This document is an Architects Supplemental Instructions (ASI) Number 001 issued on October 1, 2026, for the Rosebud Agency Boiler & HVAC System Design for Building #1004, a Bureau of Indian Affairs project.

The ASI mandates revisions to the Dedicated Outdoor Air System ductwork on Mechanical Sheets MH101 and MH102. Currently, 74 ventilation air connections route from the supply main directly to room-located variable refrigerant fan coils; this configuration will be modified so that 70 connections redirect from direct unit connections to sidewall grille connections, while four basement areas will be ducted to supply diffusers in their respective rooms. The ventilation air will no longer connect to the variable refrigerant blower coil but instead terminate at a sidewall grille, which will discharge all required ventilation air into the room. The sidewall grille must be positioned on the opposite side of the corridor wall, away from the transfer grille to ensure proper air circulation and mixing. Revised mechanical sheets MH101 and MH102 reflect the new ventilation air ductwork routing, and Sheet MH702 is submitted with specifications for the double deflection sidewall grille required for this modification. The ASI is distributed to the file and the Owner/Agent (Bureau of Indian Affairs), with copies directed to the BIA Contractor, and was issued by Bradley J. Kennedy, a professional mechanical engineer registered in Nebraska.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARCHITECTS SUPPLEMENTAL INSTRUCTIONS (ASI)

ASI NUMBER: 001

DATE: 10/1/2026

PROJECT: Rosebud Agency Boiler & HVAC System Design Building #1004 OWNER/AGENT: Bureau of Indian Affairs

CONTRACTOR:

DISTRIBUTION: X File X Owner/Agent (BIA) By BIA Contractor

1. Original Mechanical Sheets MH101 and MH102 need the Dedicated Outdoor Air System Ductwork changed. Replace the current connection to the variable refrigerant flow equipment with the following:

Mechanical sheets MH101 and MH102 will revise the ducting of ventilation air into each office. Currently, 74 connections show ventilation air ducted from the supply main to the room-located variable refrigerant fan coil. These connections will change: 70 of those connections will move from direct connections at the unit to a sidewall grille connection. Four areas in the basement will be ducted to supply diffusers inside their respective rooms. The ventilation air will not connect to the variable refrigerant blower coil as originally shown. Instead, the new 4” round ventilation duct will terminate at a sidewall grille. The sidewall grille will discharge all needed ventilation air into the room. The sidewall grille must be located on the opposite side of the corridor wall, away from the transfer grille to maintain good air circulation and mixing. Refer to revised sheets MH101 and MH102 for new routing of ventilation air ductwork. Sheet MH702 is also being submitted with the proper double deflection sidewall grille to be used for this change.

ISSUED BY: DATE: 10/1/2026

01 BASEMENT HVAC PLAN

1/8" = 1'-0"MH101

JOSEPH DAVID ASSOCIATES

REVISIONS

DRAWN BY

CHECKED BY

19970 CHLOE LAYNE RD.

SPIRO, OK 74959

JOSEPHDAVIDASSOCIATES.COM

FARRIS ENGINEERING

12700 West Dodge Road, Omaha, NE 68154

Proj ID

Project Status Issue Date 100% CD Issue for Construction

09-18-24

140A1622F0214 the copyright law.

OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS

FARRIS ENGINEERING

farris-usa.com

COPYRIGHT

This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by

FEI #232013NOTICE:

DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.

PRINTS IN A DIFFERENT FORMAT MAY NOT BE

REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL

DIMENSIONS AND CLEARANCES ON SITE.

R O

SE

BU

D A

G

EN

C Y

BO

IL

ER

H

VA

C S

YS

TE

M (S

) D

ES

IG

N

BU

IL

D

IN

G

ASI #001 10-01-26

MH101

BASEMENT HVAC PLAN

MKM

RER

BA

SE

M

EN

T H

VA

C

P

LA

N

01 1ST FLOOR MECHANICAL PLAN

1/8" = 1'-0"MH102

JOSEPH DAVID ASSOCIATES

REVISIONS

DRAWN BY

CHECKED BY

19970 CHLOE LAYNE RD.

SPIRO, OK 74959

JOSEPHDAVIDASSOCIATES.COM

FARRIS ENGINEERING

12700 West Dodge Road, Omaha, NE 68154

Proj ID

Project Status Issue Date 100% CD Issue for Construction

09-18-24

140A1622F0214 the copyright law.

OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS

FARRIS ENGINEERING

farris-usa.com

COPYRIGHT

This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by

FEI #232013NOTICE:

DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.

PRINTS IN A DIFFERENT FORMAT MAY NOT BE

REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL

DIMENSIONS AND CLEARANCES ON SITE.

R O

SE

BU

D A

G

EN

C Y

BO

IL

ER

H

VA

C S

YS

TE

M (S

) D

ES

IG

N

BU

IL

D

IN

G

ASI #001 10-01-26

MH102

1ST FLOOR HVAC PLAN

MKM

RER

1S T

FL

O

O R

H

VA

C P

LA

DEDICATED OUTDOOR AIR UNIT SCHEDULE

MARK LOCATION APPLICATION /

SERVES

SUPPLY AIR

(CFM)

OA

(CFM)

HEATING SECTION (ELECTRIC) COOLING SECTION SUPPLY FAN EXHAUST FAN ELECTRICAL

REFRIG WEIGHT

(LBS)

MANUFACTURER &

MODEL NO. REMARKSEAT

DB (°F)

DES

LAT

(°F)

ELEC

STAGES

EAT

DB/WB

(°F)

LAT

DB/WB

(°F)

TOTAL

CAP

(MBH)

SENS

CAP

(MBH)

COMP.

FACE

VEL.

(FPM)

EER NO.

FANS

ESP

(IN

WG)

POWER

(BHP)

NO.

FANS

AIRFLOW

(CFM)

ESP

(IN

WG)

POWER

(HP) V PH SCCR

(A)KW

DOAS-1 ON GRADE WEST WING 1,500 1,500 55.8 89.1 15.0 MOD 79 /

63.6

50.9 /

50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP

B072 1, 2

DOAS-2 ON GRADE EAST WING 1,500 1,500 55.8 89.1 15.0 MOD 79 /

63.6

50.9 /

50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP

B072 1, 2

DOAS-3 ON GRADE INTERIOR 1,500 1,500 55.8 89.1 15.0 MOD 79 /

63.6

50.9 /

50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP

B072 1, 2

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. CAPACITY BASED ON 95°F OUTDOOR AIR TEMPERATURE.

ELECTRIC BASEBOARD HEATER

MARK TYPE LOCATION CAPACITY

(KW)

LENGTH

(FT)

ELECTRICAL DATA MANUFACTURER &

MODEL NO. REMARKS

V PH AMPS

BH-1 SLANT TOP SEE PLANS 1.5 6 120 1 7.2 INDEECO 903U015 1

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

JOSEPH DAVID ASSOCIATES

REVISIONS

DRAWN BY

CHECKED BY

19970 CHLOE LAYNE RD.

SPIRO, OK 74959

JOSEPHDAVIDASSOCIATES.COM

FARRIS ENGINEERING

12700 West Dodge Road, Omaha, NE 68154

Proj ID

Project Status Issue Date 100% CD Issue for Construction

09-18-24

140A1622F0214 the copyright law.

OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS

FARRIS ENGINEERING

farris-usa.com

COPYRIGHT

This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by

FEI #232013NOTICE:

DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.

PRINTS IN A DIFFERENT FORMAT MAY NOT BE

REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL

DIMENSIONS AND CLEARANCES ON SITE.

R O

SE

BU

D A

G

EN

C Y

BO

IL

ER

H

VA

C S

YS

TE

M (S

) D

ES

IG

N

BU

IL

D

IN

G

ASI #001 10-01-26

ELECTRIC CABINET AND UNIT HEATER SCHEDULE

MARK TYPE ARRANGEMENT LOCATION AIRFLOW

(CFM)

CAPACITY

(KW)

ELECTRICAL DATA MANUFACTURER &

MODEL NO. REMARKS

V PH TOTAL AMPS

EUH-1 FAN-FORCED HORIZONTAL STORAGE 300 1.5 208 1 7.6 INDEECO ULIR 925U020 1, 2, 3, 4, 5, 6

EUH-2 FAN-FORCED HORIZONTAL STORAGE 300 1.5 208 1 7.6 INDEECO ULIR 925U020 1, 2, 3, 4, 5, 6

ECUH-1 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-2 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-3 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-4 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-5 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-6 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

ECUH-7 FAN-FORCED HORIZONTAL

SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. PROVIDE WITH TWO STAGE HEATING.

3. PROVIDE WITH INTEGRAL DISCONNECT.

4. PROVIDE WITH INTERGRAL THERMOSTAT.

5. PROVIDE WITH WALL MOUNTING BRACKETS.

6. MOUNT UNIT AT 8'-0" A.F.F.

DOMESTIC WATER HEATER SCHEDULE (ELECTRIC)

MARK CAPACITY

(GAL)

RECOVERY

(GPH)

TEMP. RISE

(°F)

INPUT

(KW)

ELECTRICAL MANUFACTURER &

MODEL NO. REMARKS

V PH

EWH-1 50 12 100 3 208 3 BRADFORD WHITE

LE350S3 1

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

FAN SCHEDULE

MARK TYPE

FAN POWER AIRFLOW

(CFM)

ESP

(IN WG)

MANUFACTURER &

MODEL NO. REMARKS

(W)

TF-1 TRANSFER FAN 82 360 0.25 LOREN COOK CBF 1

TF-2 TRANSFER FAN 82 360 0.25 LOREN COOK CBF 1

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

REGISTER - GRILLE - DIFFUSER SCHEDULE

MARK FUNCTION TYPE

CFM MAX FACE SIZE NECK SIZE

MATERIAL FINISH

MANUFACTURER

REMARKS

RANGE N.C. (INCHES) (INCHES) & MODEL NO.

S-1 SUPPLY SQUARE FACE NOMINAL

PANEL 0 - 100 25 24 x 24 6" Ø STEEL WHITE KRUEGER 1450 1, 2, 3

S-2 SUPPLY SQUARE FACE NOMINAL

PANEL 101 - 150 25 24 x 24 8" Ø STEEL WHITE KRUEGER 1450 1, 2, 3

S-3 SUPPLY DOUBLE DEFLECTION 0 - 150 25 6 x 6 - STEEL WHITE KRUEGER 5880H 1, 2, 3

R-1 RETURN SINGLE DEFL. 35° BLADE 0 - 300 25 12 X 8 - STEEL WHITE KRUEGER 5880H 1, 2, 3

R-2 RETURN SINGLE DEFL. 35° BLADE 301 - 425 25 12 X 12 - STEEL WHITE KRUEGER 5880H 1, 2, 3

R-3 RETURN SINGLE DEFL. 35° BLADE 426 - 920 25 24 X 12 - STEEL WHITE KRUEGER 5880H 1, 2, 3

REMARKS:

1. PROVIDE SPECIFIC NOISE CRITERIA (NC) DATA FOR EACH LINE ITEM WITH SHOP DRAWINGS.

2. COORDINATE BORDER OR FRAME TYPE WITH CEILING TYPE.

3. COORDINATE FINISH/COLOR WITH ARCHITECT.

M-702

MECHANICAL SCHEDULES

MKM

RER

M

EC

H

AN

IC

AL

S C

H

ED

U

LE

S

PLUMBING PUMP SCHEDULE

MARK SERVES TYPE GPM

HEAD

RPM HP

MANUFACTURER

REMARKS

FT. & MODEL NO.

PP-1 HOT WATER

CIRCULATING INLINE 3.0 8 3,250 1/40 TACO MODEL 006-BC4 1, 2

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. ALL BRONZE CONSTRUCTION.