POWER (1PH, 20A)

- DOCK HOUSE/ SHED (1PH,100A)

Y & Z

AA

BB

CC

DD

LINE CROSSES

INTO WETLAND

LOCATION "AA"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

LOCATION "T"

KETTLE FALLS HOTEL, EXIST. 3-1 PH,

100KVA TRANSFORMER, PAD

MOUNTED, SUPPLY POWER TO:

- HOTEL

- OUTDOOR PUMP STATIONS

- WATER PUMP HOUSE

- GENERATOR SHED

- FISH CLEANING SHED

T

LOCATION "CC"

EXISTING 75KVA, 3PH TRANSFORMER, PAD

MOUNTED, PROVIDES POWER TO:

- BUILDING 108 (HOTEL EMPLOYEE HOUSING)

LOCATION "DD"

EXIST. KF MAIN LAND POTTING

WATER PUMP HOUSE (BUILDING 112),

45KVA, 3 PH TRANSFORMER FEEDS

PUMP HOUSE BUILDING

BOAT

HOUSE

TRADING

POST

EXIST. MV 3-PH SERVICE FEEDER IN

DUCTBANK ABOVE GROUND AND

UNDERGROUND RUN

PROPOSED 3PH MV SERVICE

FEEDER ROUTE IN DUCTBANK

RUN UNDERGROUND UNDER

ROADWAY (IF PROPOSED

BACKUP POWER GENERATOR

GEN-1 LOCATION IS

CONSIDERED ADJACENT OR

BEHIND MAINTENANCE SHOP)

LOCATION FOR 4 - FUTURE CABINS

(CAMP LOGS) (EACH CABIN SHALL

REQUIRE 7.5KW SINGLE PHASE POWER)

PROPOSED 3PH MV MAIN

SERVICE FEEDER ROUTE

IN DUCTBANK RUN ABOVE

GROUND IN WOODS

PROPOSED BACKUP POWER DIESEL

GENERATOR GEN-1 SET, TRANSFORMER, ATS,

LV DISTRIBUTION PANEL LOCATION #1A-2

SEWAGE PUMPS

STATION AREA

EXIST. MV 3PH SERVICE

FEEDER RUN IN RIVER

EXIST. MV 3PH SERVICE

FEEDER ENTER KF DISTRICT

MAIN LAND HERE

DIESEL FUEL

PUMPING STATION

DIESEL FUEL

STORAGE TANKS

(2 QTY)

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

EXIST. MV 3PH SERVICE

FEEDER ENTER KF

DISTRICT MAIN LAND HERE

EXIST. MV 3PH SERVICE

FEEDER IN RIVER

EXIST. MV 3PH SERVICE

FEEDER ENTER KF

DISTRICT MAIN LAND HERE

LOCATION "U"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

LOCATION "R"

EXIST. MV SERVICE

FEEDER

SECTIONALIZED

JUNCTION BOX,

PAD MOUNTED

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

LOCATION "Y"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED

EXIST. MV 3PH SERVICE FEEDER ENTER

KF DISTRICT MAIN LAND HERE

LIFT PUMPS STATION AREA

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

MV

MV

MV

MV

MV

MV

MV

MV MV MV MV

MV

MV

MV

MV

MV

MV MV MV MV MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

EXIST. FACILITY MAINTENANCE SHOP SHED

PROPOSED BACKUP POWER DIESEL

GENERATOR GEN-1 LOCATION #1A-1

EXIST. MV 3-PH SERVICE

FEEDER IN DUCTBANK RUN

UNDERGROUND TO

LOCATION "P" SECTIONALIZED

JUNCTION BOX

EXIST. MV SERVICE FEEDER IN DUCTBANK RUN

UNDERGROUND UNDER CRIBBED WALKWAY PATH

LOCATION "BB"

EXIST. LIFT PUMPS STATION 3PH, 45KVA PAD MOUNTED

TRANSFORMER PROVIDES POWER TO LIFT PUMPS.

J

J

J

J

J

J

J

LV

LV

LV

LV

LV

MV

MV

MV

MV

MV

MV

LOCATION "X"

75KVA, 3PH TRANSFORMER, PAD MOUNTED POWER SUPPLY TO:

- GUEST VILLA HOUSE #110 (JESSIE HOUSE) (3PH, 125A SERVICE)

- GUEST VILLA HOUSE #111 (BEAR POINT LODGE LEARNING

CENTER) (3PH, 200A SERVICE)

- WASTE WATER LIFT PUMPS STATION

MV

MV

LOCATION "N" - DISCONNECT EXISTING INCOMING

KF DISTRICT POWER SUPPLY MV SERVICE FEEDER

ENTERING FROM UNDERWATER AND LANDING TO

KF DISTRICT AT SECT. JB

PROPOSED MV FEEDER RUN

PARTIAL IN ABOVE GROUND

CONDUIT AND PARTIAL

UNDER GROUND

(APPROX. TOTAL PROPOSED

MV FEEDER LENGTH IS 900')

PROVIDE NEW MV FEEDER SECTIONALIZED 4-WAY JB

AT LOCATION 'O' ADJACENT TO TRANSFORMER.

- CONNECT PROPOSED MV FEEDER

- DISCONNECT EXISTING MV FEEDER CONNECTED TO

TRANSFORMER AND RE-CONNECT TRANSFORMER AND

EXISTING MV FEEDER WITHIN PROPOSED SECT. JB

J

MV

MV

J

MV

Prepared/Date: NES 1/23/24 Checked/Date: 1/23/24

N

SCALE IN FEET

NPS VOYA - Voyageurs National Park, MN

0 100 200

LEGEND VOYA WAYPOINTS

PAD MOUNTED JUNCTION BOX

PAD MOUNTED TRANSFORMER

GROUND ELEVATION CONTOUR

5 FOOT

1 FOOT

ABOVE GROUND

RUN IN RIVER

DEMOLISH

J

EXISTING ELECTRICAL LOCATIONS:

3 PHASE LEG - A

3 PHASE LEG - B

3 PHASE LEG - C

3 PHASE TRANSMISSION LINE

ABBREVIATIONS:

MV - MEDIUM VOLTAGE

LV - LOW VOLTAGE

PROPOSED ELECTRICAL LOCATIONS:

PROPOSED PATH (NEW) - A

Figure 12

Kettle Falls District Existing & Proposed Plan

MV Cable Replacement Waterline Only

EXIST. MV SECTION

JB (LOCATION "M")

AT ISLAND (TO BE

DEMOLISHED)

EXIST. MV 3PH

SERVICE FEEDER

RUN IN RIVER

UNDERWATER (TO

BE DEMOLISHED)

KETTLE FALLS

ISLAND BOUNDARY

EXIST. MV 3PH SERVICE

FEEDER ENTERS KF

DISTRICT MAIN LAND TO

BE DEMOLISHED AND

DISCONNECTED FROM

EXIST. SECTION JB

(LOCATION "N")

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERWATER

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERGROUND

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

KETTLE FALLS ISLAND - MV & LV POWER DISTRIBUTION EXISTING AND DEMOLITION SINGLE LINE DIAGRAM

RIVERSIDE

(UNDERWATER)

BOUNDARY

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

EXIST. MV 3PH SERVICE

FEEDER ENTERS KF

DISTRICT MAIN LAND

GFI

M

(LOCATION "O")

EXIST. MAINT.

SHOP BLDG

EXIST. 100A, 1PH, 208/120V,

3W + GND FEEDER RUN IN

CONDUIT UNDERGROUND

EXIST. MV SECTION

JB (LOCATION "P-Q")

EXIST. TRANSFORMER 1PH, 37.5KVA,

PRIMARY - 12.47/ 7.2KV, 1PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3W + GND. PAD MOUNTED

(LOCATION "P-Q")

DIESEL FUEL

STORAGE

TANKS

DIESEL FUEL

DISP. PUMP

STATION

EXIST. MV SECTION

JB (LOCATION "R")

EXIST. LV 50A, 1PH, 208V, 3W + GND

FEEDER RUN IN UNDERGROUND CONDUIT

(LOCATION "R")

(LOCATION "T")

EXIST. MV SECTION

JB (LOCATION "U")

EXIST. MV SECTION

JB (LOCATION "V")

(LOCATION "V")

(LOCATION "X")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH, 4W +

GND. PAD MOUNTED

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "J"

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "A"

EXIST.

LV

PNL "J"

EXIST. GUEST VILLA HOUSE

#110 (JESSIE HOUSE)

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. GUEST VILLA HOUSE #109

(LEARNING PINE LODGE)

(LOCATION "W")

EXIST. TRANSFORMER 3PH,

75KVA, PRIMARY - 12.47/ 7.2KV,

3PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH,

4W + GND. PAD MOUNTED

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT BLDG "L"

EXIST. WATER PUMP

HOUSE BLDG #112

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

(LOCATION "DD")

EXIST. TRANSFORMER

3PH, 45KVA, PRIMARY -

12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

3PH, 4W + GND. PAD

MOUNTED

(LOCATION "U")

EXIST. MV SECTION

JB (LOCATION "AA")

(LOCATION "AA")

(LOCATION "CC")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

EXIST. LIFT

PUMP STATIONS

POWER

(LOCATION "BB")

EXIST. TRANSFORMER 3PH, 45KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

EXIST. GUEST VILLA HOUSE #111 (BEAR

POINT LODGE LEARNING CENTER)

EXIST. LV 200A FEEDER IN

UNDERGROUND CONDUIT

EXIST.

LV

PANEL

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV SECTION

JB (LOCATION "Y")

EXIST. TRANSFORMER

1PH, 37.5KVA, PRIMARY -

12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

1PH, 3W + GND. PAD

MOUNTED

(LOCATION "Y")

EXIST. MV SECTION

JB (LOCATION "N")

EXIST. MV 3PH

LINE IN CONDUIT

UNDERGROUND

EXIST. LV 208/120V AC FEEDERS

IN CONDUIT RUN UNDERGROUND

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV 3PH

LINE IN

UNDERGROUND

CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

NOTES:

1. FOR SITE LAYOUT - REFER TO FIGURE 09.

2. ALL EQUIPMENT AND FEEDERS SHOWN ARE

EXISTING TO REMAIN UNLESS OTHERWISE

NOTED.

DOCK

POWER

DIESEL

FUEL DISP.

PUMP

DOCK

HOUSE

SHED

DIESEL

FUEL

PUMP

EXIST.

LV PNL

NPS

GARAGE

TRADING

POST

BLDG

BOAT

HOUSE

EXIST.

LV PNL

EXIST.

LV PNL

EXIST.

LV PNL

M M

M

M

M

M

EXIST.

LV

PNL "A1"

EXIST.

LV

PNL "A"

M

M

M

M

EXIST.

LV

PNL "B"

EXIST.

LV

PNL "B1"

EXIST.

LV

PANEL

EXIST.

LV

PANEL

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

EXIST. TRANSFORMER

PRIMARY - 12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W +

GND, 3-100KVA, 208/120V, 3W,

PAD MOUNTED

LOCATED OUTSIDE EXIST.

KETTLE FALLS HOTEL BLDG

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

FEED

PUMPS

STATIONS

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

M

EXIST.

LV

SWITCHBOARD

EXIST. GENERATOR HOUSE

EXIST. FIRE PUMP FUSED

DISCONNECT, 100A, 208V

AC RATED, 3PH, 3W, 60HZ

TO EXIST. FIRE PUMP

FOR HOTEL BLDG

FIRE PROTECTION

EXIST. LV FEEDER

EN

L

NOTE: THERE IS NO

EXIST. EM GENERATOR

EQUIPMENT

EM POWER

PANEL "ED"

EXIST. ATS (AUTOMATIC

TRANSFER SWITCH),

200A, 208/120V AC RATED,

3PH, 4W, GND, 60 HZ

EXIST. EM POWER PANEL

"ED", 100A, 3PH, 4W,

208/120V AC RATED, 60 HZ

EXIST. LV FEEDER TO EXIST.

FISH CLEANING SHED

EXIST. LV FEEDER

EXIST. LV FEEDER TO MOTEL/ HOTEL

BUILDING EXTERIOR LOCATED PANEL

"E" (PANEL SUPPLIES POWER TO EM

LIGHTING, FIRE ALARM AND FIRE

SUPPRESSION SYSTEM EQUIPMENT

EXIST.

LV

PANEL

EXIST.

LV

PANEL

COMPANY

HOUSE

EXIST.

LV PNL

M M

EXIST.

LV PNL

EXIST.

LV

PANEL

EXIST.

LV

PANEL

EXIST. TRANSFORMER 1PH, 15KVA, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W + GND. PAD MOUNTED

EXIST. 100A, 1PH, 208/120V, 3W + GND

PANELBOARD WITH 2P, 100A MAIN CB

EXIST. 100A, 1PH,

208/120V, 3W + GND

PANELBOARD WITH MLO

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND

PANELBOARD WITH MLO

EXIST. LV FEEDER

(20A, 120V AC) IN

UNDERGROUND

CONDUIT

EXIST. LV FEEDER

(20A, 120V AC) IN

UNDERGROUND

CONDUIT

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND

PANELBOARD WITH 2P,

100A MAIN CB

EXIST. 100A, 1PH,

208/120V RATED,

3W + GND

PANELBOARD

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND PANELBOARD

WITH 2P, 100A BRANCH CB

FEEDS MAINT. WORKSHOP

LOCATED PANEL

EXIST. TRANSFORMERS 3-1PH, 7.5KVA EACH, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED, SECONDARY -

208/120V, 3W + GND. PAD MOUNTED

EXIST. BOAT

SHED STORAGE

EXIST. 50A, 1PH,

208/120V, 3W + GND

PANELBOARD WITH

2P, 50A MAIN CB

EXIST. 200A, 3PH, 208/120V RATED,

4W + GND PANELBOARD "B" WITH MLO

EXIST. 100A, 3PH,

208/120V RATED, 4W +

GND PANELBOARD "B1"

WITH MLO

EXIST. LV FEEDER (3P, 45A CB)

BRANCH FEEDER IN PANEL "B"

EXIST. 100A, 3PH,

208/120V RATED,

4W + GND

PANELBOARD WITH

3P, 100A MAIN CB

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND PANELBOARD

"D" WITH 3P, 200A MAIN CB

EXIST. BLDG #108 (HOUSE FOR

HOTEL EMPLOYEES)

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "D1" WITH

3P, 200A MAIN SERVICE CB

EXIST. 125A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "J" WITH 3P,

125A MAIN CB

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "A" WITH 3P,

200A MAIN CB

EXIST. 100A, 3PH,

208/120V RATED,

4W + GND

PANELBOARD "A1"

WITH MLO

EXIST. 200A, 1PH, 208/120V RATED, 3W + GND

PANELBOARD "A" WITH 2P, 200A MAIN CB

EXIST. 200A, 1PH,

208/120V RATED, 3W

+ GND PANELBOARD

WITH MLO

EXIST. 1200A, 3PH,

208/120V RATED, 4W + GND

POWER DISTRIBUTION

SWITCHBOARD WITH 3P,

1200A MAIN CB

EXIST. 3PH, 100A, 208V, 4W

RATED, FUSED DISCONNECT

Prepared/Date: NES 1/23/24 Checked/Date: AKD 1/23/24

N

NPS VOYA - Voyageurs National Park, MN

Figure 13

Kettle Falls District Existing and Demolition

Single Line Diagram - Waterline Replacement Only

KETTLE FALLS ISLAND - MV & LV POWER DISTRIBUTION EXISTING AND PROPOSED SINGLE LINE DIAGRAM

PROPOSED NEW MV

SECTION JB (LOCATION

"L") AT ISLAND

PROPOSED NEW

MV 3PH SERVICE

FEEDER RUN IN

RIVER

UNDERWATER

KETTLE FALLS

ISLAND BOUNDARY

EXIST. MV 3PH SERVICE

FEEDER ENTERS KF

DISTRICT MAIN LAND

EXIST. TRANSFORMERS 3-1PH, 7.5KVA EACH, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED, SECONDARY -

208/120V, 3W + GND. PAD MOUNTED

GFI

M

(LOCATION "O")

EXIST. MAINT.

SHOP BLDG

EXIST. MV SECTION

JB (LOCATION "P-Q")

EXIST. TRANSFORMER 1PH, 37.5KVA,

PRIMARY - 12.47/ 7.2KV, 1PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3W + GND. PAD MOUNTED

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERWATER

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERGROUND

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

DIESEL FUEL

STORAGE

TANKS

DIESEL FUEL

DISP. PUMP

STATION

EXIST. LV 50A, 1PH, 208V, 3W + GND

FEEDER RUN IN UNDERGROUND CONDUIT

(LOCATION "R")

(LOCATION "T")

EXIST. MV SECTION

JB (LOCATION "U")

EXIST. MV SECTION

JB (LOCATION "V")

(LOCATION "V")

(LOCATION "X")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH, 4W +

GND. PAD MOUNTED

(LOCATION "W")

EXIST. TRANSFORMER 3PH,

75KVA, PRIMARY - 12.47/ 7.2KV,

3PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH,

4W + GND. PAD MOUNTED

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

(LOCATION "DD")

EXIST. TRANSFORMER

3PH, 45KVA, PRIMARY -

12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

3PH, 4W + GND. PAD

MOUNTED

(LOCATION "U")

EXIST. MV SECTION

JB (LOCATION "AA")

(LOCATION "AA")

(LOCATION "CC")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

EXIST. LIFT

PUMP STATIONS

POWER

(LOCATION "BB")

EXIST. TRANSFORMER 3PH, 45KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

EXIST.

LV

PANEL

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV SECTION

JB (LOCATION "Y")

EXIST. TRANSFORMER

1PH, 37.5KVA, PRIMARY -

12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

1PH, 3W + GND. PAD

MOUNTED

(LOCATION "Y")

RIVERSIDE (UNDERWATER) BOUNDARY

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

EXIST. MV SECTION

JB (LOCATION "N")

PROPOSED NEW

3PH MV MAIN

SERVICE FEEDER

LOCATION "EE": PROPOSED NEW

3PH MV LINE 4-WAY SECTION JB "1A"

PROP. NEW MV SECTION

JB (LOCATION "O")

EXIST. MV 3PH

LINE IN CONDUIT

UNDERGROUND

EXIST. MV 3PH

LINE IN

UNDERGROUND

CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

NOTES:

1. FOR SITE LAYOUT - REFER TO FIGURE 10.

2. ALL EQUIPMENT AND FEEDERS SHOWN ARE

EXISTING UNLESS OTHERWISE NOTED.

PROPOSED NEW MAIN MV 3PH SERVICE

FEEDER ENTERS KF DISTRICT MAIN LAND

DOCK

POWER

DIESEL

FUEL DISP.

PUMP

DOCK

HOUSE

SHED

DIESEL

FUEL

PUMP

EXIST.

LV PNL

NPS

GARAGE

TRADING

POST

BLDG

BOAT

HOUSE

EXIST.

LV PNL

EXIST.

LV PNL

EXIST.

LV PNL

(LOCATION "P-Q")

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

LOCATED OUTSIDE EXIST.

KETTLE FALLS HOTEL BLDG

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

FEED

PUMPS

STATIONS

M

EXIST.

LV

SWITCHBOARD

EXIST. GENERATOR HOUSE

EXIST. FIRE PUMP FUSED

DISCONNECT, 100A, 208V

AC RATED, 3PH, 3W, 60HZ

TO EXIST. FIRE PUMP

FOR HOTEL BLDG

FIRE PROTECTION

EXIST. LV FEEDER

EN

L

EM POWER

PANEL "ED"

EXIST. ATS (AUTOMATIC

TRANSFER SWITCH),

200A, 208/120V AC RATED,

3PH, 4W, GND, 60 HZ

EXIST. EM POWER PANEL

"ED", 100A, 3PH, 4W,

208/120V AC RATED, 60 HZ

EXIST. LV FEEDER TO EXIST.

FISH CLEANING SHED

EXIST. LV FEEDER

EXIST. LV FEEDER TO MOTEL/ HOTEL

BUILDING EXTERIOR LOCATED PANEL

"E" (PANEL SUPPLIES POWER TO EM

LIGHTING, FIRE ALARM AND FIRE

SUPPRESSION SYSTEM EQUIPMENT

EXIST. TRANSFORMER

PRIMARY - 12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W +

GND, 3-100KVA, 208/120V, 3W,

PAD MOUNTED

M M

EXIST. GUEST VILLA HOUSE #109

(LEARNING PINE LODGE)

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT BLDG "L"

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

M

EXIST.

LV

PNL "B"

EXIST.

LV

PNL "B1"

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

M

EXIST.

LV

PANEL

EXIST.

LV

PNL "J"

EXIST. GUEST VILLA HOUSE

#110 (JESSIE HOUSE)

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. GUEST VILLA HOUSE #111 (BEAR

POINT LODGE LEARNING CENTER)

EXIST. LV 200A FEEDER IN

UNDERGROUND CONDUIT

M

M

EXIST.

LV

PNL "A1"

EXIST.

LV

PNL "A"

M

M

M

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "J"

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "A"

EXIST.

LV

PANEL

EXIST.

LV

PANEL

NOTE: THERE IS NO

EXIST. EM GENERATOR

EQUIPMENT

COMPANY

HOUSE

EXIST.

LV PNL

M M

EXIST.

LV PNL

EXIST.

LV

PANEL

EXIST.

LV

PANEL

EXIST. 125A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "J" WITH 3P,

125A MAIN CB

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "A" WITH 3P,

200A MAIN CB

EXIST. 100A, 3PH,

208/120V RATED,

4W + GND

PANELBOARD "A1"

WITH MLO

EXIST. 200A, 1PH,

208/120V RATED, 3W

+ GND PANELBOARD

WITH MLO

EXIST. 200A, 3PH, 208/120V RATED,

4W + GND PANELBOARD "B" WITH MLO

EXIST. 100A, 3PH,

208/120V RATED, 4W +

GND PANELBOARD "B1"

WITH MLO

EXIST. LV FEEDER (3P, 45A CB)

BRANCH FEEDER IN PANEL "B"

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND PANELBOARD

"D" WITH 3P, 200A MAIN CB

EXIST. BLDG #108 (HOUSE FOR

HOTEL EMPLOYEES)

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "D1" WITH

3P, 200A MAIN SERVICE CB

EXIST. 1200A, 3PH,

208/120V RATED, 4W + GND

POWER DISTRIBUTION

SWITCHBOARD WITH 3P,

1200A MAIN CB

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND PANELBOARD

WITH 2P, 100A BRANCH CB

FEEDS MAINT. WORKSHOP

LOCATED PANEL

EXIST. 100A, 1PH, 208/120V,

3W + GND FEEDER RUN IN

CONDUIT UNDERGROUND

EXIST. 100A, 1PH,

208/120V RATED,

3W + GND

PANELBOARD

EXIST. LV FEEDER

(20A, 120V AC) IN

UNDERGROUND

CONDUIT

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND

PANELBOARD WITH 2P,

100A MAIN CB

EXIST. LV FEEDER (20A,

120V AC) IN UNDERGROUND

CONDUIT

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND

PANELBOARD WITH MLO

EXIST. LV 208/120V AC FEEDERS

IN CONDUIT RUN UNDERGROUND

EXIST. 100A, 1PH,

208/120V, 3W + GND

PANELBOARD WITH MLO

EXIST. 100A, 1PH, 208/120V, 3W + GND

PANELBOARD WITH 2P, 100A MAIN CB

EXIST. 50A, 1PH,

208/120V, 3W + GND

PANELBOARD

EXIST. BOAT

SHED STORAGE

EXIST. TRANSFORMER 1PH, 15KVA, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W + GND. PAD MOUNTED

EXIST. 200A, 1PH, 208/120V RATED, 3W + GND

PANELBOARD "A" WITH 2P, 200A MAIN CB

EXIST. WATER PUMP

HOUSE BLDG #112

M

EXIST.

LV

PANEL

EXIST. 100A, 3PH,

208/120V RATED,

4W + GND

PANELBOARD WITH

3P, 100A MAIN CB

EXIST. 3PH, 100A, 208V, 4W

RATED, FUSED DISCONNECT

Prepared/Date: NES 1/23/24 Checked/Date: AKD 1/23/24

N

NPS VOYA - Voyageurs National Park, MN

Figure 14

Kettle Falls District Existing and Proposed

Single Line Diagram - Waterline Replacement Only

LOCATION "EE": 3PH MV

MAIN SERVICE FEEDER PAD

MOUNT SECTIONALIZED

JUNCTION BOX "1A" (4 WAY)

LOCATION "N" - EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX

PAD MOUNTED. (TO BE DEMOLISHED)

O

N

P & Q

LOCATION"Q": 1PH, 37.5KVA TRANSFORMER

SUPPLY POWER TO:

- COMPANY HOUSE

- NPS GARAGE

- TRADING POST BUILDING

- BOAT HOUSE

- DIESEL FUEL STORAGE TANKS PUMPS

- DIESEL FUEL DISPENSING PUMP STATION

LOCATION "P" EXIST. MV SERVICE

FEEDER SECTIONALIZED JUNCTION BOX,

PAD MOUNTED (TO BE DEMOLISHED)

HISTORIC

HOUSE

R & S

SHARED

TRENCH

CROSS

LOCATION "V"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED (TO BE

DEMOLISHED)

LOCATION "S"

EXIST. 15KVA , 1PH

TRANSFORMER

SUPPLY POWER

TO:

- STORAGE SHED

(EXIST.

TRANSFORMER TO

BE DEMOLISHED)

V & W

X

U

LOCATION LOCATION "W" - EXIST. 75KVA, 3PH

TRANSFORMER POWER SUPPLIES TO:

- GUEST VILLA HOUSE #109 (LEANING PINE LODGE) (3PH,

200A SERVICE)

- SEWAGE WATER LIFT PUMPS STATION (EXIST.

TRANSFORMER TO BE DEMOLISHED)

LOCATION "Z" - EXIST. 1PH, 37.5KVA TRANSFORMER, PAD

MOUNTED PROVIDES POWER TO:

- FUEL DIESEL TANK PUMP (1PH, 20A)

- FUEL DISPENSER PUMP STATION AT BOAT LANDING (1PH, 20A)

- DOCK POWER (1PH, 20A)

- DOCK HOUSE/ SHED (1PH,100A)

(EXIST. TRANSFORMER TO BE DEMOLISHED)

Y & Z

AA

BB

CC

DD

LINE CROSSES

INTO WETLAND

LOCATION "AA"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED (TO BE

DEMOLISHED)

LOCATION "T"

KETTLE FALLS HOTEL, EXIST. 3-1 PH,

100KVA TRANSFORMER, PAD

MOUNTED, SUPPLY POWER TO:

- HOTEL

- OUTDOOR PUMP STATIONS

- WATER PUMP HOUSE

- GENERATOR SHED

- FISH CLEANING SHED

(EXIST. TRANSFORMER TO BE

DEMOLISHED)

T

LOCATION "CC"

EXISTING 75KVA, 3PH TRANSFORMER, PAD

MOUNTED, PROVIDES POWER TO:

- BUILDING 108 (HOTEL EMPLOYEE HOUSING)

(EXIST. TRANSFORMER TO BE DEMOLISHED)

LOCATION "DD"

EXIST. KF MAIN LAND POTTING

WATER PUMP HOUSE (BUILDING 112),

45KVA, 3 PH TRANSFORMER FEEDS

PUMP HOUSE BUILDING (EXIST.

TRANSFORMER TO BE DEMOLISHED)

BOAT

HOUSE

TRADING

POST

EXIST. MV 3-PH SERVICE FEEDER IN

DUCTBANK ABOVE GROUND AND

UNDERGROUND RUN (TO BE DEMOLISHED)

PROPOSED 3PH MV SERVICE

FEEDER ROUTE IN DUCTBANK

RUN UNDERGROUND UNDER

ROADWAY (IF PROPOSED

BACKUP POWER GENERATOR

GEN-1 LOCATION IS

CONSIDERED ADJACENT OR

BEHIND MAINTENANCE SHOP)

LOCATION FOR 4 - FUTURE CABINS

(CAMP LOGS) (EACH CABIN SHALL

REQUIRE 7.5KW SINGLE PHASE POWER)

3PH MV MAIN SERVICE

FEEDER ROUTE IN

DUCTBANK RUN ABOVE

GROUND IN WOODS

SEWAGE PUMPS

STATION AREA

EXIST. MV 3PH SERVICE

FEEDER RUN IN RIVER

(TO BE DEMOLISHED)

EXIST. MV 3PH SERVICE

FEEDER ENTER KF DISTRICT

MAIN LAND HERE

DIESEL FUEL

PUMPING STATION

DIESEL FUEL

STORAGE TANKS

(2 QTY)

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

(TO BE DEMOLISHED)

EXIST. MV 3PH SERVICE

FEEDER ENTER KF

DISTRICT MAIN LAND HERE

EXIST. MV 3PH SERVICE

FEEDER IN RIVER (TO

BE DEMOLISHED)

EXIST. MV 3PH SERVICE FEEDER

ENTER KF DISTRICT MAIN LAND

HERE (TO BE DEMOLISHED)

LOCATION "U"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED (TO BE

DEMOLISHED)

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

(TO BE DEMOLISHED)

LOCATION "R"

EXIST. MV SERVICE

FEEDER

SECTIONALIZED

JUNCTION BOX, PAD

MOUNTED (TO BE

DEMOLISHED)

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

(TO BE DEMOLISHED)

LOCATION "Y"

EXIST. MV SERVICE FEEDER

SECTIONALIZED JUNCTION

BOX, PAD MOUNTED (TO BE

DEMOLISHED)

EXIST. MV 3PH SERVICE FEEDER ENTER KF

DISTRICT MAIN LAND HERE (TO BE DEMOLISHED)

LIFT PUMPS STATION AREA

EXIST. MV 3PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND

(TO BE DEMOLISHED)

MV

MV

MV

MV

MV

MV

MV

MV MV MV MV

MV

MV

MV

MV

MV

MV MV MV MV MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

EXIST. MV 3-PH SERVICE

FEEDER IN DUCTBANK

RUN UNDERGROUND TO

LOCATION "P"

SECTIONALIZED JUNCTION

BOX (TO BE DEMOLISHED)

CRIBBED WALKWAY PATH, EXIST. MV CABLE

FEEDER RUN UNDERGROUND CONDUIT. EXISTING

MV FEEDER SHALL BE REMOVED AND DEMOLISHED.

EXISTING CONDUIT SHALL REMAIN.

LOCATION "BB"

EXIST. LIFT PUMPS STATION 3PH, 45KVA PAD MOUNTED

TRANSFORMER PROVIDES POWER TO LIFT PUMPS

(EXIST. TRANSFORMER TO BE DEMOLISHED)

J

J

J

J

J

J

J

EXIST. MV 3 PH SERVICE FEEDER

CABLE RUN WITHIN EXIST. 6" PVC

CONDUIT IS TO BE REMOVED FROM

EXIST. DUCTBANK. EXIST. 6" PVC

CONDUIT AND DUCTBANK TO REMAIN

MV

MV

MV

MV

MV

MV

LOCATION "X"

75KVA, 3PH TRANSFORMER, PAD MOUNTED POWER SUPPLY TO:

- GUEST VILLA HOUSE #110 (JESSIE HOUSE) (3PH, 125A SERVICE)

- GUEST VILLA HOUSE #111 (BEAR POINT LODGE LEARNING

CENTER) (3PH, 200A SERVICE)

- WASTE WATER LIFT PUMPS STATION (EXIST. TRANSFORMER TO

BE DEMOLISHED)

J

LOCATION "O"

FACILITY MAINTENANCE SHOP SHED:

EXISTING PAD MOUNT 3-SINGLE PHASE, 7.5KVA

TRANSFORMERS, ELECTRIC METER, LV POWER

DISCONNECT (2 POLE, 100A, 240/120V RATED).

SUPPLY POWER TO FACILITY MAINTENANCE

SHOP BUILDING.

LOCATION "O"

LOCATION FOR 3PH MV SERVICE FEEDER SECTIONALIZED

JUNCTION BOX (4-WAY), PAD MOUNTED

EXIST. FACILITY MAINTENANCE SHOP SHED

MV FEEDER SECTIONALIZED 4-WAY JB AT LOCATION 'O'

ADJACENT TO TRANSFORMER.

- CONNECT PROPOSED MV FEEDER

- DISCONNECT EXISTING MV FEEDER CONNECTED TO

TRANSFORMER AND RE-CONNECT TRANSFORMER AND

EXISTING MV FEEDER WITHIN PROPOSED SECT. JB

MV

MV

J

MV

PROPOSED NEW MAIN MV

SERVICE FEEDER 3PH, 12.4KV

RATED TO KF DISTRICT MAIN

LAND FROM RIVER FROM NEW

SECTIONALIZED JUNCTION BOX

AT LOCATION "L".

Prepared/Date: NES 1/23/24 Checked/Date: AKD 1/23/24

N

SCALE IN FEET

NPS VOYA - Voyageurs National Park, MN

0 100 200

LEGEND VOYA WAYPOINTS

PAD MOUNTED JUNCTION BOX

PAD MOUNTED TRANSFORMER

GROUND ELEVATION CONTOUR

5 FOOT

1 FOOT

ABOVE GROUND

RUN IN RIVER

DEMOLISH

J

EXISTING ELECTRICAL LOCATIONS:

3 PHASE LEG - A

3 PHASE LEG - B

3 PHASE LEG - C

3 PHASE TRANSMISSION LINE

ABBREVIATIONS:

MV - MEDIUM VOLTAGE

LV - LOW VOLTAGE

PROPOSED ELECTRICAL LOCATIONS:

PROPOSED PATH (EXISTING) - A

PROPOSED PATH (EXISTING) - B

PROPOSED PATH (NEW) - A

PROPOSED PATH (NEW) - B

PROPOSED PATH (NEW) - C

PROPOSED PATH (NEW) - D

Figure 15

Kettle Falls District Existing and Demolition Plan

Two Backup Power Generators Option

O

P & Q

LOCATION"Q": 1PH, PROPOSED LV FEEDER 100A,

208/120V, 3PH, 4W, GROUND AS INDICATED TO BE

CONNECTED TO EXISTING LV FEEDERS SUPPLY

POWER TO:

- COMPANY HOUSE

- NPS GARAGE

- TRADING POST BUILDING

- BOAT HOUSE

- DIESEL FUEL STORAGE TANKS PUMPS

- DIESEL FUEL DISPENSING PUMP STATION

HISTORIC

HOUSE

R & S

SHARED

TRENCH

CROSS

LOCATION "S"

NEW LV FEEDER - 100A, 1PH, 3W, GROUND TO BE

PROVIDED FROM POWER DISTRIBUTION BOARD

"PDB-2" LOCATED ADJACENT TO GEN 2 LOCATION

AS INDICATED TO BE CONNECTED TO EXISTING LV

POWER PANELBOARD 100A, 1P, 3W, 208/120V AC

RATED LOCATED WITHIN STORAGE SHED. SUPPLY

POWER TO:

- STORAGE SHED

V & W

X

LOCATION LOCATION "W": NEW LV FEEDER - 200A, 3PH,

4W, GROUND TO BE PROVIDED FROM POWER

DISTRIBUTION BOARD "PDB-2" LOCATED ADJACENT TO

GEN 2 LOCATION AS INDICATED TO BE CONNECTED TO

EXISTING LV POWER 200A, 3P, 4W, 208/120V AC RATED

DISCONNECT POWER SUPPLIES TO:

- GUEST VILLA HOUSE #109 (LEANING PINE LODGE) (3PH,

200A SERVICE)

- SEWAGE WATER LIFT PUMPS STATION (EXIST.

TRANSFORMER TO BE DEMOLISHED)

LOCATION "Z": NEW LV FEEDER - 200A, 1PH, 3W, GROUND TO BE

PROVIDED FROM POWER DISTRIBUTION BOARD "PDB-2"

LOCATED ADJACENT TO GEN 2 LOCATION AS INDICATED TO BE

CONNECTED TO EXISTING LV POWER PANELBOARD 200A, 1P,

3W, 208/120V AC RATED PROVIDES POWER TO:

- FUEL DIESEL TANK PUMP (1PH, 20A)

- FUEL DISPENSER PUMP STATION AT BOAT LANDING (1PH, 20A)

- DOCK POWER (1PH, 20A)

- DOCK HOUSE/ SHED (1PH,100A)

(EXIST. TRANSFORMER TO BE DEMOLISHED)

Y & Z

BB

CC

DD

LINE CROSSES

INTO WETLAND

PROPOSED LV 1PH, 100A

RATED CABLE FEEDER FROM

KF HOTEL EXISTING 1200A

POWER DISTRIBUTION

SWITCHBOARD RUN WITHIN

EXIST. 6" PVC CONDUIT IN

EXIST. DUCTBANK

LOCATION "T"

KETTLE FALLS HOTEL, NEW LV FEEDER - 1000A

3PH, 4W, GROUND TO BE PROVIDED FROM

POWER DISTRIBUTION BOARD "PDB-1"

LOCATED ADJACENT TO GEN 1 LOCATION AS

INDICATED TO BE CONNECTED TO HOTEL MAIN

SERVICE DISTRIBUTION SWITCHBOARD "XXXX",

1200A, 208/120V AC RATED, 3PH, 4W, GROUND

LOCATED OUTDOOR ADJACENT TO THE

TRANSFORMER, SUPPLY POWER TO:

- HOTEL

- OUTDOOR PUMP STATIONS

- WATER PUMP HOUSE

- GENERATOR SHED

- FISH CLEANING SHED

- PROPOSED LOCATION "S" STORAGE SHED

T

LOCATION "CC": NEW LV FEEDER - 200A, 3PH, 4W, GROUND TO BE

PROVIDED FROM POWER DISTRIBUTION BOARD "PDB-2" LOCATED

ADJACENT TO GEN 2 LOCATION AS INDICATED TO BE CONNECTED

TO EXISTING 3P, 200A, 3PH, 4W, DISCONNECT, PROVIDES POWER TO:

- BUILDING 108 (HOTEL EMPLOYEE HOUSING)

LOCATION "DD": EXIST. KF MAIN LAND

POTTING WATER PUMP HOUSE

(BUILDING 112),

NEW LV FEEDER - 125A, 3PH, 4W,

GROUND TO BE PROVIDED FROM

POWER DISTRIBUTION BOARD "PDB-2"

LOCATED ADJACENT TO GEN 2

LOCATION AS INDICATED TO BE

CONNECTED TO EXISTING PUMP HOUSE

BUILDING LOCATED POWER PANEL.

BOAT

HOUSE

TRADING

POST

3PH MV SERVICE FEEDER

ROUTE IN DUCTBANK RUN

UNDERGROUND UNDER

ROADWAY (IF PROPOSED

BACKUP POWER GENERATOR

GEN-1 LOCATION IS

CONSIDERED ADJACENT OR

BEHIND MAINTENANCE SHOP)

LOCATION FOR 4 - FUTURE CABINS

(CAMP LOGS) (EACH CABIN SHALL

REQUIRE 7.5KW SINGLE PHASE POWER) 3PH MV MAIN SERVICE

FEEDER ROUTE IN

DUCTBANK RUN ABOVE

GROUND IN WOODS

PROPOSED BACKUP POWER DIESEL

GENERATOR GEN-1 LOCATION #1A-2

PROPOSED 3PH MV SERVICE

FEEDER AND LV FEEDER 1000A,

3PH, 4W, 208/120V AC FROM

"PDB-1" LOCATED ADJACENT TO

GEN-1 LOCATION ROUTE IN

DUCTBANK RUN UNDERGROUND

UNDER ROADWAY

ALTERNATE BACKUP POWER

DIESEL GENERATOR (GEN-1)

(ALTERNATE LOCATION #1B)

NOTE: IF THIS LOCATION IS

SELECTED FOR BACKUP

GENERATOR, PROPOSED MV

SERVICE FEEDER AND MV

FEEDER SECTION JB SHALL

BE LOCATED AT THIS

LOCATION INSTEAD OF

INDICATED LOCATION AT "O".

SEWAGE PUMPS

STATION AREA

DIESEL FUEL

PUMPING STATION

DIESEL FUEL

STORAGE TANKS

(2 QTY)

PROPOSED LV

SERVICE FEEDER

ROUTE IN DUCTBANK,

RUN UNDERGROUND

UNDER ROADWAY

PROPOSED 3PH MV SERVICE

FEEDER ROUTE IN DUCTBANK

RUN UNDERGROUND UNDER

ROADWAY

WETLAND AREA - PROPOSED

3PH MV SERVICE FEEDER

ROUTE IN DUCTBANK RUN

ABOVE GROUND, MOUNTED

UNDER RAISED WALKWAY

PROPOSED BACKUP POWER

DIESEL GENERATOR GEN-2,

LOCATION #2A

PROPOSED 3PH MV SERVICE

FEEDER ROUTE IN DUCTBANK

RUN UNDERGROUND UNDER

ROADWAY

FUTURE 4-RV TRAILERS LOCATION (EACH TRAILER

WILL REQUIRE 10.0KW, 50A, 1PH POWER)

REQUIRED LV POWER (208/120V AC, 1PH, 3W,

GROUNDED SHALL BE OBTAINED FROM PROPOSED

POWER DISTRIBUTION BOARD "PDB-2"

PROPOSED 3PH LV SERVICE

FEEDER ROUTE IN DUCTBANK RUN

UNDERGROUND UNDER ROADWAY

PROPOSED LV SERVICE FEEDER ROUTE IN

DUCTBANK RUN UNDERGROUND UNDER ROADWAY

PROPOSED LV SERVICE FEEDER ROUTE IN

DUCTBANK RUN UNDERGROUND UNDER ROADWAY

PROPOSED BACKUP POWER DIESEL GENERATOR

GEN-2 LOCATION #2B IN LIFT PUMP STATION AREA,

LOCATION #2BNOTE: IF THIS LOCATION IS

SELECTED FOR BACKUP POWER GENERATOR,

PROPOSED MV SERVICE FEEDER AND MV FEEDER

SECTION JB SHALL BE LOCATED TO THIS LOCATION

INSTEAD INDICATED LOCATION AT "DD".

LIFT PUMPS STATION AREA

PROPOSED LV SERVICE FEEDER ROUTE IN

DUCTBANK RUN UNDERGROUND UNDER ROADWAY

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

MV

LV

LV

LV

LV

LV

PROPOSED BACKUP POWER DIESEL

GENERATOR GEN-1 LOCATION #1A-1

PROPOSED LV FEEDER 100A, 3PH, 4W,

GROUND IN CONDUIT RUN UNDERGROUND

FROM POWER DISTRIBUTION BOARD "PDB-1"

LOCATED ADJACENT TO GEN 1 LOCATION.

CRIBBED WALKWAY PATH, EXIST. MV CABLE

FEEDER RUN UNDERGROUND CONDUIT. EXISTING

MV FEEDER SHALL BE REMOVED AND DEMOLISHED.

EXISTING CONDUIT SHALL REMAIN.

LOCATION "BB"

NEW LV FEEDER - 200A, 3PH, 4W, GROUND TO BE

PROVIDED FROM POWER DISTRIBUTION BOARD "PDB-2"

LOCATED ADJACENT TO GEN 2 LOCATION AS

INDICATED TO BE CONNECTED TO EXISTING LIFT

STATION PUMPS POWER PANEL PROVIDES POWER TO

LIFT PUMPS

J

LV

LV

LV

LV

LV

LV

LV

LOCATION "X"

NEW LV FEEDER - 200A, 3PH, 4W, GROUND TO BE PROVIDED FROM

POWER DISTRIBUTION BOARD "PDB-2" LOCATED ADJACENT TO

GEN 2 LOCATION AS INDICATED TO BE CONNECTED TO EXISTING

LV POWER 3P, 4W, 208/120V AC RATED DISCONNECTS, ONE (200A

RATED AND SECOND (125A RATED) POWER SUPPLY TO:

- GUEST VILLA HOUSE #110 (JESSIE HOUSE) (3PH, 125A SERVICE)

- GUEST VILLA HOUSE #111 (BEAR POINT LODGE LEARNING

CENTER) (3PH, 200A SERVICE)

- WASTE WATER LIFT PUMPS STATION

LOCATION "O"

NEW LV FEEDER - 200A, 3PH, 4W, GROUND TO BE PROVIDED FROM

POWER DISTRIBUTION BOARD "PDB-1" LOCATED ADJACENT TO GEN 1

LOCATION. EXISTING ENERGY METER SHALL BE DEMOLISHED AND

REPLACED WITH NEW 200A, 3PH, 4W, 208/120V, 60HZ SERVICE IN

NEMA 3R ENCLOSOURE, PROVIDE 3 POLE, 200A RATED HEAVY DUTY

LOCKABLE DISCONNECT IN NEMA 3R OUTDOOR RATED ENCLOSURE

WITH (3) 150A FUSES. PROVIDES POWER TO FOLLOWING LOADS:

1. LOAD END OF NEW DISCONNECT SHALL BE CONNECTED TO

EXISTING 1PH, 100A, 3W DISCONNECT TO SUPPLY POWER TO

EXISTING LV POWER DISCONNECT (2 POLE, 100A, 240/120V RATED).

SUPPLY POWER TO FACILITY MAINTENANCE SHOP BUILDING.

2. TO FUTURE FOUR(4) CAMP CABINS TO BE INSTALLED AS

INDICATED LOCATION. EACH CABIN PROVIDED WITH 7.5KW, 1PH, 3

WIRE LOAD DISCONNECT - 40A, 1PH, 3W, 208/120V RATED

DISCONNECT.

LOCATION "O"

LOCATION FOR 3PH MV SERVICE FEEDER

SECTIONALIZED JUNCTION BOX (4-WAY), PAD MOUNTED

(IF GEN-1 LOCATION IS CONSIDERED IN THIS AREA)

EXIST. FACILITY MAINTENANCE SHOP SHED

PROPOSED LOCATION FOR,

- TRANSFORMER "T1",

- LV AUTOMATIC TRANSFER SWITCH "ATS-1",

- LV POWER DISTRIBUTION BOARD "PDB-1".

LOCATION OF THESE EQUIPMENT IS

ADJACENT TO GEN-1 LOCATION AND ON PAD

MOUNT, OUTDOOR TYPE NEMA 3R RATED

LV

LOCATION "DD": PROPOSED LOCATION FOR 3PH

NEW MV SERVICE FEEDER SECTIONALIZED

JUNCTION BOX (3-WAY), PAD MOUNTED (IF GEN-2

LOCATION IS CONSIDERED IN THIS AREA)

J

LOCATION "EE"

3PH MV MAIN SERVICE FEEDER

PAD MOUNT SECTIONALIZED

JUNCTION BOX "1A" (4 WAY)

J

PROPOSED LOCATION FOR,

- TRANSFORMER "T2",

- LV AUTOMATIC TRANSFER SWITCH "ATS-2",

- LV POWER DISTRIBUTION BOARD "PDB-2".

LOCATION OF THESE EQUIPMENT IS ADJACENT TO

GEN 1 LOCATION AND ON PAD MOUNT, OUTDOOR

TYPE NEMA 3R RATED

LV

LV

LV

LV

LV

LV

LV

LV

LV

LV

LV

LV

LV

MV

MV

MV

MV

MV

MV

MV

MV

PROPOSED NEW MAIN MV

SERVICE FEEDER 3PH, 12.4KV

RATED TO KF DISTRICT MAIN

LAND FROM RIVER FROM NEW

SECTIONALIZED JUNCTION BOX

AT LOCATION "L".

Prepared/Date: NES 1/23/24 Checked/Date: AKD 1/23/24

N

SCALE IN FEET

NPS VOYA - Voyageurs National Park, MN

0 100 200

LEGEND VOYA WAYPOINTS

PAD MOUNTED JUNCTION BOX

PAD MOUNTED TRANSFORMER

GROUND ELEVATION CONTOUR

5 FOOT

1 FOOT

ABOVE GROUND

BELOW GROUND

DEMOLISH

J

EXISTING ELECTRICAL LOCATIONS:

3 PHASE LEG - A

3 PHASE LEG - B

3 PHASE LEG - C

3 PHASE TRANSMISSION LINE

ABBREVIATIONS:

MV - MEDIUM VOLTAGE

LV - LOW VOLTAGE

PROPOSED ELECTRICAL LOCATIONS:

PROPOSED PATH (EXISTING) - A

PROPOSED PATH (EXISTING) - B

PROPOSED PATH (NEW) - A

PROPOSED PATH (NEW) - B

PROPOSED PATH (NEW) - C

PROPOSED PATH (NEW) - D

Figure 16

Kettle Falls District Existing and Proposed Plan

Two Backup Power Generators Option

NOTE:

1. FOR DUCTBANK \ CONDUIT LENGTHS

REFER TO DRAWING FIGURE 13.

MV 3PH SERVICE

FEEDER RUN IN

RIVER

UNDERWATER

KETTLE FALLS

ISLAND BOUNDARY

GFI

M

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERWATER

EXIST. MV 3PH

FEEDER LINE RUNS

UNDERGROUND

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

COMPANY

HOUSE

NPS

GARAGE

TRADING

POST

BLDG

BOAT

HOUSE

DIESEL FUEL

STORAGE

TANKS

DIESEL FUEL

DISP. PUMP

STATION

EXIST.

LV

PANEL

EXIST. LIFT

PUMP STATIONS

POWER PANELS

EXIST.

LV

PANEL

DOCK

POWER

DIESEL

FUEL DISP.

PUMP

DOCK

HOUSE

SHED

DIESEL

FUEL

PUMP

KETTLE FALLS ISLAND - MV & LV POWER DISTRIBUTION EXISTING AND DEMOLITION SINGLE LINE DIAGRAM

RIVERSIDE (UNDERWATER) BOUNDARY

EXIST. MV 3PH

SERVICE FEEDER

ENTERS KF DISTRICT

MAIN LAND

EXIST. MV 3PH

FEEDER LINE RUNS IN

RIVER UNDERWATER

EXIST. MV 3PH SERVICE

FEEDER ENTERS KF

DISTRICT MAIN LAND

EXIST. TRANSFORMERS 3-1PH, 7.5KVA EACH, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED, SECONDARY -

208/120V, 3W + GND. PAD MOUNTED

EXIST. 100A, 1PH, 208/120V

RATED, 3W + GND PANELBOARD

WITH 2P, 100A BRANCH CB

FEEDS MAINT. WORKSHOP

LOCATED PANEL

(LOCATION "O")

EXIST. MAINT.

SHOP BLDG

EXIST. 100A, 1PH, 208/120V,

3W + GND FEEDER RUN IN

CONDUIT UNDERGROUND

EXIST. MV SECTION

JB (LOCATION "P-Q")

EXIST. TRANSFORMER 1PH, 37.5KVA,

PRIMARY - 12.47/ 7.2KV, 1PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3W + GND. PAD MOUNTED

EXIST. MV SECTION

JB (LOCATION "R")

EXIST. TRANSFORMER 1PH, 15KVA, PRIMARY -

12.47/ 7.2KV, 1PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W + GND. PAD MOUNTED

EXIST. BOAT

SHED STORAGE

EXIST. LV 50A, 1PH, 208V, 3W + GND

FEEDER RUN IN UNDERGROUND CONDUIT

EXIST. 50A, 1PH,

208/120V, 3W + GND

PANELBOARD WITH

2P, 50A MAIN CB

(LOCATION "R")

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

(LOCATION "T")

EXIST. TRANSFORMER

PRIMARY - 12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3W +

GND, 3-100KVA, 208/120V, 3W,

PAD MOUNTED

EXIST. MV SECTION

JB (LOCATION "U")

EXIST. MV SECTION

JB (LOCATION "V")

(LOCATION "V")

(LOCATION "X")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH, 4W +

GND. PAD MOUNTED

(LOCATION "W")

EXIST. TRANSFORMER 3PH,

75KVA, PRIMARY - 12.47/ 7.2KV,

3PH, NEUTRAL GROUNDED,

SECONDARY - 208/120V, 3PH,

4W + GND. PAD MOUNTED

EXIST. 3PH, 200A, 208V,

4W, FUSED DISCONNECT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

(LOCATION "DD")

EXIST. TRANSFORMER

3PH, 45KVA, PRIMARY -

12.47/ 7.2KV, 3PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

3PH, 4W + GND. PAD

MOUNTED

(LOCATION "U")

(LOCATION "AA")

EXIST. BLDG #108 (HOUSE FOR

HOTEL EMPLOYEES)

(LOCATION "CC")

EXIST. TRANSFORMER 3PH, 75KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

(LOCATION "BB")

EXIST. TRANSFORMER 3PH, 45KVA,

PRIMARY - 12.47/ 7.2KV, 3PH, NEUTRAL

GROUNDED, SECONDARY - 208/120V,

3PH, 4W + GND. PAD MOUNTED

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. 200A, 1PH,

208/120V RATED, 3W

+ GND PANELBOARD

WITH MLO

EXIST. MV SECTION

JB (LOCATION "Y")

EXIST. TRANSFORMER

1PH, 37.5KVA, PRIMARY -

12.47/ 7.2KV, 1PH,

NEUTRAL GROUNDED,

SECONDARY - 208/120V,

1PH, 3W + GND. PAD

MOUNTED

(LOCATION "Y")

EXIST. MV SECTION

JB (LOCATION "N")

MV SECTION JB (4-WAY)

(LOCATION "O")

EXIST. MV 3PH

LINE IN CONDUIT

UNDERGROUND

EXIST. LV 208/120V AC FEEDERS

IN CONDUIT RUN UNDERGROUND

EXIST. LV FEEDER

(20A, 120V AC) IN

UNDERGROUND

CONDUIT

EXIST. LV FEEDER

(20A, 120V AC) IN

UNDERGROUND

CONDUIT

EXIST. MV 3PH

LINE IN

UNDERGROUND

CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. MV 3PH LINE IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

NOTES:

1. FOR SITE LAYOUT - REFER TO FIGURE 13.

2. ALL EQUIPMENT AND FEEDERS SHOWN ARE

EXISTING UNLESS OTHERWISE NOTED.

MV SECTION JB

(LOCATION "L")

AT ISLAND

3PH MV MAIN

SERVICE FEEDER

LOCATION "EE": 3PH MV LINE

4-WAY SECTION JB "1A"

MAIN MV 3PH SERVICE FEEDER

ENTERS KF DISTRICT MAIN LAND

EXIST.

LV PNL

EXIST.

LV PNL

EXIST.

LV PNL

EXIST.

LV PNL

EXIST.

LV PNL

(LOCATION "P-Q")

LOCATED OUTSIDE EXIST.

KETTLE FALLS HOTEL BLDG

EXIST. LV 1200A, 3PH,

208/120V, 4W + GND FEEDER

EXIST. 1200A, 3PH,

208/120V RATED, 4W + GND

POWER DISTRIBUTION

SWITCHBOARD WITH 3P,

1200A MAIN CB

FEED

PUMPS

STATIONS

EXIST. LV FEEDER IN

UNDERGROUND CONDUIT

M

EXIST.

LV

SWITCHBOARD

EXIST. GENERATOR HOUSE

EXIST. FIRE PUMP FUSED

DISCONNECT, 100A, 208V

AC RATED, 3PH, 3W, 60HZ

TO BE DEMOLISHED

TO EXIST. FIRE PUMP

FOR HOTEL BLDG

FIRE PROTECTION

EXIST. LV FEEDER TO BE DISCONNECTED

AND REMOVED AND RECONNECTED

FROM MOTEL/ HOTEL SECONDARY

SERVICE FEEDER

EN

L

NOTE: THERE IS NO

EXIST. EM GENERATOR

EQUIPMENT

EM POWER

PANEL "ED"

EXIST. ATS (AUTOMATIC

TRANSFER SWITCH),

200A, 208/120V AC RATED,

3PH, 4W, GND, 60 HZ TO

BE DEMOLISHED

EXIST. EM POWER PANEL

"ED", 100A, 3PH, 4W,

208/120V AC RATED, 60 HZ

TO BE DEMOLISHED

EXIST. LV FEEDER TO EXIST. FISH CLEANING SHED

POWER SHALL BE DISCONNECTED AND REMOVED.

POWER SUPPLY AND NEW FEEDER IN CONDUIT TO

FISH CLEANING SHED SHALL BE INSTALLED FROM

EXIST. MOTEL/ HOTEL LV POWER PANEL

EXIST. LV FEEDER TO BE

DISCONNECTED AND

REMOVED

EXIST. LV FEEDER TO MOTEL/ HOTEL

BUILDING EXTERIOR LOCATED

PANEL "E" (PANEL SUPPLIES POWER

TO EM LIGHTING, FIRE ALARM AND

FIRE SUPPRESSION SYSTEM

EQUIPMENT. PANEL "E" POWER

SUPPLY SHALL BE CONNECTED TO

SWITCHBOARD.

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "J"

EXIST. 3PH, 200A, 208V, 4W,

FUSED DISCONNECT "A"

EXIST.

LV

PNL "J"

EXIST. GUEST VILLA HOUSE

#110 (JESSIE HOUSE)

EXIST. LV 125A FEEDER IN

UNDERGROUND CONDUIT

EXIST. 125A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "J" WITH 3P,

125A MAIN CB

EXIST. GUEST VILLA HOUSE #111 (BEAR

POINT LODGE LEARNING CENTER)

EXIST. LV 200A FEEDER IN

UNDERGROUND CONDUIT

EXIST. 200A, 3PH, 208/120V

RATED, 4W + GND

PANELBOARD "A" WITH 3P,

200A MAIN CB

M

M

EXIST.

LV

PNL "A1"

EXIST.

LV

PNL "A"

EXIST. 100A, 3PH,

208/120V RATED,

4W + GND

PANELBOARD "A1"

WITH MLO

EXIST. GUEST VILLA HOUSE #109

(LEARNING PINE LODGE)

EXIST. 200A, 3PH, 208/120V RATED,

4W + GND PANELBOARD "B" WITH MLO

M

EXIST.

LV

PNL "B"

EXIST.

LV

PNL "B1"

EXIST. 100A, 3PH,

208/120V RATED, 4W +

GND PANELBOARD "B1"

WITH MLO

M M MM

EXIST.

LV

PANEL

EXIST.

LV

PANEL

M

M

M

M

EXIST.

LV PNL

EXIST. 100A, 1PH,

208/120V, 3W + GND

PANELBOARD WITH MLO

EXIST. 100A, 1PH, 208/120V, 3W + GND

PANELBOARD WITH 2P, 100A MAIN CB

EXIST. METER SHALL REMAIN

AND SHALL BE RELOCATED

EXIST.

LV

PANEL

EXIST. 100A, 1PH,

208/120V RATED,

3W + GND

PANELBOARD

EXIST. 100A, 1PH, 208/120V

RATED,…