This document is an amendment to the pre-bid instructions for Solicitation 140P2024R0130, titled "Voya 308690: Replace Power Distribution". The solicitation is issued by the Department of the Interior National Park Service National Office to replace the main underwater high voltage cable and multiple transformer boxes, as well as install improved emergency backup generation, for the Kettle Falls district. The project is necessary due to safety risks posed by the compromised neutral wire, which can lead to power outages and issues with fire suppression and concessions operations. The amendment provides clarification and updates to the pre-bid instructions, including revised dates for the site visit and submission of questions. No further details about required products or services, pricing, or award information are provided in this specific document.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PreBid Instructions – September 5, 2024 Subject: VOYA 308690 – Replace Electrical Line to Kettle Falls, Voyageurs National Park

Solicitation Number: 140P2024R0130

A Prebid Conference is scheduled for Tuesday, September 17, 2024 on site at Voyageurs

National Park, To receive an invite, please send an email to:

Subject: “VOYA 308690 ‐ Request PreBid Invitation”

To: timothy_burger@nps.gov; and brian_baugh@contractor.nps.gov

Include contact info for all attendees: (Company, Name, Email, Phone#)

Please note that the site visit will include a ride on an NPS vessel along the project site (following the existing power line alignment and junction boxes along the shore) and tour of the Kettle Falls developed area. Pending the amount of interested firms a second day may be necessary to accommodate and would take place on Wednesday, September 18, 2024.

Please send any questions to timothy_burger@nps.gov and brian_baugh@contractor.nps.gov.

Pre Bid Meeting Location: Lavine Cabin (near Ashe River Visitor Center Area) 9763 Meadwood Rd Orr, MN 55771

A Virtual Meeting at the Cabin near the dock on Tuesday Sept 17 at 9:00 Central (8:00 MST) will take place to discuss administrative requirements followed by a briefing from contracting.

Plan for +/‐ 5 hrs on site.

It is recommended to bring water, snacks, Bug spray and sunscreen.

NPS shall provide life vests.

St ag in g

A re a

B ar ge

B oa t D oc ki ng

St ag in g

A re a

Fi gu re

As h

R iv er C on tra ct or

A re a

N

PS

V O

YA

Ke ttl e Fa lls Vo ya ge ur s

N at io na l P ar k, M

N

.5

Fe et

Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 3 - Ash River Contractor Area.pdf 03/15/2024 11:45 AM nathan.soule

Le ge nd

W or k an d St ag in g Ar ea

Pr ep ar ed

/D at e:

N

ES

3/

/2

C he ck ed

/D at e:

J

W P

/1

5/

"AA

"AA

NPS Side

Barge Launch Area

Boat Docking Overnight

Legend "AAWork and Staging Location

Work and Staging Area

075 37.5 Feet

Prepared/Date: NES 03/15/24Checked/Date: JWP 03/15/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 4 - Alternate Docking Area.pdf 03/15/2024 11:45 AM nathan.soule

Figure 4 Alternate Docking Area

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

"AA

"AA

"AA

Kettle Falls Docking Area

Alternative Docking Area

Ash River Docking Area

04 2 Miles

Index Map

Active working area for NPS.

Can't block bays or left side.

Can't close road.

NPS Staff & Concessions use this road daily during the season.

"Road Closed to Public" Sign

Barge Offload & Fueling

Concession House Used During the Season

Concession Garage & Work Area by Road

"Road Closed to Public" Sign

Road to Staging & Storage Area

Storage Area, Limited Parking Area, Work Zone

Barge, Fueling, & Docking Area - Concession Owned -

Need permission to use docks.

More slips are missing (winter image)

Approved Houseboat Docking Area for Barge

Legend

AA

Docking and Staging Areas

0150 75 Feet

Prepared/Date: NES 03/15/24Checked/Date: JWP 03/15/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 5 - Kettle Falls Contractor Area.pdf 03/15/2024 11:45 AM nathan.soule

Figure 5 Kettle Falls Contractor Area

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

A

B

C

D

E

Hoist Bay

%UJ

%UJ

%UJ

Í w ABC

"AM

Legend

%UJJunction Box

"AMCT Metering Junction Box

22Recloser

Í w ABC 3UG Transformer

Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Approximate Existing 1-Phase Transmission Line 01,100 550

Feet

Prepared/Date: NES 04/02/24Checked/Date: JWP 04/02/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_TLine_Route_Fig4_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 06_Locations A-E.pdf 04/02/2024 8:05 AM nathan.soule

Figure 6 Locations A-E

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

03 1.5 Miles

* Bathymetric data source: Minnesota Geospatial Information Office

E

F

G

H

%UJ

%UJ

%UJ

%UJ

50 30

CANADA

UNIT

ED

STA

TES

Legend

%UJJunction BoxBathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line United States - Canada Border

01,100 550 Feet

Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 05_Locations E-H.pdf 01/24/2024 8:05 AM nathan.soule

Figure 7 Locations E-H

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

03 1.5 Miles

H

I

J

%UJ

%UJ

CANADA

UNIT

ED

STA

TES

Legend

%UJJunction Box

22Recloser

Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Approximate Transmission Line Cable Replaced CIRA 2021 United States - Canada Border

01,100 550 Feet

Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 06_Locations H-J.pdf 01/24/2024 8:05 AM nathan.soule

Figure 8 Locations H-J

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

03 1.5 Miles

J

K

L M

N

O

P & Q

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

Í w

Í w

CANADA

UNITEDSTATES

Legend

%UJJunction Box

Í wUG Transformer

Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls United States - Canada Border 01,100 550

Feet

Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 07_Locations J-Q.pdf 01/24/2024 8:05 AM nathan.soule

Figure 9 Locations J-Q

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

03 1.5 Miles

N

O

P & Q

R & S

T

U V & W

X

Y & Z

AA

BB

CC

DD

%UJ

%UJ

%UJ

%UJ

%UJ

%UJ

Í w

Í w

Í w

Í w

Í w

Í w

Í w

Í w Í w

Í w

425 10

CANADA

UNITEDSTATES

Legend

%UJJunction Box

Í wUG Transformer

Bathymetric Contour Interval*:

5-foot 10-foot

Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls United States - Canada Border 0300 150

Feet

Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_KF_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 08_KF Historical District.pdf 01/24/2024 8:05 AM nathan.soule

Figure 10 Kettle Falls District

NPS VOYA - Kettle Falls Voyageurs National Park, MN

Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe

!î

03 1.5 Miles

File details come from the government source that posted it. Updated .