DO_08_Ross_Point_Final_Phase_1_Drawings_Amend_2_tjs_20210722_0002.pdf
PDF 12 MB Posted
- Attached to
- ROSS POINT RECREATION SITE IMPROVEMENTS PHASE 1
- Solicitation number
- 140L2621R0006
About this file
This document outlines a federal contract opportunity for recreation site improvements. The Bureau of Land Management Idaho Region is soliciting proposals under solicitation number 140L2621R0006 for Phase 1 of the Ross Point Recreation Site Improvements. The contract description involves improvements to the Ross Point recreation area. Proposals are due by the date specified in the solicitation. The contract type and period of performance or other pricing terms are not stated. The opportunity is open to all qualified vendors.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bryce Marsh
2021.03.31 09:53:08
-06'00'
2021.03.31
09:57:50 -06'00'
09:54:16 -06'00'
09:58:16 -06'00'
09:58:42 -06'00'
09:59:10 -06'00'
09:59:39 -06'00'
10:00:01 -06'00'
10:00:26 -06'00'
2021.03.31 10:00:51
Bryce Marsh 2021.03.31 10:01:17
Bryce Marsh 2021.03.31 10:02:02
60"1
Am en dm en t0
7/ /2 T.
J.
S.
IBC GUARDRAILS
TO MATCH DOCK
ALUMINUM PLANK DECKING
WITH TRACTION RIBS
SWING SHACKLE SYSTEM
USING GALVANIZED
D-SHACKLES IS
ACCEPTABLE AS WELL.
EXTERNAL PILE CONNECTORS ARE
ACCEPTABLE IF PILES INSTALLED
ALONG SWIM (NORTH) SIDE OF DOCK
PER DELEGATED DESIGN.
2021.03.31 10:02:36
10:03:08 -06'00'
2021.03.31 10:03:33
UGPUGPUGPCOM
G
AS
GAS
LEGEND
LIGHT FIXTURE, WITH TEXT DENOTING LIGHT
FIXTURE TYPE.
110V DUPLEX RECEPTACLE
OCCUPANCY SENSOR
HOME RUN, WITH CIRCUIT CALLOUT
DISCONNECT SWITCH
GROUND ROD
TRANSFORMER
METER
1. PANEL 'LP1' FEEDERS SHALL BE (3) #8 CU. BURIED
IN (1) 1" CONDUIT. METER SHALL BE CONNECTED
BEFORE DISCONNECT SWITCH.
2. PANEL 'LP1' SHALL BE LOCKABLE AND MOUNTED
WITH UNISTRUT. PANEL ACCESS HANDLE SHALL
BE LOCATED AT 48" ABOVE GRADE.
KEY NOTES:
EDGE OF WATER
SP
O
KA
N
E R
IV
ER
M
AP
LE
W
O O
D A
VE
(1) 1" CONDUIT
PAVILLION
FOOTPRINT
TRANSFORMER
PANEL 'LP1'
DISCONNECT SWITCH
AND METER
OS
GROUND
ROD
PR
OFESS IONAL ENG INEER
D A R R E L L D E A
N
L
I C E N S E D
STA T E OF I DA HO
19543
SHEET NOTES:
1. GROUND AND NEUTRAL SHALL BE BONDED TOGETHER IN PANEL 'LP1'. IN
ADDITION TO CONDUCTOR WIRES, A #12 GND WIRE SHALL BE RAN WITH EACH
RUN. SERVICE SHALL BE SIZED WITH #8 GND WIRE. SIZE ALL OTHERS IN
ACCORDANCE WITH NEC TABLE 250.66.
2. CEILING OR SWITCH MOUNTED OCCUPANCY SENSORS ARE ACCEPTABLE.
3. ELECTRICAL EQUIPMENT ON SUPPLY SIDE OF SERVICE DISCONNECT SHALL
ADHERE TO NEC 230.82 AND NEC 250.25.
4. DSW-1 IS TO BE SERVICE RATED AND LABELED EMERGENCY DISCONNECT.
NOT SERVICE EQUIPMENT PER NEC 230.85.
120/240V
12400V
DSW-1: LABELED "EMERGENCY DISCONNECT, SERVICE DISCONNECT"
RATED 60AMP WITH CLASS 'H' OR 'K', 60AMP FUSE
PANEL
'LP1'
50A MCB
TO UTILITY
GN
PAVILLION POWER AND LIGHTING PLAN1
E102
SCALE: NTS
SINGLE LINE DIAGRAM2
E102
SCALE: NTS
PANEL SCHEDULE3
E102
SCALE: NTS
LIGHT FIXTURE SCHEDULE4
E102
(3) #8 CU W/ #8 GND IN 1" SCH 40 PVC
(3) #8 CU W/ #8 GND IN 1" SCH 40 PVC
PR
OFESS IONAL ENG INEER
D A R R E L L D E A
N
L
I C E N S E D
PANEL AND CIRCUIT
OF DEVICE, TYP
LABEL WITH BROTHER "P-TOUCH" SYSTEM. USE
CLEAR OR WHITE TAPE WITH BLACK LETTERING.
RATED NON-REVERSIBLE OR
EXOTHERMIC WELD CONNECTION
GROUNDING CONDUCTOR
GROUNDING ELECTRODE (ROD)
FINISHED GRADE
SCALE: NTS
DEVICE LABELING DETAIL1
E501 SCALE: NTS
GROUNDING ROD DETAIL2
E501
LEGEND
FINAL BACKFILL
PIPE ZONE
BEDDING
12" MAX.
6" MIN
12" MAX.
6" MIN
4"
" M
IN
" M
AX
IM
U
M
REJECT SAND OR SELECT 3/4" MINUS GRANULAR
EXCAVATED MATERIAL OR IMPORTED AGGREGATE
BACKFILL, COMPACTED TO 90% OF MAXIMUM
DENSITY. 85% FOR FINE GRAINED MATERIAL.
EXISTING GRANULAR MATERIAL
TO 90% OF MAX. DENSITY, 85%
FOR FINE GRAINED MATERIAL
EXISTING GRADE
WARNING TAPE
12" BELOW
GRADE
3" MIN FOR
LIKE CONDUIT6" MIN BETWEEN
POWER AND
COMM LINES
SCALE: NTS
TYPICAL ELECTRICAL TRENCH3
E501
PR
OFESS IONAL ENG INEER
D A R R E L L D E A
N
L
I C E N S E D