This is an Asbestos Inspection Report for the Southern Plains Indian Museum located at 801 East Central Boulevard in Anadarko, Oklahoma. The inspection was conducted on June 26, 2019, by licensed inspector Grayson Cook (Oklahoma License #159935) using OSHA 29 CFR 1926.1101 sampling methods. The report documents the results of a limited asbestos inspection of the museum's main building and includes polarized light microscopy (PLM) analysis conducted by QuantTEM Laboratories.
The inspection identified asbestos-containing building materials (ACBM) in three locations: exterior door caulking on all exterior door frames containing 4% Chrysotile fibers (34 linear feet, non-friable); red 9x9 floor tile and black mastic in the library, break room, and storage room containing 7% Chrysotile in the tile and 5% Chrysotile in the mastic (500 square feet, non-friable); and black tar pipe mastic wrap in the basement containing 4% Chrysotile fibers (20 linear feet, non-friable). Out of 34 samples collected from 14 homogeneous areas, 11 samples tested negative for asbestos, including wall textures, joint compounds, plaster ceilings, roof shingles, and various floor tiles in other areas. The report recommends that if the identified asbestos-containing materials are disturbed during renovation activities, they must be removed following OSHA Class II Non-Friable Asbestos Abatement Requirements, and if any suspect materials are discovered during renovation or demolition, work should stop and the material should be tested using PLM procedures.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Southern Plains Indian Museum Asbestos Inspection Report Page 1 of 22
1 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / info@tec-an.com / www.tec-an.com
Asbestos Inspection
Report
801 East Central Blvd.
Anadarko, OK
July 30, 2019 mailto:info@tec-an.com http://www.tec-an.com/
Southern Plains Indian Museum Asbestos Inspection Report Page 2 of 22
2 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Asbestos Inspection Report
The following is a report for the limited asbestos inspection performed for the Southern Plains Indian Museum. The inspection was performed within the main building of the Southern Plains Indian Museum located at 801 E Central Blvd. Anadarko, OK. Samples were collected by licensed inspectors Grayson Cook (Oklahoma License #-159935) on 06/26/2019. The sampling methods used were based on the guidelines of OSHA 29 CFR 1926.1101. This report consists of the following sections; definitions, sampling results, sampled material description, analytical results, chain of custody, asbestos location maps and training certificates.
Definitions
1. Asbestos Containing Building Material (ACBM) - Defined as any building material that contains more than 1% asbestos fibers.
2. Homogeneous Area - An area of thermal systems insulation (TSI), surfacing material or miscellaneous material that is uniform in color, texture and date of application. If a building material tests positive for asbestos fibers, then the entire quantity of the homogeneous area is considered positive.
3. Miscellaneous Material - Any interior building material on structural components, structural members of fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
4. Surfacing Material - Any material in a building that is sprayed-on, troweled-on or otherwise applied to surfaces for acoustical, fireproofing or other purposes.
5. Thermal System Insulation (TSI)- Any building material applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss/gain, or water condensation or for other purposes.
Sampling Results
Homogeneous Area/ Sample Numbers
Description Material Type Friable Quantity
HA04
Sample #’s 09, 10
Exterior Door Caulking on the Frames of the Exterior Doors
Miscellaneous No 34 ft
HA12
Sample #’s 29, 30
Red 9x9 Floor Tile and Black Mastic in Library, Break Room and Storage Room
Miscellaneous No 500 ft2
HA14
Sample #’s 33, 34
Black Tar Pipe Mastic Wrap found in the Basement
Miscellaneous No 20 ft
Southern Plains Indian Museum Asbestos Inspection Report Page 3 of 22
3 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Homogeneous Area/Sample Description
A total of 34 samples from 14 homogeneous areas were collected from the property during this inspection.
HA01/ Sample #’s 01, 02, 03 - This Homogeneous Area represents the heavy knock down wall texture found in the gift shop area. This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The wall texture tested negative for asbestos fibers.
HA02/ Sample #’s 04, 05, 06- This Homogeneous Area represents the light orange peel wall texture found on the walls of galleries, main office and part of the gift shop. This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The wall texture tested negative for asbestos fibers.
HA03/ Sample #’s 07, 08 - This Homogeneous Area represents the joint compound associated with the light orange peel textured sheetrock walls of the gift shop. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The joint compound tested negative for asbestos fibers.
HA04/ Sample #’s 09, 10- This Homogeneous Area represents the white exterior door frame caulking found on all the exterior door frames. This material is classified as a non-friable miscellaneous material.
Samples were collected and tested according to the Oklahoma asbestos regulations. The exterior door caulking tested positive for asbestos with 4% Chrysotile fibers.
HA05/ Sample #’s 11, 12, 13- This Homogeneous Area represents the flat texture found on the plaster walls of the break room, storage and library. This material is classified as a friable surfacing material.
Samples were collected and tested according to the Oklahoma asbestos regulations. The flat texture tested negative for asbestos fibers.
HA06/ Sample #’s 14, 15, 16- This Homogeneous Area represents the rough textured plaster ceilings.
This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The plaster ceilings tested negative for asbestos fibers.
HA07/ Sample #’s 17, 18, 19- This Homogeneous Area represents the composite roof shingles found on the gabled roof sections of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The roof shingles tested negative for asbestos fibers.
HA08/ Sample #’s 20, 21, 22 - This Homogeneous Area represents the orange peel ceiling texture found in the new addition (gallery 3). This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The ceiling texture tested negative for asbestos fibers.
Southern Plains Indian Museum Asbestos Inspection Report Page 4 of 22
4 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
HA09/ Sample #’s 23, 24- This Homogeneous Area represents the joint compound associated with the orange peel textured ceilings of the new addition. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The joint compound tested negative for asbestos fibers.
HA10/ Sample #’ 25, 26- This Homogeneous Area represents 12x12 tan and brown spot floor tile found in the gift shop. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile and mastic tested negative for asbestos fibers.
HA11/ Sample #’s 27, 28- This Homogeneous Area represents the 12x12 tan marbled floor tile found in the at the north west exit of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile and mastic tested negative for asbestos fibers.
HA12/ Sample #’s 29, 30- This Homogeneous Area represents the brown 9x9 floor tile and mastic found in the library, storage, break room and office closets. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile and mastic tested positive for asbestos 7% Chrysotile (9x9 tile) and 5% Chrysotile (black mastic) fibers.
HA13/ Sample #’s 31, 32- This Homogeneous Area represents the 2x4 hole and fissure ceiling tile found in the office area. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The ceiling tile tested negative for asbestos fibers.
HA14/ Sample #’s 33, 34- This Homogeneous Area represents the black tar pipe wrap found on the pipes in the basement. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The black tar pipe wrap tested positive for asbestos with 4% Chrysotile fibers.
Recommendations for Response
If the asbestos containing floor tile/mastic, exterior door caulking and/or the black tar pipe mastic wrap are to be disturbed by renovation activities, then the materials must be removed following the OSHA Class II Non-Friable Asbestos Abatement Requirements.
If suspect asbestos containing material is uncovered during renovation/demolition, stop work and have the material tested using PLM procedures.
Respectfully, Grayson Cook Tec-An, Inc. Oklahoma License # 159935 Report Date –07/31/2019
Southern Plains Indian Museum Asbestos Inspection Report Page 5 of 22
5 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Analytical Results
Southern Plains Indian Museum Asbestos Inspection Report Page 6 of 22
6 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 7 of 22
7 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 8 of 22
8 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 9 of 22
9 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 10 of 22
10 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 11 of 22
11 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 12 of 22
12 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 13 of 22
13 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 14 of 22
14 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 15 of 22
15 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Chain of Custody
Southern Plains Indian Museum Asbestos Inspection Report Page 16 of 22
16 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 17 of 22
17 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 18 of 22
18 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 19 of 22
19 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Sample Location Map
Southern Plains Indian Museum Asbestos Inspection Report Page 20 of 22
20 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /
Southern Plains Indian Museum Asbestos Inspection Report Page 21 of 22