B09-_P1525Q0097_Amendment_Questions_and_Answers_0001.pdf
PDF 141 KB Posted
- Solicitation number
- 140P1525Q0097
About this file
This document is an Amendment (Amendment #0001) to a National Park Service solicitation for a pressure pump replacement project at Tuzigoot National Monument in Clarkdale, Arizona. The amendment includes a questions and answers section addressing technical details about the pump installation. Specifically, the document responds to two contractor questions: one requesting pictures of pump and motor installation, which are provided in the attachment, and another about potential use of a Variable Frequency Drive (VFD). The government clarified that the pumps are controlled by mercoid switches with on/off setpoints based on pressure tank levels, and do not require a VFD. The solicitation number is 140P1525Q0097, and the contracting officer is Taylor Jones, who can be reached at Taylor_A_Jones@nps.gov or 520-780-9294. The attached image shows blue pumps mounted on a concrete base with complex piping and valves in what appears to be a mechanical room or booster pump station.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B09-_P1525Q0097_Amendment__2_0002.pdf | ||
| Sol_140P1525Q0097_Amd_0002.pdf | ||
| Sol_140P1525Q0097_Amd_0001.pdf | ||
| Sol_140P1525Q0097.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of the Interior
NATIONAL PARK SERVICE
CONTRACTING OPERATIONS - CENTRAL
1849 C Street
NW Washington, DC 20240
General: No other solicitation clauses or dates change with this Amendment.
Contracting Officer: Taylor Jones, Taylor_A_Jones@nps.gov, 520-780-9294
Solicitation #: 140P1525Q0097
Amendment #: 0001
Pressure Pump Replacement – TUZI
Questions and Government Responses listed below:
QUESTIONS:
Question # Question Answer/Response
1. Could you please provide pictures showing how the pumps and motor are installed within the booster pump room?
Refer to below picture.
2. Additionally, we understand that a Variable Frequency
Drive (VFD) is recommended. Can you also share pictures of the electrical installations, including any existing VFD panel or motor starters?
The pumps are not controlled by a variable frequency drive (VFD), nor do they require one in this situation.
They are controlled by mercoid switches with on off setpoints based on pressure in the pressure tank.
mailto:Taylor_A_Jones@nps.gov
United States Department of the Interior
NATIONAL PARK SERVICE
CONTRACTING OPERATIONS - CENTRAL
1849 C Street
NW Washington, DC 20240
General: No other solicitation clauses or dates change with this Amendment.