Cedar_Butte_Pipeline_Survey_wellAug1225-Well_0002.pdf
PDF 298 KB Posted
- Attached to
- CEDAR BUTTE EASTSIDE WELL
- Solicitation number
- 140L2625Q0050
About this file
This document is a detailed technical drawing for a well design by the United States Department of the Interior's Bureau of Land Management, specifically for the Cedar Butte Eastside Well located in the Twin Falls District of Idaho. The drawing provides a comprehensive vertical cross-section of the proposed well, specifying critical technical specifications including an 8" diameter overbore, 38'-0" minimum steel casing below ground, 8" steel casing with 40' minimum length and 0.25" minimum thickness, and an anticipated static water line at 850' depth. Additional key details include a 12" diameter overbore, NSF-approved pitless adaptor with compression-style fitting, a watertight vented well cap (Baker P/N K-8 or approved equal), and a 3/4"-minus crushed base compacted to 4" minimum thickness with a 3% minimum slope away from the well. The document notes that power cable is not included in this contract, and a 2" HDPE waterline extension is planned but will not be installed during this project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FROSTLINE
CEMENT GROUT OR BENTONITE - 2" (min). THICKNESS
IMPERVIOUS MATERIAL OR
GROUND LINE
DEPTH SPECIFIED
FROM SURFACE TO 38' (min) DEPTH
3/4"-MINUS CRUSHED BASE COMPACTED
TO 4" MIN THICKNESS WITH 3% MIN
SLOPE AWAY FROM WELL
NSF APPROVED PITLESS ADAPTOR,
COMPRESSION STYLE FITTING
S
T E
E L
C
A S
I N
G
B
E L
O W
G
R O
U N
D m i n
100' DEPTH FROM STATIC
WATER LINE
8" DIAMETER OVERBORE
ANTICIPATED STATIC WATER
LINE AT 850'
8" STEEL CASING 40' LENGTH (min)
AND .25" THICKNESS (min)
WATERTIGHT VENTED WELL CAP
BAKER P/N K-8 OR APPROVED EQUAL
EXTEND 2"Ø HDPE
WATERLINE 10 FT
THEN CAP
(WILL NOT BE
INSTALLED DURRING
THIS PROJECT)
POWER CABLE IS NOT
INCLUDED IN THIS
CONTRACT.
12" DIAMETER OVERBORE
8" STEEL CASING (IF NEEDED)
CHK'D BY:
DESIGN OFFICE:
DESIGNED BY:
PROJECT NO:
DRAWN BY:
S H
E E
T
APPROVED BY:
O F
DATE: DESCRIPTIONMARK APPROVEDDATE
UNITED STATES DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
WELL
CEDAR BUTTE EASTSIDE WELL
TWIN FALLS DISTRICT IDAHO
LLID956000
CSTINE
CSTINE
AOLSEN
AUG 2025