G01

N

PROJECT LOCATION

SARATOGA, WY

REVISED SET PER RFI#1 08/08/2024

SENSOR SCHEDULE

PLAN CODE SERVICE BASIS OF DESIGN SENSOR MODEL TRANSMITTER MODEL SENSOR BODY MATERIAL / FLOW RATE SENSOR TRANSMITTER OR SENSOR

INPUT POWER

TRANSMITTER

SIGNAL OUTPUT NOTES

XXXX-DO/WT-X DISOLVED OXYGEN /

TEMPERATURE SENSOR M4KNICK SE 740/1 E401N.030 / FW-E052 POLYSULFONE /STAINLESS STEEL SILICON 80-230 VAC/24-60VDC

< 15VA/10W 2-WIRE 4-20 MA 1, 2, 3, 4, 5, 6

XXX-WL-X ULTRA SONIC WATER LEVEL

SENSOR DREXELBROOK US-12 N/A ELECTRICAL ENCLOSURE PBT-RF.

'SENSOR 6.5” CPVC - NEMA-4X

6.5” CPVC -

NEMA-4X

19-30 VDC. 19 VDC

REQUIRED@ 4 MA MIN 2-WIRE 4-20 MA 1, 7, 8, 9, 10

XXX-O2-MASS-FLOW-X OXYGEN MASS FLOW SENSOR -

3/4" PIPE SIZE

FLUID COMPONENTS

INTERNATIONAL (FCI)

ST75V-2F2FET0JT00 INTEGRAL - NEMA-4X 316 STAINLESS STEEL THERMAL

DISPERSION

85 VAC TO 265 VAC (12 WATT

MAXIMUM

2-WIRE 4-20 MA 11

XXX-O2-FLOW OXYGEN NEEDLE VALAVE / FLOW

SENSOR - 1/2" PIPE SIZE BRONKHORST MV-106 INTEGRAL OXYGEN FLOW RATE '0.7 CFM - 7 CFM (

2…200 L /M)

OXYGEN +15 TO A1124 VDC (+/- 10%) 2-WIRE 0 … 5 VDC 12

SCHEDULE NOTES:

1. SENSOR LEGEND: DO - DISOLVED OXYGEN; WT - WATER TEMPERATURE (COMBINATION SENSOR); ULTRA-SONIC WATER LEVEL - WL.

2. TRANSMITTER CURRENT OUTPUT POWER: DUAL 0-20 MA, 4-20 MA, 0-5 V, 1-5 V, AND ±10 V INPUT.

3. TRANSMITTER CAN RECEIVE 2 UP TO 4 ADDITIONAL SENSOR INPUTS WITH ADDITIONAL DIN MOUNTED TRANSMITTERS.

4. TRANSMITTER PANEL MOUNTED LED SCREEN WITH DUAL-LINE, SIX-DIGIT DISPLAY.

5. TRANSMITTER BOX MATERIAL - NEMA-4X

6. 2-WIRE SERIES WIRED LOOP POWER CIRCUIT.

7. SENSOR RANGE: 1 TO 30 FT.

8. 2-LINE, 7-DIGIT LCD DISPLAY.

9. RESPONSE TIME: 300 MILLISECOND. SIGNAL DAMPING: USER PROGRAMMABLE FROM 0 – 99 SECONDS.

10. SENSING ELEMENT CONNECTION: 2-INCH NPT FTTING, CPVC. FLANGE MOUNTING (VIA THREADED FLANGES)

11. REPEATABILITY: ± 0.5% READING; TURNDOWN RATIO: 3:1 to 100; ACCURACY ± 2% READING ± 0.5% FULL SCALE.

12. OLED SCREEN WITH PASSWORD SECURITY AND PROGRAMMABLE MENU.

AQUATIC PUMP WATER FLOW METER SCHEDULE

PLAN CODE SERVICE TYPE BASIS OF DESIGN MODEL SIZE CAPACITY GPM

(MAX)

TRANMITTER ELECTRICAL NOTES

SW-FM-1 SURFACE WATER (SW) IN-LINE ELECTROMAGNETIC TOSHIBA LF654/LF620F 8" 1000 INTEGRAL NOTE #4 1, 2, 3, 4, 5, 6

SW-FM-2 SURFACE WATER (SW) IN-LINE ELECTROMAGNETIC TOSHIBA LF654/LF620F 8" 1000 INTEGRAL NOTE #4 1, 2, 3, 4, 5, 6

SCHEDULE NOTES:

1. TRANSMITTER CURRENT OUTPUT: 4–20MADC (LOAD RESISTANCE 0 TO 750W).

2. PROVIDE WITH 150 # FLANGED WATER CONNECTIONS AND PTFE LINER MATERIAL.

3. PROVIDE STAINLESS STEEL GROUNDING RINGS.

4. POWER SUPPLY: 110VDC (ALLOWABLE VOLTAGE 90 TO 130VDC). STANDARD 10W (14VA) AT AC100V AND EXCITATION CURRENT: 0.2A. MAX:15W (22VA).

5. TERMINAL BOX MATERIAL — ADC12 (ALUMINUM ALLOY DIE CASTING OR ALTERNATE PVC) – NEMA-4X

6. LCD DISPLAY: FULL DOT-MATRIX 128×128 DOT LCD DISPLAY.

CATCH BASIN AND CONNECTION SCHEDULE

PLAN DESCRIPTION

NOTES

CODE ITEM BASIS OF DESIGN MODEL TYPE MATERIAL DRAIN VENT

CB-1 CATCH BASIN CONNECTED TO SUMP PUMP JAY R SMITH 9860 PRE CAST POLYMER POLYMER 2" N/A 1, 2

SCHEDULE NOTES:

1. PROVIDE WITH HEAVY DUTY FIBERGLASS GRATE.

2. PROVIDE WITH PLASTIC SEDIMENT BUCKET.

RADON EXHAUST FAN SCHEDULE

PLAN TYPE BASIS OF DESIGN SERVES DRIVE CFM E.S.P. MOTOR DUCT

DIAMETER

POWER NOTESCODE MFGR MODEL (IN) WATT (V/PH/HZ)

RF-1 IN-LINE RADON AWAY GP 301 SURFACE WATER DRUM FILTER DISCHARGE VENT DIRECT 50 1.50 100 3" 120/1/60 1, 2, 3

RF-2 IN-LINE RADON AWAY GP 301 SURFACE WATER CHANNEL DIRECT 50 1.50 100 3" 120/1/60 1, 2, 3

1. FAN SELECTIONS ARE AT 6801 FT ABOVE SEA LEVEL.

2. PROVIDE WITH BACKDRAFT DAMPER ON WALL CAP DISCHARGE, AND WALL MOUNTING FLANGE BRACKET.

3. FANS RUN CONTINUOUS.

AQUATIC ROTARY DRUM FILTER SCHEDULE

PLAN CODE SERVICE BASIS OF DESIGN MODEL NO. APPLICATION TYPE MAXIMUM

FLOW (GPM)

SCREEN SIZE

(MICRON)

NUMBER OF

SCREEN PANELS

MIN DRUM

SUBMERGENCE

FILTER DRIVE

MOTOR HP

BACKWASH

PUMP HP

BACKWASH

PUMP PSI

TANK AND COVER

MATERIAL

POWER WEIGHT

(LBS)

NOTES

(V/PH/HZ)

SW-DF-1 DRUM FILTER - SOLIDS REMOVAL CM AQUA TECHNOLOGIES HEX X2-4T SURFACE WATER FILTER FULL TANK 1200 30 BY MANUF 40% 0.25 2.00 100 PEHD 208/3/60 370 1, 2, 3, 4

SW-DF-2 DRUM FILTER - SOLIDS REMOVAL CM AQUA TECHNOLOGIES HEX X2-4T SURFACE WATER FILTER FULL TANK 1200 30 BY MANUF 40% 0.25 2.00 100 PEHD 208/3/60 370 1, 2, 3, 4

SCHEDULE NOTES:

1. PROVIDE WITH POWER BACKWASH PUMP, WATER LEVEL SWITCHES, CONTROL VALVES, PROGRAMMABLE LOGIC CONTROL PANELS.

2. PROVIDE THE FOLLOWING ALARMS: DRUM FILTER HIGH-HIGH ALARM, DRUM FILTER MOTOR OVERLOAD, BACKWASH PUMP TROUBLE, E-STOP.

3. FILTERS TO MIRROR EACH OTHER TO SHARE COMMON SERVICE ACCESS.

4. PROVIDE 50% EXTRA SPARE SCREENS AND 25 SCREEN PATCHES.

AQUATIC VERTICAL TURBINE PUMP SCHEDULE

PLAN CODE SERVICE TYPE BASIS OF DESIGN MODEL STAGES CAPACITY

GPM

HEAD LOSS

FEET RPM TPL FEET PUMP

EFFICIENCY CONSTRUCTION IMPELLER MOTOR EFFICIENCY MOTOR HP ELECTRICAL WEIGHT

(LBS)

NOTES

SW-P-1 SURFACE WATER (SW) VERTICAL TURBINE BELL & GOSSETT VIT-DITM 10DHHC 1 1000 26 1770.0 6.0 75% DUCTILE IRON BRONZE 93% VFD RATED 15.0 240/3/60 804 1, 2, 3, 4 SW-P-2 SURFACE WATER (SW) VERTICAL TURBINE BELL & GOSSETT VIT-DITM 10DHHC 1 1000 26 1770.0 6.0 75% DUCTILE IRON BRONZE 93% VFD RATED 15.0 240/3/60 804 1, 2, 3, 4

SCHEDULE NOTES:

1. PROVIDE MOTOR SPEED CONTROL WITH VARIABLE FREQENCY DRIVE (VFD), REFERENCE SPEC DIVISION 26.

2. PROVIDE DIGITAL PUMP CONTROLLER WITH SIGNAL OUTPUT - TWO WIRE 4- 20 Ma.

3. CONTINUOUS DUTY INVERTOR DUTY, PREMIUM EFFICIENCY MOTORS.

4. PROVIDE SHAFT GROUNDING RINGS AND GROUNDING CONDUCTOR.

SUMP PUMP SCHEDULE

PLAN

CODE SERVICE TYPE BASIS OF DESIGN MODEL CAPACITY

GPM

HEAD LOSS

FEET BASIN MATERIAL MINIMUM BASIN

DIMENSIONS HP ELECTRICAL NOTES

SP-1 FLOOR WATER DRAINAGE SIMPLEX ZOELLER 57 10 15 FIBERGLASS 24" DIA X 36" TALL 0.3 115/1/60 1, 2, 3, 4

SCHEDULE NOTES:

1. PROVIDE FLOAT CONTROL AND ZOELLER SIMPLEX PANEL INTERIOR CONTROL PANEL .

2. PROVIDE WITH SINGLE SEAL PUMP, 20 FT CORD, 1 1/2" DISCHARGE, NEMA-4X EXTERIOR ALARM WITH AUDIBLE AND VISUAL BEACON AND DRY AUX CONTACTS FOR HIGH LEVEL ALARM.

3. PROVIDE STEEL SUMP COVER WITH GROMMETS FOR PIPE AND CONTROL WIRING CONNECTIONS.

4. PROVIDE PUMP STAND.

WATER SPIKE SCHEDULE - LOW HEAD OXYGENATOR

PLAN CODE TYPE

BASIS OF DESIGN

DESCRIPTION MATERIAL WATER

FLOW (GPM)

WATER PRESSURE

RANGE (PSI)

OXYGEN

SATURATION NOTESMANUFACTURER SIZE

SW-WS-1 THRU 10 SUBMERGED WARREN WATER BROOM 46"H X 24" L X 6"W NITROGEN PURGE / LOW HEAD OXYGENATOR 6063 ALUMINUM 250 30-60 180-200% 1, 2, 3

1. 3" QUICK COUPLING TOP MOUNTED ON MANIFOLD WITH 2" CLEANOUT BALL VALVE.

2. 1/2" ALUMINUM NITROGEN BURB TUBE AND 1/2" OXYGEN CONNECTION.

3. ALUMINUM ANGLE WELDED TO SPIKE BODY FOR SECURING SPIKE TO SUPPORT.

HEADTANK / DISINFECTION / SOUTH RACEWAY

BUILDING PLUMBING EQUIPMENT SCHEDULES P01

8/9/2024

HEADTANK / DISINFECTION

BUILDING PLUMBING DEMOLITION PLAN P02

6779.0'

6775.0

6786.0'

GRADE 6784.0'

6786.0'

6779.0'

6785.0'

(E)6782.0'

6778.5'

6786.0' 6786.0'6786.0'

6785.0'

PR

IM

AR

Y

BY

PA

SS

W

EI

R

SURFACE WATER

BYPASS SUMP SURFACE WATER CHANNEL

PUMP

CHANNEL

BEYOND

6779.0'

IE = 6779.4'

6784.5'

WW OVERFLOW

W W

O

VE

R

FL

O W

SURFACE WATER HEADTANK

WELL WATER

HEADTANK

SURFACE WATER HEADTANK

SW CHANNEL -

BY-PASS SUMP

BEYOND

6779.0' 6778.5'6778.5'

PUMP CHANNEL

BEYOND

(E)21" SW DRAIN TO

SOUTH RACEWAY

SW

OVER

FLOW

HEADTANK / DISINFECTION BUILDING

PLUMBING DEMOLITION SECTIONS P03

HEADTANK / DISINFECTION BUILDING

PLUMBING PLANS P04

6779.0'

6775.0

6786.0'

GRADE 6784.0'

6786.0'

6779.0'

6785.0'

(E)6782.0'

6778.5'

6786.0' 6786.0'6786.0'

6785.0'

PR

IM

AR

Y

BY

PA

SS

W

EI

R

SURFACE WATER

BYPASS SUMP

SURFACE WATER CHANNEL

PUMP

CHANNEL

BEYOND

6779.0'

IE = 6779.4'

6784.5'

WW OVERFLOW

W W

O

VE

R

FL

O W

SURFACE WATER HEADTANK

WELL WATER

HEADTANK

SURFACE WATER HEADTANK

SW CHANNEL -

BY-PASS SUMP

BEYOND

6779.0' 6778.5'6778.5'

PUMP CHANNEL

BEYOND

(E)21" SW DRAIN TO

SOUTH RACEWAY

SW

OVER

FLOW

6779.0'

6775.0

6786.0'

GRADE 6784.0'

6786.0'

6779.0'

6785.0'

(E)6782.0'

SW CHANNEL -

BY-PASS SUMP

BEYOND

PUMP CHANNEL

BEYOND

6776.0

6778.0

6780.0

6782.0

6784.0

6786.0

6788.0

6790.0

6792.0

6794.0

6796.0

6774.0

HEADTANK / DISINFECTION BUILDING

PLUMBING SECTIONS P05

CV

SW-12

FINISHED

FLOOR

ELEVATION

6786.0

LAKE CREEK

LAKE SPRING

CV

SW

-1

SW-12

SURFACE WATER

CHANNEL

BY-PASS BASIN BEHIND

DISINFECTION AREA

PUMP 2

400 GPM

M SP

SW-21

BLV BLV

INV 6779.4

PUMP

CHANNEL

BLV

DF-1

DF-2

UV -1

UV-2

PO

LOW LEVEL

ALARM

VENT

TG

RDCR

SW

-6

SW

-8

SW-10SW-10

SW

-1

RDCR

DP-6

SW

-1

TG

RCHV

O G

-1

INV 6782.5

INV 6782.5

CV

BLV

BLV

6786.0

PUMP STOP

6779.0

PUMP ON

6782.0

SW-10

SW-6SW-6

WS

6782.0

24" DIA.

SEALED

COLUMN

24" DIA.

SEALED

COLUMN

24" DIA.

PACKED

COLUMN

24" DIA.

PACKED

COLUMN

INTERMEDIATE

WATER TANK

TO RACEWAYS

PS

LSL

BP

-1

BP

-1

TOP OF

SLAB

ELEVATION

6775.0'

TOP

OF

SLAB

ELEVATION

6779.0

DO WT WL

WL

XXX

HEADTANK/DISINFECTION BUILDING SENSORS AND ALARMS

WATER

LEVEL

DF

XXX

DRUM

FILTER

UV

XXX

UV

SYSTEM

DO

XXX

DO

LEVEL

WT

XXX

WATER

TEMPERATURE

DO WT WL

BLV

BLV BLVBLVBLV

10 TYPICAL

DO

WT

WL

6786.0

13 11

SW-21

SURFACE

WATER

HEADTANK

NOT TO SCALE

TOP OF PRIMARY

BY-PASS WEIR INV 6785.0

PUMP 1

400 GPM

O

VE

R

FL

O W

HEADTANK / DISINFECTION BUILDING

PLUMBING DEMOLITION DIAGRAM P06

SW-12

LAKE CREEK

LAKE

WL

HEADTANK/DISINFECTION BUILDING SENSORS AND ALARMS

DF UV DO

SW-12

M

LSL

SW-21

INV 6779.4

DF-1

TG

8" F

LO

W

M

ET

ER

6" PVC

TGRCHV

INV 6782.5

INV 6782.5

8"

BFV

SB-12

INV 6779.0

TO SOUTH RACEWAYS

DF-2

12"

BFV

12"

BFV

12" PVC

8"

BFV

8"

CV

8"

CV

DO WT

VFDVFD

8" F

LO

W

M

ET

ER

SW-FM-1 SW-FM-2

17 17

WT

15 DO WT WL

CV

SP-1 CB-1

" P

VC

4" PVC

" P

VC

" P

VC

" P

VC

4" P

VC

8" P

VC

8" P

VC

D

DO WT WL

BOTTOM OF

PUMP PIT

6783.0 TOS 6775.0

6790.0

6786.06786.0

PUMP CHANNEL

SURFACE WATER HEADTANK

WL

DF

CP

DF

CP

8"

BFV

02 INJECTION

" P

VC

O

VE

R

FL

O

W

O

VE

R

FL

O W

3" PVC

3" P

VC

PUMP

SW-P-1

PUMP

SW-P-2

RADON

FAN RF-2

RADON

FAN RF-1

2" PVC

1 1/2" PVC

DO

LEVEL

UV

SYSTEM

DRUM

FILTER

WATER

TEMPERATURE

WATER

LEVEL

NOT TO SCALE

SW-P-1

VFD

SW-P-2

VFD

PUMP SUCTION

INTAKE 6774.83

6778.5

SURFACE CHANNEL

BY-PASS SUMP

BEYOND

PUMP

CONTROL

PANEL (PC)

EXISTING UV

CONTROL PANEL

WATER SPIKES SW-WS-1 THRU 10

12" PVC

8" P

VC

P

U M

P

BY

-P

AS

S

TO

B Y-

PA

SS

S U

M P

BFV

BFV

8"

" P

VC

" P

VC

" P

VC

EXISTING 16"

BELOW SLAB

HEADTANK / DISINFECTION BUILDING

PLUMBING SYSTEM DIAGRAM P07

CONTROL AND SOUTH RACEWAY BUILDING

PLUMBING DEMOLITION PLANS P08

CONTROL AND SOUTH RACEWAY BUILDING

PLUMBING PLANS P09

PLUMBING DETAILS P10

PLUMBING SYSTEM

SENSOR / FLOW / AND PUMP CONTROL DETAILS P11

HEAD TANK SENSOR PLAN CODE SCHEDULE

PANEL PLAN CODE DESCRIPTION AND LOCATION MONITORING POINT INPUT POWER OUTPUT TO I/O NOTES

HTMP I/O CODE HEAD TANK BUILDING MONITORING PANEL

INPUT SWCH-DO/WT-1 SURFACE WATER INTAKE CHANNEL D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SURFACE WATER INTAKE CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SWCH-WL-1 SURFACE WATER CHANNEL WATER LEVEL WATER LEVEL SENSOR 19 TO 30 VDC 19 VDC REQUIRED @ 4 MA MIN 2-WIRE, 4-20MA CIRCUIT LOOP POWER

INPUT SW-PUCH-DO/WT-1 PUMP CHANNEL D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. PUMP CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SW-PUCH-WL-1 PUMP CHANNEL WATER LEVEL WATER LEVEL SENSOR 19 TO 30 VDC 19 VDC REQUIRED @ 4 MA MIN 2-WIRE, 4-20MA CIRCUIT LOOP POWER

INPUT SWHT-DO/WT-1 SURFACE WATER HEADTANK D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SURFACE WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SWHT-WL-1 SURFACE WATER HEADTANK WATER LEVEL WATER LEVEL SENSOR 19 TO 30 VDC 19 VDC REQUIRED @ 4 MA MIN 2-WIRE, 4-20MA CIRCUIT LOOP POWER

INPUT WWHT-DO/WT-1 WELL WATER HEAD TANK D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. WELL WATER HEAD TANK TEMPERATURE WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT WWHT-WL-1 WELL WATER HEAD TANK WATER LEVEL WATER LEVEL SENSOR 19 TO 30 VDC 19 VDC REQUIRED @ 4 MA MIN 2-WIRE, 4-20MA CIRCUIT LOOP POWER

INPUT SWHT-O2-MASSFLOW-1 SURFACE WATER HEADTANK O2 MASS FLOW SENSOR O2 MASS FLOW SENSOR 115/1/60 2-WIRE, 4-20MA INPUT SWHT-WS-O2-FLOW-1 WATER SPIKE-1 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-2 WATER SPIKE-2 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-3 WATER SPIKE-3 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-4 WATER SPIKE-4 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-5 WATER SPIKE-5 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-6 WATER SPIKE-6 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-7 WATER SPIKE-7 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-8 WATER SPIKE-8 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-9 WATER SPIKE-9 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SWHT-WS-O2-FLOW-10 WATER SPIKE-10 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC

INPUT WWHT-O2-FLOW-1 WELL WATER SEALED CHAMBER O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT WWHT-O2-FLOW-2 WELL WATER SEALED CHAMBER O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC

INPUT SW-UV-1 ALARM UV ALARM CONTACTS ON UV CONTROL PANEL 115/1/60 DIGITAL ALL SIGNALS FROM THRU THE UV CONTROLLER INPUT SW-UV-1 LAMPS-ON LAMPS ON SIGNAL CONTACTS ON UV CONTROL PANEL DIGITAL ALL SIGNALS FROM THRU THE UV CONTROLLER INPUT SW-UV-1 INTENSITY UV-INTENSITY CONTACTS ON UV CONTROL PANEL 2-WIRE, 4-20MA ALL SIGNALS FROM THRU THE UV CONTROLLER INPUT SW-UV-2 ALARM UV ALARM CONTACTS ON UV CONTROL PANEL 115/1/60 DIGITAL ALL SIGNALS FROM THRU THE UV CONTROLLER INPUT SW-UV-2 LAMPS-ON LAMPS ON SIGNAL CONTACTS ON UV CONTROL PANEL DIGITAL ALL SIGNALS FROM THRU THE UV CONTROLLER INPUT SW-UV-2 INTENSITY UV-INTENSITY CONTACTS ON UV CONTROL PANEL 2-WIRE, 4-20MA ALL SIGNALS FROM THRU THE UV CONTROLLER

INPUT PC-WL-1 PUMP CHANNEL WATER LEVEL WATER LEVEL SENSOR 19 TO 30 VDC 19 VDC @ 4 MA MIN 2-WIRE, 4-20MA, HART (ISOLATED), FOR PUMP CONTROL

INPUT PCP-1 PUMP CONTROL PANEL - POWER 115/1/60 2-WIRE, 4-20MA DIGITAL PUMP CONTROLLER

INPUT SW-P-1-RUN SURFACE WATER PUMP P-1 RUN PUMP CONTROL PANEL 115/1/60 2-WIRE, 4-20MA PUMP CONTROL PANEL INPUT SW-P-1-FAIL SURFACE WATER PUMP P-1 FAIL PUMP CONTROL PANEL PUMP CONTROL PANEL INPUT SW-P-1-NOT-IN-AUTO SURFACE WATER PUMP P-1 NOT IN AUTO PUMP CONTROL PANEL PUMP CONTROL PANEL INPUT SW-P-1-FLOW SURFACE WATER PUMP P-1 FLOW METER - GPM FLOW METER 115/1/60 2-WIRE, 4-20MA FLOW METER OUTPUT SIGNAL

INPUT SW-P-2-RUN SURFACE WATER PUMP P-2 RUN PUMP CONTROL PANEL 115/1/60 2-WIRE, 4-20MA PUMP CONTROL PANEL INPUT SW-P-2-FAIL SURFACE WATER PUMP P-2 FAIL PUMP CONTROL PANEL PUMP CONTROL PANEL INPUT SW-P-2-NOT-IN-AUTO SURFACE WATER PUMP P-2 NOT IN AUTO PUMP CONTROL PANEL PUMP CONTROL PANEL INPUT SW-P-2-FLOW SURFACE WATER PUMP P-1 FLOW METER - GPM FLOW METER 115/1/60 2-WIRE, 4-20MA FLOW METER OUTPUT SIGNAL

INPUT SW-SP-1-HL SUMP PUMP HIGH LEVEL ALARM - EXTERIOR PUMP CONTROL PANEL 115/1/60 DRY CONTACTS

INPUT HT-O2-MASSFLOW-1 SURFACE/WELL WATER HEADTANK O2 MASS FLOW SENSOR O2 MASS FLOW SENSOR 115/1/60 2-WIRE, 4-20MA

INPUT WWHT-O2-FLOW-1 WELL WATER SEALED CHAMBER O2 FLOW SENSOR O2 FOW SENSOR 2-WIRE, 4-20MA INPUT WWHT-O2-FLOW-2 WELL WATER SEALED CHAMBER O2 FLOW SENSOR O2 FOW SENSOR 2-WIRE, 4-20MA

INPUT SW-RD-1 RADON LEVEL IN AIR BACKGROUND RADON DETECTOR 12 TO 24 VDC 2 X AAA BATTERY POWER BACKUP INTERIOR EXTERIOR AUDIO / VISUAL HIGH RADON ALARM

INPUT SW-DF-1-HWL HIGH WATER LEVEL CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF MASTER CONTROLLER INPUT SW-DF-1-HHWL HIGH HIGH WATER LEVEL CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF MASTER CONTROLLER INPUT SW-DF-1-MTR DRUM FILTER MOTOR OVERLOAD CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF MASTER CONTROLLER INPUT SW-DF-1-BWP BACKWASH PUMP OVERLOAD CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF MASTER CONTROLLER INPUT SW-DF-1-E-STOP E-STOP CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF MASTER CONTROLLER

INPUT SW-DF-2-HWL HIGH WATER LEVEL CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF SLAVE CONTROLLER INPUT SW-DF-2-HHWL HIGH HIGH WATER LEVEL CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF SLAVE CONTROLLER INPUT SW-DF-2-MTR DRUM FILTER MOTOR OVERLOAD CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF SLAVE CONTROLLER INPUT SW-DF-2-BWP BACKWASH PUMP OVERLOAD CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF SLAVE CONTROLLER INPUT SW-DF-2-E-STOP E-STOP CONTACTS ON DF CONTROL PANEL 24 VDC 2-WIRE, 4-20MA ALARM SIGNALS FROM THE DF SLAVE CONTROLLER

SOUTH RACEWAY BUILDING SENSOR PLAN CODE SCHEDULE

PANEL PLAN CODE DESCRIPTION AND LOCATION MONITORING POINT INPUT POWER OUTPUT TO I/O NOTES

SRMP I/O CODE SOUTH RACE BUILDING MONITORING PANEL

INPUT SR-O2-MASSFLOW-1 SOUTH RACEWAY WATER O2 MASS FLOW SENSOR O2 MASS FLOW SENSOR 115/1/60 2-WIRE, 4-20MA

INPUT SR-O2-FLOW-N1 SOUTH RACE WAY NORTH CHANNEL 1 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-N2 SOUTH RACE WAY NORTH CHANNEL 2 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-N3 SOUTH RACE WAY NORTH CHANNEL 3 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-N4 SOUTH RACE WAY NORTH CHANNEL 4 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-N5 SOUTH RACE WAY NORTH CHANNEL 5 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-N6 SOUTH RACE WAY NORTH CHANNEL 6 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC

INPUT SR-O2-FLOW-S1 SOUTH RACE WAY SOUTH CHANNEL 1 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-S2 SOUTH RACE WAY SOUTH CHANNEL 2 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-S3 SOUTH RACE WAY SOUTH CHANNEL 3 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-S4 SOUTH RACE WAY SOUTH CHANNEL 4 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-S5 SOUTH RACE WAY SOUTH CHANNEL 5 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC INPUT SR-O2-FLOW-S6 SOUTH RACE WAY SOUTH CHANNEL 6 O2 FLOW SENSOR O2 NEEDLE VALVE / FLOW SENSOR 15 TO 24VDC 2-WIRE, 0 TO 5 VDC

INPUT SR-DO/WT-1 SOUTH RACEWAY CHANNEL WATER D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SOUTH RACEWAY CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SR-DO/WT-2 SOUTH RACEWAY CHANNEL WATER D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SOUTH RACEWAY CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SR-DO/WT-3 SOUTH RACEWAY CHANNEL WATER D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SOUTH RACEWAY CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SR-DO/WT-4 SOUTH RACEWAY CHANNEL WATER D.O. D.O. / WATER TEMPERATURE SENSOR 115/1/60 POWERS BOTH D.O. AND WT SENSORS 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS INPUT SAME SENSOR AS D.O. SOUTH RACEWAY CHANNEL WATER TEMPERATURE D.O. / WATER TEMPERATURE SENSOR 2-WIRE, 4-20MA COMBINATION SENSOR WITH WT TWO OUTPUTS

PLUMBING SYSTEM

SENSOR PLAN CODE SCHEDULES AND LEGEND P12

HEADTANK/DISINFECTION

BUILDING DEMOLITION FLOOR PLAN A01

A. UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO FACE OF

STUD.

B. SEE STRUCTURAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

REQUIREMENTS.

1. NEW SOLID FIBERGLASS FLOOR PANEL ABOVE MODIFIED WATER

FLOW CHANNEL. SEE STRUCTURAL DRAWINGS.

2. NEW REMOVABLE HANDRAIL SECTIONS, SEE STRUCTURAL

DRAWINGS.

3. OPENING IN NEW FLOOR SYSTEM FOR ACCESS TO PUMP CHANNEL.

4. NOT USED.

5. NEW FLOOR BAR GRATING AS INDICATED FOR SERVICE ACCESS TO

EQUIPMENT. COORDINATE WITH STRUCTURAL AND PLUMBING

DRAWINGS.

6. INSTALL FRP UP TO 4'-0" ABOVE CONCRETE BASE.

7. NEW CONCRETE PAD. SEE STRUCTURAL DRAWINGS.

8. INSTALL 3 NEW COURSE OF EXTERIOR CMU WALL SECTION

REMOVED DUE TO DETERIORATION. FIELD VERIFY QUANTITY WITH

CONTRACTING OFFICER'S REPRESENTATIVE.

9. NEW STAIRS WITH HAND RAILS, SEE STRUCTURAL DRAWINGS.

10. NEW EQUIPMENT AND PIPING. COORDINATE WITH STRUCTURAL

AND PLUMBING DRAWINGS (TYP).

11. RAISE BAR GRATE FLOORING. COORDINATE WITH STRUCTURAL

AND PLUMBING DRAWINGS.

12. 30"X42" (FIELD VERIFY SIZE) OPENING IN NEW SOLID FIBERGLASS

FLOOR PANEL FOR SERVICE ACCESS, SEE STRUCTURAL

DRAWINGS. PROVIDE WALL MOUNTED CONFINED SPACE WARNING

SIGNS.

DENOTES NEW CONCRETE PAD.

DENOTES EXISTING BAR GRATE FLOOR PANELS

TO REMAIN.

DENOTES NEW FIBERGLASS BAR GRATE FLOOR PANELS

PROVIDE ACCESS PANELS TO EQUIPMENT OR LADDERS

THAT ARE BELOW GRATING.

DENOTES NEW SOLID FIBERGLASS FLOOR PANEL

PROVIDE ACCESS PANELS TO EQUIPMENT OR

LADDERS THAT ARE BELOW FLOOR PANELS.

6786.0'

6783.5'

FIELD

VERIFY

6779.0'

6784.0'

FINISHED

GRADE

6784.0'

6784.0'

6786.0'

OPEN TO LOWER FLOOR LEVEL 6779.0'

HEADTANK/DISINFECTION

BUILDING NEW WORK FLOOR PLAN A02

MATERIALS:

GENERAL STRUCTURAL NOTES S00

08.29.2022

4. ALUMINUM FRAMING:

XX'-X"

TOF

PLAN NOTES

* FOR GENERAL STRUCTURAL NOTES, SEE SHEET 17.0

* THE DIMENSIONS SHOWN HERE APPLY TO GRIDS & PRIMARY ELEMENTS ONLY. SEE

ARCHITECTURAL PLANS FOR ADDITIONAL DIMENSIONS NOT SHOWN HERE.

DENOTES ELEVATIONS:

TOF = TOP OF FOOTING

TOCW = TOP OF CONC WALL

TOM = TOP OF MASONRY WALL

TOB = TOP OF BEAM

TOL = TOP OF LEDGER

TOS = TOP OF STEEL

1. FOUNDATIONS & BASEMENT WALLS:

* FOR MISC CONCRETE REINFORCING SEE DETAIL 3/21.0

DECK CONNECTIONS:

* AT FLOOR GRATING:

PROVIDE 'M' SADDLE CLIP AT EA PERP & EDGE SUPPORT @ 24" OC, MIN (4) PER PANEL

* AT FLOOR PLATE (OPTIONAL):

PROVIDE 1/ 4" Ø TRUSS HEAD FASTENER w/ NUT & WASHER @ 24" OC AT EA PERP &

EDGE SUPPORT. PERMIT 1/ 4" GAP BTWN ADJ PANELS

3. MASONRY WALLS:

(E) 8" MASONRY WALLS:

REMOVE AND REPLACE SPALLED CMU, SEE DET 1,2/18.0

2. SPECIAL FLOOR AREA:

DENOTES (N) 3/4" FIBERGLASS FLOOR PLATE,SLIP-RESISTANT,

YELLOW RESIN,SEE DETAILS 7,8/18.0 FOR SUBFRAMING

DENOTES (N) 1 1/ 2" DP 'I-4015' PULTRUDED GRATING,

YELLOW RESIN

SPAN

I8x6.18 <110'-0">

WIDE FLANGE FLOOR BEAMS:

DENOTES WIDE FLANGE BEAM SIZE

DENOTES TOB ELEVATION

SPAN

* FOR TYPICAL BEAM SHEAR TAB CONNECTION, SEE DET 11/ 18.0

DENOTES EXTENTS OF PLATFORM HAND RAILING,

SEE DET 6/22.0

DEMOLITION PLAN S01

4. ALUMINUM FRAMING:

XX'-X"

TOF

PLAN NOTES

* FOR GENERAL STRUCTURAL NOTES, SEE SHEET 17.0

* THE DIMENSIONS SHOWN HERE APPLY TO GRIDS & PRIMARY ELEMENTS ONLY. SEE

ARCHITECTURAL PLANS FOR ADDITIONAL DIMENSIONS NOT SHOWN HERE.

DENOTES ELEVATIONS:

TOF = TOP OF FOOTING

TOCW = TOP OF CONC WALL

TOM = TOP OF MASONRY WALL

TOB = TOP OF BEAM

TOL = TOP OF LEDGER

TOS = TOP OF STEEL

1. FOUNDATIONS & BASEMENT WALLS:

* FOR MISC CONCRETE REINFORCING SEE DETAIL 3/21.0

DECK CONNECTIONS:

* AT FLOOR GRATING:

PROVIDE 'M' SADDLE CLIP AT EA PERP & EDGE SUPPORT @ 24" OC, MIN (4) PER PANEL

* AT FLOOR PLATE (OPTIONAL):

PROVIDE 1/ 4" Ø TRUSS HEAD FASTENER w/ NUT & WASHER @ 24" OC AT EA PERP &

EDGE SUPPORT. PERMIT 1/ 4" GAP BTWN ADJ PANELS

3. MASONRY WALLS:

(E) 8" MASONRY WALLS:

REMOVE AND REPLACE SPALLED CMU, SEE DET 1,2/18.0

2. SPECIAL FLOOR AREA:

DENOTES (N) 3/4" FIBERGLASS FLOOR PLATE,SLIP-RESISTANT,

YELLOW RESIN,SEE DETAILS 7,8/18.0 FOR SUBFRAMING

DENOTES (N) 1 1/ 2" DP 'I-4015' PULTRUDED GRATING,

YELLOW RESIN

SPAN

I8x6.18 <110'-0">

WIDE FLANGE FLOOR BEAMS:

DENOTES WIDE FLANGE BEAM SIZE

DENOTES TOB ELEVATION

SPAN

* FOR TYPICAL BEAM SHEAR TAB CONNECTION, SEE DET 11/ 18.0

DENOTES EXTENTS OF PLATFORM HAND RAILING,

SEE DET 6/22.0

FOUNDATION AND FLOOR FRAMING PLAN S02

REINFORCING BAR LAP SCHEDULE

REBAR SIZE TOP BARVERT & HORIZ

NORMAL WEIGHT CONCRETE

STRUCTURAL DETAILS S03

SEE PLAN

TO BEAM

WF EDGE BEAM,

SEE PLAN

ALUMINUM POST SLEEVE,

SEE DET 6/22.0

ALUMINUM HAND RAIL POST,

SEE DET 6/22.0

1 1/4"

1/

2"

3/16

FIBERGLASS GRATING BY MANUF (NOTCH

AROUND HAND RAIL POST), SEE PLAN FOR

SPAN AND ORIENTATION

SEE PLAN

FF ELEV

SEE PLAN

FF ELEV

STRINGER, SEE PLAN

STAIR LANDING

BEAM, SEE PLAN

2"

1/4

NOTE:

PROVIDE MIN OF 2 1/2"

OF STRINGER BEARING

ON LANDING BEAM

CJP

1"

SEE

ARCH

GRATING TREADS

w/ CLOSED RISER

SE

E

AR

C

H

1/4

SE

E

PL

AN

CONC TOPPING SLAB,

SEE PLAN

STRINGER, SEE PLAN

L3x3x1/4 x 0'-3" LONG

CLIP ANGLE EA LEG

w/ 1/2"Ø SCREW ANC

3/16

2"

GRATING TREADS w/

CLOSED RISER

(E) MAT SLAB,

SEE PLAN

TYP @

POST

3/16" x 5 1/2" TOE KICK, ATTACHED TO HANDRAIL

POST

2.250ODX0.250

HANDRAIL POST, TYP

1.875ODX0.125 MID

HORIZ RAIL, TYP

2.500ODX0.125X5 1/2" TALL POST

SLEEVE, TYP AT HANDRAIL POST

3/16 TYP

3/16 TYP

4" RADIUS, TYP

SEE PLAN

TOS

1' -9

1'

-9

3' -6

NOTE:

· SHOP VERIFY SLIP CONN AT HAND RAIL

POST AND SLEEVE, ADJUST AS REQ.

· FIBERGLASS GRATING NOT SHOWN

FOR CLARITY

· SIZE DESIGNATIONS CONFORM TO

SECTIONS LISTED IN ADM 2020

WF EDGE BEAM, SEE PLAN

w/ TOE KICK SEE DET

3/16

3 SIDES,

FIELD REQ AT

(E) WF BEAM

FULL-HEIGHT STIFFENERS

BELOW EA POST EA SIDE

OF BEAM WEB (MATCH

BEAM WEB THK), TYP

STRUCTURAL DETAILS S04

FIELD WELD AT

SHEET WORK NOTES

GENERAL NOTES

A. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70 (NEC) AND ANY STATE AND LOCAL

CODES ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

B. CIRCUITS OR CONDUITS SHOWN WITH A DASHED LINE DENOTE UNDERGROUND

INSTALLATION. MINIMUM BURIAL DEPTH SHALL BE 30". HORIZONTAL CONDUIT RUNS IN

CONCRETE PADS OR SLABS NOT PERMITTED.

C. ALL HORIZONTAL RUNS OF CONDUIT BELOW GRADE OR SLAB SHALL BE SCHEDULE 80 PVC

WITH LARGE RADIUS PVC COATED RMC SWEEPS. SHORT RADIUS ELBOWS NOT PERMITTED.

TRANSITIONS FROM UNDERGROUND HORIZONTAL RUN TO VERTICAL RISER SHALL BE MADE

WITH LARGE RADIUS PVC COATED RMC SWEEPS AND PVC COATED RMC CONDUIT RISING

VERTICALLY TO AT LEAST 12" ABOVE GRADE OR SLAB. BEYOND 12" ABOVE GRADE OR SLAB

USE TYPE RMC CONDUIT UNLESS NOTED OTHERWISE.

D. COORDINATE INSTALLATION OF CONDUIT WITH STRUCTURAL COMPONENTS AND OTHER

SYSTEM INSTALLATIONS. CREATE PENETRATIONS IN EXISTING BUILDINGS AND PATCH AND

REPAIR SURFACES AS REQUIRED TO MATCH EXISTING. ALL PENETRATIONS THROUGH

EXTERIOR WALLS SHALL BE WATER-TITE.

E. SEAL ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES WITH U.L. APPROVED

FIRE-RATED SYSTEM.

F. THE BUILDING WILL CONTINUE TO BE OCCUPIED DURING CONSTRUCTION WITH THE

EXCEPTION THAT A PORTION OF THE BUILDING MUST BE EVACUATED DURING ANY CRANE

LIFT.

G. PHASING SCHEDULE MUST BE PRE-APPROVED BY THE GOVERNMENT PRIOR TO

COMMENCING WORK.

H. PROJECT LAY DOWN, CRANE AND DELIVERY ROUTING MUST BE PRE-APPROVED BY THE

GOVERNMENT PRIOR TO COMMENCING WORK.

I. COORDINATE INSTALLATION AND CALIBRATION OF LIMIT SWITCHES WITH FACILITY

PERSONNEL AS DIRECTED BY GOVERNMENT. MAKE FINE ADJUSTMENTS TO LIMIT SWITCHES

FOR PROPER OPERATION OF ALL EQUIPMENT.

J. MOUNT LEVER TYPE LIMIT SWITCHES USING GALVANIZED STRUT, BRACKETS AND MISC.

HARDWARE IN A MANNER THAT DOES NOT CONFLICT WITH MOVING PARTS OF EQUIPMENT

AND PROVIDES A REASONABLE DEGREE OF POSITION ADJUSTMENT.

K. ADD TABS OR OTHER SMALL PROJECTIONS TO MOVING PIECES OF EQUIPMENT AS NEEDED

TO PROVIDE RELIABLE MEANS OF ACTUATING LIMIT SWITCHES. USE COMPATIBLE MATERIALS

AND ENSURE ADDED ITEMS DO NOT INTERFERE OR CONFLICT WITH EXISTING STRUCTURES,

CABLES, ETC.

1. EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT TO REMAIN.

2. DISCONNECT AND REMOVE EXISTING GENERATOR FOR DEMOLITION. PRESERVE CONDUIT

AND CONDUCTORS THAT CONNECT ATS AND BATTERY CHARGER. PREPARE GENERATOR

ROOM AND CONNECTIONS FOR NEW REPLACEMENT GENERATOR INSTALLATION.

3. REMOVE EXISTING CIRCUIT BREAKER, CONDUIT AND CONDUCTORS FOR CIRCUIT TO

EQUIPMENT SERVED. REMOVE ANY BREAKER SPECIFIC BRACKETRY/ADAPTERS AND

PROVIDE FILLER/COVER PLATES TO RETURN BUSSING AND PANELS FOR FUTURE

CONNECTION. REUSE BREAKERS IN NEW GE BOARD EDP

4. PROVIDE NEW CIRCUIT BREAKER IN EXISTING BUSSED SPACE WITH ALL

BRACKETRY/ADAPTERS AS NECESSARY FOR INSTALLATION IN EXISTING DISTRIBUTION

PANELBOARD. PROVIDE NEW COVERPLATE AND PHENOLIC LABELING PER NEC.

5. INTERCEPT EXISTING FEEDER AND EXTEND TO PANEL AS SHOWN. PROVIDE MATERIALS,

SIZED AS NECESSARY.

6. PROVIDE NEW FEEDER TO EDP FROM EP

LEGEND

DASHED HEAVY-LINED ITEMS ARE EXISTING

DEVICES TO BE REMOVED OR RELOCATED.

SOLID LIGHT-LINED ITEMS ARE EXISTING

DEVICES TO REMAIN.

SOLID HEAVY-LINED ITEMS ARE NEW

DEVICES TO BE INSTALLED.

CONTROL ROOM

DISTRIBUTION PANELBOARD

'MDC' - 240/120V, 3Ø, 4W, 800A

20A/3P

3 4 5

150A/3P

6 7

15/3P200A/3P 100A/3P 100A/3P

800A /3P

5.0 KW

HEATER

15A/3P

SPARE

SURGE

SUPPRESSOR

20A/3P

50,000 A.I.C.

PANEL

'P2'

240/120V, 3Ø, 4W

M/G 150A / 3P

JACKET BATTERY

55KW GENSET

CHARGER WATER HTR

PANEL

'P1'

SPARE

400/5 CT'S

CONTROL ROOM

DISTRIBUTION PANELBOARD

'MDC' - 240/120V, 3Ø, 4W, 800A

20A/3P

3 5 6 7

15/3P300A/3P 100A/3P 100A/3P

800A /3P

5.0 KW

HEATER

15A/3P

SPARE

SURGE

SUPPRESSOR

20A/3P

(E)

PANEL

'P2'

240/120V, 3Ø, 4W

M/G 300A / 3P

JACKET BATTERY

100KW GENSET

CHARGER WATER HTR

PANEL

'P1'

SPARE

400/5 CT'S

NEW GE DISTRIBUTION BOARD

'EDP' - 240/120V, 3Ø, 4W, 400A

200A/3P

150A/3P

PULL

BOX

NEW

DEMO

200A ATS

DEMO

NEW

400A ATS

NEW

50,000 A.I.C.

NEW ONE-LINE DIAGRAM

PANEL

EP

PANEL

EP

4#1/0, 1#6G, 1-1/2" C 4#3/0, #6G, 2-1/2" C

GND, #4 COPPER GROUND, 3/4" C

(2) 2" C

EACH W/

(4)#3/0, (1)#3G

NEW

PANEL

'P2DRUM

FILTERS'

NEW 30KVA

240Δ /120-208Y 3∅

XFMR

PANEL

EP-1

TO PANEL EP

CONTRACTOR SHALL PROVIDE TEMPORARY

GENERATOR UNTIL SUCH TIME AS NEW

GENERATOR IS COMMISSIONED --

3#6, #10G, 1" C

4#6, #10G, 1" C

HEADTANK/DISINFECTION

ELECTRICAL LEGENDS, PANELS AND ONE-LINE E01

A. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70 (NEC) AND ANY STATE AND LOCAL

CODES ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

B. CIRCUITS OR CONDUITS SHOWN WITH A DASHED LINE DENOTE UNDERGROUND

INSTALLATION. MINIMUM BURIAL DEPTH SHALL BE 30". HORIZONTAL CONDUIT RUNS IN

CONCRETE PADS OR SLABS NOT PERMITTED.

C. ALL HORIZONTAL RUNS OF CONDUIT BELOW GRADE OR SLAB SHALL BE SCHEDULE 80 PVC

WITH LARGE RADIUS PVC COATED RMC SWEEPS. SHORT RADIUS ELBOWS NOT PERMITTED.

TRANSITIONS FROM UNDERGROUND HORIZONTAL RUN TO VERTICAL RISER SHALL BE MADE

WITH LARGE RADIUS PVC COATED RMC SWEEPS AND PVC COATED RMC CONDUIT RISING

VERTICALLY TO AT LEAST 12" ABOVE GRADE OR SLAB. BEYOND 12" ABOVE GRADE OR SLAB

USE TYPE RMC CONDUIT UNLESS NOTED OTHERWISE.

D. COORDINATE INSTALLATION OF CONDUIT WITH STRUCTURAL COMPONENTS AND OTHER

SYSTEM INSTALLATIONS. CREATE PENETRATIONS IN EXISTING BUILDINGS AND PATCH AND

REPAIR SURFACES AS REQUIRED TO MATCH EXISTING. ALL PENETRATIONS THROUGH

EXTERIOR WALLS SHALL BE WATER-TITE.

E. SEAL ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES WITH U.L. APPROVED

FIRE-RATED SYSTEM.

F. THE BUILDING WILL CONTINUE TO BE OCCUPIED DURING CONSTRUCTION WITH THE

EXCEPTION THAT A PORTION OF THE BUILDING MUST BE EVACUATED DURING ANY CRANE

LIFT.

G. PHASING SCHEDULE MUST BE PRE-APPROVED BY THE GOVERNMENT PRIOR TO

COMMENCING WORK.

H. PROJECT LAY DOWN, CRANE AND DELIVERY ROUTING MUST BE PRE-APPROVED BY THE

GOVERNMENT PRIOR TO COMMENCING WORK.

I. COORDINATE INSTALLATION AND CALIBRATION OF LIMIT SWITCHES WITH FACILITY

PERSONNEL AS DIRECTED BY GOVERNMENT. MAKE FINE ADJUSTMENTS TO LIMIT SWITCHES

FOR PROPER OPERATION OF ALL EQUIPMENT.

J. MOUNT LEVER TYPE LIMIT SWITCHES USING GALVANIZED STRUT, BRACKETS AND MISC.

HARDWARE IN A MANNER THAT DOES NOT CONFLICT WITH MOVING PARTS OF EQUIPMENT

AND PROVIDES A REASONABLE DEGREE OF POSITION ADJUSTMENT.

K. ADD TABS OR OTHER SMALL PROJECTIONS TO MOVING PIECES OF EQUIPMENT AS NEEDED

TO PROVIDE RELIABLE MEANS OF ACTUATING LIMIT SWITCHES. USE COMPATIBLE MATERIALS

AND ENSURE ADDED ITEMS DO NOT INTERFERE OR CONFLICT WITH EXISTING STRUCTURES,

CABLES, ETC.

1. EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT TO REMAIN.

2. DISCONNECT AND REMOVE EXISTING GENERATOR FOR DEMOLITION. PRESERVE CONDUIT

AND CONDUCTORS THAT CONNECT ATS, GENSET BATTERY CHARGER AND BLOCK HEATER.

PREPARE GENERATOR ROOM AND CONNECTIONS FOR NEW REPLACEMENT GENERATOR

INSTALLATION.

3. NEW 100KW 240V/3P STANDBY GENERATOR TO REPLACE EXISTING 55KW. INTERCEPT

EXISTING BATTERY CHARGER AND BLOCK HEATER CIRCUITS AND CONNECT TO NEW.

EXTEND NEW FEEDERS TO NEW MAIN BREAKER IN 'MDC' AND NEW 'ATS'. COORDINATE INTAKE

AND EXHAUST ROUTING WITH OTHER TRADES.

4. NEW 400A AUTOMATIC TRANSFER SWITCH 'ATS'. INTERCEPT EXISTING 'EP' FEED AND EXTEND

TO NEW. PROVIDE NEW FEED AND PULLBOX AS REQUIRED TO INTERCEPT EXISTING

5. INTERCEPT EXISTING CIRCUIT AND EXTEND TO NEW DEVICE AS SHOWN. PROVIDE MATERIALS

AS NECESSARY TO MATCH EXISTING FEEDER TYPE.

6. LOCATION OF NEW GENERATOR ANNUNCIATION/CONTROL PANELS. COORDINATE

PLACEMENT WITH GENERATOR SUPPLIER AND INSTALLER AND EXTEND CONNECTIONS AS

REQUIRED. PROVIDE CONDUIT AND CONDUCTORS FOR 120V AND UP, PROVIDE CONDUIT AS

REQUIRED FOR LOW VOLTAGE CONTROL/COMMUNICATION.

7. NEW MONITOR AND ALARM PANEL TO REPLACE EXISTING. PRESERVE EXISTING CONDUIT(S)

AND CONDUCTORS. INTERCEPT EXISTING FIBER OPTIC AND ETHERNET BACKBONE AND

EXTEND TO NEW/REPLACEMENT PANEL. COORDINATE NEW INSTALLATION WITH INTEGRATED

AQUA SYSTEMS.

8. EXISTING CONDUIT TO PANEL P2. INTERCEPT AND RUN NEW FEEDER TO NEW EDP

9. PROVIDE (2) BELDON 83322E TO SRMP. ONE FOR 115 V SUPPLY AND THE OTHER FOR 4020MA

SIGNAL

LEGEND

DASHED HEAVY-LINED ITEMS ARE EXISTING

DEVICES TO BE REMOVED OR RELOCATED.

SOLID LIGHT-LINED ITEMS ARE EXISTING

DEVICES TO REMAIN.

SOLID HEAVY-LINED ITEMS ARE NEW

DEVICES TO BE INSTALLED.

(E)CNTRL

(E)DIALER

(E)30

KVA

XFMR

(E)112.5

KVA

XFMR

(E)MDC

(E)'P3'

(E)'EP'

(N)

CMP

(N)100KW NG

(E )R

O

LL

-U P

D O

O R

GENERATOR

(N)'EDP'

BATTERY

CHARGER

BLOCK

HEATER

'NORMAL'

'RUN'

'TROUBLE'

SEE SHEET C10.18

(D)GENERATOR2

(D)ATS

(E)PC

(E)30

KVA

XFMR

(E)112.5

KVA

XFMR

(D)BATTERY

CHARGER 2

(E )R

O

LL

-U P

D O

O R

(E)MDC

(E)'P3'

(E)'EP'

(D)CMP

(E)CNTRL

(E)DIALER

(N)

SRMP

D0 WT

SRW-3

D0 WT

SRW-4

D0 WT

SRW-2

D0 WT

SRW-1

9 9

NORTH REF

NORTH REF

HEADTANK/DISINFECTION

CONTROL BUILDING ELECTRICAL PLANS E02

NORTH REF

08/26/2022

A. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70 (NEC) AND ANY STATE AND LOCAL

CODES ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

B. CIRCUITS OR CONDUITS SHOWN WITH A DASHED LINE DENOTE UNDERGROUND

INSTALLATION. MINIMUM BURIAL DEPTH SHALL BE 30". HORIZONTAL CONDUIT RUNS IN

CONCRETE PADS OR SLABS NOT PERMITTED.

C. ALL HORIZONTAL RUNS OF CONDUIT BELOW GRADE OR SLAB SHALL BE SCHEDULE 80 PVC

WITH LARGE RADIUS PVC COATED RMC SWEEPS. SHORT RADIUS ELBOWS NOT PERMITTED.

TRANSITIONS FROM UNDERGROUND HORIZONTAL RUN TO VERTICAL RISER SHALL BE MADE

WITH LARGE RADIUS PVC COATED RMC SWEEPS AND PVC COATED RMC CONDUIT RISING

VERTICALLY TO AT LEAST 12" ABOVE GRADE OR SLAB. BEYOND 12" ABOVE GRADE OR SLAB

USE TYPE SCH40 PVC CONDUIT OR PVC COATED RACEWAYS, BOXES AND COMPONENTS

UNLESS NOTED OTHERWISE FOR CORROSIVE ENVORINMENTS.

D. COORDINATE INSTALLATION OF CONDUIT WITH STRUCTURAL COMPONENTS AND OTHER

SYSTEM INSTALLATIONS. CREATE PENETRATIONS IN EXISTING BUILDINGS AND PATCH AND

REPAIR SURFACES AS REQUIRED TO MATCH EXISTING. ALL PENETRATIONS THROUGH

EXTERIOR WALLS SHALL BE WATER-TITE OR EQUAL.

E. SEAL ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES WITH U.L. APPROVED

FIRE-RATED SYSTEM.

F. THE BUILDING WILL CONTINUE TO BE OCCUPIED DURING CONSTRUCTION WITH THE

EXCEPTION THAT A PORTION OF THE BUILDING MUST BE EVACUATED DURING ANY CRANE

LIFT.

G. PHASING SCHEDULE MUST BE PRE-APPROVED BY THE GOVERNMENT PRIOR TO

COMMENCING WORK.

H. PROJECT LAY DOWN, CRANE AND DELIVERY ROUTING MUST BE PRE-APPROVED BY THE

GOVERNMENT PRIOR TO COMMENCING WORK.

I. COORDINATE INSTALLATION AND CALIBRATION OF LIMIT SWITCHES WITH FACILITY

PERSONNEL AS DIRECTED BY GOVERNMENT. MAKE FINE ADJUSTMENTS TO LIMIT SWITCHES

FOR PROPER OPERATION OF ALL EQUIPMENT.

J. MOUNT LEVER TYPE LIMIT SWITCHES USING GALVANIZED STRUT, BRACKETS AND MISC.

HARDWARE IN A MANNER THAT DOES NOT CONFLICT WITH MOVING PARTS OF EQUIPMENT

AND PROVIDES A REASONABLE DEGREE OF POSITION ADJUSTMENT.

K. ADD TABS OR OTHER SMALL PROJECTIONS TO MOVING PIECES OF EQUIPMENT AS NEEDED

TO PROVIDE RELIABLE MEANS OF ACTUATING LIMIT SWITCHES. USE COMPATIBLE MATERIALS

AND ENSURE ADDED ITEMS DO NOT INTERFERE OR CONFLICT WITH EXISTING STRUCTURES,

CABLES, ETC.

L. PROVIDE 3Ø MOTOR PROTECTION FOR ALL MOTOR LOADS CONNECTED TO GENERATOR

POWER.

1. EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT TO REMAIN.

2. DISCONNECT AND REMOVE EXISTING PUMP FOR DEMOLITION. PRESERVE CONDUIT AND

CONDUCTORS AT NEAREST JUNCTION BOX. MARK ACCORDINGLY AND PREPARE

CONNECTIONS FOR NEW REPLACEMENT PUMP ASSEMBLY INSTALLATION.

3. NOT USED

4. DISCONNECT AND REMOVE EXISTING DRUM FILTER MOTOR AND ELECTRICAL CONNECTIONS

FOR DEMOLITION. PRESERVE CONDUIT AND CONDUCTORS AT NEAREST JUNCTION BOX.

MARK ACCORDINGLY AND PREPARE CONNECTIONS FOR NEW REPLACEMENT DRUM FILTER

ASSEMBLY.

5. DISCONNECT AND REMOVE EXISTING ELECTRICAL DEVICE OR EQUIPMENT AS INDICATED

FOR DEMOLITION. PRESERVE CONDUIT AND CONDUCTORS AT NEAREST JUNCTION BOX.

MARK ACCORDINGLY AND PREPARE CONNECTIONS FOR NEW REPLACEMENT AS INDICATED

ON NEW ELECTRICAL PLAN(S).

6. COORDINATE CONDUIT PATHS TO NEW DRUM FILTERS WITH APPROVED SHOP DRAWINGS

AND EQUIPMENT SUPPLIER, CONDUIT RISER LOCATION SHOWN IS GENERAL.

7. INTERCEPT EXISTING CIRCUIT AND EXTEND TO NEW DEVICE AS SHOWN. PROVIDE MATERIALS

AS NECESSARY TO MATCH EXISTING FEEDER TYPE. EXISTING CONDUIT MAY BE REUSED.

8. NEW HTMP HEAD TANK MONITORING PANEL PROVIDE 20A 120V POWER FROM PANEL P2

9. NEW LITHONIA DMW2 L24 4000LM PFL MD MVOLT GZ10 40K 80CRI LIGHT FIXTURE. SURFACE

MOUNT. CONNECT TO EXISTING LIGHTING CIRCUIT UNDER EXISTING CONTROL. MAINTAIN

EXISTING LOCAL SWITCHING AND EXTEND TO REPLACEMENT FIXTURES AS NECESSARY.

10. 45 KVA NEMA 12 20V DELTA PRIMARY /208/120 V WYE SECONDARY

11. VFDS FOR P1,2. SEE SPECS . NEMA 12

12 PUMP CONTROL PANEL . BY MECHANICAL

13. RADON DETECTOR . PROVIDE 120V CONNECTION

14.PROVIDE BELDON CABLE 83322E TO HTCP FOR 115V

15, PROVIDE BELDON CABLES 83322E FOR 4-20MA `

(D)GENERATOR2

(E)DIALER

(E)30

KVA

XFMR

(E)112.5

KVA

XFMR

(E)'P3'

(E)'EP'

(E)O2

CNTRL

(N)100KW NG

(N)400A

ATS

(E )R

O

LL

-U P

D O

O R

GENERATOR

(N)'EDP'

M

M

M

6 6

P2 DRUM-1,3,5P2DRUM -2,4,6

RF-1

SW-P-1

SW-FM-1

SW-1-P-2

SW-FM-2

EXISTING UV-1

POWER SUPPLY

P2-20,22,24

M

M

P2-8,10,12 P2-7,9,11

P2DRUM-15

P2DRUM-14

(N)

HTMP 8 P2UV

(MOUNT TO

BOTTOM OF

TANK)

(REPLACE

EXISTING WALL

MOUNTED

FIXTURE)

CLG MTD

DE-GAS

COLUMN

CONTROL

RF-1

RF-2

WL

PC-

WL-1

WL DO WT

SWHT-

DO/WT-1

SWHT-

WL-1

DO WT

SWCH-

DO/WT-1

WL

DO

WT

SW-PUCH--

DO/WT-1

SW-PUCH--

WL-1

11 12 15 15 15

15 14

WL

SWHT-

WL-1

P2 DRUM-13

SP-1

SWU-UV-1-ALARM

SW-UV-1-LAMPS ON

SW-UV-1-INTENSITY EXISTING -UV-2

POWER SUPPLY

SWU-UV-2-ALARM

SW-UV-2-LAMPS ON

SW-UV-2-INTENSITY

MASS FLOW

METER

SWHT-WS-02-FLOW-1,2,3,4,5,6,7,8,9,10

SWHT--02- MASS FLOW-1

5 12

5 11

5 12

5 11

5 12

5 11

5 12

5 11

5 12

SW-P-2

VFD-OUT-HZ

VFD-CURRENT

VFD-TOURQUE

VFD-SPEED

VFD-SP-HZ

SW-P-2-RUN

SW-P-2-FAIL

SW-P-2-NOT-IN-AUTO

SW-P-2-FLOW

SW-P-1

VFD-OUT-HZ

VFD-CURRENT

VFD-TOURQUE

VFD-SPEED

VFD-SP-HZ

SW-P-1-RUN

SW-P-1-FAIL

SW-P-1-NOT-IN-AUTO

SW-P-1-FLOW

SW-DF-1-HWL

SW-DF-1-HHWL

SW-DF-1-MTR

SW-DF-1-BWP

SW-DF-1-E-STOP

SW-DF-2-HWL

SW-DF-2-HHWL

SW-DF-2-MTR

SW-DF-2-BWP

SW-DF-2-E-STOP

15 15

M M

4 4

PS

PS

LWL DO WT LWL DO WTLWL DO WT

LWL

DO

WT

55 5

M

NORTH REF

NORTH REF

HEADTANK/DISINFECTION

HEADTANK/DISINFECTION ELECTRICAL PLANS E03

EXISTING CONDUIT WITH 2 STR AND

FIBER. REMOVE OLD FIBER AND PULL

NEW 6 STRAND SINGLE MODE FIBER

CABLE . TERMINATE 2 STRANDS FOR

EACH CONTROL PANEL . REMAINING 4

STRAND ARE SPARES

EXISTING MDP. INTERCEPT P2 FEEDER

CONDUIT AND PROVIDE NEW IN

GROUND SPICE BOX . RUN NEW P2

FEEDER FROM EDP AND SPLICE IN

BOX.

SHEET WORK NOTES?

1.

2.

THIS SITE PLAN IS BASED UPON EXISTING

DRAWINGS AND SITE OBSERVATIONS. IT IS

PROVIDED TO ASSIST THE CONTRACTOR IN

LOCATING SPECIFIC LOCATIONS INDICATED ON

OTHER DRAWINGS.

HEADTANK/DISINFECTION

CONTROL BUILDING ELECTRICAL SITE PLAN E04

NORTH REF

120'60'30'0

SCALE: 1" = 60'-0"

SRMP

HTMP

CMP

08/26/2022REVISED SET PER RFI#1 08/08/2024

CONTROLS NETWORK DIAGRAM E-05

CENTRAL ALARM CONTROL PANEL

BILL OF MATERIALS E-06

ITEM TAGS QTY SUB CATALOG MFG DESCRIPTION

1 HMI5132 1 2711P-T12W21D8S AB PanelView Plus 7 Standard, Touch Screen 12.1 Inches, Color, Single Ethernet, 24VDC

2 RECPT5029 1 P-R2-K3RF3 GRACEPORT Graceport Module

3 6 199-DR1 AB 35mm Din Rail - Standard 1m

4 PLC5110 1 5069-L320ER AB CompactLogix 5380 Controller, 2MB

5 PLC5200

PLC5300

PLC5400

3 5069-IB16 AB 5069 Compact I/O 16 Channel 24VDC Sink Input Module

6 PLC5500

PLC5600

2 5069-OW16 AB 5069 Compact I/O 16 Channel Normally Open Non-Isolated Relay Output Module

7 PLC5700

PLC5800

2 5069-IF8 AB 5069 Compact I/O 8 Channel Voltage/Current Analog Input Module

8 1 5069-ECR AB 5069 Compact I/O End Cap Right

9 PS5037 1 1606-XLE80E AB Essential 120VAC 1P, 24VDC Power Supply 80W

10 PS5031 1 1606-XLE480EP AB Essential 120VAC 1P, 24VDC Power Supply 480W

11 7 1492-EBJ3 AB End Barrier; 1492-J

12 CB5003 1 1489-M1C200 AB 1489-M Thermal Magnetic CB, UL489, Trip Curve C, 20A

13 24 1492-JG4 AB Terminal Block, Grounding, Green/Yellow, 4mm

14 18 1492-EBJ3-Y AB Terminal Block End Barrier, Yellow

16 CB5005 1 1489-M1C010 AB 1489-M Thermal Magnetic CB, UL489, Trip Curve C, 1A

17 12 CA903 ALTECH CORP Din Rail Support Bracket, 3inch

18 1 JPM398A BLACK BOX DIN Rail Fiber Patch Panel Enclosure

*1 JPM455C-R2 BLACK BOX LGX Adapter Duplex Connector

*2 FOSM-LSZH-001M-LCLC BLACK BOX Connect OS2 90-Micron Single-Mode Fiber Optic Patch Cable - OFNR PVC, LC-LC, 1m

19 180 1492-J3 AB Terminal Block, 25A, 600V AC/DC, Gray 2.5mm Feed Through screw connection

20 DV5103 1 *1 IE-2000-4TS-L CISCO IE 2000 Managed Switch, 6 Ports, LAN Lite

*1 GLC-FE-100ZX= CISCO SFP Tranciever, 100BASE-ZX Singlemode FE

21 LT5021 1 *1 LEDA2S35 HOFFMAN Enclosure Light - Omni Motion Sensor

*1 LEDA20C HOFFMAN Enclosure Light - Cord w/Connector

22 1 DAH1001A HOFFMAN Electric Heater, 115V, 100W, Aluminum

23 1 CP6036 HOFFMAN Panel 60 x 36 , White, Steel

24 1 CSD603612 HOFFMAN Concept Single Door Enclosure, 60 x 36 x 12, Gray, Steel

25 2 *1 F1.5X3LG6 PANDUIT 1.5x3 Narrow Slot Wiring Duct - Gray - 6ft.

*1 C1.5LG6 PANDUIT 1.5" Wide Wire Duct Cover - Gray - 6ft.

26 3 *1 F2X3LG6 PANDUIT 2x3 Narrow Slot Wiring Duct - Gray - 6ft.

*1 C2LG6 PANDUIT 2" Wide Wire Duct Cover - Gray - 6ft.

27 2 TRD815SRA1BL-7 L-COM CAT 5E Shielded Right Angle to Straight Patch Cable, 7ft.

28 1 TRD815SRA1BL-20 L-COM CAT 5E Shielded Right Angle to Straight Patch Cable, 20ft.

29 PS5011 1 2320283 PHOENIX

CONTACT

Uninterruptible power supply - QUINT4-UPS/1AC/1AC/1KVA

30 BAT5014

BAT5017

2 1274118 PHOENIX

CONTACT

Energy storage, VRLA-AGM, 24 V DC, 7 Ah, automatic detection and communication with

QUINT UPS-IQ

31 DV5106 1 PLX31-EIP-MBS PROSOFT EtherNet/IP to Modbus Serial - RS232

32 1 2200 CATTRON EliteIQ with Keypad & Display in panel / flush mount metal enclosure

33 1 2200-2050 CATTRON EliteIQ AT&T CATM1 Modem Kit in NEMA 4X Enclosure

34 1 1950-0033 CATTRON EliteIQ 8 Channel Digital Input Card (installed)

35 1 1600-3000 CATTRON 3 Yr. Remote IQ Standard Plan - Text, Voice, and Email

36 FU5022

FU5029

FU5031

FU5037

FU5043

FU5044

FU5045

FU5046

FU5047

FU5048

10 3004142 PHOENIX

CONTACT

Fuse terminal block, AWG26-10, Block 5x20mm - 120VAC w/LED Indicator

37 FU5110

FU5112

FU5114

FU5116

FU5118

FU5120

FU5122

FU5130

FU5132

FU5134

FU5136

FU5138

FU5140

FU5142

FU5144

31 3004126 PHOENIX

CONTACT

Fuse terminal block, AWG26-10, Block 5x20mm - 24VDC w/LED Indicator

38 31 1492-EAJ35 AB Terminal Block End Anchor, Normal Duty

39 3 3118135 PHOENIX

CONTACT

Insertion Bridge - EBS 10 Position

40 15 235.500 LITTLEFUSE 1/2A Fast Acting, 250V Rated 5 x 20mm

41 5 235.1600 LITTLEFUSE 1-1/2A Fast Acting, 250V Rated 5 x 20mm

42 25 235.250 LITTLEFUSE 1/4A Fast Acting, 250V Rated 5 x 20mm

43 15 235.1000 LITTLEFUSE 1A Fast Acting, 250V Rated 5 x 20mm

44 5 235.4000 LITTLEFUSE 4A Fast Acting, 250V Rated 5 x 20mm

45 10 235.2000 LITTLEFUSE 2A Fast Acting, 250V Rated 5 x 20mm

PANEL DOOR LAYOUT E-07

ENC.

TYPE 4

GracePort® Interface

P-R2-K3RF0

FOR COMPUTER USE ONLY120VAC, 5A (MAX)

GFCI Inside - Outlet®

ETHERNET

BACK PANEL LAYOUT E-08

120VAC POWER DISTRIBUTION E-09

24VDC POWER DISTRIBUTION E-10

5069-IB16 DC INPUTS (SLOT 1) E-11

5069-IB16 DC INPUTS (SLOT 2) E-12

5069-IB16 DC INPUTS (SLOT 3) E-13

5069-OW16 RELAY OUTPUTS (SLOT 4) E-14

5069-IF8 ANALOG INPUTS (SLOT 6) E-16

5069-IF8 ANALOG INPUTS (SLOT 7) E-17

HEAD TANK CONTROL PANEL

BILL OF MATERIALS E-18

ITEM TAGS QTY SUB CATALOG MFG DESCRIPTION

1 1 CSD603612 HOFFMAN Concept Single Door Enclosure, 60 x 36 x 12, Gray, Steel

2 1 CP6036 HOFFMAN Panel 60 x 36 , White, Steel

3 LT5021 1 *1 LEDA2S35 HOFFMAN LED Enclosure Light, IR Motion Sensor

*1 LEDA20C HOFFMAN Enclosure Light - Cord w/Connector

4 2 *1 F1.5X3LG6 PANDUIT 1.5x3 Narrow Slot Wiring Duct - Gray - 6ft.

*1 C1.5LG6 PANDUIT 1.5" Wide Wire Duct Cover - Gray - 6ft.

5 3 *1 F2X3LG6 PANDUIT 2x3 Narrow Slot Wiring Duct - Gray - 6ft.

*1 C2LG6 PANDUIT 2" Wide Wire Duct Cover - Gray - 6ft.

6 6 199-DR1 AB ZINC/STEEL DIN RAIL EN 50022 (35mm x 7.5mm x 1m)

7 CB5004 1 1489-M1C200 AB 1489-M Thermal Magnetic CB, UL489, Trip Curve C, 20A

8 CB5006 1 1489-M1C010 AB 1489-M Thermal Magnetic CB, UL489, Trip Curve C, 1.0A

9 FU5010

FU5012

FU5014

FU5016

FU5018

FU5020

FU5022

FU5029

FU5030

FU5031

10 3004142 PHOENIX Fuse terminal block, AWG26-10, Block 5x20mm - 120VAC w/LED Indicator

10 FU5110

FU5112

FU5114

FU5116

FU5118

FU5120

FU5122

FU5030

FU5032

FU5034

FU5036

FU5038

FU5040

FU5042

FU5044

15 3004126 PHOENIX Fuse terminal block, AWG26-10, Block 5x20mm - 24VDC w/LED Indicator

11 51 1492-EBJ3-Y AB END BARRIER; 1492-J , YELLOW

12 10 1492-EBJ3 AB END BARRIER; 1492-J

13 55 1492-JG4 AB Terminal Block, Grounding, Green/Yellow, 4mm

14 PS5011 1 2320283 PHOENIX

CONTACT

Uninterruptible power supply - QUINT4-UPS/1AC/1AC/1KVA

15 PS5031 1 1606-XLE480EP AB Essential 120VAC 1P, 24VDC Power Supply 480W

16 PS5037 1 1606-XLE80E AB Essential 120VAC 1P, 24VDC Power Supply 80W

17 BAT5014

BAT5017

2 1274118 PHOENIX

CONTACT

Energy storage, VRLA-AGM, 24 V DC, 7 Ah, automatic detection and communication with

QUINT UPS-IQ

18 DV5103 1 *1 IE-2000-4TS-L CISCO IE 2000 Managed Switch, 6 Ports, LAN Lite

*1 GLC-FE-100ZX= CISCO SFP Tranciever, 100BASE-ZX Singlemode FE

19 171 1492-J3 AB SCREW CONNECTION TERMINAL BLOCK; 1492-J

20 CR5304

CR5305

CR5306

CR5307

CR5308

CR5309

CR5310

CR5311

CR5313

CR5314

CR5315

CR5316

CR5317

CR5318

CR5319

CR5320

16 *1 700-HK32Z24 AB GP Slim Line Relay, 24VDC, Standard Contacts, DPDT, 8A

*1 700-HN222 AB GP Slim Line Relay Base

21 12 CA903 ALTECH CORP Din Rail Support Bracket, 3inch

22 PLC5000 1 5069-AENTR AB 5069 Compact I/O Ethernet/IP Adapter

23 PLC5200 1 5069-IA16 AB 5069 Compact I/O 16 Channel AC Input Module

24 PLC5300 1 5069-FPD AB 5069 Compact I/O Field Potential Distributor Module

25 PLC5400 1 5069-OW16 AB 5069 Compact I/O 16 Channel Normally Open Non-Isolated Relay Output Module

26 PLC5500

PLC5600

PLC5700

PLC5800

PLC5900

6 5069-IF8 AB 5069 Compact I/O 8 Channel Voltage/Current Analog Input Module

27 HMI5132 1 2711P-T12W21D8S AB PanelView Plus 7 Standard, Touch Screen 12.1 Inches, Color, Single Ethernet, 24VDC

28 RECEPT5029 1 P-R2-K3RF3 GRACEPORT

29 1 *1 JPM398A BLACK BOX DIN Rail Fiber Patch Panel Enclosure

*1 JPM455C-R2 BLACK BOX LGX Adapter Duplex Connector

*2 FOSM-LSZH-001M-LCLC BLACK BOX Connect OS2 90-Micron Single-Mode Fiber Optic Patch Cable - OFNR PVC, LC-LC, 1m

30 37 1492-EAJ35 AB Terminal Block End Anchor, Normal Duty

31 1 5069-ECR AB 5069 Compact I/O End Cap Right

32 1 TRD815SRA1BL-7 LCOM CAT 5E Shielded Right Angle to Straight Patch Cable, 7ft.

33 1 TRD815SRA1BL-20 LCOM CAT 5E Shielded Right Angle to Straight Patch Cable, 20ft.

34 1 3118135 PHOENIX

CONTACT

Insertion Bridge - EBS 10 Pole

35 HTR5008 1 DAH1001A HOFFMAN Electric Heater, 115V, 100W, Aluminum

36 15 235.500 LITTLEFUSE 1/2A Fast Acting, 250V Rated 5 x 20mm

37 60 235.250 LITTLEFUSE 1/4A Fast Acting, 250V Rated 5 x 20mm

38 5 235.4000 LITTLEFUSE 4A Fast Acting, 250V Rated 5 x 20mm

39 20 235.2000 LITTLEFUSE 2A Fast Acting, 250V Rated 5 x 20mm

40 20 235.1000 LITTLEFUSE 1A Fast Acting, 250V Rated 5 x 20mm

PANEL DOOR LAYOUT E-19

ENC.

TYPE 4

GracePort® Interface

P-R2-K3RF0

FOR COMPUTER USE ONLY120VAC, 5A (MAX)

GFCI Inside - Outlet®

ETHERNET

BACK PANEL LAYOUT E-20

120VAC POWER DISTRIBUTION E-21

24VDC POWER DISTRIBUTION E-22

5069-IA16 AC INPUTS (SLOT 1) E-23

5069-OW16 RELAY OUTPUTS (SLOT 2) E-24

5069-IF8 ANALOG INPUTS (SLOT 3) E-25

08/26/2022

REVISED SET PER RFI#1 08/08/2024

SWCH-DO/WT-1

SWCH-DO/WT-1

PUMP CHANNEL D.O---SW-PUCH--DO/WT-1

PUMP CHANNEL WATER TEMP ----SW-PUCH--DO/WT-1

PUMP CHANNEL WATER LEVEL ---SW-PUCH--WL1

SWHT-DO/WT-1

SWHT-DO/WT-1

SWHT-WL-1

5069-IF8 ANALOG INPUTS (SLOT 4) E-26

08/26/2022

REVISED SET PER RFI#1 08/08/2024

WWHT-DO/WT-1

WWHT-DO/WT-1

WWHT-WL-1

PC-WL-1

PC-1

SW-P-1-FLOW

SURFACE WATER P1-FAIL SW-P-1-FAIL

5069-IF8 ANALOG INPUTS (SLOT 5) E-27

08/26/2022

REVISED SET PER RFI#1 08/08/2024

SW-P2-FLOW

SURFACE WATER P1-NOT-IN-AUTO SW-P-1-NOT-IN AUTO

P-2

SURFACE WATER P2-RUN SW-P-1-RUN

SURFACE WATER P2-FAIL-SW-P-1-FAIL

SURFACE WATER P2-NOT-IN-AUTO SW-P-1-NOT-IN AUTO

SSUMP PUMHIGH LEVEL ALARM -EXTERIOR--SW-SP-HL

5069-IF8 ANALOG INPUTS (SLOT 6) E-28

08/26/2022

REVISED SET PER RFI#1 08/08/2024

SWHT-02-MASSFLOW-1

WWHT-02-FLOW-1

WWHT-02-FLOW-2W

SW-RD-1

SURFACE/WELL WATER HEADTANK02 MASS FLOW SENSOR

HT-02 MASSFLOW-1

5069-IF8 ANALOG INPUTS (SLOT 7) E-29

08/26/2022

REVISED SET PER RFI#1 08/08/2024

WATER SPIKE 1 02 FLOW SENSOR

SWHT-WS-02-FLOW-1

WATER SPIKE 2 02 FLOW SENSOR

SWHT-WS-02-FLOW-2

WATER SPIKE 3 02 FLOW SENSOR

SWHT-WS-02-FLOW-3

WATER SPIKE 4 02 FLOW SENSOR

SWHT-WS-02-FLOW-4

WATER SPIKE 5 02 FLOW SENSOR

SWHT-WS-02-FLOW-5

WATER SPIKE 6 02 FLOW SENSOR

SWHT-WS-02-FLOW-6

WATER SPIKE 7 02 FLOW SENSOR

SWHT-WS-02-FLOW-7

WATER SPIKE 8 02 FLOW SENSOR

SWHT-WS-02-FLOW-8

5069-IF8 ANALOG INPUTS (SLOT 8) E-30

08/26/2022

REVISED SET PER RFI#1 08/08/2024

UV 1 ALARM SW-UV-1-ALARM

UV 1 LAMPS ON SIGNAL -- SW-UV-1-LAMPS ON

UV 1 INTENSITY SW-UV-1-INTENSITY

UV 2 ALARM SW-UV-2-ALARM

UV 2 LAMPS ON SIGNAL -- SW-UV-2-LAMPS ON

UV 2 INTENSITY SW-UV-2-INTENSITY

WATER SPIKE 9 02 FLOW SENSOR

SWHT-WS-02-FLOW-9

WATER SPIKE 10 02 FLOW SENSOR

SWHT-WS-02-FLOW-10

HEAD TANK CONTROL PANEL

5069-IF8 ANALOG INPUTS (SLOT 8)

REVISED SET

UV 1 ALARM SW-UV-1-ALARM

UV 1 LAMPS ON SIGNAL -- SW-UV-1-LAMPS ON

UV 1 INTENSITY SW-UV-1-INTENSITY

UV 2 ALARM SW-UV-2-ALARM

UV 2 LAMPS ON SIGNAL -- SW-UV-2-LAMPS ON

UV 2 INTENSITY SW-UV-2-INTENSITY

WATER SPIKE 9 02 FLOW SENSOR

SWHT-WS-02-FLOW-9

WATER SPIKE 10 02 FLOW SENSOR

SWHT-WS-02-FLOW-10

NEED TO ADD THESE

ADDTIONAL POINTS

HIGH WATER LEVEL SW-DF-1-HWL

HIGH HIGH WATER LEVEL SW-DF-1-HHWL

DRUM FILTERMOTOR LOAD SW-DF-1-MTR

BACKWASH PUMP OVERLOAD SW-DF-1-BWP

E-STOP SW-DF-1-E-STOP

HIGH WATER LEVEL SW-DF-2-HWL

HIGH HIGH WATER LEVEL SW-DF-2-HHWL

DRUM FILTERMOTOR LOAD SW-DF-2-MTR

BACKWASH PUMP OVERLOAD SW-DF-2-BWP

E-STOP…