This document is a Standard Form 30 Amendment of Solicitation/Modification of Contract for the NIFC 300 JWH MPR Suite and NICC Repairs project. Amendment 0003, effective 06/10/2025, was issued by the Bureau of Land Management Fire and Aviation division in Boise, Idaho. The amendment provides responses to Request for Information (RFI) and questions received during the solicitation process, updates specifications and drawings, and removes references to Bid Alternate B, which involved an exterior rooftop patio.

Key details include clarifications on multiple technical aspects such as access control system requirements (FICAM compliant PACS with CSEIP certification), furniture removal and replacement, raised floor specifications (TECCRETE System 1250 with 900 lbs dynamic load rating), and confirmation that the project is an interior tenant improvement with no sitework. The solicitation covers infrastructure repairs for two areas: the Multi-Purpose Room (MPR) and the National Interagency Fire Center (NICC), with specific instructions for mechanical, electrical, and architectural modifications. The project is tax-exempt and has a targeted completion date of 11/14/2025 for the MPR suite.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140L3725R0004 x x

1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

LFA

BOISE ID 83705

3833 S. DEVELOPMENT AVE.

BLM FA-NTL INTRAGCY FIRE CTR(FA250)

06/10/20250003

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

04/24/2025

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PROJECT: NIFC 300 JWH MPR Suite and NICC Repairs

The purpose of this Amendment is to:

1. Provide responses to RFIs/Questions received.

2. Provide Specification/Drawing list of edited/changed by questions/responses.

3. Provide updated Specifications/Drawings, (attached separately).

Continued ...

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Matthew Steele

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

2 15

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

140L3725R0004/0003

This amendment must be acknowledged in accordance with the solicitation.

All other terms and conditions set forth within this solicitation remain unchanged.

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

United States Department of the Interior

BUREAU OF LAND MANAGEMENT

Fire and Aviation 3833 S Development Ave

Boise, Idaho 83705-5354

POST SITE VISIT Q&A June 9, 2025

NIFC 300 JWH MPR Suite/NICC Repairs Solicitation Number 140L3725R0004

CONTRACTOR QUESTIONS GOVERNMENT RESPONSE

1. Access Control Notes state that, "SYSTEM SHALL BE

INSTALLED BY AMAG FACTORY TRAINED/CERTIFIED

TECHNICIAN AND BE A FACTORY AUTHORIZED

INTEGRATOR. ON SITE STAFF SHALL HAVE A CERTIFIED

SYSTEM ENGINEER ICAM PACS (CSEIP)."

I have reached out to an authorized AMAG Dealer and received the following “While we are an Amag Dealer, we currently do not have techs that hold that specification and will therefore not be able to provide you with a proposal for this project…. Honestly, I don't know another integrator that has that certification currently.”

Please evaluate and advise.

1. Our current PACS system is a FICAM Compliant PACS. CSEIP certified is required. Other project on the NIFC campus have been completed within the last year with this same security requirement.

2. Please provide direction regarding the existing furniture, accessories, and other items that currently occupy the space. There is no direction in the current drawings. If the Government wants the contractor to include this item it is imperative that this is addressed in a timely manner to afford time to solicit subcontractor pricing.

2. Construction contractor shall remove and dispose of existing modular furniture as part of this solicitation.

New furniture will be installed by a separate modular furniture contractor under the direction of the government.

Refer to Supplemental Info attachment note 3.

Tables and chairs in MPR Suite will be removed and stored by government

3. Please consider reissuing drawings that cloud or remove all references to alternate “B” for the NICC. This will help the contractor and subcontractors clearly understand the Government’s design intentions and avoid confusion.

3. Solicitation attachment

A06_NIFC_300-JWH_-

_Supplemental_Info lists specific sheets and notes regarding removal of Bid Alternate B, which refers to construction work that would create an exterior rooftop patio.

4. Please clarify the brand and model of the existing raised access flooring as called out on NICC Plans, Sheet AD101A, Keynote 9.

4. Raised floor panel system is a TECCRETE System (1250). Dynamic load rating is 900lbs at 10,000 pass.

5. Please clarify BABA requirements.

5. Refer to Part II “Clauses” 52.225-9

6. Spec Section 281000 Access Controls Specs state that SYSTEM SHALL BE INSTALLED BY AMAG

FACTORY TRAINED/CERTIFIED TECHNICIAN AND BE A

FACTORY AUTHORIZED INTEGRATOR. ON SITE STAFF SHALL

HAVE A CERTIFIED SYSTEM ENGINEER ICAM PACS (CSEIP)."

Our Suppliers are AMAG trained/certified technicians and factory authorized integrators, but do not have CSEIP Certificate. Is this acceptable?

6. Refer to question 1 response.

7. Suite 206 – Server Room Flooring:

What is the floor load capacity for the server room flooring in this suite? We are considering bringing in a scissor lift and need to confirm whether the flooring can support it.

Additionally, we believe this area falls under Alternate B. If Alternate B is no longer being quoted, what is the intended scope for the window sills in that area? What finish should be provided?

7. Refer to question 4 response.

All interior windowsills to be replaced, refer to Keynote 3/4 on sheet IN101A for windowsill finish.

8. Plan Reference – Yellow Area:

Are we able to obtain elevations for the yellow-highlighted area shown in the plans?

8. Yellow area is part of Bid alternative B.

Bid alternate B has been removed from project scope.

No elevations will be provided.

9. TV Wall Area (Photos Attached):

The photos below show an area behind the TV that needs to be covered. Can you confirm whether we need to provide acoustical material to match the panels on the left and right sides?

If so, is there a specific manufacturer or product you recommend to ensure consistency?

9.TV picture appears to be from conference room that is not in scope but was used as a waiting point during the walkthrough.

TV to remain. Refer to drawings and specifications for acoustical panels and their requirement that are specific to this solicitation.

10. What is the load capacity of the raised access floor?

10.Refer to question 4 response

11. NICC - Specification section 096900 Part 2.1.A requires the contractor to engage a qualified professional engineer, as defined in section 014000 “Quality Requirements,” to design access flooring for seismic performance, including loads imposed on the access flooring by items and equipment install on the access flooring. Will this be required? It would seem there is already a design, and it seems more practical to match the existing system rather than have an engineer design one. Please advise.

11. Per sheet AE101A, the existing raised access floor remains with some modifications. The specification requirement for a qualified profession engineer to seismic performance is not required. See response to question 4 for floor type and loading.

12. Will either of these spaces be occupied while construction is taking place?

12. Each suite has its own separate construction schedule as outlined in the contract documents. During this construction schedule, the area will be unoccupied. The remainder of the building will be occupied during construction.

13. At the site visit it was discussed that the elevator would be available for contractor use. What are the dimensions of the elevator?

13. Elevator floor dimensions are approx.

64” x 78”

14. What is the load capacity of the elevator?

14. 3500 lbs max.

15. What are the dimensions of the elevator?

15. Refer to question 13 response.

16. In the NICC plans, plan sheet AD101A keynote 9 calls for demolition of the existing framed raised platform. Is this platform constructed from below the existing raised floor?

16. All raised platforms are installed on top of raised flooring system.

17. Please provide a manufacturer for the existing raised flooring in the NICC area.

17. Refer to question 4 response

18. What are the dimensions of the existing can lights in the soffit of the MPR suite?

18. Existing can lights are 6” diameter.

19. The document titled “A06_NIFC_300-JWH_- _Supplemental_Info (1) states to remove all reference to Bid Alternate B in the plans and specifications. Please confirm the contractor is to disregard anything that references Bid Alternate B.

19. Confirmed.

20. Who is responsible for moving the existing government modular furniture in the MPR and NICC areas prior to and after construction?

20. Refer to question 2 response.

21. The SF1442 states the work in the MPR suite must be completed by 11/14/25. What date will the contractor be able to start work in this area?

21. MPR Suite construction can begin per line item “11. The contractor shall begin performance withing 10 calendar days…”

22. The current bid date is set for Tuesday 11/27/2025 at 10:00 AM. This is the day after Memorial Day. With the long weekend preceding the bid date, would the government consider extending the bid due date by a day or two to allow for more time to coordinate with subcontractors prior to bid?

22. Proposal due date has been extended, see amendment.

23. In the NICC area, room 211 Huddle there is a section of exposed wood framed wall with electrical equipment inside. Is the contractor to leave this wall exposed?

23. Refer to sheet AE101A for wall framing. IT and cable items will be removed prior to award by Government.

Wall shall be covered.

24. Onsite working hours are 8 am to 4:30 pm. Are these hours not negotiable or is it possible for the contractor to work 10 hour days?

24. This will be decided on a case by case basis after award based on security requirements for the building and site.

25. Section 092216 2.2 Framing Systems do not provide a gauge metal thickness for the studs, top and bottom plates.

Please provide.

25. Specifications state thickness is per performance requirements for horizontal deflection. Refer to 092216 2.1 for requirements.

26. I would like to verify that the owner will be removing and storing all cubicles. Please advise.

26. Refer to response of question 20.

27. AD101B Keynote 3: remove all acoustical panels. What is to be done with the acoustic panels?

27. Acoustical panels to be disposed of according to specifications regarding salvage/demolition.

28. The existing carpet in the multi-purpose room, is that rolls or squares?

28. Existing carpet is rolls.

29. Who will be responsible for removing the tables, chairs, and cabinets out of the multi-purpose area? If the contractor is responsible, where will it be taken and will they be required to store it?

29. Refer to response of question 2.

30. The acoustic ceiling in the multi-purpose has 2 long black steel looking plates in the ceiling. What are they?

30. Refer to Keynote 5 on sheet ED10B

31. Sound-Absorbing Wall Units AP2 on the material list size is 3’x5’ but in the specs 2.3, A. 13 & 14 states panel width 48” and panel height 10”. Please advise what the correct sizes are.

31. Follow dimensions on sheet IN601B

32. Sound-Absorbing Wall Units Material list for AP2 Notes:

Install with 2” standoffs-stainless steel. Turf wall panels do not sell standoffs. Please provide standoff manufacture, type, model number that you want as the prices vary.

31. Updated detail included in drawings.

33. Multi-purpose building, the equipment room has ACT but the plans show gyp board ceiling. Sheet AD102B keynote 3 states existing ceiling to remain. I want to confirm that no ceiling work will be required in this room?

Please advise

33. All ACT ceiling tile to be removed and replaced, including in Equipment room 157.

34. MPR gyp board finish specs calls for level 5 finish, but the existing walls are textured. The NICC gyp board finish specs calls for level 4 finish, but the existing walls are textured. Would you like contractors to match textured finish and not the spec?

34. Finishes shall match existing textured walls.

35. MPR & NICC - Specification section 015000 Temporary Facilities and Controls subsection 1.4 E requires the contractor to provide a water pollution prevention plan not less than 30 days prior to the start of construction. Will this be required?

35. No, a plan is not required for the interior work areas.

36. MPR & NICC - Specification section 015000 Temporary Facilities and Controls subsection 1.4 F requires the contractor to submit a Spill Prevention Control and Countermeasure plan and have the plan reviewed and certified by a registered professional engineer. Will this be required?

36. Contractor to provide safety plan to include spill prevention control and countermeasures. Certification by a registered professional engineer is not required.

37. MPR & NICC - Specification section 015000 Temporary Facilities and Controls subsection 3.4 A2 states “Utilize designated area within existing building for temporary field offices.” Please identify the designated area for the contractor’s temporary field office inside the building.

37. Area will be coordinated between contractor and government after award of contract.

38. MPR & NICC - Specification section 015000 Temporary Facilities and Controls subsection 3.4 G states “Safety Facilities: Provide safety showers, eyewash fountains, and similar facilities for safety and sanitation of personnel.” Will this be required?

38. Confirmed, contractor shall provide required safety and sanitation for the construction personnel.

39. MPR & NICC - Specification section 015000 Temporary Facilities and Controls subsection 3.6 D states “Temporary Egress: Provide temporary egress from existing occupied facilities as indicated and as required by authorities having jurisdiction. Provide signage directing occupants to temporary egress.” Please confirm this requirement.

39. Confirmed, contractor shall ensure egress is maintained during construction.

40. NICC - Specification section 084113 Aluminum-Framed Entrances and Storefronts subsection 1.3 D requires submittals to be signed and stamped by a qualified professional engineer. This isn’t typical for storefront assemblies. Please confirm this will be required.

40. Pertains to Bid alternate B, does not apply to project.

41. NICC - Specification section 084113 Aluminum-Framed Entrances and Storefronts subsection 2.2 A requires the contractor to engage a qualified professional engineer to design aluminum-framed entrance and storefront systems.

This isn’t typical for storefront assemblies. Please confirm this will be required.

41. Pertains to Bid alternate B, does not

42. NICC - Specification section 088000 Glazing subsection

1.5 D requires submittals to be signed and stamped by a

qualified professional engineer. Please confirm this will be required.

42. Pertains to Bid alternate B, does not

43. NICC - Specification section 088000 Glazing subsection

2.2 B requires the contractor to engage a qualified

professional engineer to design glazing. Please confirm this will be required.

43. Pertains to Bid alternate B, does not

44. NICC - Specification section 095113 Acoustical Panel Ceilings subsection 2.2 A requires the contractor to engage a qualified professional engineer to design seismic restraints for ceiling systems. Please confirm this requirement

44. Refer to section 014000 1.3 :.

Products and systems need to comply with specific seismic (performance) and design criteria.

45. MPR & NICC - Specification section 013100 Project Management and Coordination subsection 1.4 A & B require the contractor to prepare coordination drawings for individual sections. We do not anticipate any conflicts as all the new mechanical equipment is going back to a similar location to what is existing. Please confirm the contractor will need to provide these coordination drawings throughout the course of the project.

45. Contractor to provide and review shop drawings, and provided drawings from government to ensure conflicts do not arise during construction amongst different subcontractors and trades.

46. In the NICC plans, plan sheet AE101A keynote 2 calls for the contractor to build out walls at panel as part of alt A in room 211 Huddle.

a. Where is the panel referenced in this note?

b. What is the electrical equipment mounted on the walls in this room?

c. Is the contractor expected to cover the equipment inside the newly framed walls?

46. Refer to drawing labeled A1 Second Floor Plan on sheet AE101A near grid lines G7 and between grid lines G8 and G9. Refer to drawingAE001A D3 Partition Wall B for detail. Existing panels are data pass throughs. Equipment will be removed by Government prior to award.

47. Do the Superintendent, SSHO and QC Manager need to be 3 separate individuals?

47. No, however each person identified for these roles shall be qualified for the role.

48. (If building is occupied) Are there any phasing requirements? How many people will be in the building?

Are there any temporary heating/cooling requirements?

48. Refer to question 12 response.

49. Can the period of performance be extended after award once the material/equipment lead times are confirmed due to current market conditions for the equipment for this project?

49. Period of performance cannot be extended due to operational needs in support of wildland fire season. Material lead time has been taken into account for scheduling.

50. Are soil boring reports available? If not, it will be assumed that excavation will be clear of rocks and obstructions.

50. Project is interior tenant improvement suites, no sitework included. No soil reports will be provided.

51. Please provide bidding quantities for deteriorated underlayment (roofing)/base course (paving).

51. Refer to questions 50 response.

52. Please confirm the manufacturer of the existing roofing system and who carries the current warranty of the roofing system.

52. Refer to question 50 response.

Roofing work noted is part of Bid Alternate B that does not apply to this solicitation.

53. Please provide the site visit attendee sign in sheet. 53. This roster has been provided

54. Is there a bulk water fill i.e. a hydrant or water source we can pump from for grading operations in proximity?

54. Refer to question 50 response.

55. Please confirm whether asbestos or lead is present on this project, and if so, provide relevant the documentation.

55. No lead or asbestos is present in building.

56. Is this project tax exempt? 56. Yes, this is a Federal Government contract, it’s tax exempt

57. Please provide any other documents such as full drawings, as-builts, redlines, IOMs, etc.

57. Provided solicitation package contains relevant information required to perform work in these spaces.

58. MPR Specifications, Section 011000 - Summary: Please confirm whether modular furniture systems referenced in the scope will be procured and installed by the Government or the Contractor. If Contractor-installed, please provide specifications or procurement guidance.

58. Refer to question 2 response.

59. MPR Specifications, Section 012000 - Bid Item 10:

Please clarify what specific items are included under "building specialties" for Bid Item 10 – Specialties, and whether any Government-furnished items are involved.

59. Signage, wall guards, and wall protection

60. MPR Specifications, Section 012000 - Bid Item 26:

Please confirm if structured cabling and all IT/COM components are within this scope, or if separate coordination is expected with a Government IT provider.

60. Refer to Specification section 271000 and electrical drawings for scope.

61. MPR Specifications, Section 230800: Please confirm which controls are to be salvaged and whether any commissioning agent is Government-provided or Contractor-submitted.

61. Refer to specification section 019113 as well as 230800, commissioning provided by Contractor. The existing VAV unit controllers may be salvaged for the MPR project, per M601B.

62. MPR Specifications, Section 017839: Please confirm if AutoCAD or Revit-compatible as-built files are required, or if scanned mark-ups are acceptable for closeout.

62. Refer to spec section 017839 1.3 for acceptable formats.

63. MPR Plans, Sheet GI002B, Note K: Please confirm if HVAC can support negative pressure, whether HEPA machines are required, and if return air filter media must be provided (and in what quantity/spec).

63. Refer to specification section 015000 Temporary Facilities and Controls for further information on dust control measures.

64. MPR Plans, Sheet AE102B: Please confirm specific locations requiring ceiling tile repairs.

64. Refer to AD102B keynote 1 for ceiling tile information. Refer to electrical and mechanical demolition sheets for any adjustments to grid needed.

65. MPR Plans, Sheet AE102B: Please confirm whether the ceiling grid must be replaced or only the ceiling tiles.

65. Refer to question 64 response.

66. MPR Specs, Section 095113: Please provide required performance specs (NRC, fire-resistance) for replacement ceiling tiles.

66. Refer to specification section 095113- 2 2.2 for Performance requirements.

67. MPR Specs, Section 017419: Please confirm storage location and packaging standards for salvaged materials.

67. Contractor to provide records of salvaged materials to government.

Government does not have preferred off site storage location.

68. MPR Plans, Sheets AE101B & AE102B: Please confirm which areas are rated fire-resistive assemblies.

68. Per sheet E-101B floor is rated. Walls at grid lines surrounding area of work are rated.

69. MPR Specs, Sections 230713 & 230719: Please clarify submittal/permit requirements for core drilling in rated assemblies.

69. Specifications identified are for duct insulation and piping insulation. Unsure of what this question is referring to.

70. MPR Specs, Sections 230713 & 230719: Please confirm documentation required for penetrations in rated assemblies.

70. Refer to specification section 078413 Penetration Firestopping.

71. NICC Specs, Section 024119: Please confirm location where salvaged items will be delivered and if on-site storage is allowed.

71. Refer to question 67 response.

72. NICC Specs, Section 024119: Please confirm which items must be salvaged and how they are to be marked.

72. Refer to question 67 response.

73. NICC Specs, Section 230713: Please confirm if there’s a preapproved UL firestopping detail for penetrations.

73. Refer to specification section 078413 Penetration Firestopping.

74. NICC Specs, Section 101423.16: Who is responsible for removing and salvaging existing signage/artwork?

74. Artwork will be removed by government prior to construction.

75. NICC Specs, Section 230719: Are HVAC items exempt from insulation at rated partitions, and how should firestopping be handled?

75. Any items penetrating rated partitions are required to follow adopted code requirements. Firestopping shall follow manufacturer and UL listing requirements to comply and spec section 078413.

76. NICC Specs, Section 024119: Does the Government have a preferred off-site storage location for salvaged materials?

76. Refer to question 67 response.

77. NICC Specs, Section 017419: Will the Government provide a staging area for on-site sorting of recyclable materials?

77. Yes, staging area will be provided and coordinated with government COR upon award.

78. NICC Specs, Section 017419: Can Contractor use bins near construction zones for recyclable/salvaged items?

78. Yes, staging area will be provided and coordinated with government COR upon award.

79. NICC Specs, Section 024119: Is documentation/photography required for salvaged items before turnover?

79. Refer to question 67 response.

80. NICC Plans, AD101A, Note 9: Please confirm patching scope for access floor after platform demolition—partial or full?

80. All areas within room will require raised floor to be flush and of equal height throughout. It appears all raised platforms are built on top of the raised floor system.

81. NICC Plans, AD101A, Note 19: Will Government provide pre-cut replacement access floor panels or must Contractor fabricate?

81. Contractor to provide panels, refer to specifications section 096900-Access Flooring, and other answers within this Q&A document.

82. NICC Plans, AD101A, Note 20: Clarify scope and provider for new access control hardware at reused door frames.

82. Contractor to provide and install new hardware at locations called out.

83. NICC Plans, AD101A, Note 21: Is floor penetration within a rated assembly, and what firestop details are required?

83. Refer to specification section 078413 for requirements.

84. NICC Plans, AD101A, Note 12: Should removed raised access flooring from ramp be salvaged or discarded? If salvaged, where?

84. Note 12 pertains to Bid Alternative B.

Bid Alternate B has been removed from scope.

85. NICC Plans, AD101A, Note 18: Confirm whether 6'x8' new opening is in a rated wall and what protection is required.

85. Opening is non-rated.

86. Are there any fire suppression systems impacted or new work required for Multi-Purpose Room renovation?

86. Existing fire suppression systems shall be maintained as part of the solicitation package for the Multi-Purpose Room.

Refer to the solicitation package for full scope of work required.

87. MPR, Sheet M-401B, Please clarify if there are new domestic water lines or sanitary systems routed through the area?

87. No new domestic or sanitary plumbing work in the MPR scope.

88. Provide sequences of operation for all HVAC terminal units

88. Refer to drawing sheets NICC – M- 601A and MPR – M-601B

89. Is integration of controls with existing campus BAS required?

89. Integration with existing controls is required, refer to response 88 and Division 23 specification sections.

90. Clarify if existing circuits can be re-used for lighting and devices?

90. Refer to electrical drawings: E-102A

91. Please confirm if pre-demolition TAB or baseline testing is required for either the MPR or NICC buildings prior to starting HVAC demolition or disconnection. If applicable, please clarify whether documentation of existing airflows, temperatures, or control sequences must be submitted prior to any modification.

91. Refer to specification section 230593

3.1. Baseline testing is not required.

92. Will the structured cabling scope require new terminations or patch panels?

92. Refer to Specification section 27100 – Structured cabling as well as sheet E-101B for MPR and sheet E101A for

NICC.

93. No plumbing fixture schedule is provided in the contract documents. Please confirm if new fixtures or plumbing connections are required in these areas or if existing systems are to remain as-is.

93. Refer to sheet P-101A plumbing fixture schedule and P-103A for plumbing work required. (NICC)

94. NICC, Sheet M-101A and M-401A, Please confirm if any existing ductwork is to remain or be modified.

94. NICC sheet M-101A refers to Bid Alternate B, which has been removed from this solicitation.

Refer to NICC sheets MD401A for demo and M-401A for new ductwork layout.

95. Does new HVAC control system need to tie into existing fire alarm?

95. The HVAC control system is being modified with new units and new controllers and new graphics, refer to specifications and plans for extent of work. Existing control system does have elements tied into the existing fire alarm system, those elements should not be changed as part of this solicitation.

96. Are emergency light fixtures to remain or be upgraded? 96.Refer to sheets E102A and E-601A for the NICC and to sheets E-101B and E- 601B for MPR.

97. What is the scope of reuse vs. new for the existing communications cabling?

97. Refer to drawing sheets NICC – ED101A and Keynotes, E-101A and Keynotes, MPR ED101B drawings and keynotes, E-101B and Keynotes

98. "Section 230923 outlines the performance and certification requirements for the Direct Digital Control (DDC) system, including adherence to BACnet protocols and use of BTL-certified devices. However, no specific DDC controls manufacturer or installer is named in the specifications.

Please confirm if the Government has a preferred or pre-approved controls vendor or system (e.g., Johnson Controls, Siemens, Honeywell, etc.) for this project.

If no specific vendor is preferred, would the Government accept any BTL-certified system provided the installer meets the training and certification requirements listed in the specification?"

98. Refer to drawing sheets NICC – M- 601A and MPR – M-601B “Utilizing existing Johnson controls”. As well as the qualifications identified in the specification section 230923.

99. "Specification Sections 230800 and 019113 indicate that commissioning is to be performed by a third-party Commissioning Authority (CxA) not employed by the Contractor, the Government, or equipment manufacturers.

Please confirm:

Is it the Contractor’s responsibility to retain and manage the independent Commissioning Authority (CxA)?

Will the Government be providing its own commissioning agent, or should all commissioning be included in the Contractor's scope?"

99. All commissioning to be included in contractor scope.

See Specs 019113 1.2 C

100. Please confirm that commissioning for both the MPR and NICC scopes is limited to MEP systems, specifically HVAC, BAS/DDC controls, and TAB processes. Are any additional systems (e.g., lighting, electrical, architectural finishes, or envelope systems) required to be commissioned under this contract?

100. Refer to specification section 230800 and 019113 for specific requirements for commissioning.

United States Department of the Interior

BUREAU OF LAND MANAGEMENT

Fire and Aviation 3833 S Development Ave

Boise, Idaho 83705-5354

June 9, 2025

AMENDMENT

Solicitation 140L3725R0004

NIFC 300-JWH NICC & MPR Infrastructure Repairs

The following sheet revisions shall be made part of these solicitation documents. The attached Specifications and Drawing set include identified revisions with revision delta, cloud, and date.

NIFC 300-JWH MPR Specifications and Drawings:

1. Specification Section 011000 – Summary

2. Specification Section 012000 – Unit Prices and Schedule of Values

3. Specification Section 078413 – Penetration Firestopping

4. Sheet AD102B – changed Equipment 157 ceiling type.

5. Sheet AE102B – corrected ceiling callouts to match keynotes.

6. Sheet IN101B – added interior elevation callout.

7. Sheet IN201B – corrected notes for mounting logos, added missing callouts, etc.

8. Sheet M-001B – added Mechanical General Note 19.

9. Sheet MD101B – changed HVAC layout to show first floor area to clarify where the work is to be completed.

10. Sheet M-101B – changed HVAC layout to show first floor area to clarify where the work is to be completed, updated general notes and sheet keynotes.

11. M-401B – changed HVAC layout to show first floor area to clarify where the work is to be completed.

NIFC 300-JWH NICC Specifications and Drawings:

12. Specification Section 078413 – Penetration Firestopping

13. Sheet AD101A – Added Office 208B callout

14. Sheet AD103A – Added Office 208B callout

15. Sheet AE001A – Added dimension to detail B3

16. Sheet AE101A – Added door identifiers to existing doors in area of work

17. Sheet AE502A – revised notes for details A1 and B1

18. Sheet AE601A – added requirements for existing doors to door scheduled and clarified notes for frames

19. IN201A – revised detail C4

20. FP001A – corrected C1 site plan shown

21. M-401A – revised General Sheet Notes and Sheet Keynotes

22. E102A – revised lighting fixture callout/layout

File details come from the government source that posted it. Updated .