This document is an amendment to the pre-bid instructions for Solicitation 140P2024R0130, titled "Voya 308690: Replace Power Distribution". The solicitation is issued by the Department of the Interior National Park Service National Office to replace the main underwater high voltage cable and multiple transformer boxes, as well as install improved emergency backup generation, for the Kettle Falls district. The project is necessary due to safety risks posed by the compromised neutral wire, which can lead to power outages and issues with fire suppression and concessions operations. The amendment provides clarification and updates to the pre-bid instructions, including revised dates for the site visit and submission of questions. No further details about required products or services, pricing, or award information are provided in this specific document.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PreBid Instructions – September 5, 2024 Subject: VOYA 308690 – Replace Electrical Line to Kettle Falls, Voyageurs National Park
Solicitation Number: 140P2024R0130
A Prebid Conference is scheduled for Tuesday, September 17, 2024 on site at Voyageurs
National Park, To receive an invite, please send an email to:
Subject: “VOYA 308690 ‐ Request PreBid Invitation”
To: timothy_burger@nps.gov; and brian_baugh@contractor.nps.gov
Include contact info for all attendees: (Company, Name, Email, Phone#)
Please note that the site visit will include a ride on an NPS vessel along the project site (following the existing power line alignment and junction boxes along the shore) and tour of the Kettle Falls developed area. Pending the amount of interested firms a second day may be necessary to accommodate and would take place on Wednesday, September 18, 2024.
Please send any questions to timothy_burger@nps.gov and brian_baugh@contractor.nps.gov.
Pre Bid Meeting Location: Lavine Cabin (near Ashe River Visitor Center Area) 9763 Meadwood Rd Orr, MN 55771
A Virtual Meeting at the Cabin near the dock on Tuesday Sept 17 at 9:00 Central (8:00 MST) will take place to discuss administrative requirements followed by a briefing from contracting.
Plan for +/‐ 5 hrs on site.
It is recommended to bring water, snacks, Bug spray and sunscreen.
NPS shall provide life vests.
St ag in g
A re a
B ar ge
B oa t D oc ki ng
St ag in g
A re a
Fi gu re
As h
R iv er C on tra ct or
A re a
N
PS
V O
YA
Ke ttl e Fa lls Vo ya ge ur s
N at io na l P ar k, M
N
.5
Fe et
Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 3 - Ash River Contractor Area.pdf 03/15/2024 11:45 AM nathan.soule
Le ge nd
W or k an d St ag in g Ar ea
Pr ep ar ed
/D at e:
N
ES
3/
/2
C he ck ed
/D at e:
J
W P
/1
5/
"AA
"AA
NPS Side
Barge Launch Area
Boat Docking Overnight
Legend "AAWork and Staging Location
Work and Staging Area
075 37.5 Feet
Prepared/Date: NES 03/15/24Checked/Date: JWP 03/15/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 4 - Alternate Docking Area.pdf 03/15/2024 11:45 AM nathan.soule
Figure 4 Alternate Docking Area
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
"AA
"AA
"AA
Kettle Falls Docking Area
Alternative Docking Area
Ash River Docking Area
04 2 Miles
Index Map
Active working area for NPS.
Can't block bays or left side.
Can't close road.
NPS Staff & Concessions use this road daily during the season.
"Road Closed to Public" Sign
Barge Offload & Fueling
Concession House Used During the Season
Concession Garage & Work Area by Road
"Road Closed to Public" Sign
Road to Staging & Storage Area
Storage Area, Limited Parking Area, Work Zone
Barge, Fueling, & Docking Area - Concession Owned -
Need permission to use docks.
More slips are missing (winter image)
Approved Houseboat Docking Area for Barge
Legend
AA
Docking and Staging Areas
0150 75 Feet
Prepared/Date: NES 03/15/24Checked/Date: JWP 03/15/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_WorkAreas_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Figure 5 - Kettle Falls Contractor Area.pdf 03/15/2024 11:45 AM nathan.soule
Figure 5 Kettle Falls Contractor Area
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
A
B
C
D
E
Hoist Bay
%UJ
%UJ
%UJ
Í w ABC
"AM
Legend
%UJJunction Box
"AMCT Metering Junction Box
22Recloser
Í w ABC 3UG Transformer
Bathymetric Contour Interval*:
5-foot 10-foot
Approximate Existing 3-Phase Transmission Line Approximate Existing 1-Phase Transmission Line 01,100 550
Feet
Prepared/Date: NES 04/02/24Checked/Date: JWP 04/02/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_TLine_Route_Fig4_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 06_Locations A-E.pdf 04/02/2024 8:05 AM nathan.soule
Figure 6 Locations A-E
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
!î
03 1.5 Miles
* Bathymetric data source: Minnesota Geospatial Information Office
E
F
G
H
%UJ
%UJ
%UJ
%UJ
50 30
CANADA
UNIT
ED
STA
TES
Legend
%UJJunction BoxBathymetric Contour Interval*:
5-foot 10-foot
Approximate Existing 3-Phase Transmission Line United States - Canada Border
01,100 550 Feet
Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 05_Locations E-H.pdf 01/24/2024 8:05 AM nathan.soule
Figure 7 Locations E-H
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
!î
03 1.5 Miles
H
I
J
%UJ
%UJ
CANADA
UNIT
ED
STA
TES
Legend
%UJJunction Box
22Recloser
Bathymetric Contour Interval*:
5-foot 10-foot
Approximate Existing 3-Phase Transmission Line Approximate Transmission Line Cable Replaced CIRA 2021 United States - Canada Border
01,100 550 Feet
Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 06_Locations H-J.pdf 01/24/2024 8:05 AM nathan.soule
Figure 8 Locations H-J
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
!î
03 1.5 Miles
J
K
L M
N
O
P & Q
%UJ
%UJ
%UJ
%UJ
%UJ
%UJ
Í w
Í w
CANADA
UNITEDSTATES
Legend
%UJJunction Box
Í wUG Transformer
Bathymetric Contour Interval*:
5-foot 10-foot
Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls United States - Canada Border 01,100 550
Feet
Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 07_Locations J-Q.pdf 01/24/2024 8:05 AM nathan.soule
Figure 9 Locations J-Q
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
!î
03 1.5 Miles
N
O
P & Q
R & S
T
U V & W
X
Y & Z
AA
BB
CC
DD
%UJ
%UJ
%UJ
%UJ
%UJ
%UJ
Í w
Í w
Í w
Í w
Í w
Í w
Í w
Í w Í w
Í w
425 10
CANADA
UNITEDSTATES
Legend
%UJJunction Box
Í wUG Transformer
Bathymetric Contour Interval*:
5-foot 10-foot
Approximate Existing 3-Phase Transmission Line Proposed Approach to Kettle Falls United States - Canada Border 0300 150
Feet
Prepared/Date: NES 01/24/24Checked/Date: JWP 01/24/24 ¯ Document: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\MapDocuments\NPS_VOYA_Tline_Route_KF_11x17LS.mxd PDF: X:\US\USPWM100-PLD2\Project\Projects\NPS VOYA GIS\NPS_VOYA_GIS\Figures\Fig 08_KF Historical District.pdf 01/24/2024 8:05 AM nathan.soule
Figure 10 Kettle Falls District
NPS VOYA - Kettle Falls Voyageurs National Park, MN
Imagery: Google, Maxar Technologies, Landsat/Copernicus, DigitalGlobe
!î
03 1.5 Miles
File details come from the government source that posted it. Updated .