1. What type of floor paint is asking to be applied? Is it just basic floor epoxy or is it a more industrial floor epoxy paint? Don't know if your looking to get two years compared to 20 years.

a. We are expecting an industrial/commercial grade, non-slip, heavy duty floor coating that meets the specifications as outlined in the SOW

2. What area's are getting new epoxy flooring? As I did not come across any drawings.

a. Please see SOW for square footage requiring coating.

3. Is there water, electricity and restrooms available for contractors?

a. yes, there is electricity, restrooms and water available.

4. Are there any metal plates on the floor?

a. The photos will show there are metal grates (not plates) in the floor. These need to be covered so as not to allow for debris to enter. The water in these drains goes directly to the river and cannot discharge debris.

5. Is there an option to work after hours?

a. Yes after hours and weekend work can be approved w/ Hatchery Manager

6. Can you provide photos?

a. Photos attached.

7. Please provide what type of traffic this area will see for selecting the appropriate epoxy floor surfacing. Will there just be foot traffic or equipment such as pallet jacks, forklifts, etc…?

a. Foot traffic only, no heavy equipment

8. What size are the doors for entry? (What size equipment can be utilized)

a. The size of the front and side double doors are 71" W x 79" H

b. The distance between the stacks for equipment is 4 ft

c. There are some areas that are tighter (down to 12”). In the areas 12” or less between fish tanks, we would accept minimal prep and a best effort to coat to the edge of the tanks.

9. Will power be supplied? 110V / 220V single or three phase?

a. The voltage available at the facility is 110/220V single phase.