This document is a specifications volume related to the federal contract opportunity Notice of Intent - 140FC223R0011 A/E DESIGN SF330. The specifications volume outlines requirements for architecture and engineering design services for the Prime Hook National Wildlife Refuge in Sussex County, Delaware. Key details include that the Department of the Interior Fish and Wildlife Service is seeking proposals from qualified architecture and engineering firms to provide design services. The design scope includes site improvements, repairs and renovations to buildings and structures, and upgrades to utilities and infrastructure. The response deadline is February 14, 2022. The contract is set aside for small businesses and proposals must demonstrate relevant experience with federal wildlife refuge projects. The award date is anticipated for Spring 2022 and the contract period of performance is 24 months.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S P E C I F I C A T I O N S

Volume 2 of 2 Divisions 22-33

Visitor Contact Station Prime Hook National Wildlife Refuge

Milton, Delaware

Prepared By:

Prepared For:

United States Fish and Wildlife Service Northeast Region 5 300 Westgate Center Drive Hadley, Massachusetts 01035

Project No. 5R-DEL-630-14.0

January 14, 2022

U.S. Fish and Wildlife Service

VISITOR CONTACT STATION PROJECT NO. 5R-DEL-630-14.0

PRIME HOOK NATIONAL WILDLIFE REFUGE

U.S. FISH & WILDLIFE SERVICE

MILTON, DELAWARE

TABLE OF CONTENTS PAGE - 1

TABLE OF CONTENTS

DIVISION 01 – GENERAL REQUIREMENTS

010000 SEALS PAGE

011000 SUMMARY

012100 ALLOWANCES

012300 ADDITIVES

012600 CONTRACT MODIFICATION PROCEDURES

012900 PAYMENT PROCEDURES

013100 PROJECT MANAGEMENT AND COORDINATION

013200 CONSTRUCTION PROGRESS DOCUMENTATION

013300 SUBMITTAL PROCEDURES

014000 QUALITY REQUIREMENTS

014200 REFERENCES

014300 ENVIRONMENTAL PROTECTION

014535 SPECIAL INSPECTIONS (WITH SCHEDULE ATTACHED)

015000 TEMPORARY FACILITIES AND CONTROLS

015639 TEMPORARY TREE AND PLANT PROTECTION

017300 EXECUTION

017419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

017700 CLOSEOUT PROCEDURES

017823 OPERATION AND MAINTENANCE DATA

017839 PROJECT RECORD DOCUMENTS

019000 GENERAL SAFETY REQUIREMENTS

019113 GENERAL COMMISSIONING REQUIREMENTS

DIVISION 03 – CONCRETE

031000 CONCRETE FORMING AND ACCESSORIES

032000 CONCRETE REINFORCING

033000 CAST-IN-PLACE CONCRETE

DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES

061000 ROUGH CARPENTRY

061516 WOOD ROOF DECKING

061600 SHEATHING

061753 SHOP-FABRICATED WOOD TRUSSES

062023 INTERIOR FINISH CARPENTRY

064113 WOOD-VENEER-FACED ARCHITECTURAL CABINETS

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

072100 THERMAL INSULATION

072500 WEATHER BARRIERS

074113.16 STANDING-SEAM METAL ROOF PANELS

074646 FIBER-CEMENT SIDING

076200 SHEET METAL FLASHING AND TRIM

078413 PENETRATION FIRESTOPPING

079200 JOINT SEALANTS

U.S. FISH & WILDLIFE SERVICE

TABLE OF CONTENTS PAGE - 2

DIVISION 08 - OPENINGS

081113 HOLLOW METAL DOORS AND FRAMES

081416 FLUSH WOOD DOORS

084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

084126 ALL-GLASS ENTRANCES AND STOREFRONTS

085200 WOOD WINDOWS

087111 DOOR HARDWARE (DESCRIPIVE SPECIFICATION)

DIVISION 09 – FINISHES

092900 GYPSUM BOARD

093013 CERAMIC TILING

095113 ACOUSTICAL PANEL CEILINGS

096513 RESILIENT BASE AND ACCESSORIES

096813 TILE CARPETING

099113 EXTERIOR PAINTING

099123 INTERIOR PAINTING

099300 STAINING AND TRANSPARENT FINISHING

DIVISION 10 – SPECIALTIES

101423.16 ROOM-IDENTIFICATION PANEL SIGNAGE AND DIRECTORIES

102113.19 PLASTIC TOILET COMPARTMENTS

102800 TOILET, BATH, AND LAUNDRY ACCESSORIES

104413 FIRE PROTECTION CABINETS

104416 FIRE EXTINGUISHERS

107500 FLAGPOLES

DIVISION 12 - FURNISHINGS

122413 ROLLER WINDOW SHADES

123623.13 PLASTIC-LAMINATE-CLAD COUNTERTOPS

123640 STONE COUNTERTOPS

123661.16 SOLID SURFACING COUNTERTOPS

DIVISION 22 – PLUMBING

220517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

220518 ESCUTCHEONS FOR PLUMBING PIPING

220519 METERS AND GAGES FOR PLUMBING PIPING

220523.12 BALL VALVES FOR PLUMBING PIPING

220523.14 CHECK VALVES FOR PLUMBING PIPING

220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

220719 PLUMBING PIPING INSULATION

221113 FACILITY WATER DISTRIBUTION PIPING

221116 DOMESTIC WATER PIPING

221119 DOMESTIC WATER PIPING SPECIALTIES

221123.21 INLINE, DOMESTIC-WATER PUMPS

U.S. FISH & WILDLIFE SERVICE

MILTON, DELAWARE

TABLE OF CONTENTS PAGE - 3

221316 SANITARY WASTE AND VENT PIPING

221319 SANITARY WASTE PIPING SPECIALTIES

221319.13 SANITARY DRAINS

221353 FACILITY SEPTIC TANKS

223100 DOMESTIC WATER SOFTENERS

223200 DOMESTIC WATER FILTRATION EQUIPMENT

223300 ELECTRIC, DOMESTIC-WATER HEATERS

224213.13 COMMERCIAL WATER CLOSETS

224213.16 COMMERCIAL URINALS

224216.13 COMMERCIAL LAVATORIES

224216.16 COMMERCIAL SINKS

224716 PRESSURE WATER COOLERS

DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

230517 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING

230518 ESCUTCHEONS FOR HVAC PIPING

230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC

230713 DUCT INSULATION

230719 HVAC PIPING INSULATION

230800 COMMISSIONING OF HVAC

233113 METAL DUCTS

233300 AIR DUCT ACCESSORIES

233346 FLEXIBLE DUCTS

233423 HVAC POWER VENTILATORS

233713.13 AIR DIFFUSERS

233713.23 REGISTERS AND GRILLES

237223.19 PACKAGED INDOOR FIXED PLATE ENERGY RECOVERY UNITS

238126 SPLIT-SYSTSEM AIR-CONDITIONERS

238129 VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS

238239.13 CABINET UNIT HEATERS

238239.16 PROPELLER UNIT HEATERS

238239.19 WALL AND CEILING UNIT HEATERS

238323 RADIANT-HEATING ELECTRIC PANELS

DIVISION 26 - ELECTRICAL

260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

260523 CONTROL-VOLTAGE ELECTRICAL POWER CABLES

260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS

260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS

260923 LIGHTING CONTROL DEVICES

U.S. FISH & WILDLIFE SERVICE

MILTON, DELAWARE

TABLE OF CONTENTS PAGE - 4

260943.23 LIGHTING CONTROL SYSTEMS

262416 PANELBOARDS

262713 ELECTRICITY METERING

262726 WIRING DEVICES

262813 FUSES

262816 ENCLOSED SWITCHES

263100 PHOTOVOLTAIC SYSTEM

263600 TRANSFER SWITCHES

265119 LED INTERIOR LIGHTING

265213 EMERGENCY AND EXIT LIGHTING

DIVISION 27 - COMMUNICATIONS

270526 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS

271100 COMMUNICATIONS EQUIPMENT ROOM FITTINGS

271116 COMMUNICATIONS RACKS, FRAMES, AND ENCLOSURES

271313 COMMUNICATIONS COPPER BACKBONE CABLING

271513 COMMUNICATIONS COPPER HORIZONTAL CABLING

275116 AUDIO VISUAL SYSTEMS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

280513 CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

282000 VIDEO SURVEILLANCE

283100 INTRUSION DETECTION

284621.11 ADDRESSABLE FIRE-ALARM SYSTEMS

DIVISION 31 – EARTHWORK

310000 SITE CLEARING

312000 EARTH MOVING

DIVISION 32 – EXTERIOR IMPROVEMENTS

321216 ASPHALT PAVING

321316 DECORATIVE CONCRETE WALKS AND SLABS

323113 CHAIN LINK FENCES AND GATES

329115 SOIL PREPARATION (PERFORMANCE SPECIFICATION)

329200 TURF AND GRASSES

DIVISION 33 – UTILITIES

331113 POTABLE WATER SUPPLY WELLS

334200 STORMWATER CONVEYANCE

END OF TABLE OF CONTENTS

U.S. FISH & WILDLIFE SERVICE

SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 1

SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Sleeves.

2. Sleeve-seal systems.

3. Grout.

1.3 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of product. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

1.4 INFORMATIONAL SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Field quality-control reports.

PART 2 - PRODUCTS

2.1 SLEEVES

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Advance Products & Systems, Inc.

2. CALPICO, Inc.

http://www.specagent.com/Lookup?ulid=13012 http://www.specagent.com/Lookup?uid=123457078113 http://www.specagent.com/Lookup?uid=123457078112

SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 2

3. GPT; an EnPro Industries company.

B. Cast-Iron Pipe Sleeves: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop collar.

C. Galvanized-Steel Pipe Sleeves: ASTM A53/A53M, Type E, Grade B, Schedule 40, anticorrosion coated, with plain ends and integral welded waterstop collar.

2.2 SLEEVE-SEAL SYSTEMS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Advance Products & Systems, Inc.

2. CALPICO, Inc.

3. GPT; an EnPro Industries company.

4. Metraflex Company (The).

5. Proco Products, Inc.

B. Description:

1. Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve.

2. Designed to form a hydrostatic seal of 20 psig minimum.

3. Sealing Elements: EPDM-rubber or NBR interlocking links shaped to fit surface of pipe.

Include type and number required for pipe material and size of pipe.

4. Pressure Plates: Carbon steel or stainless steel.

5. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, ASTM B633 or stainless steel of length required to secure pressure plates to sealing elements.

2.3 GROUT

A. Description: Nonshrink, for interior and exterior sealing openings in non-fire-rated walls or floors.

B. Standard: ASTM C1107/C1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.

C. Design Mix: 5000-psi, 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

http://www.specagent.com/Lookup?uid=123457078114 http://www.specagent.com/Lookup?ulid=1677 http://www.specagent.com/Lookup?uid=123457073327 http://www.specagent.com/Lookup?uid=123457073328 http://www.specagent.com/Lookup?uid=123457074355 http://www.specagent.com/Lookup?uid=123457073329 http://www.specagent.com/Lookup?uid=123457073331

SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 3

PART 3 - EXECUTION

3.1 SLEEVE INSTALLATION

A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.

B. For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch annular clear space between piping and concrete slabs and walls.

C. Install sleeves in concrete floors, and concrete walls as new slabs and walls are constructed.

1. Cut sleeves to length for mounting flush with both surfaces.

a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level.

2. Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system.

3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size depth, and location of joint. Comply with requirements for sealants specified in Section 079200 “Joint Sealants”.

D. Install sleeves for pipes passing through interior partitions.

1. Extend sleeves installed in concealed interior partitions a minimum of 1 inch beyond finished wall surface.

2. Cut sleeves to length in exposed locations to mount flush with finished surface where escutcheons are required.

3. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation.

4. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified in Section 079200 “Joint Sealants”.

E. Fire-Resistance-Rated Penetrations, Horizontal Assembly Penetrations, and Smoke Barrier Penetrations: Maintain indicated fire or smoke rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with fire- and smoke-stop materials. Comply with requirements for firestopping and fill materials specified in Section 078413 "Penetration Firestopping."

3.2 SLEEVE-SEAL-SYSTEM INSTALLATION

A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building.

B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING 220517 - 4 assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal.

3.3 FIELD QUALITY CONTROL

A. Perform the following tests and inspections:

1. Leak Test: After allowing for a full cure, test sleeves and sleeve seals for leaks. Repair leaks and retest until no leaks exist.

B. Sleeves and sleeve seals will be considered defective if they do not pass tests and inspections.

3.4 SLEEVE AND SLEEVE-SEAL SCHEDULE

A. Use sleeves and sleeve seals for the following piping-penetration applications:

1. Exterior Concrete Walls below Grade:

a. Piping Smaller Than NPS 6: Cast-iron pipe sleeves with sleeve-seal system.

1) Select sleeve size to allow for 1-inch annular clear space between piping and sleeve for installing sleeve-seal system.

2. Concrete Slabs-on-Grade:

a. Piping Smaller Than NPS 6: Cast-iron pipe sleeves with sleeve-seal system.

1) Select sleeve size to allow for 1-inch annular clear space between piping and sleeve for installing sleeve-seal system.

3. Interior Partitions:

a. Piping Smaller Than NPS 6: Galvanized-steel pipe sleeves.

END OF SECTION

ESCUTCHEONS FOR PLUMBING PIPING 220518 - 1

SECTION 220518 - ESCUTCHEONS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Escutcheons.

1.3 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of product. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. BrassCraft Manufacturing Co.; a Masco company.

2. Dearborn Brass.

3. Jones Stephens Corp.

4. Keeney Manufacturing Company (The).

5. Mid-America Fittings, Inc.

6. ProFlo; a Ferguson Enterprises, Inc. brand.

2.2 ESCUTCHEONS

A. One-Piece, Cast-Brass Type: With polished, chrome-plated finish and setscrew fastener.

http://www.specagent.com/Lookup?ulid=13050 http://www.specagent.com/Lookup?uid=123457079850 http://www.specagent.com/Lookup?uid=123457079844 http://www.specagent.com/Lookup?uid=123457079852 http://www.specagent.com/Lookup?uid=123457079845 http://www.specagent.com/Lookup?uid=123457079846 http://www.specagent.com/Lookup?uid=123457079851

ESCUTCHEONS FOR PLUMBING PIPING 220518 - 2

B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with polished, chrome-plated finish and spring-clip fasteners.

C. One-Piece, Stamped-Steel Type: With polished, chrome-plated finish and spring-clip fasteners.

D. Split-Plate, Stamped-Steel Type: With polished, chrome-plated finish; concealed and exposed-rivet hinge; and spring-clip fasteners.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors.

B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of insulated piping and with OD that completely covers opening.

1. Escutcheons for New Piping:

a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep pattern.

b. Chrome-Plated Piping: One-piece cast brass with polished, chrome-plated finish.

c. Insulated Piping: One-piece stamped steel or split-plate, stamped steel with concealed hinge with polished, chrome-plated finish.

d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece stamped steel or split-plate, stamped steel with concealed hinge with polished, chrome-plated finish.

e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece cast brass with polished, chrome-plated finish.

f. Bare Piping in Unfinished Service Spaces: One-piece stamped steel or split-plate, stamped steel with exposed-rivet hinge with polished, chrome-plated finish.

3.2 FIELD QUALITY CONTROL

A. Using new materials, replace broken and damaged escutcheons.

METERS AND GAGES FOR PLUMBING PIPING 220519 - 1

SECTION 220519 - METERS AND GAGES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Liquid-in-glass thermometers.

2. Thermowells.

3. Dial-type pressure gages.

4. Gage attachments.

5. Test plugs.

1.3 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of product. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

1.4 INFORMATIONAL SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Certificates: For each type of meter and gage.

1.5 CLOSEOUT SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Operation and Maintenance Data: For meters and gages to include in operation and maintenance manuals.

METERS AND GAGES FOR PLUMBING PIPING 220519 - 2

PART 2 - PRODUCTS

2.1 LIQUID-IN-GLASS THERMOMETERS

A. Metal-Case, Industrial-Style, Liquid-in-Glass Thermometers:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Flo Fab Inc.

b. Miljoco Corporation.

c. Palmer Wahl Instrumentation Group.

d. Tel-Tru Manufacturing Company.

e. Trerice, H. O. Co.

f. Weiss Instruments, Inc.

g. Weksler Glass Thermometer Corp.

h. Winters Instruments - U.S.

2. Standard: ASME B40.200.

3. Case: Cast aluminum; 9-inch nominal size unless otherwise indicated.

4. Case Form: Adjustable angle unless otherwise indicated.

5. Tube: Glass with magnifying lens and blue or red organic liquid.

6. Tube Background: Nonreflective aluminum with permanently etched scale markings graduated in deg F and deg C.

7. Window: Glass or plastic.

8. Stem: Aluminum and of length to suit installation.

a. Design for Thermowell Installation: Bare stem.

9. Connector: 1-1/4 inches, with ASME B1.1 screw threads.

10. Accuracy: Plus or minus 1 percent of scale range or one scale division, to a maximum of

1.5 percent of scale range.

2.2 THERMOWELLS

A. Thermowells:

1. Standard: ASME B40.200.

2. Description: Pressure-tight, socket-type fitting made for insertion into piping tee fitting.

3. Material for Use with Copper Tubing: CNR or CUNI.

4. Material for Use with Steel Piping: CRES or CSA.

5. Type: Stepped shank unless straight or tapered shank is indicated.

6. External Threads: NPS 1/2, NPS 3/4, or NPS 1, ASME B1.20.1 pipe threads.

7. Internal Threads: 1/2, 3/4, and 1 inch, with ASME B1.1 screw threads.

8. Bore: Diameter required to match thermometer bulb or stem.

9. Insertion Length: Length required to match thermometer bulb or stem.

http://www.specagent.com/Lookup?ulid=1690 http://www.specagent.com/Lookup?uid=123457058297 http://www.specagent.com/Lookup?uid=123457058293 http://www.specagent.com/Lookup?uid=123457058294 http://www.specagent.com/Lookup?uid=123457058295 http://www.specagent.com/Lookup?uid=123457058299 http://www.specagent.com/Lookup?uid=123457058298 http://www.specagent.com/Lookup?uid=123457058301 http://www.specagent.com/Lookup?uid=123457058296

METERS AND GAGES FOR PLUMBING PIPING 220519 - 3

10. Lagging Extension: Include on thermowells for insulated piping and tubing.

11. Bushings: For converting size of thermowell's internal screw thread to size of thermometer connection.

B. Heat-Transfer Medium: Mixture of graphite and glycerin.

2.3 PRESSURE GAGES

A. Direct-Mounted, Metal-Case, Dial-Type Pressure Gages:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Ametek U.S. Gauge.

b. Ashcroft Inc.

c. Ernst Flow Industries.

d. Flo Fab Inc.

e. Marsh Bellofram.

f. Miljoco Corporation.

g. Noshok.

h. Palmer Wahl Instrumentation Group.

i. REOTEMP Instrument Corporation.

j. Tel-Tru Manufacturing Company.

k. Trerice, H. O. Co.

l. WATTS.

m. Weiss Instruments, Inc.

n. Weksler Glass Thermometer Corp.

o. WIKA Instrument Corporation.

p. Winters Instruments - U.S.

2. Standard: ASME B40.100.

3. Case: Liquid-filled type(s); cast aluminum or drawn steel; 4-1/2-inch nominal diameter.

4. Pressure-Element Assembly: Bourdon tube unless otherwise indicated.

5. Pressure Connection: Brass, with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and bottom-outlet type unless back-outlet type is indicated.

6. Movement: Mechanical, with link to pressure element and connection to pointer.

7. Dial: Nonreflective aluminum with permanently etched scale markings graduated in psi.

8. Pointer: Dark-colored metal.

9. Window: Glass or plastic.

10. Ring: Metal.

11. Accuracy: Grade B, plus or minus 2 percent of middle half of scale range.

http://www.specagent.com/Lookup?ulid=1695 http://www.specagent.com/Lookup?uid=123457058426 http://www.specagent.com/Lookup?uid=123457058322 http://www.specagent.com/Lookup?uid=123457058323 http://www.specagent.com/Lookup?uid=123457058327 http://www.specagent.com/Lookup?uid=123457058328 http://www.specagent.com/Lookup?uid=123457058329 http://www.specagent.com/Lookup?uid=123457058330 http://www.specagent.com/Lookup?uid=123457058331 http://www.specagent.com/Lookup?uid=123457058332 http://www.specagent.com/Lookup?uid=123457058333 http://www.specagent.com/Lookup?uid=123457058334 http://www.specagent.com/Lookup?uid=123457058336 http://www.specagent.com/Lookup?uid=123457058324 http://www.specagent.com/Lookup?uid=123457058338 http://www.specagent.com/Lookup?uid=123457058325 http://www.specagent.com/Lookup?uid=123457058326

METERS AND GAGES FOR PLUMBING PIPING 220519 - 4

2.4 GAGE ATTACHMENTS

A. Snubbers: ASME B40.100, brass; with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and piston or porous-metal-type surge-dampening device. Include extension for use on insulated piping.

B. Valves: Brass or stainless-steel needle, with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads.

2.5 TEST PLUGS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Flow Design, Inc.

2. Miljoco Corporation.

3. Nexus Valve, Inc.

4. Peterson Equipment Co., Inc.

5. Sisco Manufacturing Company, Inc.

6. Trerice, H. O. Co.

7. WATTS.

8. Weiss Instruments, Inc.

9. Weksler Glass Thermometer Corp.

B. Description: Test-station fitting made for insertion into piping tee fitting.

C. Body: Brass or stainless steel with core inserts and gasketed and threaded cap. Include extended stem on units to be installed in insulated piping.

D. Thread Size: NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe thread.

E. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F.

F. Core Inserts: Chlorosulfonated polyethylene synthetic and EPDM self-sealing rubber.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install thermowells with socket extending to center of pipe and in vertical position in piping tees.

B. Install thermowells of sizes required to match thermometer connectors. Include bushings if required to match sizes.

C. Install thermowells with extension on insulated piping.

http://www.specagent.com/Lookup?ulid=1700 http://www.specagent.com/Lookup?uid=123457058382 http://www.specagent.com/Lookup?uid=123457058383 http://www.specagent.com/Lookup?uid=123457058390 http://www.specagent.com/Lookup?uid=123457058385 http://www.specagent.com/Lookup?uid=123457058386 http://www.specagent.com/Lookup?uid=123457058387 http://www.specagent.com/Lookup?uid=123457058389 http://www.specagent.com/Lookup?uid=123457058388 http://www.specagent.com/Lookup?uid=123457058391

METERS AND GAGES FOR PLUMBING PIPING 220519 - 5

D. Fill thermowells with heat-transfer medium.

E. Install direct-mounted thermometers in thermowells and adjust vertical and tilted positions.

F. Install direct-mounted pressure gages in piping tees with pressure gage located on pipe at the most readable position.

G. Install valve and snubber in piping for each pressure gage for fluids.

H. Install test plugs in piping tees.

I. Install thermometers in the following locations:

1. Inlet and outlet of each water heater.

2. As indicated on drawings.

J. Install pressure gages in the following locations:

1. Building water service entrance into building.

2. Inlet and outlet of water treatment system.

3. Inlet and outlet of each pressure-reducing valve.

4. As indicated on drawings.

K. Install meters and gages adjacent to machines and equipment to allow service and maintenance of meters, gages, machines, and equipment.

L. Adjust faces of meters and gages to proper angle for best visibility.

3.2 CONNECTIONS

3.3 ADJUSTING

3.4 THERMOMETER SCALE-RANGE SCHEDULE

A. Scale Range for Domestic Cold-Water Piping: 0 to 100 deg F.

B. Scale Range for Domestic Hot-Water Piping: 0 to 250 deg F.

3.5 PRESSURE-GAGE SCALE-RANGE SCHEDULE

A. Scale Range for Water Service Piping: 0 to 100 psi.

B. Scale Range for Domestic Water Piping: 0 to 100 psi.

BALL VALVES FOR PLUMBING PIPING 220523.12 - 1

SECTION 220523.12 - BALL VALVES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Bronze ball valves.

1.3 DEFINITIONS

A. CWP: Cold working pressure.

1.4 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of valve. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

1. Certification that products comply with NSF 61and NSF 372.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Prepare valves for shipping as follows:

1. Protect internal parts against rust and corrosion.

2. Protect threads, flange faces, and soldered ends.

3. Set ball valves open to minimize exposure of functional surfaces.

B. Use the following precautions during storage:

1. Maintain valve end protection.

2. Store valves indoors and maintain at higher-than-ambient-dew-point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures.

BALL VALVES FOR PLUMBING PIPING 220523.12 - 2

2.1 GENERAL REQUIREMENTS FOR VALVES

A. Source Limitations for Valves: Obtain each type of valve from single source from single manufacturer.

B. ASME Compliance:

1. ASME B1.20.1 for threads for threaded end valves.

2. ASME B16.18 for solder-joint connections.

3. ASME B31.9 for building services piping valves.

C. NSF Compliance: NSF 61 and NSF 372 for valve materials for potable-water service.

D. Bronze valves shall be made with dezincification-resistant materials. Bronze valves made with copper alloy (brass) containing more than 15 percent zinc are not permitted.

E. Valve Pressure-Temperature Ratings: Not less than indicated and as required for system pressures and temperatures.

F. Valve Sizes: Same as upstream piping unless otherwise indicated.

G. Valve Actuator Types:

1. Handlever: For quarter-turn valves smaller than NPS 4.

H. Valves in Insulated Piping:

1. Include 2-inch stem extensions.

2. Extended operating handles of nonthermal-conductive material and protective sleeves that allow operation of valves without breaking vapor seals or disturbing insulation.

3. Memory stops that are fully adjustable after insulation is applied.

2.2 BRONZE BALL VALVES

A. Bronze Ball Valves, Two-Piece with Full Port, and Bronze or Brass Trim, Threaded or Soldered Ends:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Apollo Flow Controls; Conbraco Industries, Inc.

b. Crane; Crane Energy Flow Solutions.

c. FNW; Ferguson Enterprises, Inc.

d. Hammond Valve.

http://www.specagent.com/Lookup?ulid=9499 http://www.specagent.com/Lookup?uid=123457114764 http://www.specagent.com/Lookup?uid=123457114765 http://www.specagent.com/Lookup?uid=123457114771 http://www.specagent.com/Lookup?uid=123457114766

BALL VALVES FOR PLUMBING PIPING 220523.12 - 3

e. Lance Valves.

f. Milwaukee Valve Company.

g. NIBCO INC.

h. WATTS.

i. Zurn Industries, LLC.

2. Description:

a. Standard: MSS SP-110 or MSS-145.

b. CWP Rating: 600 psig.

c. Body Design: Two piece.

d. Body Material: Bronze.

e. Ends: Threaded and soldered.

f. Seats: PTFE.

g. Stem: Bronze or brass.

h. Ball: Chrome-plated brass.

i. Port: Full.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling.

B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations.

C. Examine threads on valve and mating pipe for form and cleanliness.

D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage.

E. Do not attempt to repair defective valves; replace with new valves.

3.2 VALVE INSTALLATION

A. Install valves with unions or flanges at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown.

B. Locate valves for easy access and provide separate support where necessary.

C. Install valves in horizontal piping with stem at or above center of pipe.

http://www.specagent.com/Lookup?uid=123457114767 http://www.specagent.com/Lookup?uid=123457114768 http://www.specagent.com/Lookup?uid=123457114769 http://www.specagent.com/Lookup?uid=123457114770 http://www.specagent.com/Lookup?uid=123457114763

BALL VALVES FOR PLUMBING PIPING 220523.12 - 4

D. Install valves in position to allow full stem movement.

E. Install valve tags. Comply with requirements in Section 220553 "Identification for Plumbing Piping and Equipment" for valve tags and schedules.

3.3 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

A. If valves with specified CWP ratings are unavailable, the same types of valves with higher CWP ratings may be substituted.

B. Select valves with the following end connections:

1. For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder-joint valve-end option or press-end option is indicated in valve schedules below.

3.4 DOMESTIC HOT- AND COLD-WATER VALVE SCHEDULE

A. Pipe NPS 2 and Smaller:

1. Bronze ball valves, two-piece with full port and bronze or brass trim. Provide with threaded-joint ends.

CHECK VALVES FOR PLUMBING PIPING 220523.14 - 1

SECTION 220523.14 - CHECK VALVES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Bronze swing check valves.

1.3 DEFINITIONS

A. CWP: Cold working pressure.

B. EPDM: Ethylene propylene-diene terpolymer rubber.

C. NBR: Acrylonitrile-butadiene, Buna-N, or nitrile rubber.

1.4 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of valve. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

1. Certification that products comply with NSF 61 and NSF 372.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Prepare valves for shipping as follows:

1. Protect internal parts against rust and corrosion.

2. Protect threads, flange faces, grooves, and weld ends.

3. Set check valves in either closed or open position.

B. Use the following precautions during storage:

CHECK VALVES FOR PLUMBING PIPING 220523.14 - 2

1. Maintain valve end protection.

2. Store valves indoors and maintain at higher-than-ambient-dew-point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures.

PART 2 - PRODUCTS

2.1 GENERAL REQUIREMENTS FOR VALVES

A. Source Limitations for Valves: Obtain each type of valve from single source from single manufacturer.

B. ASME Compliance:

1. ASME B1.20.1 for threads for threaded end valves.

2. ASME B16.18 for solder joint.

3. ASME B31.9 for building services piping valves.

C. Drinking Water System Components - Health Effects and Drinking Water System Components

- Lead Content Compliance: NSF 61 and NSF 372.

D. Bronze valves shall be made with dezincification-resistant materials. Bronze valves made with copper alloy (brass) containing more than 15 percent zinc are not permitted.

E. Valve Pressure-Temperature Ratings: Not less than indicated and as required for system pressures and temperatures.

F. Valve Sizes: Same as upstream piping unless otherwise indicated.

G. Valve Bypass and Drain Connections: MSS SP-45.

2.2 BRONZE SWING CHECK VALVES

A. Bronze Swing Check Valves with Nonmetallic Disc, Class 125:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Apollo Flow Controls; Conbraco Industries, Inc.

b. Crane; Crane Energy Flow Solutions.

c. Hammond Valve.

d. Jenkins Valves; Crane Energy Flow Solutions.

e. KITZ Corporation.

f. Milwaukee Valve Company.

g. NIBCO INC.

h. Red White Valve Corp.

http://www.specagent.com/Lookup?ulid=9520

CHECK VALVES FOR PLUMBING PIPING 220523.14 - 3

i. Stockham; Crane Energy Flow Solutions.

j. WATTS.

2. Description:

a. Standard: MSS SP-80, Type 4.

b. CWP Rating: 200 psig.

c. Body Design: Horizontal flow.

d. Body Material: ASTM B62, bronze.

e. Ends: Threaded or soldered. See valve schedule articles.

f. Disc: PTFE.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling.

B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations.

C. Examine threads on valve and mating pipe for form and cleanliness.

D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage.

E. Do not attempt to repair defective valves; replace with new valves.

3.2 VALVE INSTALLATION

A. Install valves with unions or flanges at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown.

B. Locate valves for easy access and provide separate support where necessary.

C. Install valves in horizontal piping with stem at or above center of pipe.

D. Install valves in position to allow full stem movement.

E. Check Valves: Install check valves for proper direction of flow.

1. Swing Check Valves: In horizontal position with hinge pin level.

CHECK VALVES FOR PLUMBING PIPING 220523.14 - 4

F. Install valve tags. Comply with requirements in Section 220553 "Identification for Plumbing Piping and Equipment" for valve tags and schedules.

3.3 ADJUSTING

A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs.

3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

A. If valve applications are not indicated, use the following:

1. Pump-Discharge Check Valves:

a. NPS 2 and Smaller: Bronze swing check valves with nonmetallic disc.

B. If valves with specified CWP ratings are unavailable, the same types of valves with higher CWP ratings may be substituted.

3.5 DOMESTIC HOT- AND COLD-WATER VALVE SCHEDULE

A. Pipe NPS 2 and Smaller:

1. Bronze swing check valves with nonmetallic disc, Class 125, with soldered or threaded end connections.

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 1

SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Metal pipe hangers and supports.

2. Thermal hanger-shield inserts.

3. Fastener systems.

4. Pipe-positioning systems.

1.3 ACTION SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Product Data: For each type of product. On data submittal sheets where more than one product is described, clearly annotate which product(s) is to be supplied.

1.4 INFORMATIONAL SUBMITTALS

A. Submittals shall comply with the requirements of Section 013300 “Submittal Procedures” and the individual sections specifying the work.

B. Welding certificates.

1.5 QUALITY ASSURANCE

A. Structural-Steel Welding Qualifications: Qualify procedures and personnel according to

AWS D1.1/D1.1M.

B. Pipe Welding Qualifications: Qualify procedures and operators according to 2015 ASME Boiler and Pressure Vessel Code, Section IX.

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 2

2.1 METAL PIPE HANGERS AND SUPPORTS

A. Carbon-Steel Pipe Hangers and Supports:

1. Description: MSS SP-58, Types 1 through 58, factory-fabricated components.

2. Galvanized Metallic Coatings: Pregalvanized, hot-dip galvanized, or electro-galvanized.

3. Nonmetallic Coatings: Plastic coated or epoxy powder coated.

4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.

5. Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel.

B. Copper Pipe and Tube Hangers:

1. Description: MSS SP-58, Types 1 through 58, copper-coated-steel, factory-fabricated components.

2. Hanger Rods: Continuous-thread rod, nuts, and washer made of copper-coated or steel stainless steel.

2.2 THERMAL HANGER-SHIELD INSERTS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Buckaroos, Inc.

2. CADDY; a brand of nVent.

3. Carpenter & Paterson, Inc.

4. Clement Support Services.

5. National Pipe Hanger Corporation.

6. Pipe Shields Inc.

7. Piping Technology & Products, Inc.

8. Rilco Manufacturing Co., Inc.

9. Value Engineered Products, Inc.

B. Insulation-Insert Material for Cold Piping: ASTM C552, Type II cellular glass with 100-psig or ASTM C591, Type VI, Grade 1 polyisocyanurate with 125-psig minimum compressive strength and vapor barrier.

C. Insulation-Insert Material for Hot Piping: Water-repellent-treated, ASTM C533, Type I calcium silicate with 100-psig, ASTM C552, Type II cellular glass with 100-psig or ASTM C591, Type VI, Grade 1 polyisocyanurate with 125-psig minimum compressive strength.

D. For Clamped Systems: Insert and shield shall cover entire circumference of pipe.

E. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.

http://www.specagent.com/Lookup?ulid=1832 http://www.specagent.com/Lookup?uid=123457103627 http://www.specagent.com/Lookup?uid=123457148540 http://www.specagent.com/Lookup?uid=123457086642 http://www.specagent.com/Lookup?uid=123457086643 http://www.specagent.com/Lookup?uid=123457086638 http://www.specagent.com/Lookup?uid=123457086646 http://www.specagent.com/Lookup?uid=123457086645 http://www.specagent.com/Lookup?uid=123457086640 http://www.specagent.com/Lookup?uid=123457086641

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 3

F. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient air temperature.

2.3 FASTENER SYSTEMS

A. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Hilti, Inc.

b. ITW Ramset/Red Head; Illinois Tool Works, Inc.

c. MKT Fastening, LLC.

d. Simpson Strong-Tie Co., Inc.

B. Mechanical-Expansion Anchors: Insert-wedge-type anchors, for use in hardened portland cement concrete, with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. B-line, an Eaton business.

b. Empire Tool and Manufacturing Co., Inc.

c. Hilti, Inc.

d. ITW Ramset/Red Head; Illinois Tool Works, Inc.

e. MKT Fastening, LLC.

2. Indoor Applications: Zinc-coated or stainless steel.

2.4 PIPE-POSITIONING SYSTEMS

A. Description: IAPMO PS 42 positioning system composed of metal brackets, clips, and straps for positioning piping in pipe spaces; for plumbing fixtures in commercial applications.

2.5 MATERIALS

A. Structural Steel: ASTM A36/A36M carbon-steel plates, shapes, and bars; black and galvanized.

http://www.specagent.com/Lookup?ulid=13286 http://www.specagent.com/Lookup?uid=123457101430 http://www.specagent.com/Lookup?uid=123457101431 http://www.specagent.com/Lookup?uid=123457101432 http://www.specagent.com/Lookup?uid=123457101433 http://www.specagent.com/Lookup?ulid=13287 http://www.specagent.com/Lookup?uid=123457101435 http://www.specagent.com/Lookup?uid=123457101436 http://www.specagent.com/Lookup?uid=123457101437 http://www.specagent.com/Lookup?uid=123457101438 http://www.specagent.com/Lookup?uid=123457101439

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 4

PART 3 - EXECUTION

3.1 APPLICATION

A. Comply with requirements in Section 078413 "Penetration Firestopping" for firestopping materials and installation, for penetrations through fire-rated walls, ceilings, and assemblies.

B. Strength of Support Assemblies: Where not indicated, select sizes of components, so strength will be adequate to carry present and future static loads within specified loading limits.

Minimum static design load used for strength determination shall be weight of supported components plus 200 lb.

3.2 HANGER AND SUPPORT INSTALLATION

A. Metal Pipe-Hanger Installation: Comply with MSS SP-58. Install hangers, supports, clamps, and attachments as required to properly support piping form building structure.

B. Thermal Hanger-Shield Installation: Install in pipe hanger or shield for insulated piping.

C. Fastener System Installation:

1. Install powder-actuated fasteners for use in concrete slabs less than 4 inches thick in concrete, after concrete is placed and completely cured. Use operators that are licensed by powder-actuated tool manufacturer. Install fasteners according to powder-actuated tool manufacturer's operating manual.

2. Install mechanical-expansion anchors in concrete, after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions.

D. Pipe-Positioning-System Installation: Install support devices to make rigid supply and waste piping connections to each plumbing fixture.

E. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories.

F. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.

G. Install lateral bracing with pipe hangers and supports to prevent swaying.

H. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms, and install reinforcing bars through openings at top of inserts.

I. Load Distribution: Install hangers and supports, so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment.

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 5

J. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping.

K. Insulated Piping:

1. Attach clamps and spacers to piping.

a. Piping Operating Above Ambient Air Temperature: Clamp may project through insulation.

b. Piping Operating Below Ambient Air Temperature: Use thermal hanger-shield insert with clamp sized to match OD of insert.

c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping.

2. Install MSS SP-58, Type 39 protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.

a. Option: Thermal hanger-shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.

3. Install MSS SP-58, Type 40 protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees.

a. Option: Thermal hanger-shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.

4. Shield Dimensions for Pipe: Not less than the following:

a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick.

b. NPS 4: 12 inches long and 0.06 inch thick.

5. Thermal Hanger Shields: Install with insulation of same thickness as piping insulation.

3.3 METAL FABRICATIONS

A. Cut, drill, and fit miscellaneous metal fabrications for equipment supports.

B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations.

C. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding;

appearance and quality of welds; and methods used in correcting welding work; and with the following:

1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.

2. Obtain fusion without undercut or overlap.

3. Remove welding flux immediately.

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 6

4. Finish welds at exposed connections, so no roughness shows after finishing and so contours of welded surfaces match adjacent contours.

3.4 ADJUSTING

A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.

B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.

3.5 PAINTING

A. Touchup: Cleaning and touchup painting of field welds, bolted connections, and abraded, shop-painted areas on miscellaneous metal are specified in Section 099113 "Exterior Painting" and Section 099123 "Interior Painting."

B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas, and apply galvanizing-repair paint to comply with ASTM A780/A780M.

3.6 HANGER AND SUPPORT SCHEDULE

A. Specific hanger and support requirements are in Sections specifying piping systems and equipment.

B. Comply with MSS SP-58 for pipe-hanger selections and applications that are not specified in piping system Sections.

C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field-applied finishes.

D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.

E. Use carbon-steel pipe hangers and supports and metal framing systems and attachments for general service applications.

F. Use copper-plated pipe hangers and copper or stainless-steel attachments for copper piping and tubing.

G. Use thermal hanger-shield inserts for insulated piping and tubing.

H. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated, stationary pipes NPS 1/2 to NPS 30.

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 7

2. Carbon- or Alloy-Steel, Double-Bolt Pipe Clamps (MSS Type 3): For suspension of pipes NPS 3/4 to NPS 36, requiring clamp flexibility and up to 4 inches of insulation.

3. Steel Pipe Clamps (MSS Type 4): For suspension of cold and hot pipes NPS 1/2 to NPS 24 if little or no insulation is required.

4. Pipe Hangers (MSS Type 5): For suspension of pipes NPS 1/2 to NPS 4, to allow off-center closure for hanger installation before pipe erection.

5. Adjustable, Swivel Split- or Solid-Ring Hangers (MSS Type 6): For suspension of noninsulated, stationary pipes NPS 3/4 to NPS 8.

I. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to

NPS 24.

2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers NPS 3/4 to NPS 24 if longer ends are required for riser clamps.

J. Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Steel Turnbuckles (MSS Type 13): For adjustment of up to 6 inches for heavy loads.

2. Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations.

3. Swivel Turnbuckles (MSS Type 15): For use with MSS Type 11 split pipe rings.

4. Malleable-Iron…