Cedar_Butte_Pipeline_Survey_wellAug25_Amd_0003_0003.pdf

PDF 161 KB Posted

Attached to
CEDAR BUTTE EASTSIDE WELL
Solicitation number
140L2625Q0050
Issued by

About this file

This document is a detailed engineering design drawing for a water well project by the U.S. Department of the Interior's Bureau of Land Management, specifically for the Cedar Butte Eastside Well located in the Twin Falls District of Idaho. The technical schematic provides comprehensive specifications for well construction, including requirements for an 8" steel casing (minimum 40' length and 0.25" thickness), a minimum 38'-0" steel casing below ground, and a total depth of 100' from the static water line (anticipated at 850').

Key technical specifications include a watertight vented well cap (Baker P/N K-8 or approved equal), an NSF-approved pitless adaptor with compression-style fitting, and a minimum 2" cement grout or bentonite layer from the surface to 38' depth. The drawing mandates compliance with multiple construction standards including AWWA A100, IDAPA 37, and ANSI/NGWA-01-14 water well construction standards. The contractor is required to coordinate construction with the Idaho Department of Water Resources (IDWR) and utilize appropriate well drilling techniques to meet the specified nominal well hole diameter requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FROSTLINE

IMPERVIOUS MATERIAL OR

GROUND LINE

1' -0

DEPTH SPECIFIED

3/4"-MINUS CRUSHED BASE COMPACTED

TO 4" MIN THICKNESS WITH 3% MIN

SLOPE AWAY FROM WELL

NSF APPROVED PITLESS ADAPTOR,

COMPRESSION STYLE FITTING

'-0

" S

TE

EL

C

AS

IN

G B

EL

O

W G

R O

U N

D (m in

100' DEPTH FROM STATIC

WATER LINE

BORE HOLE DIAMETER AS

NECESSARY TO ACCOMMODATE 8"

STEEL CASING (IF REQ'D)

ANTICIPATED STATIC WATER

LINE AT 850'

8" STEEL CASING 40' LENGTH (min) AND .25" THICKNESS (min)

WATERTIGHT VENTED WELL CAP

BAKER P/N K-8 OR APPROVED EQUAL

EXTEND 2"Ø HDPE

WATERLINE 10 FT

THEN CAP

(WILL NOT BE

INSTALLED DURRING

THIS PROJECT)

POWER CABLE IS NOT

INCLUDED IN THIS

CONTRACT.

OVERBORE AS REQ'D TO ACCOMMODATE

8" CASING AND GROUT

8" STEEL CASING (IF REQ'D); IF CASING IS

NOT REQUIRED, ENSURE WELL DIAMETER

IS EQUAL OR GREATER TO THE I.D. OF A

SCHEDULE 20 (0.25" WALL THICKNESS) 8"

WELL CASING. FINISHED WELL MUST BE

LARGE ENOUGH TO ACCOMMODATE A 6"

DIAMETER PUMP.

CEMENT GROUT OR BENTONITE - 2" (min). THICKNESS FROM SURFACE TO 38' (min) DEPTH

NOTES:

1. WELL CONSTRUCTION SHALL COMPLY WITH

SPECIFICATION 02525 1.4 B. (INCLUDING AWWA

A100, IDAPA 37 AND ANSI/NGWA-01-14 WATER

WELL CONSTRUCTION STANDARDS).

2. DRAWING DEPICTS MINIMUM REQUIREMENTS.

CONTRACTOR WILL COORDINATE

CONSTRUCTION WITH IDWR AS REQUIRED BY

SPECIFICATION 02525 1.3, AND 3.2 C.

3. DRILLED WELL HOLE DIAMETERS LISTED IN THE

BID SCHEDULE ARE NOMINAL SIZES;

CONTRACTOR SHALL UTILIZE APPROPRIATE

WELL DRILLING TECHNIQUES TO CONSTRUCT

WELL AS SHOWN.

CHK'D BY:

DESIGN OFFICE:

DESIGNED BY:

PROJECT NO:

DRAWN BY:

SH

EET

APPROVED BY:

O F

DATE: DESCRIPTIONMARK APPROVEDDATE

UNITED STATES DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT U.S. DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT

WELL

CEDAR BUTTE EASTSIDE WELL

TWIN FALLS DISTRICT IDAHO

LLID956000

CSTINE

CSTINE

AOLSEN

AUG 2025

3 1 AMMENDMENT NO. 3 8/14/25 JCB

Sheets and Views
Well