power.cummins.com ©2017 Cummins Inc. | D-3535 (09/17)
Generator set data sheet
Model: DQFAH
Frequency: 60 Hz
Fuel type: Ultra low sulphur diesel (15 ppm sulphur) kW rating: 1000 Standby
900 Prime
Emissions level: EPA Stationary Non-emergency Tier 4 interim
Exhaust emission data sheet Tier 4i: EDS-1133
Exhaust emission compliance sheet Tier 4i: EPA-1232
Exhaust emission data sheet Tier 4F: EDS-1156
Exhaust emission compliance sheet Tier4F EPA-1195
Sound performance data sheet: MSP-1119
Cooling performance data sheet: MCP-217
Prototype test summary data sheet: PTS-304
Standard set-mounted radiator cooling outline: A034N275
Optional remote radiator cooling outline: A034N273
After-treatment outline drawing Tier 4i: A042R682
After-treatment outline drawing Tier 4i w/ILB: A042R680
After-treatment outline drawing Tier 4F A041V017
Fuel consumption
Standby Prime kW (kVA) kW (kVA)
Ratings 1000 (1250) 900 (1125)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 19.1 35.8 54.1 72.2 17.3 32.1 47.5 63.9
L/hr 72.3 135.5 204.8 273.3 65.5 121.5 179.8 241.9
DEF consumption
Standby Prime kW (kVA) kW (kVA)
Ratings 1000 (1250) 900 (1125)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 0.94 1.41 2.17 3.03 0.86 1.32 1.94 2.68
L/hr 3.48 5.22 8.03 11.21 3.18 4.88 7.18 9.92
Engine Standby rating Prime rating
Engine manufacturer Cummins Inc.
Engine model QST30-G17
Configuration Cast iron, V 12 cylinder
Aspiration Turbocharged and low temperature after-cooled
Gross engine power output, kWm (bhp) 1112 (1490) 1007 (1350)
BMEP at set rated load, kPa (psi) 2417 (351) 2160 (313)
Bore, mm (in.) 140 (5.51)
Stroke, mm (in.) 165 (6.5)
Rated speed, rpm 1800
Piston speed, m/s (ft/min) 9.91 (1950)
Compression ratio 14.7:1
Lube oil capacity, L (qt) 154 (162.8)
Overspeed limit, rpm 2100 ±50
Regenerative power, kW 82
Fuel flow
Maximum fuel flow, L/hr (US gph) 570 (150)
Maximum fuel inlet restriction, kPa (in Hg) 27 (8.0)
Maximum fuel inlet temperature, °C (°F) 66 (150)
Air
Combustion air, m /min (scfm) 88 (3150) 81 (2880)
Maximum air cleaner restriction, kPa (in H2O) 6.2 (25)
Alternator cooling air, m /min (cfm) 204 (7300)
Exhaust
Exhaust flow at set rated load, m /min (cfm) 211 (7540) 195 (6950)
Exhaust temperature, °C (°F) 477 (890) 467 (873)
Maximum back pressure, kPa (in H2O) 6.8 (27)
Standard set-mounted radiator cooling
Ambient design, °C (°F) 50 (122)
Fan load, kWm (HP) 43 (57))
Coolant capacity (with radiator), L (US gal) 201 (53.2)
Cooling system air flow, m /min (scfm) 952 (34000)
Total heat rejection, MJ/min (Btu/min) 48.9 (46455) 43.9 (41660)
Maximum cooling air flow static restriction, kPa (in H2O) 0.12 (0.5)
Maximum fuel return line restriction kPa (in Hg) 67.5 (20)
Heat radiated to room from after-treatment (Btu/min) 109200
Optional remote radiator cooling1
Max flow rate at max friction head, jacket water circuit, L/min (US gal/min)
992 (262)
Max flow rate at max friction head, after-cooler circuit, L/min (US gal/min)
303 (80)
Heat rejected, jacket water circuit, MJ/min (Btu/min) 22.67 (21500) 21.01 (19925)
Heat rejected, after-cooler circuit, MJ/min (Btu/min) 18.35 (17400) 15.69 (14885)
Total heat radiated to room, MJ/min (Btu/min) 6.1 (5753) 5.6 (5301)
Maximum friction head, jacket water circuit, kPa (psi) 69 (10)
Maximum friction head, after-cooler circuit, kPa (psi) 48 (7)
Maximum static head, jacket water circuit, m (ft) 14 (46)
Maximum static head, after-cooler circuit, m (ft) 14 (46)
Maximum jacket water outlet temp, °C (°F) 104 (220) 100 (212)
Maximum after-cooler inlet temp at 25 °C (77 °F) ambient, °C (°F)
41 (105)
Maximum after-cooler inlet temp, °C (°F) 62 (143) 56 (133)
Maximum fuel return line restriction, kPa (in Hg) 67.5 (20)
Heat radiated to room from after-treatment (Btu/min) 109200
For non-standard remote installations contact your local Cummins representative.
After-treatment system T4i T4i with heater T4F
Pressure drop across after-treatment, kPa (in H2O) 4 (16) 4 (16) 6.2 (25)
Available back pressure for exhaust system piping, kPa (in H2O) 2.7 (11) 2.7 (11) 0.5 (2)
Exhaust heater rating (kW) - 250 250
Exhaust heater input requirements (Amps at 480 V) - 300 300
Minimum unaided ambient operating temperature °C (°F) 2 (35) 2 (35) 2 (35)
Maximum ambient operating temperature (warning) °C (°F) 52 (125) 52 (125) 52 (125)
DEF tank capacity (usable) L (gal) 765 (202) 765 (202) 765 (202)
DEF flow
Maximum supply flow, L/hr (US gph) 98 (26)
Maximum return flow, L/hr (US gph) 87 (23)
Maximum static head (from pump to injector), m (ft) 6.4 (21)
Weights1
Unit dry weight kgs (lbs) 7633 (16824)
Unit wet weight kgs (lbs) 7931 (17480)
After-treatment weight kgs (lbs) 1981 (4367)
Derating factors2
Standby Engine power available up to 701 m (2300 ft) at ambient temperatures up to 40 °C (104 °F). Above these elevations, derate at 3.5% per 305 m (1000 ft) and 7% per 10 °C (18 °F).
Prime Engine power available up to 727 m (2385 ft) at ambient temperatures up to 40 °C (104 °F). Above these elevations, derate at 3.5% per 305 m (1000 ft) and 7% per 10 °C (18 °F).
Notes:
Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors do not include after-treatment system.
jt370
For more information contact your local Cummins distributor or visit power.cummins.com
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
D-3535 (09/17)
Ratings definitions Emergency Standby Power (ESP):
Limited-Time Running Power (LTP):
Prime Power (PRP): Base Load (Continuous) Power (COP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO
3046, AS 2789, DIN 6271
and BS 5514.
Applicable for supplying power to a constant electrical load for limited hours. Limited-Time Running Power (LTP) is in accordance with ISO 8528.
Applicable for supplying power to varying electrical load for unlimited hours.
Prime Power (PRP) is in accordance with ISO 8528.
Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) is in accordance with ISO 8528, ISO 3046, AS 2789, DIN
6271 and BS 5514.
Alternator data
Voltage Connection
Temp rise degrees C Duty
Single phase factor
Max surge kVA
Surge kW
Alternator data sheet
Feature code
120/208-139/240 12-lead 125/105 S/P 4234 1019 ADS-312 B252
240/416-277/480 12-lead 125/105 S/P 4234 1019 ADS-312 B252
277/480 Wye, 3-phase 125/105 S/P 3866 1018 ADS-311 B276
220/380-277/480 Wye, 3-phase 125/105 S/P 4602 1018 ADS-330 B282
220/380-277/480 Wye, 3-phase 105/80 S/P 4602 1018 ADS-330 B283
210/380-277/480 Wye, 3-phase 80 S 5521 1024 ADS-331 B284
240/416-277/480 Wye 125/105 S/P 4234 1019 ADS-312 B288
347/600 3-phase 125/105 S/P 3866 1021 ADS-311 B300
347/600 3-phase 105/80 S/P 4234 1024 ADS-312 B301
347/600 3-phase 80 S 4602 1004 ADS-330 B604
Notes:
Limited single phase capability is available from some three phase rated configurations. To obtain single phase rating, multiply the three phase kW rating by the Single Phase Factor3. All single phase ratings are at unity power factor.
Standby (S), Prime (P) and Continuous ratings (C).
Factor for the Single phase output from Three phase alternator formula listed below.
Maximum rated starting kVA that results in a minimum of 90% of rated sustained voltage during starting.
Formulas for calculating full load currents:
Three phase output Single phase output kW x 1000 kW x SinglePhaseFactor x 1000
Voltage x 1.73 x 0.8 Voltage
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.
http://power.cummins.com/