DO_08_Ross_Point_Final_Phase_1_Drawings_Amend_2_tjs_20210722_0002.pdf

PDF 12 MB Posted

Attached to
ROSS POINT RECREATION SITE IMPROVEMENTS PHASE 1
Solicitation number
140L2621R0006
Issued by

About this file

This document outlines a federal contract opportunity for recreation site improvements. The Bureau of Land Management Idaho Region is soliciting proposals under solicitation number 140L2621R0006 for Phase 1 of the Ross Point Recreation Site Improvements. The contract description involves improvements to the Ross Point recreation area. Proposals are due by the date specified in the solicitation. The contract type and period of performance or other pricing terms are not stated. The opportunity is open to all qualified vendors.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bryce Marsh

2021.03.31 09:53:08

-06'00'

2021.03.31

09:57:50 -06'00'

09:54:16 -06'00'

09:58:16 -06'00'

09:58:42 -06'00'

09:59:10 -06'00'

09:59:39 -06'00'

10:00:01 -06'00'

10:00:26 -06'00'

2021.03.31 10:00:51

Bryce Marsh 2021.03.31 10:01:17

Bryce Marsh 2021.03.31 10:02:02

60"1

Am en dm en t0

7/ /2 T.

J.

S.

IBC GUARDRAILS

TO MATCH DOCK

ALUMINUM PLANK DECKING

WITH TRACTION RIBS

SWING SHACKLE SYSTEM

USING GALVANIZED

D-SHACKLES IS

ACCEPTABLE AS WELL.

EXTERNAL PILE CONNECTORS ARE

ACCEPTABLE IF PILES INSTALLED

ALONG SWIM (NORTH) SIDE OF DOCK

PER DELEGATED DESIGN.

2021.03.31 10:02:36

10:03:08 -06'00'

2021.03.31 10:03:33

UGPUGPUGPCOM

G

AS

GAS

LEGEND

LIGHT FIXTURE, WITH TEXT DENOTING LIGHT

FIXTURE TYPE.

110V DUPLEX RECEPTACLE

OCCUPANCY SENSOR

HOME RUN, WITH CIRCUIT CALLOUT

DISCONNECT SWITCH

GROUND ROD

TRANSFORMER

METER

1. PANEL 'LP1' FEEDERS SHALL BE (3) #8 CU. BURIED

IN (1) 1" CONDUIT. METER SHALL BE CONNECTED

BEFORE DISCONNECT SWITCH.

2. PANEL 'LP1' SHALL BE LOCKABLE AND MOUNTED

WITH UNISTRUT. PANEL ACCESS HANDLE SHALL

BE LOCATED AT 48" ABOVE GRADE.

KEY NOTES:

EDGE OF WATER

SP

O

KA

N

E R

IV

ER

M

AP

LE

W

O O

D A

VE

(1) 1" CONDUIT

PAVILLION

FOOTPRINT

TRANSFORMER

PANEL 'LP1'

DISCONNECT SWITCH

AND METER

OS

GROUND

ROD

PR

OFESS IONAL ENG INEER

D A R R E L L D E A

N

L

I C E N S E D

STA T E OF I DA HO

19543

SHEET NOTES:

1. GROUND AND NEUTRAL SHALL BE BONDED TOGETHER IN PANEL 'LP1'. IN

ADDITION TO CONDUCTOR WIRES, A #12 GND WIRE SHALL BE RAN WITH EACH

RUN. SERVICE SHALL BE SIZED WITH #8 GND WIRE. SIZE ALL OTHERS IN

ACCORDANCE WITH NEC TABLE 250.66.

2. CEILING OR SWITCH MOUNTED OCCUPANCY SENSORS ARE ACCEPTABLE.

3. ELECTRICAL EQUIPMENT ON SUPPLY SIDE OF SERVICE DISCONNECT SHALL

ADHERE TO NEC 230.82 AND NEC 250.25.

4. DSW-1 IS TO BE SERVICE RATED AND LABELED EMERGENCY DISCONNECT.

NOT SERVICE EQUIPMENT PER NEC 230.85.

120/240V

12400V

DSW-1: LABELED "EMERGENCY DISCONNECT, SERVICE DISCONNECT"

RATED 60AMP WITH CLASS 'H' OR 'K', 60AMP FUSE

PANEL

'LP1'

50A MCB

TO UTILITY

GN

PAVILLION POWER AND LIGHTING PLAN1

E102

SCALE: NTS

SINGLE LINE DIAGRAM2

E102

SCALE: NTS

PANEL SCHEDULE3

E102

SCALE: NTS

LIGHT FIXTURE SCHEDULE4

E102

(3) #8 CU W/ #8 GND IN 1" SCH 40 PVC

(3) #8 CU W/ #8 GND IN 1" SCH 40 PVC

PR

OFESS IONAL ENG INEER

D A R R E L L D E A

N

L

I C E N S E D

PANEL AND CIRCUIT

OF DEVICE, TYP

LABEL WITH BROTHER "P-TOUCH" SYSTEM. USE

CLEAR OR WHITE TAPE WITH BLACK LETTERING.

RATED NON-REVERSIBLE OR

EXOTHERMIC WELD CONNECTION

GROUNDING CONDUCTOR

GROUNDING ELECTRODE (ROD)

FINISHED GRADE

SCALE: NTS

DEVICE LABELING DETAIL1

E501 SCALE: NTS

GROUNDING ROD DETAIL2

E501

LEGEND

FINAL BACKFILL

PIPE ZONE

BEDDING

12" MAX.

6" MIN

12" MAX.

6" MIN

4"

" M

IN

" M

AX

IM

U

M

REJECT SAND OR SELECT 3/4" MINUS GRANULAR

EXCAVATED MATERIAL OR IMPORTED AGGREGATE

BACKFILL, COMPACTED TO 90% OF MAXIMUM

DENSITY. 85% FOR FINE GRAINED MATERIAL.

EXISTING GRANULAR MATERIAL

TO 90% OF MAX. DENSITY, 85%

FOR FINE GRAINED MATERIAL

EXISTING GRADE

WARNING TAPE

12" BELOW

GRADE

3" MIN FOR

LIKE CONDUIT6" MIN BETWEEN

POWER AND

COMM LINES

SCALE: NTS

TYPICAL ELECTRICAL TRENCH3

E501

PR

OFESS IONAL ENG INEER

D A R R E L L D E A

N

L

I C E N S E D